KERR COMPACT-multi Installation, Operation And Maintenance Manual

COMPACT- multi
HIGH EFFICIENCY OIL-FIRED MULTI-POSITIONAL FURNACE
Installation, Operation and
Maintenance Manual
CODES THAT MAY DIFFER FROM THIS MANUAL
Please read this complete manual before beginning installation. These instructions must be kept with the furnace for future reference.
CERTIFIED TO: CAN/CSA Std. B140.0 & Std. B140.4 CONFORMS TO: UL 727
c/o Parrsboro Metal Fabricators Ltd. 12118 Hwy 209 PO Box 637 Parrsboro, Nova Scotia, Canada B0M 1S0
www.kerrheating.com
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
Table of Contents
1.0 Introduction 2
2.0 Homeowner Information 2
2.1 Air Filters 2
2.2 Regular Maintenance 2
2.3 Warnings 2
2.4 Direct Vent 2
2.5 Shutting Furnace Down 3
2.6 Restarting Furnace 3
3.0 Installation 3
3.1 Important 3
3.2 Caution 3
3.3 Installation Codes 4
3.4 Multi-Position 4
3.5 Placement, Venting & Ventilation 4
3.6 Installation 5
3.7 Assemble & Install Burner 6
3.8 Changing Nozzle 7
3.9 Set Burner for Efficient Operation 7
3.10 Blower Setting 8
3.11 Cooling – AC Models 8
3.12 Humidifier 8
3.13 Thermostat Anticipator Setting 8
3.14 Blocked Vent Switch 8
3.15 Fan Control 9
3.16 Combustion & Ventilation Air 9
3.17 Off Cycle Air Circulation 9
4.0 Comfort Adjustments 10
5.0 Regular Maintenance & Cleaning 10
6.0 Oil Tanks & Piping 11
7.0 Blower Removal 11
8.0 Burner Specifications 12
9.0 General Specifications 12
10.0 Trouble Shooting Guide 14
11.0 Appendix
K4C Compact-multi Feb-06
1
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
1.0 INTRODUCTION
Please read and understand this manual before installing, operating or maintaining the furnace. The K4C Compact-multi can be installed as a regular high
boy, in an upflow configuration, as well as horizontal and downflow. This appliance features an insulated cabinet, which greatly reduces operating noise. The “Quick Heat” heat exchanger ensures extremely fast warm up which provides heat on demand. This advanced system means savings on your home heating bills, fewer maintenance calls and a greater level of comfort. To ensure you have a clear understanding of the operating procedures of the appliance please take the time to read Section 2 (Home Owner Information) of this manual. If you have any questions, your KERR dealer will be happy to answer them for you.
2.0 HOME OWNER INFORMATION
2.1 AIR FILTERS
To maintain furnace performance and safety, replace dirty filters as required or at least once every heating season. Use new approved disposable filters of the same size and type, or clean permanent filters according to manufacturer’s instructions. Replace the filters or clean the filters more often if dusty conditions exist. Dirty, clogged or wrongly sized filters will impair the furnace performance and may cause the furnace to shut down or overheat.
2.2 REGULAR MAINTENANCE
Have qualified technician check complete furnace operation at least once a year.
2.3 WARNINGS
NEVER BURN GARBAGE OR PAPER IN THE UNIT AND NEVER STORE COMBUSTIBLE MATERIAL AROUND IT.
DO NOT ATTEMPT TO START BURNER WHEN EXCESS OIL HAS ACCUMULATED, WHEN UNIT IS FULL OF VAPOUR, OR WHEN HEAT EXCHANGER IS VERY HOT.
DO NOT USE GASOLINE, CRANKCASE DRAININGS OR ANY OIL CONTAINING GASOLINE.
2.4 DIRECT VENT
It is the responsibility of the homeowner to ensure that the area around the Direct Vent terminal and air intake is free of snow, ice, and debris. The vent terminal should be checked during heavy snowstorms to ensure proper operation.
K4C Compact-multi Feb-06
2
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
2.5 SHUTTING FURNACE DOWN
POWER OFF Turn off main power switch. FUEL OFF Shut off manual fuel supply valve.
Always keep manual fuel supply valve shut off if the burner is shut down for an extended period of time.
2.6 RESTARTING FURNACE
Follow this procedure before restarting a unit that has been shut down for an extended period of time.
