This manual is written for those who own or are responsible for Kidde® FE-13™ Fire Suppression System cylinders.
IMPORTANT
Kidde assumes no responsibility for the application of any systems other than those addressed in this manual. The
technical data contained herein is limited strictly for information purposes only . Kidde believes this data to be accurate, but
it is published and presented without any guarantee or warranty whatsoever . Kidde disclaims any liability for any use that
may be made of the data and information contained herein by any and all other parties.
Kidde FE-13 Fire Series Fire Suppression Systems are to be designed, installed, inspected, maintained, tested and
recharged by qualified, trained personnel in accordance with the following:
•St andard of the National Fire Protection Association No. 2001, titled Clean Agent Fire Extinguishing Systems.
•All instructions, limitations, etc. contained in this manual, P/N 96-FE13MA-000 and/or 96-FE13MA-002.
•All information contained on the system container nameplate(s).
Storage, handling, transportation, service, maintenance, recharge and test of agent storage containers shall be performed only by qualified and trained personnel in accordance with the information in this manual and Compressed Gas
Association pamphlets C-1, C-6 and P-1:
•C-1, Methods for Hydrostatic Testing of Compressed Gas Cylinders.
•C-6, St andards for V isual Inspection of Compressed Gas Cylinders.
•P-1, Safe Handling of Compressed Gases In Containers.
CGA p amphlets are published by the Compressed Gas Association, Cryst al Square T wo, 1725 Jef ferson Davis Highway ,
Arlington, V A 22202-4102.
Any questions concerning the information presented in this manual should be addressed to:
Kidde-Fenwal Inc.
400 Main Street
Ashland, MA 01721
Phone: (508) 881-2000
Fax: (508) 881-8920
2-7Additional S pecifications and Documentation............................................................................2-2
iii
THIS P AGE INTENTIONALLY LEFT BLANK.
iv
A TTENTION INST ALLER
This form must be signed by the system owner indicating that he/she has received a copy of this Owner’s Manual
P/N 96-FE13MA-001. Have the system installer fill-out this form.
2.Listing of Major System Components:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
3.Description of Hazard Protected by System:
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
_________________________________________________________
Owner or Authorized Represent ativeDate
____________________________________________
Title
v
THIS P AGE INTENTIONALLY LEFT BLANK.
vi
SAFETY SUMMAR Y
Safety precautions are essential whenever electrical or mechanical equipment is involved. Take precautions when handling, servicing, and charging FE-13™ fire suppression systems cylinders. Using this equipment with the respect and
caution demanded will considerably lessen the possibility of personal injury. If safety precautions are overlooked or ignored, personal injury or property damage may occur.
The following symbols are used throughout this manual. Always heed these precautions. They are essential to the safe
use of the equipment described in this manual.
WARNING
!
The warning symbol identifies immediate hazards and provides specific instructions or procedures which
if not correctly followed will result in severe personal injury or death.
CAUTION
!
This caution symbol identifies specific instructions or procedures which if not correctly followed could
result in minor personal injury or equipment or property damage.
The following safety precautions should always be followed:
WARNING
!
Pressurized (charged) cylinders are extremely hazardous and if not handled properly are capable of causing
bodily injury , death or property damage.
1. Read and understand this manual and the other documents referenced herein.
2. The valve outlet safety cap and the actuation port protection cap MUST be installed on the cylinder valve at all times
and only removed when performing charging, testing, or salvaging operations in accordance with the procedures
contained in this manual.
3. Wear safety glasses when working with pressurized cylinders and charging equipment
4. Make sure that all control heads, pressure operated control heads, or other type of actuation devices have been
removed from the cylinder valves. Ensure the protection caps are installed before performing any charging, leak tests
or salvage operations.
Don’t get careless. Never assume a cylinder is empty . Treat all cylinders as if they are fully charged.
Smoking is prohibited in FE-13 fill and charging areas.
vii
THIS P AGE INTENTIONALLY LEFT BLANK.
viii
FE-13™ Fire Suppression System Owner's Manual
WARNING
!
