Kidde CB, CC, CEC Owner's Manual

Battery-Powered Single
Station Smoke Alarm
Owner’s Manual
111-281
Thank you for purchasing a Firex®smoke alarm. It is an important
component of your home security system. Please read this booklet
thoroughly. The more familiar you are with the information it
contains, the easier you will find it to install, operate, and
maintain your smoke alarm properly, which ultimately means
greater security and peace of mind for you and your family.
Maple Chase Company
1 Smoke Alarm Features 2 Proper Placement of Your Smoke Alarm 3 Where You Should Not Site Smoke Alarms 4 How to Install Your Smoke Alarm 4 Testing Your Smoke Alarm 5 LED Power/Alarm Indicator 5
Special Features of Models CC and CEC 5 Maintenance and Cleaning 6 Troubleshooting 6 Important Safety Information 6 Home Fire Safety Tips and Procedures 7 Limited Warranty
Table Of Contents
CB, CC, CEC – Ionisation-type sensor
Smoke Alarm Features
• Models CB, CC and CEC are ionisation-type smoke alarms.
• Unique “battery missing” feature. The smoke alarm will not attach to the mounting bracket if a battery is not in the battery pocket.
• Low battery signal. The smoke alarm will sound a short beep about once a minute if the battery needs to be replaced.
• Optional tamper-resist feature can serve as a safeguard against tampering.
• Visual LED flashes about once a minute. This indicates the smoke alarm is receiving power.
• Loud alarm horn—85 decibels at 10 feet—sounds to alert you to an emergency.
• Test button checks smoke alarm operation. Models CC and CEC feature Alarm Control
(Quick-Quiet). When activated, this quiets unwanted alarms for a maximum of 15 min­utes.
• Model CEC features the Safety Light
. This is a small light which will turn on when the
smoke alarm sounds its alarm horn, illuminating emergency exits.
2000
111-281 English new 7/25/01 4:24 PM Page 1
®
Smoke Alarm
2
Proper Placement of Your Smoke Alarm
For the highest standard of protection, you should install a smoke or heat alarm in every room of your home. Site smoke alarms in accordance with BS 5839 : Part 6. For the minimum level of protection, there should be at least one smoke alarm on each level of the dwelling (e.g., one in the hallway of a bungalow, one on the ground floor and the upstairs landing of a two-storey house, etc.). If there are long hallways, even the minimum standard may necessitate additional interconnected smoke alarms. Where a higher stan­dard of protection is required, or where the fire risk justifies it, additional smoke or heat alarms should be installed in some or all rooms of the property. This may be necessary if the dwelling does not comply with modern fire safety standards, or if there are other factors to be considered, such as the presence of young children, elderly or disabled people, smokers, the use of portable heaters or solid fuel fires during the night, or the use of electric blankets, particularly by elderly people.
FOR BEST PROTECTION, IT IS RECOMMENDED THAT YOU INSTALL A SMOKE ALARM IN EVERY ROOM.
In addition, it is recommended that all smoke alarms be interconnected.
THE FOLLOWING INFORMATION WILL HELP YOU SITE YOUR SMOKE ALARMS SAFELY:
Typical Single Storey Dwelling (Bungalow or Flat)
• Install a smoke alarm in the hallway between the bedrooms and the living room or kitchen, close to the living room, but no more than 3m from bedroom doors. No door to a room should be further than 7.5m from the nearest smoke alarm. This may require additional smoke alarms. Where there are rooms (other than bed­rooms or toilets) on either side of a bedroom, a smoke alarm should be sited midway between the doors to these rooms. For the highest level of protection, install smoke or heat alarms in all other rooms, except bath­rooms or toilets.
FIGURE 1:
Siting of Smoke Alarms (For Minimum Protection): Single Storey Dwellings
Typical Two-Storey House
At least one smoke alarm should be located on the ground floor between the staircase and any rooms in which a fire might start. An additional interconnected smoke alarm should be installed on the first floor landing, within 3m of bedroom doors. No doors to other rooms should be further than 7.5m from the nearest smoke alarm. This may require additional smoke alarms. Where there are rooms (other than bathrooms or toilets) on either side of a bedroom, a smoke alarm should be sited midway between the doors to these rooms. For the highest level of protection, install smoke or heat alarms in all other rooms, except bathrooms or toilets.