INSPECTION Have the furnace/system serviced and inspected by a
qualified technician.
CHECK Furnace/system has not been tampered with. FUEL ON & CHECK Turn on fuel supply and check that there are no leaks. POWER ON & CHECK Turn on power switch and check that the furnace starts and
operates as usual.
CHECK If the furnace/system fails to operate or operates in an
unusual manner, call your service technician.
OPERATION If the burner fails to operate at any time, call a qualified
burner technician.
3.0 INSTALLATION
3.1 IMPORTANT
Read this instruction manual thoroughly before installing furnace or starting burner. Consult local authorities about your local Fire Safety Regulations. All installations must be in accordance with local state or provincial codes. Improper installation will result in voiding of warranty.
3.2 CAUTION
DO NOT START THE BURNER UNTIL ALL FITTINGS, COVERS AND DOORS ARE
IN PLACE. DO NOT TAMPER WITH THE FURNACE OR CONTROLS CALL A QUALIFIED BURNER TECHNICIAN. FOR YOUR SAFETY: DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPOURS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
K4C Compact-multi Feb-06
3
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
3.3 INSTALLATION CODES
INSTALLATION MUST COMPLY WITH THE REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. All local and national codes governing the installation of oil burning equipment, wiring, and venting must be followed. Some of the applicable codes are:
CAN/CSA B139 Installation Code for Oil Burning Equipment. NFPA 31 Installation Code for Oil Burning Equipment. ANSI/NFPA 90B Warm Air Heating and Air Conditioning Systems. ANSI/NFPA 70 National Electrical Code. CSA C22.1 Canadian Electrical Code. ANSI/NFPA 211 Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances.
The latest versions of the above codes, which have been approved for use in the location of the installation, must be used.
3.4 MULTI - POSITION
The Compact-multi is designed to operate in the conventional upflow mode, in horizontal mode or as a downflow furnace. The breech is convertible from front to rear by switching the breech pipe and cover plates. The burner is always installed in an upright position by four nuts.
3.5 PLACEMENT, VENTING & VENTILATION
Furnace installation should conform to the required installation code for oil-fired equipment (USA: NFPA 31, Canada: CSA B139).
UPFLOW The furnace may be placed on a combustible floor or, if required,
on four rigid blocks. The floor must be strong enough to carry the weight of the furnace.
DOWNFLOW Install the plenum and sub base as shown in the illustration
(included with sub base). For furnaces installed on a combustible floor, ensure that the requirements of the authorities having jurisdiction are satisfied. The floor must be strong enough to carry the weight of the furnace.
HORIZONTAL In suspended horizontal positions use the eyebolts provided in kit
(K4C-KA-0200-00). For installations where the furnace will be supported from below, use 4” long 3/8” UNC bolts as adjustable legs.
K4C Compact-multi Feb-06
4
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
CLEARANCES Before placing unit, review installation clearances as shown on
furnace operating label and “GENERAL SPECIFICATIONS”.
LOCATION Install the furnace close to chimney or vent and central to ductwork. BREECH Move the breech pipe to the rear if rear breech is required. CHIMNEY/VENT Connect the furnace to a chimney/vent system of size and condition
required by the installation code. Furnace is approved for factory built chimney type “A” or type “L” vent. See furnace-marking label for approved vent/flue pipe sizes. Maximum flue gas temperature is 575°F.
THROUGH THE Furnace is approved for Kerr Direct Vent. WALL VENTING
COMBUSTION & Install openings and ductwork to the furnace room to provide fresh VENTILATION AIR outside combustion air and circulation air for cooling the furnace
casing as installations code requires (USA: NFPA 31, Canada: B139). If installed in a closed room provide two free air ventilation openings of at least 8 x 12” (96sq. in.) free flow area near ceiling and floor. Oil burners must have sufficient air to allow vent systems to operate properly. See furnace operating label. Not applicable to Direct Vent.
3.6 INSTALLATION
ELECTRICAL Wire according to the National Electrical Code (Canadian Electrical
Code in Canada) or local codes. Use a separately fused #12 electrical line directly from the service panel to the furnace junction box. Install a manual shut off switch at the door or stairway to furnace room so furnace can be shut off remotely.
