KEPCO KIT 219-0445 User Manual

INSTRUCTION SHEET
KEPCO
An ISO 9001 Company.
CABLE
KIT
219-0445
CABLE KIT NO. 219-0445
BOP 1000W MODELS (2) IN PARALLEL
I.
DESCRIPTION.
This kit contains the three cables, Power Output, Bitbus and Master/Slave Control, required to operate two 1000 Watt BOP High Power models in parallel, effectively doubling the output current capacity. Only two identical models may be configured to operate in parallel. Table 1 lists the equipment supplies in this Kit.

TABLE 1. EQUIPMENT SUPPLIED

Item Purpose Kepco Part Number
Connects the power output terminals of the slave unit (OUT
Power Output Cable
Master/Slave
Control Cable
and COMMON) to the corresponding power output terminals of the master.
Connects the slave control ports of the master and slave for parallel operation.
118-1112
118-1107
Bitbus Cable Allows communication between Master and Slave via Bitbus 118-1108
Instruction Manual
This manual is arranged as follows:
Section I lists the equipment supplied.
Section II explains how to install the cables and configure the two units to operate in parallel, including initial calibration.
Section III describes how to calibrate a previously installed parallel configuration.
Section IV lists the specifications for the parallel combination.
Section V provides special operating instructions for the parallel combination.
II.
INSTALLATION.
Provides installation and operation instructions for operating two 1000W BOP models in Parallel
WARNING
BE SURE ALL POWER IS DISCONNECTED FROM
POWER SUPPLIES BEFORE INSTALLING CABLES
228-1472
KEPCO, INC. " 131-38 SANFORD AVENUE " FLUSHING, NY. 11352 U.S.A. " TEL (718) 461-7000 " FAX (718) 767-1102
©2003, KEPCO, INC Data subject to change without notice
228-1472 REV 3 091903
email: hq@kepcopower.com
NOTE: The following procedure assumes that both individual units are properly calibrated. If not, refer
to the associated technical manuals to calibrate the individual units prior to connecting them as a parallel pair. Perform all calibration steps for both master and slave unit.
1. Before powering up the parallel combination, connect the Power Output, Bitbus, and Master/ Slave Control cables (supplied) to the master and slave units in parallel star type configuration (load connected to the master output) as shown in Figure 1 for local sensing or Figure 2 for remote sensing. Always remove link between COM and COM S terminals for the slave. For a master configured for remote sensing, remove both links between OUT and OUT S and between COM and COM S terminals.
CAUTION:The connectors of the Master/slave Control cable are marked Master and Slave.
Make sure these are installed properly. Installing the cable backwards (cable con­nector marked MASTER installed in a slave, cable connector marked SLAVE installed in a master) can cause irreparable damage.
NOTE: To power down the combination, first press the STANDBY key on the master to disable the
output, then turn off the slave followed by the master.
2. To configure the unit to be designated as a slave proceed as follows:
a. Turn on power only to the unit to be designated as a slave.
b. From the main screen (power on default), press
to enter the Settings Menu.
%
c. From the Settings menu, gain access to the Protected Settings menu by first entering the
password. Scroll through the password characters using to select the character position, then press ENTER. The status message changes to
tected settings enabled
ter and
d. Press
or ADJUST control to fix it, or press CLEAR to start over.)
U
to enter the Protected Settings Menu.
$
e. From the Protected Settings menu, highlight
keys) and press ! to modify. Highlight
U
f. From the Protected Settings menu, under
modify. Highlight
Parallel
. (If unsuccessful, use T or R to highlight the incorrect charac-
Unit Type
SLAVE #1
Unit Type
and press ! apply the change.
and press ! to apply the change.
g. Exit the Protected Settings menu and return to main screen by pressing
tings upon power-up. The unit goes to REMOTE mode, the status message reads
Module not found
, the Fault indicator is lit, and the unit continues to beep once a minute
until the master is found. The only function key displayed is
or ADJUST control and T or
U
(use ADJUST control or the Y or
highlight
Expansion
- LOCAL.
!
and press ! to
to save the set-
$
MASTER
R
Pro-
CAUTION: The unit has now been properly configured as a slave to be controlled only by the
master. Do not use the slave keypad, RS 232 port or GPIB port to try to control the slave.
KEPCO, INC. " 131-38 SANFORD AVENUE " FLUSHING, NY. 11352 U.S.A. " TEL (718) 461-7000
FAX (718) 767-1102 " email: kepcopower@aol.com
2
228-1472 REV 3 091903
FIGURE 1. INTERCONNECTIONS FOR PARALLEL OPERATION OF TWO (2) BOP HIGH
POWER MODELS USING LOCAL SENSING
FIGURE 2. INTERCONNECTIONS FOR PARALLEL OPERATION OF TWO (2) BOP HIGH
POWER MODELS USING REMOTE SENSING
KEPCO, INC. " 131-38 SANFORD AVENUE " FLUSHING, NY. 11352 U.S.A. " TEL (718) 461-7000
FAX (718) 767-1102 " email: kepcopower@aol.com
091903 228-1472 REV 3
3
3. Turn on the unit to be configured as a master and note that upon power up the FAULT light will go on (this is normal). Proceed as follows:
a. From the main screen, press
to enter the Settings Menu.
%
b. From the Settings menu, gain access to the Protected Settings menu by first entering the
password (see Step 2c above).
c. From the Protected Settings menu, highlight
keys) and press ! to modify. Highlight
d. From the Protected Settings menu, under
modify. Highlight
Parallel
and press ! to apply the change.
e. Exit the Protected Settings menu by pressing
Unit Type
Master +1
Unit Type
to test the system and to save the settings
$
(use ADJUST control or Y or
and press ! to apply the change.
highlight
Expansion
and press ! to
U
for subsequent power-up cycles. The display shows the master power-up screen (see Fig­ure 3).
NOTE: Pressing
to exit will cause the unit to revert to a standalone unit.
%
f. The power-up master module screen (Figure 3) changes to show the status of Slave 1 (see
Table 2).
If the slave is recognized as ready, after about 10 seconds the master LCD reverts to the
Power On Default screen (see Figure 4). The slave also displays the Power On Default screen (see Figure 5), except the unit will be in Current Mode, no function keys are active and the Status message at the bottom is
KPAD Locked
, indicating the keypad is disabled.
The fault indicators on both units are off.
If the master power-up screen is still displayed after 10 seconds, the slave was not properly
recognized. Pressing
or turning power off, then on again, reconfigures the unit as a stan-
%
dalone unit. Verify that the BITBUS cable is installed correctly. Verify that the slave has been properly configured as a slave per step 2 above. Repeat step 3. If the power up screen still does not revert to the power on default screen, refer to troubleshooting.
VOLTAGE
CURRENT
VOLTAGE
SOURCE
CPROTECT

FIGURE 3. MASTER POWER UP SCREEN

KEPCO, INC. " 131-38 SANFORD AVENUE " FLUSHING, NY. 11352 U.S.A. " TEL (718) 461-7000
FAX (718) 767-1102 " email: kepcopower@aol.com
4
228-1472 REV 3 091903
Loading...
+ 8 hidden pages