12. Connection and configuration of status units and ancillary boards 16
12.1 Adding new status units/ancillary boards 17
12.2 Removing status units/ancillary boards 18
13. Wiring to status units/ancillary boards 19
14. Configuration 20
14.1 Extinguishing output mode 20
14.2 Configuring the activation mode 20
14.3 Reset inhibit time 21
14.4 Pre-release delay timer 21
14.5 Extinguishing release time 22
14.6 2
14.7 Released condition 22
14.8 Delay on manual release 23
14.9 Pre-release delay reset disabled 23
14.10 Release timer 24
14.11 R0V not removed on reset 24
14.12 Disable earth fault monitoring 25
14.13 Disable fault output 25
14.14 Invert low pressure switch input 25
14.15 Extinguishing output monitoring levels 26
15. Panel operation – access levels 1 & 2 27
15.1 Normal condition 27
15.2 Access level 2 27
stage alarm relay 15
nd
stage alarm relay 15
nd
stage alarm pulsing/continuous 22
15.2.1 Disable extinguishing release outputs 27
15.2.2 Disable manual release 27
15.2.3 Disable 1
st
stage output 28
TM206 2 of 35 Issue 1.0
15.2.4 Disable 2nd stage output 28
15.2.5 Disable released output 28
15.2.6 Disable extract output 29
15.2.7 Turn on extract output 29
15.3 Single input activation 29
15.4 Double input activation 29
15.5 Reset 30
15.6 Sounder fault 30
15.7 Power fault 30
15.8 System fault 30
15.9 Lamp test 30
15.10 Hold condition 31
15.11 Released condition 31
15.12 Low pressure switch 31
15.13 Manual only mode 31
15.14 Manual release 31
15.15 Abort input 31
16. Internal controls 32
16.1 Watchdog reset 32
16.2 Processor reset 32
16.3 Terminate extinguishing 32
16.4 Write enable switch 32
17. Internal indications 33
17.1 Watchdog 33
17.2 System fuse 33
17.3 Man. Release 33
18. Power supply 33
19. Maintenance 34
20. CE Mark 34
21. Commissioning instructions 35
TM206 3 of 35 Issue 1.0
1 Introduction
The FireBeta XT+ Extinguishant Coincidence Unit is designed in accordance with European standards
EN12094-1 Fixed fire fighting systems - Components for gas extinguishing systems - Part 1:
Requirements and test methods for electrical automatic control and delay devices.
The FireBeta XT+ ECU is a self contained extinguishing release control unit that can receive
activation signals at supervised inputs via volt free contacts from a fire detection control panel
or addressable output modules
The ECU has an integral, mains powered, EN54-4 compliant battery charger and power
supply.
In addition to the requirements of EN12094-1 the ECU has the following facilities:
…………Delay of extinguishing signal of up to 60 seconds. EN12094-1 Section 4.17
option with requirements.
…………Signal representing the flow of extinguishing agent to indicate the released
condition. EN12094-1 Section 4.18 option with requirements.
…………Monitoring of the status of components by way of a low pressure switch input.
EN12094-1 Section 4.19 option with requirements.
………….Emergency hold device to enable the extinguishing delay time to be
extended. EN12094-1 Section 4.20 option with requirements.
………….Contro l of flooding time to deactivate the releasing output after a set period of
time. EN12094-1 Section 4.21 option with requirements.
…………Manual only mode to disable the release of Extinguishing via
automatic detection devices. EN12094-1 Section 4.23 option with requirements.
…………Triggering of equipment outside the system by way of first and
second stage contacts, extract fan output etc. EN12094-1 Section 4.26 option with
requirements.
…………Activation of alarm devices with different signals to indicate pre-
discharge and released warnings using d ifferent sounds. EN12094-1 Section 4.30 option with
requirements.
……….Emergency Abort device to inhibi t the extinguishing signal until the emergency abort
device has been deactivated and the panel has been reset. EN12094-1 Section 4.27 option with
requirements.