VENT PIPE See NFPA 31 (USA) or CSA B139 (Canada) code. Breech is
certified for 5” vent pipe. Keep vent/flue pipe as short as possible with min. 1/4” per foot upward slope. Use approved fitting through a wall. Vent/flue pipe MUST NOT pass through a ceiling.
BREECH The breech is convertible from front to rear by switching the breech
pipe with the cover plate and cabinet cover panels.
DRAFT CONTROL Use approved draft control supplied for 5” pipe. Use two draft
controls on strong draft chimneys. Set specified draft pressure to
-0.04” wc. Not applicable to Direct Vent installations.
FILTER The filter bracket can be moved from the left side to the right side or the LOCATION bottom of the furnace. See appendix.
UPFLOW The K4C Compact-multi is configured for upflow operation as
shipped.
K4C Compact-multi Feb-06
5
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
HORIZONTAL Horizontal operation requires a conversion kit (K4C-KA-0200-00)
with an additional fan limit. Four weld nuts (3/8 - 16 UNC) are concealed behind knockouts on either side of the furnace. Determine the appropriate side and remove the knockouts. Eyebolts complete with locking nuts are available. The locking nuts should be threaded on the eyebolt 3/4” to 1”. This provides a stop for the eyebolt.
DOWNFLOW Downflow operation requires a conversion kit (K4C-KA-0200-00)
with an additional fan limit. A sub base (K4C-KA-0500-00) is required to support the furnace. This sub base maintains the clearances to combustible materials through the floor and provides a convenient attachment to the plenum.
COMBINATION The K4C Compact-multi can be used with the Scotty SS providing
the 0.60 US gph nozzle is used. This will ensure that adequate air circulates through the Scotty SS. Set blower speed to high. The factory settings for both of the fan limit controls should be:
FAN OFF - 100°F FAN ON - 130°F. If the K4C is used in a down
flow position with the Scotty SS a diverter base is available for easier duct connections. (K4C-KA-0400-00)
3.7 ASSEMBLE & INSTALL BURNER
ASSEMBLE BURNER Check burner model is correct for furnace rating required.
Assemble as per burner manufacturer’s instructions.
SET END CONE Riello - Set turbulator as per furnace operating decal.
Beckett – See Burner Manufactures Instructions.
SELECT NOZZLE Select oil input, nozzle required and burner configuration as
shown on furnace operating decal.
INSTALL NOZZLE Install selected nozzle, check for clean seating and tighten in
nozzle adaptor.
CHECK ELECTRODES See burner manufacturer’s instructions for correct setting. INSERTION LENGTH See “GENERAL SPECIFICATIONS” or diagram (Fig. 1). MOUNT BURNER Tighten top nut first so burner tips down slightly. The burner
is always installed in an upright position by four nuts.
PUMP BY-PASS PLUG For one pipe system factory setting (no plug). COMPLETE WIRING Refer to wiring diagram or furnace label for correct burner
connections. Riello 40F3 and BF3 burners use the Honeywell R8038 thermostat relay or Riello LT-1 relay.
THERMOSTAT Connect thermostat terminals.
K4C Compact-multi Feb-06
6
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
3.8 CHANGING NOZZLE
NOZZLE CHANGE If a new nozzle of a different size is installed, change the
heating blower speed according to the specifications table.
3.9 SET BURNER FOR EFFICIENT OPERATION
SET END CONE Set turbulator to furnace operating decal settings.
Particularly if you change nozzles.
PUMP PRESSURE Refer to “BURNER SPECIFICATIONS” or operating decal. BURNER AIR Set air damper as settings on operating decal. SAMPLING HOLE On smoke/vent pipe, between appliance breech and draft
control, punch or drill a 1/4” round opening. Not applicable to Direct Vent.
DRAFT PRESSURE Using an accurate draft meter, adjust the draft control to
obtain -0.04” wc draft pressure at the breech sampling hole. Use two barometric dampers if necessary. Not applicable to Direct Vent.
BURNER SETTING Set the burner to give a stable symmetrical flame. After 15
minutes of normal operation, check SMOKE for #0-trace reading and measure CO
required.
EFFICIENCY Always leave burner set with CO2 reading about 1% of CO2
lower than the peak efficiency achieved with a #0-trace smoke (e.g. a #0-trace reading of 12.5% CO2 should be set
back 1% to 11.5%). This gives better allowance for fuel and draft variations and maintains a better seasonal efficiency. When the burner is set, lock the adjustments with the locking nuts.