CHAPTER 1
GENERAL INFORMATION
1-1INTRODUCTION
This document is provided to instruct and familiarize the
owner with the Kidde® FE-13™ Fire Suppression System.
This manual covers:
•Information about the system
•How the FE-13 system operates
•How FE-13 works
•Installation of the system
•Instructions in case of fire
•Post-operation instructions
•Inspection and maintenance of the system
•Responsibilities and related equipment requirements
NAME OF KIDDE DISTRIBUTOR IS:
________________________________________________
ENTER EMERGENCY NUMBER FOR THE LOCAL FIRE
DEP ARTMENT HERE:
________________________________________________
Before handling Kidde products, all personnel must be thoroughly trained in the safe handling of the containers as well
as in the proper procedures for installation, removal, filling
and connection of other critical devices, such as solenoids,
cable assemblies, pressure switches and safety caps.
READ, UNDERST AND and ALWA YS FOLLOW the operation and maintenance manuals, owner’s manuals, service
manuals, etc., that are provided with the individual systems.
•Additional specifications and documentation
Note:IMPORT ANT–This owner's manual does not cover
every detail of step-by-step installation procedures
for the Kidde FE-13 Fire Suppression System.
The system consists of components tested within
the limitations defined in the detailed design, installation, operation and maintenance manual
(P/N 96-FE13MA-000 and -002) which is available
from Kidde. The system designer must be consulted
whenever changes are planned for the system or
area of protection.
A certified Kidde distributor must be consulted after the system has been discharged.
The technical data contained herein is limited strictly
for informational purposes only .
CAUTION
!
It is the owner's responsibility to read this
manual and to ensure proper system operation
and personnel safety .
Follow the instructions in this manual and on the FE-13
cylinder nameplates. Review this information semi-annually , or as needed. Place this manual in an accessible place
near the FE-13 system for ready reference.
Kidde believes this data to be accurate, however, it is published and presented without any guarantee or warranty
whatsoever. Kidde disclaims any liability for the information contained herein by any , and all, other parties.
Pressurized (charged) containers are extremely
hazardous and if not handled properly, are
capable of violent discharge. This may result
in serious bodily injury, death and property
damage.
The discharge of clean agent systems to extinguish a fire
can result in a potential hazard to personnel from the natural
form of the clean agent or from the products of combustion
that result from exposure of the agent to the fire or hot surfaces. Unnecessary exposure of personnel, either to the
natural agent or to the products of decomposition, shall be
avoided.
1- 2MOVING OF CONT AINERS
1-2.1Moving by Trucks
Containers must be shipped in the upright position and prop-
erly secured in place. Containers must not be rolled,
dragged, slid or allowed to be slid from tailgates of vehicles.
A suitable hand truck, fork truck, roll plat form or similar device must be used.
1-2.2Rough Handling
Containers must not be dropped or permitted to strike vio-
lently against each other or other surfaces.
1-2.3Storage
Containers must be stored standing upright and secured in
place.
October 2002
1-1
96-FE13MA-001
FE-13™ Fire Suppression System Owner's Manual
1- 3SAFETY CAP
WARNING
!
These instructions must be followed in the exact
sequence as written to prevent serious injury,
death and/or property damage.
Each FE-13 container is factory equipped with a safety cap
installed on the container outlet and securely chained to the
container to prevent loss. This device is a safety feature and
will provide controlled, safe discharge when installed in the
event the container is accidentally actuated.
The safety cap must be installed on the container outlet A T
ALL TIMES except when the containers are connected to
the system piping.
The safety cap is intentionally chained to the container to
prevent loss while in service and must not be removed from
its chain.
For additional information on safe handling of compressed
gas containers, see CGA Pamphlet P1 titled “Safe Handling of Compressed Gases in Containers.” (CGA pamphlets may be purchased from the Compressed Gas
Association, Crystal Square Two, 1725 Jefferson Davis
Highway, Arlington, V A, 22202).