FIGURE 2: Siting of Smoke Alarms (For Minimum Protection): Two Storey Dwellings
111-281 English new 7/25/01 4:24 PM Page 2
BEDROOM
BEDROOM
SECOND SMOKE ALARM
DINING ROOM
BEDROOM
NOT MORE THAN 7.5m
BEDROOM
BEDROOM
MORE
BEDROOM
BEDROOM
DINING ROOM
THAN 7.5m
DINING ROOM
BATHROOM
BATHROOM
BATHROOM
KITCHEN
LOUNGE
KITCHEN
LOUNGE
KITCHEN
NOT LESS
THAN 3OOmm
CONSER-
VATORY
CONSER­VATORY
EQUAL
EQUAL
CONSER­VATORY
LOUNGE
BEDROOM
BEDROOM
BEDROOM
BEDROOM
LIVING ROOM
KITCHEN
GARAGE
- DENOTES HEAT ALARM
- DENOTES SMOKE ALARM REQUIRED FOR MINIMUM PROTECTION
- DENOTES ADDITIONAL SMOKE ALARM
3
IMPORTANT SMOKE ALARM SITING AND EXCEPTION INFORMATION:
The best place to put a smoke alarm is on the ceil-
ing. Install a smoke alarm as close to the centre of the ceiling as possible. If this is not practical, mount no closer than 30cm from a wall or corner. Otherwise, if ceiling mounting is very difficult, you may install smoke alarms on walls, between 15 and 30cm from ceiling/wall intersections, making sure that the smoke alarm is above the level of any door openings.
Install ceiling mounted smoke alarms at the highest point in the area at which smoke is likely to collect.
FIGURE 3: Wall Mounting of Smoke Alarms (Small Rooms and Short Hallways)
Site a smoke alarm in each room that is divided by a partial wall (either coming down from the ceiling at least 20cm or coming up from the floor).
Site smoke alarms on peaked, cathedral, or gabled ceilings 90cm from the highest point (measured horizontally).
Site a smoke alarm in lived-in attics or attics which house electri­cal equipment like furnaces, air conditioners, or heaters.
Where You Should Not Site Smoke Alarms
Do not site a smoke alarm within close proximity of heating and cooling supply vents or within close proximity of return or fresh air vents. Smoke may be blown away from the smoke alarm by the supply vents, or could be diffused or reduced by being diverted into the return air vent.
Do not site your smoke alarm in an area where the temperature may fall below 5°C, or rise above 45°C. Smoke alarms are designed to work safely only within these temperature ranges, and failure to alarm, improper alarms, or nuisance alarms may result from operation outside these temperature limits.
Do not site a smoke alarm in a damp or very humid area such as bathrooms with showers, where the normal humidity may rise above 93% relative humidity. Above this level, moisture may condense inside the smoke chamber and cause false alarms.
Do not site an ionisation smoke alarm in an area where particles of combustion are normally present, such as kitchens or garages. An ionisation type smoke alarm with a FALSE ALARM CONTROL feature or a photoelectric type smoke alarm should be used to minimize nuisance alarms.
Do not site a smoke alarm in dusty or dirty areas—SUCH AN INSTALLATION CANNOT BE RELIED UPON. An accumulation of dust and dirt in the sensing chamber may block the openings and prevent an alarm, or may get inside the alarm and cause false alarms. If a smoke alarm is required in such an area, vacuum it frequently and test it according to direc­tions in Maintenance and Cleaning (page 5).
Do not site a smoke alarm in the dead air space in the corner where the wall meets the ceil­ing. If in doubt as to the exact alarm siting, for your safety, contact your local fire brigade for help in choosing a location.
Do not site a smoke alarm where bugs or insects are present before eliminating or minimiz­ing the bug problem. Although all smoke alarms built since 1986 are made to prevent bugs from entering the detection chamber, bugs may build up on chamber openings and prevent smoke from entering. As a result, unit should be vacuumed frequently as explained in Maintenance and Cleaning (page 5).
Do not site a smoke alarm within close proximity of a fluorescent light. Electrical noise may cause nuisance alarms.
Do not paint smoke alarm. Do not install smoke alarms closer than 300mm to light fittings. Do not install smoke alarms on surfaces that can become very hot or very cold, such as
poorly insulated external walls, or ceilings in houses with a ceiling heating system. Do not mount a smoke alarm in such a position that it is difficult or dangerous to reach for
maintenance or battery replacement. Do not site the alarm in an area where water or other liquids may enter the alarm.
111-281 English new 7/25/01 4:24 PM Page 3
NEVER HERE
TOP OF DETECTOR ACCEPTABLE HERE
30cm
CEILING
ACCEPTABLE HERE
150-300mm
SMOKE ALARM ABOVE TOP OF DOOR OPENING
STUB WALL
15cm
MINIMUM
30cm
MAXIMUM
SIDE
WALL
SOFFIT
PEAKED CEILING
20cm
1m
90cm
Loading...
+ 4 hidden pages