FLAME CHECK Look through view port to check the flame after setting the
burner. If the flame is not clean and symmetrical, reset the burner or replace the nozzle, use only nozzle types specified on settings label.
Always set flame with proper draft, smoke and CO
DO NOT START BURNER UNTIL ALL FITTINGS AND COVERS ARE IN PLACE.
Re adjust the burner controls as
2.
measurements.
2
K4C Compact-multi Feb-06
7
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
3.10 BLOWER SETTING
Ensure power is off when adjusting blower setting. For heating, use the blower
speeds shown on the furnace specifications to give a rise of 70 - 85°F. The #4 Lo blower speed can be used for air circulation when neither heating nor cooling are required. Set blower speeds to match the installation requirements. AC models include a fan centre relay wired to run the blower at #1 Hi speed when the cooling cycle is operating. For normal operation select “AUTO” on the T87F thermostat. When “FAN ON” is selected the blower runs constantly at the cooling speed. See “OFF CYCLE AIR CIRCULATION” section.
3.11 COOLING – AC MODELS
AC models include a fan centre relay wired to run the blower at #1 Hi speed when the cooling cycle is operating. For normal operation, select “AUTO” on the T87F thermostat. When “FAN ON” is selected the blower runs constantly at the cooling speed. See “OFF CYCLE AIR CIRCULATION”. Height of the coil above the heat
exchanger shall be no less than 4” (100 mm).
3.12 HUMIDIFIER
If a humidifier is installed ensure that no water can drip or run from it into the furnace. This would cause deterioration and void the furnace warranty.
3.13 THERMOSTAT ANTICIPATOR SETTING
0.2 amps for any burner. Check that the thermostat anticipator setting matches the primary control circuit current draw. This setting affects the thermostat’s response to the control.
3.14 BLOCKED VENT SWITCH
ONLY APPLICABLE TO CANADA NOT APPLICABLE FOR DIRECT VENT SYSTEMS
SWITCH The blocked vent switches are flue gas spillage safety devices. They OPERATION detect spillage of flue gas products due to a clocked flue system or
inadequate draft. The switch senses the spillage of hot flue gases and de-energizes the system’s burner control. NEVER reset the blocked
vent switch, unless the cause of the blockage has been corrected.
INSTALLATION
1. Pierce a 5/8” hole into the flue vent pipe near the appliance breech connection.
2. This hole must be at least 10” before the draft regulator, vertically or horizontally.
3. Remove one of the securing nuts from the threaded tube of the safety switch.
4. Tighten the other securing nut onto the pipe as far as possible.
5. Insert the threaded tube end into the pierced hole of the flue vent pipe.
6. Install the securing nut on the safety switch tube, which protrudes into the flue vent pipe. Tighten the nut securely.
K4C Compact-multi Feb-06
8
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
UNIT WIRING Caution: Disconnect the electrical power when wiring the unit. INSTRUCTIONS Wire the blocked vent switch in accordance with The National
Electrical Code and applicable local codes. Wire the safety switch in series with the burner limit control or aquastat. See the appliance-wiring diagram in the manual or wiring label. Route the wiring with an accepted wiring enclosure in accordance with The National Electrical Code and applicable local codes.
SYSTEM TEST PROCEDURE
1. With the power re-established, block the chimney or vent pipe down stream of
the switch.
2. Adjust the thermostat to call for heat.
3. Once the heating system has started the blocked vent switch should shut down
the burner with 10 minutes or sooner.
4. Once the system has cooled, the blocked vent switch can manually be reset.
5. This procedure should be tested a second time.
6. After testing the blocked vent switch the chimney should be cleared of
obstruction and the heating system tested on a long run cycle.
7. If the block vent switch shuts down the system check to ensure there is enough
draft in the chimney and venting pipes.
3.15 FAN CONTROL
LIMIT 200°F - Factory set FAN ON 130°F FAN OFF 100°F
3.16 COMBUSTION & VENTILATION AIR
Install openings and ductwork to the furnace room to provide fresh outside combustion air and circulation air for cooling the furnace casing as installation code requires (USA: NFPA 31, Canada: CSA B139). If installed in a closed room, provide two free air ventilation openings of at least 8” x 12” (96sq. in.) free flow area near ceiling and floor. Oil burners must have sufficient air to allow vent systems to operate properly. Not applicable to Direct Vent.