1- 5FE-13 OVERVIEW
FE-13 suppression agent is a compound of carbon, fluorine
and hydrogen (trifluoromethane CHF
). In its normal state,
3
FE-13 is a colorless, odorless gas, which is electrically nonconductive. The agent is stored as a liquid under pressure.
When FE-13 is discharged, it expands throughout the distribution piping system and at the nozzle, returning to the
gaseous state. In the proper concentration, FE-13 suppresses fire by breaking the chain reaction of the combustion process. FE-13 suppresses flame rapidly , helps prevent
reignition, leaves no residue and requires no cleanup after
discharge.
FE-13 will decompose upon contact with temperatures
greater than approximately 1300°F (700°C). Decomposed
FE-13 has a sharp, acrid odor, which is easily recognized
even in small amounts. Decomposed products, including
decomposed fuel, are toxic and minimized with rapid suppression of fire. FE-13 systems are designed to provide
rapid discharge (normally 10 seconds or less) and flame
suppression in order to minimize equipment damage and
reduce danger to personnel.
1-4ABOUT THE SYSTEM
The FE-13 system is designed for suppression of Class A,
B and C fires.
•Class A Surface Fires—cellulosic material (wood, paper, etc.)
•Class B–flammable liquids
•Class C–electrical equipment
Because FE-13 poses minimum risk to personnel due to
low toxicity, it is used extensively where people normally
occupy the fire hazard area. Examples of typical FE-13 system applications include:
•Industrial high ceiling spaces
•Locomotives
•Mining equipment
•Offshore oil platforms
•Oil and Gas processing facilities
•Pumping stations
•Refinery control area.
Note:IMPORTANT–Per NFP A 2001, FE-13 systems with
use concentrations below the No Obeserved Adverse
Effect Level (NOAEL, 30% v/v) are permitted for use
in occupied areas. FE-13 systems with use concentrations above the NOAEL are not permitted for
use in occupied areas.
96-FE13MA-001
1-2
October 2002
FE-13™ Fire Suppression System Owner's Manual
CHAPTER 2
INST ALLA TION AND MAINTENANCE
2-1INTRODUCTION
The FE-13™ Fire Suppression System is designed to discharge a specific amount of FE-13 through nozzles located
within the hazard area. The amount of FE-13 necessary for
the system has been carefully calculated to meet strict requirements set by Underwriters Laboratories and the National Fire Protection Association. Additional requirements
may apply depending upon the application, design specifications and the Authority Having Jurisdiction.
Simply , the FE-13 Fire Suppression System consist s of:
•FE-13 container(s), discharge piping and nozzles
•Actuation devices–electric, pneumatic, cable or
manual
•Detection, alarm devices and control panel.
The system must be provided with means for manual operation using one or both of the following UL Listed devices:
•Electric actuation station
•Automatic detector (control panel required).
Automatic system operation (if provided) can be electric
using UL Listed heat detectors, photoelectric, ionization
smoke detectors or optical flame detectors.
An electrical control head is used to open the valve, which
is part of the agent storage container. Pressure from the
discharge may be used to open the container valves on
additional containers.
If the system has a control panel, refer to the appropriate
Kidde control panel manual as applicable.
2-2INSTALLATION
The Kidde FE-13 Fire Suppression System must be installed
only by an authorized Kidde distributor. The system must
be installed using genuine Kidde components and installation materials in accordance with the Design, Installation,
Operation and Maintenance Manual (P/N 96-FE13MA-000
or -002).
Note:The installer must have a current Kidde installation
certificate.
The following items must be checked after the system is
installed:
•All areas requiring protection are protected.
•A means of manually discharging the FE-13 system is provided in a readily accessible location
where it can be operated while leaving the vicinity
of the hazard area. The manual control must be
clearly labeled. The installer of the FE-13 system
should answer any questions regarding the components and coverage of the system.
The installer must also demonstrate that the installed system conforms to the requirements of the Kidde FE-13 Design, Installation, Operation and Maintenance Manual,
(P/N 96-FE13MA-000 or -002) and the requirements of the
insurance carrier and the Authorities Having Jurisdiction in
the area.