TM206 4 of 35 Issue 1.0
2 Safety
Suppliers of articles for use at work are required under section 6 of the Health and Safety at
Work act 1974 to ensure as reasonably as is practical that the article will be safe and without
risk to health when properly used.
An article is not regarded as properly used if it is used ‘without regard to any relevant
information or advice’ relating to its use made available by the supplier.
This product should be installed, commissioned and maintained by trained service personnel
in accordance with the following:
(i) IEE regulations for electrical equipment in buildings
(ii) Codes of practice
(iii) Statutory requirements
(iv) Any instructions specifically advised by the manufacturer
According to the provisions of the Act you are therefore requested to take such steps as are
necessary to ensure that you make any appropriate information about this product available
to anyone concerned with its use.
This equipment is designed to operate from 230V 50Hz mains supplies and is of class 1
construction. As such it must be connected to a protective earth conductor in the fixed wiring
of the installation and a readily accessible double pole disconnect device meeting the
requirements of EN60950/IEC950 which disconnects live and neutral simultaneously shall be
incorporated in the fixed wiring. Switch disconnect devices such as MK Sentry 63A or similar
are suitable for this.
WARNING:
adequately bonded to the protective earth will render the equipment unsafe.
This control panel is environmental class A and is designed for indoor use only at
temperatures between -5
95%.
The IP rating for the enclosure is IP30.
Operation outside of these limits may render the equipment unsafe.
Failure to ensure that all conductive accessible parts of this equipment are
0
C (+/- 3) and +400C (+/- 2) and with a maximum relative humidity of
3 Mounting
The ECU should be mounted on a dry, flat surface, at eye height to the displays and in a level
position such that the enclosure is not distorted.
Screws or bolts of a minimum of 5mm diameter must be used to mount the enclosure in all
four mounting positions.
It should be positioned in an accessible place as agreed with the end user.
Suitable fixings should be used at all fixing points such that the unit is securely mounted and
is not liable to move once fixed.
The ECU should not be mounted in another enclosure or near sources of excessive heat.
Cables should be connected using suitable cable glands fitted to the knockouts provided. If
additional cable entry points are required, all swarf and debris caused by drilling of additional
cable entries must be cleared before power is applied to the panel.
TM206 5 of 35 Issue 1.0
Cables should not be installed in the bottom of the enclosure. This space must be kept free
for batteries
.
Side view Front view
5mm diameter screws
Fix to flat surface using suitable wall plugs
TM206 6 of 35 Issue 1.0
TM206 7 of 35 Issue 1.0
4 Technical specification
Table 1 - Electrical specifications
ITEM ELECTRICAL RATING COMMENT COMMUNICATION
PARAMETERS
Mains supply 230V AC, 50Hz +10% - 15% (100 Watts maximum) Standard European mains
connection
Mains supply fuse T2A L250V Replace only with similar type
Power supply rating 4 Amps including battery charge 28V +/- 2V
Maximum ripple current 200 millivolts
Battery type (Yuasa NP) 2 x 12 Volt sealed lead acid in series
Battery charge voltage 27.6VDC nominal (temperature compensated) Modulated DC
Battery charge current 1,5A maximum Modulated DC
Current draw in mains fail condition 60 milliamps quiescent – 107 milliamps full alarm
Maximum current draw from
batteries
4 Amps With main power source disconnected
Aux 24V output Fused at 500mA with electronic fuse 200 milliamp maximum continuous load
1st and 2nd stage Sounder outputs 21 to 28V DC Fused at 1A with electronic fuse 1.0 Amp total load over all circuits Voltage reversing DC
Fault relay contact rating 5 to 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded Volt free changeover contact
Fire relay contact rating 5 to 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded Volt free changeover contact
First stage contact rating 5 to 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded Volt free changeover contact
