Kidde 755H Owner's Manual

®
Clipsal Lifesaver
Heat Alarm
Installation / Operating Instructions and Warranty
755H Heat Alarm
240V~, 50Hz, heat alarm with 9V d.c. battery backup
Suitable for interconnection with up to 39 smoke and heat alarms. WARNING. Heat alarms alone are not suffi cient for life safety as they are not designed to detect smoke. They are intended to detect a temperature of 73°C to comply within the range of 58°C to 88°C per AS
IMPORTANT: Please leave this manual with the owner.
110-656C
HEAT ALARM DESCRIPTION:
Model 755H Heat Alarm, 240V~, 50Hz, with 9V d.c. battery backup. Thank you for purchasing a quality Clipsal Lifesaver
®
755H Heat Alarm. The 755H Heat Alarm is a mains powered device, with a battery backup that will operate in the event of mains power failure. The alarm will sound when it detects a temperature of 73° to comply within the range of 58°C to 88°C per AS1603.3-1996. Please read the following instructions carefully to ensure correct installation and maintenance. These units are not designed to detect fl ame. A 5-year warranty (excluding batteries) is included. A licensed electrician or similarly qualifi ed person to SAA Wiring Rules (AS3000) and relevant Building Codes must carry out installation of the Clipsal Lifesaver® 755H Heat Alarm.
HEAT ALARMS HAVE LIMITATIONS
The Clipsal Lifesaver® Series Heat Alarm is not foolproof and is not warranted to protect lives or property from fi re. Heat alarms are not a substitute for insurance. In addition, it is possible for the heat alarm to fail at any time. For this reason you must test the heat alarm weekly and replaced every ten years.
HEAT ALARM FEATURES
The heat alarm is powered from a 240V~ supply, and has a 9V d.c. battery back-up source. Mains powered heat alarms with battery back up offer added protection in the event of a power failure or a fl at battery.
This model 755H Heat Alarm may be interconnected with as many as 39 other heat alarms of the same model, or 39 off any of the Clipsal Lifesaver®, 755 series, 240V~ smoke alarms, connected to the same phase.
Optional tamper resistant feature serves as a safeguard against tampering.
Unique “battery missing” device. The heat alarm will not
attach to the mounting bracket if a battery is not in the battery compartment.
The heat alarm will sound a short beep about once a minute if the battery is low or improperly connected.
Multi-purpose green and red LEDs indicate that the heat alarm is connected to the a.c. supply, is working normally, or is in alarm.
Loud alarm sounder, 85 decibels [dB(A)] at 3 metres, will sound to alert you in an emergency.
Test button checks heat alarm operation.
2
SPECIFICATIONS
Model Number 755H Electrical Rating 240V~, 9V d.c. battery back up Interconnecting Up to 39 other Clipsal Lifesaver® series Smoke or Heat Alarms. Temperature Rating The alarm point of this heat alarm is 73°C to comply within the range of 58° to 88°C per AS1603.3-1996 Recommended Coverage 50m
2
Recommended Spacing 5.3m Maximum Distance from Wall 7.7m Maximum Ceiling Height 6.0m Compatible Isolation Unit Catalogue No. 756
IMPORTANT SAFETY INFORMATION Please read and save these instructions
This heat alarm requires constant 240V~ power and a healthy 9V d.c. battery to operate properly. This heat alarm will not work if a.c. supply is not connected, or has failed or been interrupted for any reason, and the batteries have been removed or are fl at or improperly connected. Do not use any other kind of battery except as specifi ed in this manual. Do not interconnect this heat alarm to any other type of smoke alarm or heat alarm or auxiliary device, except those listed in this manual.
The Push-to-Test button accurately tests all heat alarm functions. Do not use any other test method for routine testing. Test heat alarm weekly to ensure proper operation.
Higher ceilings will increase the time needed by the heat alarm to detect a fi re. In most dwellings the ceiling height will keep this reaction time within acceptable limits. However, ceilings with a height of over 6 metres may delay the reaction time of the heat alarm signifi cantly.
Advice from your local distributor or Fire Brigade should be obtained when installing a heat alarm on a ceiling higher than 6m.
Only a qualifi ed electrician or similarly qualifi ed person should install this heat alarm. The installation should comply with all prevailing local, regional and national codes.
This heat alarm is designed to be used only as part of the protection of a single-family dwelling or a house in multiple occupation of no more than two storeys. It may also be used in conjunction with smoke alarms within individual fl ats or apartments in larger houses in
3
multiple occupation, to provide an early warning to occupants of a fi re in a room within the dwelling but a communal fi re alarm system should also be provided in such cases.
Heat alarms should only be used in conjunction with smoke alarms, with which the heat alarms should be interconnected, in order to provide early warning of heat, smoke, or fi re. Smoke alarms should be installed on every level of the dwelling.
