Keri Systems IRP-1 User Manual

IRP-1: Isolation Relay Package

1.0 Purpose

The PXL-250 Tiger Controller, SB-293 Satellite Board, PXL-100 Smart Entry Controller, and SM­2000 IntelliProx Single Door Controller are designed with built-in voltage transient suppression. For most applications, this build-in protection is more than adequate - additional protection is not required. However, there are two applications that can require additional protection.
1. magnetic locking devices or dry-contact devices without built-in suppression (typically older models)
2. magnetic locking devices that draw large amounts of current (typically older models or defective devices)
For these applications, the IRP-1 should be used to isolate the PXL-250, SB-293, PXL-100, or SM­2000 from the transients these magnetic locking devices can generate, ensuring reliable operation of the controller.

2.0 Contents

The IRP-1 is made up of the following items.
one printed circuit board containing an isolation relay, diode, and connector strip
one transient suppression device (1.5KE39C nonpolarized transorb)
double sticky-sided foam tape (for mounting)

3.0 Specifications

The IRP-1's relay is rated as follows.
7 Amps max. @ 30 VDC 12 Amps max. @ 125 VAC

4.0 Application

There are two primary applications for the IRP-1. It can be used with an external locking device (such as a magnetic lock or door strike) or with a dry-contact device (such as a switch or relay controlling a motor for a parking barrier or power gate). The wiring diagram is different for these two applications. Figures 1, 3, and 5 are wiring diagrams for adding an IRP-1 to an external locking device. Figures 2, 4, and 6 are wiring diagrams for adding an IRP-1 to a dry-contact device.
Install the IRP-1 as shown in Figures 1 through 6 to meet your application's requirements. If the application uses either 12 VDC or 24 VDC, install the supplied transorb as near to the external locking device or dry-contact device as possible. Do not install the transorb if the device is being powered with greater than 30 VDC.
IRP-1Quick Start Guide
2305 Bering Drive 01833-001 Rev. G San Jose, CA 95131 USA (800) 260-5265 (408) 435-8400 FAX (408) 577-1792 Web: www.kerisys.com E-mail: sales@kerisys.com Page 1 of 4
IRP-1: Isolation Relay Package
Quick Start GuideIRP-1
Figure 1: Adding an IRP-1 to an External Locking Device - PXL-250/SB-293 Configuration
Figure 2: Adding an IRP-1 to a Dry-Contact Device - PXL-250/SB-293 Configuration
2305 Bering Drive 01833-001 Rev. G San Jose, CA 95131 USA (800) 260-5265 (408) 435-8400 FAX (408) 577-1792 Web: www.kerisys.com E-mail: sales@kerisys.com Page 2 of 4