3.17 OFF CYCLE AIR CIRCULATION
#4 LO SPEED All furnace models have the #4 Lo speed switch for optional
constant air circulation during the furnace off cycle.
“FAN ON” When “FAN ON” is selected on the T87F thermostat, the blower will
run constantly at the #1 Hi speed providing heat, cooling or neither as selected.
K4C Compact-multi Feb-06
9
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
4.0 COMFORT ADJUSTMENTS
?? Outlet air is initially too warm or too cold - adjust the “FAN ON” setting. ?? Outlet air consistently too warm or too cold - change the blower motor speed to
give the specified air temperature rise (70 - 85°F).
?? Blower motor shuts off and the oil burner keeps going - the “FAN ON” setting is
set too low or the inlet air is below 50°F.
?? Outlet air gets too warm and burner shuts down - increase air by changing the
blower motor speed to give the specified temperature rise (70 - 85°F).
?? Outlet air is too warm or too cold at the end of the heating cycle after the burner
has turned off - adjust the “FAN OFF” time higher or lower.
5.0 REGULAR MAINTENANCE & CLEANING
Check complete operation at least once a year. In Canada see B139, Section 14, Maintenance, for recommended servicing procedure. Heat exchanger ducts are accessed through breech access panel at front of unit. Replace stainless steel gas baffles after cleaning. Cerafelt (1/4”) gaskets may have to be replaced.
K4C Compact-multi Feb-06
10
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
6.0 OIL TANKS & PIPING
Tank installation must conform to local requirements.
Install according to the applicable code. Minimize number of connections in suction line and make all connections as tight as possible. Use a pipe joint compound suitable for oil on all pipe threads. To reduce possibility of air leaks, tighten stem packing gland nut on any valves installed in the suction line. Also, be sure the oil filter is tight, as filter gaskets often shrink. Check for kinks in the oil lines as well as for possible air pockets and for loose connections. Two filters as shown below are recommended. Further information is available at www.kerrheating.com.
ONE PIPE SYSTEM Where the tank is above the burner and when the oil flows
by gravity to the oil pump, a single-stage fuel unit with a single oil line to the pump may be used.
TWO PIPE SYSTEM When single line is unsuitable, use double line or see your
KERR dealer for special oil line fittings.
7.0 BLOWER REMOVAL
Use a reversing drill with 1/4” hex drive for the sheet metal screws. The KERR K4C Compact-multi has a quick release blower suspension system that is
designed to be tight and rattle free. a. Remove front panel to blower compartment.
b. Remove the screw (s) from the blower key. (Figure -2A) c. Remove the blower key and slide the blower towards the burner. (Figure -2B).
Replace the blower assembly using the reverse procedure. See diagram. DO NOT start the oil burner until installation is complete and all cleanout covers are secured in place.
K4C Compact-multi Feb-06
11
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
8.0 BURNER SPECIFICATIONS
Model Burner
Input Pump Output Heating cfm@ Blower Speed
Nozzle
USGPH L/h
(psi)
Air
Setting
Turbulator
Btu/h kW 0.2"wc 0.5"wc 0.2"wc 0.5"wc
K4CE-090(A3) Riello 40 F3
K4CG-090(A3)
Direct Vent
K4CV-090(A3) Riello BF3
K4CD-090(A3)
Beckett AFG
PA402
Beckett AFG
PA404*
0.61 2.31 0.50 80B 150 2.8 0 74,000 22 990 990 4 3
0.73 2.76 0.60 60W 150 3.5 0.5 88,000 26 1180 1090 3 2
0.59 2.23 .50 70/45B 140 6.5/0.0** 71,000 21 990 990 4 3
0.71 2.69 .60 70/45 B 140 5.0/0.0 84,000 25 1180 1090 3 2
0.61 2.31 0.50 80W 150 5.0 0.5 74,000 22 990 990 4 3
0.73 2.76 0.60 60W 150 6.0 1.5 88,000 26 1180 1090 3 2
0.59 2.23 .50 70/45 B 140 55** *** 70,000 21 990 990 4 3
0.71 2.69 .60 70/45 B 140 60 *** 84,000 25 1180 1090 3 2
* Post purge factory set to two minutes. ** Low firing rate baffle. Beckett air shutter/air band. *** Use Air Boot Flow Restrictor.