Interconnected heat alarms and smoke alarms offer maximum protection. By interconnecting heat alarms and smoke alarms, when one unit senses heat, smoke, or fi re, and sounds its alarm, all others will sound as well. Do not connect this heat alarm to any other type of alarm (except those stated in this manual) or approved auxiliary device.
Heat alarms interconnected with smoke alarms may not alert every household member in time. The alarm sounder of the heat alarm is loud in order to alert individuals of a potential danger. However, there may be limiting circumstances where an occupant may not hear the alarm (eg. outdoor or indoor noise, sounder sleepers, drug or alcohol usage, impaired hearing, etc.) Household members must hear the alarm’s warning sound and quickly respond to it to reduce the risk of damage, injury, or death that may result from fi re.
Check carefully that, when any one device operates,
the alarm signal given by interconnected devices is clearly audible throughout the building, particularly in bedrooms, where it is essential that the alarm signal will wake sleeping occupants.
This heat alarm can only sound an alarm when
it detects temperatures of 73°C to comply within the range of 58°C to 88°C per AS1603.3-1996. Heat alarms do not sense smoke or gas. In some fi res, hazardous levels of toxic chemicals and smoke can build up before a heat alarm will operate. Temperatures may not reach the alarm point to activate the heat alarm quickly enough to ensure safe escape.
Some fi res are slow smouldering, low heat-producing, or are in a different room to that in which the heat alarm is located, or the heat from the fi re may bypass the alarm, the heat alarm may not give a warning under these circumstances.
Heat alarms have limitations. This heat alarm is not guaranteed to protect lives or property. Heat alarms are not a substitute for insurance. Householders should insure their lives and property in addition, as with any electronic device, it is possible for the heat alarm to fail at any time.
Never paint this heat alarm.
4
HEAT ALARM LOCATION
Heat alarms are ideal for kitchens, garages, cellars, boiler rooms, attics and other areas where there are normally high levels of fumes, smoke or dust which preclude the use of smoke alarms due to the risk of false alarms. For normal­sized houses, two-story houses, fl ats and maisonettes, it is recommended that the minimum level of protection should comprise smoke alarms in the hallways and staircases. This minimum standard necessitates one smoke alarm in the hallway of a typical bungalow or one smoke alarm on each level of a two-story house. Heat alarms should not be used in these circulation areas. If there are, for example, long hallways, the standard necessitates additional interconnected smoke alarms. If, however, the design of the dwelling does not comply with modern fi re safety standards, or if factors such as the presence of several young children, of elderly occupants or disabled people, or of smokers, the use of portable heaters or solid fuel fi res during the night, or the use of electric blankets, it is advised that additional detection devices, installed within rooms, may be necessary.
smoke alarm
photoelectric smoke alarm
BEDROOM
BATH
heat alarm
GARAGE
LIVING AREA
BASEMENT
BEDROOM
KITCHEN
BOILER ROOM
For best protection, it is recommended that you install a smoke or heat alarm in every room. In addition, it is recommended that all smoke and heat alarms should be interconnected. Note: Smoke alarms should be installed per AS1670.6 Standard. Install heat alarm as close to the centre of the ceiling as possible. If the centre is not practical, mount the heat alarm no closer than 300mm away from a wall or corner. In rooms with open joists or beams, all ceiling-mounted alarms should be located on the bottom of such joists or beams and not up in joist channels. On sloped, peaked or
5
gabled ceilings, install Heat alarm 300mm from highest point. If only wall placement is possible, install no further than 300mm from ceiling.
DO NOT INSTALL HEAT ALARMS
Directly over the cooker, stove or oven.
In areas with high humidity, like bathrooms or shower rooms, or areas near dishwashers or washing machines. Install heat alarms at least 3m away from these areas if possible.
Adjacent to, or directly above, heaters, air-conditioning vents or ceiling fans.
In an area where the temperature may fall below +5°C or rise above +45°C.
Near fl uorescent lights. Electrical “noise” and fl ickering
may affect the operation of the heat alarm.
Closer than 300mm to light fi ttings.
In such a position that it is diffi cult or dangerous to reach for testing, maintenance or battery replacement.
HOW TO INSTALL THIS HEAT ALARM DANGER: electric shock hazards. Turn off power to the
heat alarm circuit at the main distribution board by removing the fuse or switching the circuit breaker to the off position and securing it.
WARNING, only a qualifi ed electrician in accordance with AS/NZS3000 guidelines should install this heat alarm.