Second stage contact rating 5 to 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded Volt free changeover contact
Extract contact rating 5 to 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded Volt free changeover contact
Terminal capacity 0.5mm2 to 2.5mm
2
solid or stranded wire
Number of sounders per circuit Dependent on type and current consumption See table 2 for sounder types
Monitored input end of line 6K8 +/- 5% ½ Watt resistor Supplied in terminals
Sounder circuit end of line 10K +/- 5% ¼ Watt resistor Supplied in terminals
Extinguishing output end of line 1N4004 Diode Supplied in terminals
No. of sounder circuits (2) 21 to 28V DC 1 x 1st stage and 1 x 2nd stage
Extinguishing release outputs (2) 21 to 28V DC. Fused at 1 Amp 1 Amp maximum load –for 5 minutes
3 Amps for 20 milliseconds
Voltage reversing DC with
calibration facility
Extinguishing release delay Adjustable 0 to 60 seconds (+/- 10%) 5 second steps
Extinguishing release duration Adjustable 60 to 300 seconds 5 second steps
Cabling FP200 or equivalent (Maximum capacitance 1µF, max
inductance 1Mh)
Metal cable glands must be used
Monitored inputs normal threshold
(Allowable EOL)
10K ohm to 2K ohm
Monitored inputs alarm threshold 2K ohms to 150 ohms +/-5%
Monitored inputs s/c threshold 140 ohms to 0 ohms +/-5%
Status unit/Ancillary board
connection
Two wire RS485 connection (EIA-485 specification) Maximum of 7 units per area- RS485
data cable.
(EIA-485 specification)
Status unit power output 21 to 28V DC, Fused at 500mA with electronic fuse 300 milliamp maximum load
Open the control panel lid using the two 801 lock key.
Before the chassis can be removed it will be necessary to disconnect the power cables from the
connector terminal block on the left hand side of the PCB.
The chassis is held in place by two screws. Undo the two screws and lift the chassis gently away from
the box towards you.
With the chassis removed, there is much more room inside the panel for making off and dressing cables.
When cabling work is complete, the chassis can be re-fitted and the power cables reconnected.
Important! Ensure the power cables are connected correctly.
TM206 9 of 35 Issue 1.0
TM206 10 of 35 Issue 1.0
7 System diagrams
Any number of ECU connected to addressable panel
Any number of ECU connected to conventional fire panel using zonal volt free contacts
8 Connecting to the circuit board
All connections for field wiring are to rows of terminals along the top and bottom of the circuit board.
Shielded fire alarm cable such as FP200 and metal cable glands must be used for all connections to the
panel.
The shield of the cable must be bonded securely to the enclosure earth via a metal cable gland.
The resistance of any core of any cable must not exceed 25 ohms. The shield of the cable must be
bonded securely to the enclosure via the metal gland.
Wiring should enter the enclosure at the top or back of the panel using the knockouts provided and be
formed tidily to the appropriate terminals.
Terminals are capable of accepting wires of up to 2.5mm
Wiring must not go across the front of the circuit board. If cable entries need to be in positions other than
at the knockouts provided, wiring must be fed behind and well away from the surface of the circuit board.
The space at the bottom of the enclosure is largely occupied by the standby batteries so this must be
borne in mind when considering cable entries.
8.1 Sounder circuit wiring
All sounders must be of the polarised type. If non-polarised sounders are used the control panel will
permanently show a fault condition. See table 2 for a list of compatible sounder types.
Sounder circuits are monitored for open and short circuit faults by placing a 10K 0.25W end of line
monitoring resistor across the last device on the circuit.
Sounder circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the
monitoring circuit to work correctly.
POLARISED
SOUNDER
2
.
POLARISED
SOUNDER
SOUNDER
OUTPUT
TERMINALS
+ IN
-IN
See manufacturers
details for detailed
connection information
+ OUT
-OUT
+ IN
-IN
See manufacturers
details for detailed
connection information
+ OUT
-OUT
Sounder circuit wiring through an MTL778ac I.S. barrier
TM206 11 of 35 Issue 1.0
10K end of
line resistor
Loading...
+ 24 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.