Use Delavan nozzles - Use turbulator and air settings as a guide. Set flame to #0-1 smoke before CO2 test.
When there is a discrepancy between the information from the burner manufacturer and Kerr Heating Products, the Kerr data shall be used.
9.0 GENERAL SPECIFICATIONS
CLEARANCE TO COMBUSTIBLES UPFLOW/DOWNFLOW POSITION
Top 1” (25 mm) Front 24” (610 mm) Rear - Front Breech 2” (51 mm) Rear - Rear Breech 24” (610 mm) Side - Non-Access 2” (51 mm) Side - Access 24” (610 mm) Return Air Side - Ductwork 1” (25 mm) Flue Pipe 9” (229 mm) Floor Combustible (Upflow only) (Downflow must have sub-base, K4C-KA-0500-00)
K4C Compact-multi Feb-06
12
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
Horizontal Position
Top 6” (152 mm) Front 24” (610 mm) Rear - Front Breech 6” (152 mm) Rear - Rear Breech 24” (610 mm) Side - Non-Access 6” (152 mm) Side - Access 24” (610 mm) Return Air Side - Ductwork 1” (25 mm) Flue Pipe 9” (229 mm) Floor 6” (152 mm)
DRAFT PRESSURE
Breech draft pressure -0.04” wc Overfire draft pressure
-0.01” wc (Not Applicable to Direct Vent Units)
BURNER INSERTION (overall) Riello 40F3 - BF3 & Beckett PA402 - 404 2 1/2” (63 mm)
AIR/BLOWER DATA External static - Non – AC 0.2” wc External static - AC 0.5” wc Cooling 3 tons Maximum air temperature rise 85°F High Limit, max design outlet temp. 200°F Thermostat anticipator 0.2 amps
MOTOR/BLOWER 1/3 HP 4 Speed/GT 10 DD FAN/HIGH LIMIT CONTROL
Honeywell L6064A1037 or L6064B1003, 11” FAN CENTRE RELAY – AC models only
Honeywell R8285A1048 White Rodgers 8A05A-101
DIMENSIONS
Depth 22 7/8” (581 mm) Height 44 1/4” (1124 mm) Width 19 1/2” (495 mm)
PLENUM DIMENSIONS
Cold air return 18 x 14 5/8” (457 x 371 mm) Hot air supply 18 1/4 x 21 5/8” (464 x 549 mm) Height to plenum 44” (1118 mm)
AC COIL LOCATION
Minimum height above the heat exchanger 4” (100 mm)
K4C Compact-multi Feb-06
13
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
OPENING HEIGHTS (from floor) Burner c/l 24” (610 mm) Smoke pipe c/l 37” (940 mm)
SMOKE/VENT PIPE
5” Chimney 4” Direct Vent
CLEANOUTS
Front covers, Burner opening, Front/Rear cover plate
AIR FILTERS Pleated 16” x 20” x 1” FUEL not heavier than No. 2 furnace oil. ELECTRICAL - 120 Volts, 60 Hz
Canada Less than 12 amps. US 13.3 amp, circuit protection 20 amps.
This furnace has been tested to, and meets the requirements of B212-93 Seasonal Energy Utilization Efficiencies of Oil-Fired Furnaces & Boilers & the Energy-Efficient Appliances Act of 1991.
Certified for use with Type “L” & Type ”A” vent – maximum flue gas temperature 575°F. Certified for use with Kerr Direct Vent. Certified for use with Kerr KPV-SS1C through-the-wall mechanical vent system.
10.0 TROUBLE SHOOTING GUIDE
Furnace will not start
Tripped blocked vent switch Clear vent, reset switch. Tripped breaker Determine cause, reset breaker. No oil Check tank for leaks and call oil supplier.
Oil burner keeps turning off
Dirty air filter Change air filter. Restricted air supply/return Check all air return/supply registers. Limit control Check ductwork for blockage. Motor over heating Check motor speed correct for nozzle on furnace
label settings.
Dirty nozzle Call technician to replace nozzle.
Sooty flame
Wrong pump pressure Increase or decrease pressure to correct setting. Dirty nozzle Replace nozzle. Improper burner setting See “BURNER SPECIFICATIONS. Barometric draft wrong Adjust barometric regulator for -0.04” wc draft
pressure at breech.