Heat alarms should be connected on a single independent, dedicated circuit at the main distribution board. No other electrical equipment, except compatible smoke alarms, should be connected to this circuit. If your home has residual current device protection on the electrical installation or on individual circuits, check with a qualifi ed electrician to make sure that faults on circuits serving socket outlets or portable appliances cannot cause interruption to the supply to the heat alarms. Heat alarms may also be connected to a separate electrically protected, regularly used local lighting circuit. However, this will mean that, unless a separate means of isolation is provided for the heat alarms, it will be necessary to isolate the lighting circuit every time that there is a need to isolate the supply to the heat alarms; this may cause inconvenience or hazards.
6
1. Connect the heat alarm as per the fi gure below;
To fuse or circuit breaker
A
N
Terminals
Brown
Orange
I
Blue
HEAT
ALARM
755H
2. Close the cover over the terminal block supplied and fi x the junction box in place.
3. Open the battery compartment door. Connect a healthy 9V d.c. battery to the battery connector inside the battery compartment. Be sure the battery is securely connected. The heat alarm may beep briefl y when the battery is installed.
4. Close the battery compartment door, snapping it into place.
5. Attach the connector plug to the pins on the back of the heat alarm. The plug will only fi t one way, and will snap into place.
6. Gently tug the connector to be sure it is attached securely.
7. Position the heat alarm on the mounting plate and turn it clockwise to lock it into place.
8. Test the heat alarm to verify the 9V d.c., battery back-up. See “TESTING THE HEAT ALARM”. NOTE: The heat alarm will not mount the plate if the battery is not in place.
10. Turn on the power to the heat alarm circuit at the main distribution board.
11. Test the heat alarm for mains supply operation. See “TESTING THE HEAT ALARM”.
INTERCONNECTING HEAT ALARMS
Use 1.5mm2 minimum solid or stranded cable with a rating of 240V. When interconnecting heat alarms and / or Smoke Alarms, the maximum cable length between any two should be 450m for 1.5mm2 cable (20 ohm loop resistance.) This Heat alarm may be interconnected with as many as 39 other Clipsal Lifesaver 755 Series Heat and Smoke Alarms. Do not connect to any other type of model of Heat alarm or Smoke Alarm. Connect all interconnected Heat and Smoke Alarms to a single fi nal circuit. Connecting the switch wire terminal in any other way to that shown in this instruction may result in damage to the Heat alarm, failure to operate or an electrical shock hazard. It also voids the warranty.
7
FUSE OR
Brown
AI
Blue
N
A
N
I
Active
CIRCUIT BREAKER
Neutral
A
N
I
RED AND GREEN LED INDICATORS
This heat alarm features a red and green LED indicator that can be seen through the clear light pipe on the top of alarm. The LEDs indicate the following: GREEN ON - a.c. power is present. OFF- a.c. power is not present. RED BLINKS ONCE A MINUTE - d.c. power is present indicating normal operation. OFF- d.c. power is not present. BLINKS ONCE A SECOND and unit is sounding alarm - senses temperature of 73° to comply within the range of 58°C to 88°C per AS1603.3-1996. OFF and unit is sounding alarm - Another interconnected smoke/heat alarm in the network has alarmed.
TESTING THE HEAT ALARM WARNING, Test each heat alarm and smoke alarm to
be sure that each is installed correctly and is operating properly. Stand at arm’s length from the heat alarm when testing. The alarm sounder is loud to alert you to an emergency and can be harmful to hearing. Test the heat alarm weekly and upon returning from holiday, or when the house has been unoccupied for several days. Test all heat alarms weekly by doing the following:
1. Check the Test push-button. A constant ON green light indicates the Heat alarm is receiving a.c. power.
2. Firmly depress the Test push-button for at least fi ve (5) seconds. The Heat alarm will sound a loud beep. The alarm may sound for up to ten (10) seconds after the Push-to-Test button is released. NOTE: If heat alarms are interconnected, all heat alarms should sound an alarm within three (3) seconds after any Test button is pushed and the tested heat alarm sounds.
3. If the heat alarm does not sound, turn off the power to the heat alarm circuit at the main distribution board and check the wiring. Retest the heat alarm.
4. Do not apply excessive force to the Test push-button. Doing so may damage the unit and void the warranty.
5. Never use an open fl ame of any type to test the alarm. You may damage the alarm or set fi re to your home. Operating the Test push-button will check for correct functioning.
8
WARNING, If the heat alarm sounds, and the heat alarm is not being tested, the heat alarm is activated and requires your immediate attention and action.
MAINTENANCE AND CLEANING
1. If a zinc oxide or alkaline battery is used, the battery should be renewed at least once a year.
2. Heat alarms are virtually maintenance free. However, vacuuming the unit at least once every six months will remove dust.
3. Wipe the enclosure clean with a water moistened cloth. Do not immerse this unit or use household cleaners. Do not apply paint or spray with any liquid.