2- 3INSTRUCTIONS IN CASE OF FIRE
1. Direct all occupants to leave the fire area immediately .
Note :Important–Operate the system manually using the
manual release if required.
2. Suspend all operations in the fire area.
3. Have someone contact the fire department immediately ,
no matter how small the fire appears to be. Post the
STREET ADDRESS of the building and the fire
department's phone number beside each telephone.
Be familiar with the location of the nearest fire department from outside.
4. Make sure all persons have evacuated the fire area in
accordance with individual emergency procedures.
The remote manual release is a device which works electrically. Follow the instructions on the device, i.e., “LIFT
COVER, PULL DOWN” etc. Exit the vicinity of the hazard
immediately.
After the fire is suppressed, do not re-enter the fire area
until the fire department arrives and gives approval.
2-4POST-OPERATION INSTRUCTIONS
After the system has discharged, contact the Kidde distributor to reset and recharge the system. Insist that the
system be recharged immediately and with the proper type
and quantity of agent.
October 2002
2-1
96-FE13MA-001
FE-13™ Fire Suppression System Owner's Manual
2- 5INSPECTION AND MAINTENANCE OF THE
SYSTEM
CAUTION
!
The owner of the Kidde FE-13 Fire Suppression System must comply with these instructions. Failure to do so may result in inadequate
system performance, property damage and personal injury .
See Kidde manual 96-FE13MA-000 or -002 for
additional inspection information.
2-5.1
Monthly
1. Inspect all system components, nozzles, distribution
piping and conduit runs for physical damage and/or displacement.
2. Inspect all detectors and control panels for evidence of
damage or missing components. Have damaged or
missing parts replaced immediately (contact the Kidde
distributor). Refer to applicable control panel manual
for additional pertinent inspection procedures.
3. Inspect each container. Container(s) must not show evidence of corrosion or damage.
4. Inspect remote manual release. For electric manual
release devices, check visually to ensure the device is
in the normal or ready position. The path to the remote
release must be clear and unobstructed.
If any discrepancies are noted while making this inspection, SUSPEND ALL OPERA TIONS IN THE PROTECTEDAREA. Contact the Kidde distributor for service and/or repair.
2-5.2Semi-Annual Inspection
The system must be thoroughly inspected on a semi-an-
nual basis by a certified Kidde distributor. As part of the
semi-annual inspection, the system must be functionally
tested per the instructions in the Kidde FE-13 Fire Suppression System Design, Installation, Operation and Maintenance Manual (P/N 96-FE13MA-000 or -002). These
instructions call for functional test of the system and verification of the agent quantity in each container. Agent will
not be discharged as a part of the inspection.
Read, understand and follow the instructions in this manual
and on the container nameplates. Review these instructions with employees semi-annually, or more frequently.
Place this manual in an accessible area near the FE-13
system for ready reference. Post the name, phone number
and address of the Kidde distributor near the telephone.
Also, post the emergency telephone number of the fire department and the building street address near all telephones.
If any condition exists which would render the FE-13 system inoperative or ineffective, SUSPEND ALL OPERA-TIONS IN THE PROTECTED AREA IMMEDIATEL Y . Have
the condition corrected by the Kidde distributor before resuming operations.
2-7ADDITIONAL SPECIFICATIONS AND
DOCUMENTATION
The system must be designed, installed, operated and maintained only in accordance with the following documents and
specifications:
•Kidde FE-13 Design, Installation, Operation and
Maintenance Manual, P/N 96-FE13MA-000 or -002,
available from the Kidde distributor or Kidde.
Kidde-Fenwal, Inc.
400 Main Street
Ashland, MA 01721
Phone: 508-881-2000
Fax: 508-881-8920
•National Fire Protection Association Standard No.
2001, current edition, available from:
National Fire Protection Association
1 Batterymarch Park
Quincy , MA 02269
•Copies of the Material Safety Data Sheet (MSDS)
for FE-13 are available in the back of this manual
(Appendix A).
