INSTRUCTION SHEET
KEPCO
An ISO 9001 Company.
CABLE
KIT
219-0446
CABLE KIT NO. 219-0446
BOP 1000W MODELS (3) IN PARALLEL
I. DESCRIPTION.
This kit contains the cables and terminations required to operate three identical 1000 Watt BOP High Power models in parallel, effectively multiplying the output current capacity by three. Only identical models may be configured to operate in parallel.
This kit can be used with all 1000W BOP models that have revision levels as shown in Table 1. Earlier models
!
that have been upgraded to permit multiple unit configurations must include the letter “A” following the revision
number. CAUTION: Failure to install the ground cables supplied can result in damage to the power supply.
Refer to the associated technical manual supplied with the High Power BOP power supply for all instructions
regarding installation and operation of multiple units in parallel.
TABLE 1. REVISION LEVELS APPLICABLE TO THIS KIT
MG Model Revision
BOP 6-125MG All All
BOP 10-75MG 5 or higher 3A or 4A
BOP 20-50MG 8 or higher 5A, 6A or 7A BOP 20-50GL All
BOP 25-40MG All All
BOP 36-28MG 11 or higher 8A, 9A or 10A
BOP 50-20MG 7 or higher 5A or 6A BOP 50-20GL All
BOP 72-14MG 7 or higher 6A
BOP 100-10MG 6 or higher 2A or 4A
Revisions for previously Upgraded
Units (Must include “A”)
GL Model Revision
II. SPECIFICATIONS
Table 3 lists the model parameters unique to a parallel combination of three identical 1000W BOP Power Supplies. Table 4 lists the general specifications for the parallel combinations listed in Table 3. For specifications not
listed in Table 3, refer to the General Specifications provided in the associated technical manual supplied with
each 1000W BOP power supply
Item Quantity Purpose Kepco P/N
Common power cable, **
(1.5 ft.)
Common power cable, **
(3 ft.)
Output Power cable,
(1.5 ft.)
Output Power cable,
(3 ft.)
Digital Control (Bitbus) Cable,
(3 ft)
** For GL units: Unclamp and remove ferrite from cable before installation.
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
©2012, KEPCO, INC
Data subject to change without notice
TABLE 2. EQUIPMENT SUPPLIED
1 Connects the COMMON terminal Master to the COMMON terminal of Slave
#1.
1 Connects the COMMON terminal Master to the COMMON terminal of Slave
#2.
1 Connects the OUTPUT terminal of Master to the OUTPUT terminal of Slave
#1.
1 Connects the OUTPUT terminal of Master to the OUTPUT terminal of Slave
#2.
1 Provides communication between master and two slaves 118-1148
http://www.kepcopower.com email: hq@kepcopower.com
228-1526 REV 3 062712
118-1129
118-1153
118-1112
118-1152

TABLE 2. EQUIPMENT SUPPLIED (CONTINUED)
Item Quantity Purpose Kepco P/N
Parallel Control Cable
(1.5 ft.)
Protection Cable
(1 ft.)
Master - IN Parallel Control
Termination
Protection - OUT Termination
(Slave)
Protection - IN Termination
Ground Cable mounting hard-
(Master)
Nut 2
Chassis Ground Cable 2 Connects chassis ground terminals of all units. 118-1272
3 sets Each set consists of eight parts, mounted in the following order: No. 10 star
ware
Instruction Manual 1
Provides control signals required for parallel operation.
2
Provides interlock protection signals required for multiple unit operation.
2
Provides proper termination for Parallel Control Cable.
1
Provides proper termination for the slave connection to the Protection Cable.
1
Provides proper termination for the master connection to the Protection
1
Cable.
Overcomes tight space for output cable connections. After securing bottom
cable to output terminal stud using one nut, additional cables can be oriented
for best layout and secured with separate nut.
lockwasher P/N 103-0106 (at chassis), No. 10 flat washer P/N 103-0031, No.
10 split lockwasher P/N 103-0033, 10-32X3/8 nut P/N 102-0008, No. 10 flat
washer P/N 103-0031, [lug(s) from ground cable], No. 10 flat washer P/N
103-0031, No. 10 split lockwasher P/N 103-0033, and 10-32X3/8 nut P/N
102-0008.
Lists material supplied and specifications for multiple unit combination.
118 -1119
118- 1126
195-0109
195-0108
195-0107
102-0046
228-1526
(See
Purpose
at left for
part
numbers)
TABLE 3. MODEL PARAMETERS FOR THREE (3) IDENTICAL BOP 1000 WATT UNITS (PARALLEL)
(3) Identical Models
(Parallel)
BOP 6-125MG ±6V d-c ±375A d-c 0.6 37.5
BOP 10-75MG ±10V d-c ±225A d-c 1.0 22.5
BOP 20-50MG ±20V d-c ±150A d-c 2.0 15.0
BOP 25-40MG ±25V d-c ±120A d-c 2.5 12.0
BOP 36-28MG ±36V d-c ±84A d-c 3.6 8.4
BOP 50-20MG ±50V d-c ±60A d-c 5.0 6.0
BOP 72-14MG ±72V d-c ±42A d-c 7.2 4.2
BOP 100-10MG ±100V d-c ±30A d-c 10.0 3.0
d-c Output Range Closed Loop Gain
E
O Max
I
O Max
Voltage Channel
(V/V)
Current Channel
(A/V)
TABLE 4. GENERAL SPECIFICATIONS FOR FIVE (5) IDENTICAL BOP 1000 WATT UNITS (PARALLEL)
SPECIFICATION RATING/DESCRIPTION CONDITION
INPUT CHARACTERISTICS
Current 176 Va-c 28.5A a-c maximum
264 Va-c 19.2A a-c maximum
Leakage current 10.5mA a-c 230V a-c, 47-63 Hz
OUTPUT CHARACTERISTICS
Programming
resolution / accuracy
Readback
resolution / accuracy
Voltage 14 bits / 0.2% 2% accuracy for Ext Ref Level. Unit gain
Current 14 bits / 0.5%
Voltage Limit
Current Limit
12 bits / 0.5%
12 bits / 0.5%
adjustable between 0 and E
ONOM
/10 (current).
or I
ONOM
Voltage 16 bits / 0.2% main or limit channel
Current 16 bits / 0.5% main or limit channel
/10 (voltage)
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000
FAX (718) 767-1102 email: kepcopower@aol.com
2 228-1526 REV 3 062712