4. All Clipsal heat alarms are manufactured and tested to rigorous quality standards and have a minimum life expectancy of 10 years. However, for your safety we recommend replacing your Heat alarm with a new Clipsal unit after 10 years. This will ensure that you are always protected by a heat alarm that is operating within the limits of its life expectancy. DANGER, electric shock hazard. Turn off the a.c., supply to the heat alarm at the main distribution board by removing the fuse or switching the appropriate circuit breaker to the OFF position before replacing the battery or cleaning the heat alarm.
FITTING TAMPER PIN
A tamper resistant feature on the heat alarm may be used to precent unauthorised removal of the heat alarm from the mounting plate.
From the back of the heat alarm remove the mounting plate. Twist out and remove one of the pins moulded into the plate. (Both pins are exactly the same).
Position heat alarm to mounting plate and turn clockwise to lock into place. To engage tamper resist feature, insert pin into notch on edge of heat alarm.
Insert pin here
BATTERY REPLACEMENT
Always turn off the a.c., supply to the heat alarm before replacing the battery. Replace the battery at least once annually, or immediately when the low battery signal sounds once a minute, even though the heat alarm is receiving a.c. power. Use only the following batteries as replacements in this heat alarm: Eveready 216, 522, 1222, Duracell MN 1604 or Ultralife U9VL - J. The battery should only be relaced by a qualifi ed electrician or similarly qualifi ed person.
9
Warning. Do not use any other type of battery except as specifi ed in this manual. Do not use rechargeable batteries.
1. Turn off the a.c. power supply to the heat alarm at the main distribution board.
2. Turn the heat alarm counterclockwise to detach the alarm. (Remove tamper pin if fi tted.)
3. Gently pull down the heat alarm. Be careful not to separate any wire connections.
4. Pull out the connector plug from the back of the heat alarm.
5. Remove the battery from the compartment. Disconnect the drained battery from the battery compartment and discard.
6. Connect a new, healthy 9V d.c. battery to the connector. The battery will only fi t one way. Be sure the battery connector is securely attached to the battery terminals.
7. Place the battery into the battery compartment
8. Close the battery compartment door. Push down until it
snaps into place.
9. Using the Push-to-Test button, test the heat alarm to
verify 9V d.c. battery back-up. See “TESTING THE HEAT ALARM”.
10. Replace the connector plug. The connector will “snap”
into place. Gently tug the connector to be sure it is attached properly.
11. Reattach the heat alarm to the mounting plate by
turning the heat alarm clockwise until it snaps into place.
12. Turn on the a.c. power and test the heat alarm using
the Push-to-Test button. See “TESTING THE heat alarm”.
REPAIRS AND SERVICE
This heat alarm has no user serviceable parts. Dangerous voltages are contained within, so do not attempt to repair this unit yourself. Instead, this heat alarm should be returned to the supplier for service.
WHAT TO DO IF THE ALARM SOUNDS
1. Leave immediately, following your family’s escape plan.
2. As you leave, don’t open any inside doors without fi rst feeling its surface. If the door is hot, or if you see smoke coming through the cracks, do not open the door. Use an alternative exit.
3. If the inside of the door is cool, place your shoulder
against it, open it slightly and be ready to slam it shut if heat and smoke rush in.
4. If the air is smokey, stay as close to the fl oor
as possible.
5. Breathe shallowly through a cloth, which if possible
should be wet.
10
6. Once outside, go to your pre-selected assembly area and make sure everyone else is there.
7. Call the Fire Service from a neighbour’s home - never from your own.
8. Do not return to your home until fi re offi cials give you permission to do so. For further information on fi re safety, contact your local Fire Service.
TROUBLESHOOTING
To be carried out by a licensed electrician or similarly qualifi ed person.
PROBLEM
Heat alarm does not sound when tested. Push test button for at least fi ve (5) seconds while testing!
Heat alarm beeps about once a minute.
See “Battery Replacement”
Heat alarm sounds unwanted alarms.
Interconnected heat alarms do not sound when system is tested.
SOLUTION
1. Check that a.c. power is turned on.
2. Turn off power Remove heat alarm from mounting plate and:
a. Check that connector
plug is securely attached.
b. Check that battery is
properly attached to connector.
c. Vacuum heat alarm.
Turn off a.c. power and replace battery
in the “MAINTENANCE AND CLEANING” section.
Hire an electrician to move heat alarm to a new location. See the “HEAT
ALARM LOCATION” and “DO NOT INSTALL HEAT ALARMS” sections
of this manual.
1. Press and hold button for at least three seconds after the fi rst unit sounds.
2. Turn off a.c. power or circuit breaker and check the interconnect wiring.
See "INTERCONNECTING HEAT ALARMS" section of this manual.
11
F1516/ 02
2547 7 25
12
Loading...