For more information regarding inspection and maintenance, contact the Kidde distributor or Kidde directly .
2-6ADDITIONAL REQUIREMENTS
Portable fire extinguishers are required in addition to the
FE-13 system and for areas not protected by the system.
Consult with the insurance carrier, local Authorities Having
Jurisdiction and the portable fire extinguisher distributor for
sizes, types, spacing and location requirements.
96-FE13MA-001
2-2
October 2002
FE-13™ Fire Suppression System Owner's Manual
APPENDIX A
MA TERIAL SAFETY DAT ASHEETS
A-1October 2002
96-FE13MA-001
FE-13™ Fire Suppression System Owner's Manual
THIS P AGE INTENTIONALLY LEFT BLANK.
96-FE13MA-001
A-2October 2002
The MSDS format adheres to the standards and regulatory requirements
of the United States and may not meet regulatory requirements
in other countries.
--------------------------------------------------------------------- CHEMICAL PRODUCT/COMPANY IDENTIFICATION
--------------------------------------------------------------------- Material Identification
Corporate MSDS Number : DU001064
CAS Number : 75-46-7
Formula : CHF3
CAS Name : Trifluoromethane
Company Identification
MANUFACTURER/DISTRIBUTOR
DuPont Fluoroproducts
1007 Market Street
Wilmington, DE 19898
PHONE NUMBERS
Product Information : 1-800-441-7515 (outside the U.S.
302-774-1000)
Transport Emergency : CHEMTREC 1-800-424-9300(outside U.S.
703-527-3887)
Medical Emergency : 1-800-441-3637 (outside the U.S.
302-774-1000)
--------------------------------------------------------------------- COMPOSITION/INFORMATION ON INGREDIENTS
--------------------------------------------------------------------- Potential Health Effects
Inhalation of high concentrations of vapor is harmful and
may cause heart irregularities, unconsciousness, or death.
Intentional misuse or deliberate inhalation may cause death
without warning. Vapor reduces oxygen available for
breathing and is heavier than air. Liquid contact can cause
frostbite.
HUMAN HEALTH EFFECTS:
Overexposure by inhalation may include nonspecific
discomfort such as nausea, headache, or weakness; temporary
nervous system depression with anesthetic effects such as
dizziness, headache, confusion, incoordination, and loss of
consciousness; or with gross overexposure (>20%), possibly
3017FR DuPont Page 2
Material Safety Data Sheet
(HAZARDS IDENTIFICATION - Continued)
temporary alteration of the heart’s electrical activity with
irregular pulse, palpitations, or inadequate circulation.
Individuals with preexisting diseases of the central nervous
or cardiovascular system may have increased susceptibility
to the toxicity of excessive exposures. Eye or skin contact
with the liquid may cause frostbite.
Carcinogenicity Information
None of the components present in this material at concentrations
equal to or greater than 0.1% are listed by IARC, NTP, OSHA or ACGIH
as a carcinogen.
--------------------------------------------------------------------- FIRST AID MEASURES
--------------------------------------------------------------------- First Aid
INHALATION
Immediately remove to fresh air. Keep person calm. Call
a physician. If not breathing, give artificial
respiration. If breathing is difficult, give oxygen.
SKIN CONTACT
Flush with water. Treat for frostbite if necessary by
gently warming affected areas.
EYE CONTACT
In case of liquid contact, immediately flush eyes with
plenty of water for 15 minutes. Call a physician.
INGESTION
Ingestion is not considered a potential route of
exposure.
Notes to Physicians
Because of possible disturbances of cardiac rhythm,
catecholamine drugs, such a epinephrine, should be
considered only as a last resort in life-threatening
emergencies.
--------------------------------------------------------------------- FIRE FIGHTING MEASURES
Flash Point: No flash point
Flammable Limits in air, % by Volume:
LEL : None per ASTM E681
UEL : None per ASTM E681
Autoignition: Not determined
3017FR DuPont Page 3
Material Safety Data Sheet
(FIRE FIGHTING MEASURES - Continued)
Fire and Explosion Hazards:
Containers may rupture under fire conditions. Decomposition
may occur.