K4C Compact-multi Feb-06
14
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
Using too much oil
Oil leak in line or tank Check fittings for tightness. Inspect tank and replace
if necessary.
Draft regulator set high Adjust regulator for -0.04” wc draft pressure at
breech.
Nozzle too large Replace nozzle to lower input.
Burner reset cuts out
No oil Call oil supplier. Frozen oil line Call technician or oil supplier. Dirty oil filter Replace filter. Dirty nozzle, smoky fire Replace nozzle, adjust burner air. Faulty oil pump Have pump replaced, adjust burner air. Faulty or dirty electrodes Have technician clean or replace.
Warm air register blowing cold air
Basement cooling ducts Insulate and seal ductwork to maintain duct
temperature. Ducts running through Change or insulate ductwork. unheated spaces Low speed switch is on Switch off blower low speed. “FAN OFF” set low Fan control – Set “FAN OFF” higher. Motor speed set too high Reset motor speed to slow blower.
Warm air registers blowing too hot
Blower running slow Speed blower up. Return air restricted Open up return air ductwork to ensure adequate air
flow. Nozzle too large Lower nozzle size to suit ductwork.
All rooms at different temperatures
Supply air not regulated Adjust warm air regulators to suit each room. Return air not regulated Check for sufficient return air.
Noisy operation
Loose blower wheel Tighten wheel set screw or replace. Blower wheel hitting housing Center wheel in housing. Damaged motor bearings Replace blower motor. Faulty oil pump Repair or replace oil pump. Reset to correct
pressure. Air leak in oil line Tighten all connections. Vacuum too high on pump Check pump vacuum. Check filters and pump
screen.
K4C Compact-multi Feb-06
15
K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
Installed by: ____________________________________________________________________________________________ Address: _______________________________________________________________________________________________
Telephone: ____________________________________ Date: __________________________________________________
START UP TEST RESULTS Nozzle: ________________________________________ Pressure: _______________________________________________ Air: ____________________________________________ Turbulator: ______________________________________________ CO2: ___________________________________________ Smoke Number: __________________________________________ Breech Draft: ____________________________________ Stack Temperature: _______________________________________ Test Performed By: ________________________________________________________________________________________ Staple Printout Here: Staple Smoke Spot Here:
K4C Compact-multi Feb-06
16
K4C Compact-Multi Oil Fired Furnace
Item No. Part Description
K4C-1 Smoke Pipe Collar K4C-2 Wiring Box Cover K4C-3 Wiring Box K4C-4 Cabinet Cleanout Cover (W/ Hole) K4C-5 Fanlimit Standoff Bracket K4C-6 Top Front Panel Assembly K4C-7 Lower Front Panel Assembly K4C-8 Smoke Pipe Flange Assembly
K4C-9 Cleanout Cover Plates (Set) K4C-10 Filter Frame Assembly K4C-11 Lower Side Panel
K4C-12A Top Side Panel Assemblies Left
K4C-12B Top Side Panel Assemblies Right
K4C-13 Heat Exchanger Assembly K4C-14 Rear Gap Filler K4C-15 Rear Panel Assembly K4C-16 Breech Cover K4C-17 Rear Cabinet Cleanout Cover (No Hole) K4C-18 Divider Assembly K4C-19 Base Pan K4C-20 Blower Key K4C-21 Delhi GT10 DD Blower K4C-22 Motor Run Capacitor (5 micro farad)(Not Shown) K4C-23 Motor 1/3 G.E. 5KCP39KGT192S K4C-24 Blower /Motor Assembly K4C-25 Sight Glass (Not Shown) K4C-26 Sight Glass Ring (Not Shown) K4C-27 Cleanout Cover Plate Gasket Set (Not Shown) K4C-28 Smoke Pipe Flange Gasket (Not Shown) K4C-29 Secondary Heat Exchanger Baffle - each (Not Shown) K4C-30 Fan Center Relay R8285A1006B (A/C Models) K4C-31 Fan/High Limit Control L6064A1003B (Not Shown) K4C-32 Riello R8038A1055B Switching Relay K4C-33 BF3 Riello Burner (Short) Direct Vent K4C-34 40F3 Riello Burner (Short) K4C-35 AFG-70 MB Beckett Burner PA#402 K4C-36 AFG Beckett Burner PA#404 (Direct Vent) K4C-37 Riello LT1 24v Switching Relay(Factory burner relay)