KEPCO KIT 219-0444 User Manual

Page 1
INSTRUCTION SHEET
KEPCO
An ISO 9001 Company.
CABLE
KIT
219-0444
CABLE KIT NO. 219-0444
BOP 1000W MODELS (3) IN SERIES
I. DESCRIPTION.
This kit contains the cables and terminations required to operate three identical 1000 Watt BOP High Power mod­els in series, effectively multiplying the output voltage capacity by three. Only identical models may be configured to operate in series.
This kit can be used with all 1000W BOP models that have revision levels as shown in Table 1. Earlier models
!
that have been upgraded to permit multiple unit configurations must include the letter “A” following the revision number. CAUTION: Failure to install the ground cables supplied can result in damage to the power supply.
Refer to the associated technical manual supplied with the High Power BOP power supply for all instructions regarding installation and operation of multiple units in series.
TABLE 1. REVISION LEVELS APPLICABLE TO THIS KIT
Model Revision
BOP 6-125MG All All
BOP 10-75MG 5 or higher 3A or 4A
BOP 20-50MG 8 or higher 5A, 6A or 7A
BOP 25-40MG All All
BOP 36-28MG 11 or higher 8A, 9A or 10A
BOP 50-20MG 7 or higher 5A or 6A
BOP 72-14MG 7 or higher 6A
BOP 100-10MG 6 or higher 2A or 4A
Revisions for Upgraded Units
(Must include “A”)
II. SPECIFICATIONS
Table 3 lists the model parameters unique to a series combination of three identical 1000W BOP Power Supplies. Table 4 lists the general specifications for the series combinations listed in Table 3. For specifications not listed in Table 3, refer to the General Specifications provided in the associated technical manual supplied with each 1000W BOP power supply
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
©2012, KEPCO, INC Data subject to change without notice
http://www.kepcopower.com email: hq@kepcopower.com
228-1525 REV 3 033012
Page 2
TABLE 2. EQUIPMENT SUPPLIED
Item Quantity Purpose Kepco P/N
Output Power cable (1.5 ft.)
Digital Control (Bitbus) Cable (3 ft)
Protection Cable (1 ft.)
Series Control cable (1.5 ft.)
Protection - OUT Termi­nation (Slave)
Protection - IN Termina­tion (Master)
Chassis Ground Cable 2 Connects chassis ground terminals of all units. 118-1272
Ground Cable mounting hardware
Output Sense Cable 2 Connects Output sense terminal to Common sense terminal of next unit. 118-1271
Instruction Manual 1 Lists material supplied and specifications for multiple unit combination. 228-1525
3 sets Each set consists of eight parts, mounted in the following order: No. 10 star lock-
Connects the OUTPUT terminal of Master to the COMMON terminal of Slave #1 and
2
the OUTPUT terminal of Slave #1 to the COMMON terminal of Slave #2.
Provides communication between master and two slaves.
1
Provides interlock protection signals required for multiple unit operation.
2
Provides control signals required for series operation.
2
Provides proper termination for the slave connection to the Protection Cable.
1
Provides proper termination for the master connection to the Protection Cable.
1
washer P/N 103-0106 (at chassis), No. 10 flat washer P/N 103-0031, No. 10 split lockwasher P/N 103-0033, 10-32X3/8 nut P/N 102-0008, No. 10 flat washer P/N 103­0031, [lug(s) from ground cable], No. 10 flat washer P/N 103-0031, No. 10 split lock­washer P/N 103-0033, and 10-32X3/8 nut P/N 102-0008.
118-1112
118-1148
118-1126
118-1120
195-0108
195-0107
(See
Purpose
at left for
part
numbers)
TABLE 3. MODEL PARAMETERS FOR THREE (3) IDENTICAL BOP 1000 WATT UNITS (SERIES)
(3) Identical Models
(Series)
BOP 6-125MG ±18V d-c ±125A d-c 1.8 12.5
BOP 10-75MG ±30V d-c ±75A d-c 3.0 7.5
BOP 20-50MG ±60V d-c ±50A d-c 6.0 5.0
BOP 25-40MG ±75V d-c ±40A d-c 7.5 4.0
BOP 36-28MG ±108V d-c ±28A d-c 10.8 2.8
BOP 50-20MG ±150V d-c ±20A d-c 15.0 2.0
BOP 72-14MG ±216V d-c ±14A d-c 21.6 1.4
BOP 100-10MG ±300V d-c ±10A d-c 30.0 1.0
d-c Output Range Closed Loop Gain
E
O Max
I
O Max
Voltage Channel
(V/V)
Current Channel
(A/V)
TABLE 4. GENERAL SPECIFICATIONS FOR THREE (3) IDENTICAL BOP 1000 WATT UNITS (SERIES)
SPECIFICATION RATING/DESCRIPTION CONDITION
INPUT CHARACTERISTICS
Current 176 Va-c 28.5A a-c maximum
264 Va-c
Leakage current 10.5mA a-c 230V a-c, 47-63 Hz
OUTPUT CHARACTERISTICS
Programming resolution / accuracy
Readback resolution / accuracy
Voltage 14 bits / 0.2% 2% accuracy for Ext Ref Level. Unit gain adjustable between 0 and
Current 14 bits / 0.5%
Voltage Limit 12 bits / 0.5%
Current Limit 12 bits / 0.5%
Voltage 16 bits / 0.2% main or limit channel
Current 16 bits / 0.5% main or limit channel
19.2A a-c
maximum
/10 (voltage) or I
E
ONOM
ONOM
/10 (current).
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000
FAX (718) 767-1102 email: kepcopower@aol.com
2 228-1525 REV 3 033012
Loading...