Contact of welding or soldering torch flame with high
concentrations of refrigerant can result in visible changes
in the size and color of torch flames. This flame effect
will only occur in concentrations of product well above the
recommended exposure limits, therefore, stop all work and
ventilate to disperse refrigerant vapors from the work area
before using any open flames.
HFC-23 is not flammable in air at temperatures up to 100
deg. C (212 deg. F) at atmospheric pressure. However,
mixtures of HFC-23 with high concentrations of air at
elevated pressure and/or temperature can become combustible
in the presence of an ignition source. HFC-23 can also
become combustible in an oxygen enriched environment (oxygen
concentrations greater than that in air). Whether a mixture
containing HFC-23 and air, or HFC-23 in an oxygen enriched
atmosphere become combustible depends on the
inter-relationship of 1) the temperature, 2) the pressure,
and 3) the proportion of oxygen in the mixture. In general,
HFC-23 should not be allowed to exist with air above
atmospheric pressure or at high temperatures; or in an
oxygen enriched environment. For example, HFC-23 should NOT
be mixed with air under pressure for leak testing or other
purposes.
Extinguishing Media
As appropriate for combustibles in area.
Fire Fighting Instructions
Use water spray or fog to cool containers. Self-contained
breathing apparatus (SCBA) is required if cylinders rupture
or release under fire conditions. Water runoff should be
contained and neutralized prior to release.
NOTE: Review FIRE FIGHTING MEASURES and HANDLING (PERSONNEL)
sections before proceeding with clean-up. Use appropriate
PERSONAL PROTECTIVE EQUIPMENT during clean-up.
3017FR DuPont Page 4
Material Safety Data Sheet
(ACCIDENTAL RELEASE MEASURES - Continued)
Accidental Release Measures
Material evaporates at atmospheric pressure (vaporizes).
Ventilate area, especially low places where heavy vapors
might collect. Remove open flames. Wear self-contained
breathing apparatus (SCBA) for large spills or when a
release occurs.
DuPont Fire Emergency Exposure Limits (FEEL) are established
to facilitate the safe release of a fire extinguishant into
spaces normally occupied by people to extinguish a fire or
prevent an explosion and specify airborne concentrations of
brief durations which should not result in permanent adverse
health effects or interfere with escape. For more
information on the applicability of FEEL’s, contact DuPont.
The DuPont Fire Emergency Exposure Limit (FEEL) for this
material is 20% v/v for up to 15 minutes with a 1 minute
not-to-exceed ceiling of 23% v/v.
--------------------------------------------------------------------- HANDLING AND STORAGE
Avoid breathing high concentrations of vapor. Avoid contact
of liquid with eyes and prolonged skin exposure. Use with
sufficient ventilation to keep employee exposure below
recommended limits.
Storage
Clean, dry area. Do not heat above 51.7 deg C (125 deg F).
Normal ventilation for routine manufacturing procedures is
generally adequate. Local exhaust should be used when large
amounts are released. Mechanical ventilation should be used
in low or enclosed places.
Personal Protective Equipment
Impervious gloves should be used when handling liquid.
Chemical splash goggles should be worn when handling liquid.
Under normal manufacturing conditions, no respiratory
protection is required when using this product. Self contained breathing apparatus (SCBA) is required if a large
spill or release occurs.
Exposure Guidelines
3017FR DuPont Page 5
Material Safety Data Sheet
Exposure Limits
FE-13
PEL (OSHA) : None Established
TLV (ACGIH) : None Established
AEL * (DuPont) : 1000 ppm, 8 & 12 Hr. TWA
* AEL is DuPont’s Acceptable Exposure Limit. Where governmentally
imposed occupational exposure limits which are lower than the AEL
are in effect, such limits shall take precedence.
--------------------------------------------------------------------- PHYSICAL AND CHEMICAL PROPERTIES
--------------------------------------------------------------------- Physical Data
Boiling Point : -82.1 C (-115.8 F)
Vapor Pressure : 686 psig at 25 deg C (77 deg F)
Vapor Density : 2.4 (Air = 1)
% Volatiles : 100 WT%
Solubility in Water : 0.1 WT% @ 25 C (77 F)
Odor : Slight ethereal
Form : Compressed gas or liquefied gas
Color : Clear, colorless
Density : 1.44 g/cc at -82 deg C (-115.7 deg F)
--------------------------------------------------------------------- STABILITY AND REACTIVITY
--------------------------------------------------------------------- Chemical Stability
Material is stable. However, avoid open flames and high
temperatures.
Incompatibility with Other Materials
Incompatible with alkali or alkaline earth metals - powdered
Al, Zn, Be, etc.
Decomposition
Decomposition products are hazardous. This material can be
decomposed by high temperatures (open flames, glowing metal
surfaces, etc.) forming HF, COF2, or CO. These materials
are toxic and irritating. Contact should be avoided.
Polymerization
Polymerization will not occur.
3017FR DuPont Page 6
Material Safety Data Sheet
--------------------------------------------------------------------- TOXICOLOGICAL INFORMATION
--------------------------------------------------------------------- Animal Data
Inhalation 4-hour LC50: >663,000 ppm in rats
HFC-23 is untested for skin and eye irritancy, and for
animal sensitization.
Effects from single high inhalation exposure to HFC-23
include anaesthetic effects, and nonspecific effects such as
weight loss were observed at concentrations >22%. No
cardiac sensitization was observed in dogs after breathing
800,000 ppm for periods of 5-10 minutes following
epinephrine challenge. In another test, dogs exposed to up
to 30% or up to 50% (with aditional oxygen), had no positive
responses. No cardiac sensitization occurred in baboons
exposed by inhalation to 10%, 30%, 50%, or 70% HFC-23 before
or after an epinephrine challenge; there was a dose-related
decrease in heart rates and differences in respiratory rates
during exposure.
No animal tests are available to define the carcinogenic
hazards of HFC-23. The maternal and developmental NOAEL was
50,000 ppm. HFC-23 is not considered a unique developmental
hazard to the conceptus. There were no developmental or
reproductive effects.
Tests have shown that HFC-23 does not produce genetic damage
in bacterial or mammalian cell cultures. It has not
produced genetic damage in tests on animals.
a. Received b. Action Necessity c. Priorityd. Comments
FOLD
FOLD
Place
Stamp
Here
KIDDE-FENW AL, Inc.
400 Main Street
Ashland, MA 01721
Attn. Documentation Manager
LIMITED WARRANTY STATEMENT
Kidde-Fenwal, Inc. represents that this product is free from defects in material and workmanship, and it will repair or replace
any product or part thereof which proves to be defective in workmanship or material for a period of twelve (12) months from
the date of purchase but not to exceed eighteen (18) months after shipment by Kidde-Fenwal Inc. For a full description of
Kidde-Fenwal’s LIMITED WARRANTY, which, among other things, EXCLUDES warranties of MERCHANTABILITY and
FITNESS FOR A PARTICULAR PURPOSE and liability for CONSEQUENTIAL DAMAGES, please read the entire LIMITED
WARRANTY on the Kidde-Fenwal Quotation, Acceptance of Order and/or Original Invoice which will become part of your
sales agreement. Please contact Kidde-Fenwal directly for a return material authorization (RMA) number before returning
material to the factory at Ashland, Massachusetts, shipment prepaid. Kidde-Fenwal will repair or replace and ship prepaid.
Kidde is a registered trademark of Kidde-Fenwal, Inc.
FE-13 is a trademark of DuPont.
These instructions do not purport to cover all the details or variations in the equipment
described, nor do they provide for every possible contingency to be met in connection
with installation, operation and maintenance. All specifications subject to change without
notice. Should further information be desired or should particular problems arise which
are not covered sufficiently for the purchaser’s purposes, the matter should be referred
to KIDDE-FENWAL INC., Ashland, Masssachusetts