1)This manual is valid for the following Firmware Versions:
FIRMWARE VERSIONUNIT REVISION NO.NOTE
2)A Change Page may be included at the end of the manual. All applicable changes and
3)The contents of this manual are protected by copyright. Reproduction of any part can be
3.63 and higher
revision number changes are documented with reference to the equipment serial numbers. Before using this Instruction Manual, check your equipment firmware version number to identify your model. If in doubt, contact your nearest Kepco Representative, or the
Kepco Documentation Office in New York, (718) 461-7000, requesting the correct revision
for your particular model and firmware version number.
made only with the specific written permission of Kepco, Inc.
KEPCO, INC. z 131-38 SANFORD AVENUE z FLUSHING, NY. 11355 U.S.A. z TEL (718) 461-7000 z FAX (718) 767-1102
email: hq@kepcopower.com z World Wide Web: http://www.kepcopower.com
KEPCO®
THE POWER SUPPLIER™
TABLE OF CONTENTS
SECTIONPAGE
SECTION 1 - INTRODUCTION
1.1 Scope of Manual......................................................................................................................................... 1-1
1.3 General Description .................................................................................................................................... 1-1
1.5.1 Local Control ........................................................................................................................................... 1-3
1.5.2 Remote Control ....................................................................................................................................... 1-4
1.5.3 Analog Programming............................................................................................................................... 1-4
1.5.4 Digital Calibration .................................................................................................................................... 1-4
2.1 Unpacking and Inspection .......................................................................................................................... 2-1
2.2 Terminations and Controls.......................................................................................................................... 2-1
2.2.1 Front Panel Controls and Indicators........................................................................................................ 2-1
2.3 Mains Power Requirements........................................................................................................................ 2-5
2.3.1 Changing Mains Power Voltage .............................................................................................................. 2-6
2.6.2 Unit Under Test (UUT) to Load Connection ............................................................................................ 2-9
2.6.2.1 Power Connections ............................................................................................................................ 2-9
2.6.2.2 Sense Connections ............................................................................................................................ 2-10
2.6.4 Analog Control Connections.................................................................................................................... 2-12
2.6.5 Current Monitor Connections .................................................................................................................. 2-13
2.7 Digital Connections..................................................................................................................................... 2-13
2.7.1 Standard Units......................................................................................................................................... 2-13
2.7.2 G Option - GPIB Interface ....................................................................................................................... 2-13
2.7.3 E Option - Ethernet Interface................................................................................................................... 2-13
SECTION 3 - OPERATION
3.1 General ....................................................................................................................................................... 3-1
3.3 Turning the Unit On .................................................................................................................................... 3-2
3.4 Selecting the Mode and Setpoint................................................................................................................ 3-2
SERIES EL 020498i
TABLE OF CONTENTS
SECTIONPAGE
3.5 Engaging the Load..................................................................................................................................... 3-3
3.6 Disengaging the Load ................................................................................................................................ 3-3
3.7 Viewing Configuration Information ............................................................................................................. 3-4
3.8 Changing IP Mode ..................................................................................................................................... 3-4
3.9 Changing Static IP Address or Subnet Mask............................................................................................. 3-4
3.11 Operation of Master/slave Configurations.................................................................................................. 3-5
3.11.1 Power Up................................................................................................................................................ 3-6
3.11.2 Local (Front Panel) Operation ................................................................................................................ 3-6
3.13.3.7 STATus Subsystem........................................................................................................................... 3-12
3.13.3.8 SYSTem subsystem .......................................................................................................................... 3-13
3.13.4 Program Message Structure................................................................................................................... 3-13
3.13.4.4 Data ................................................................................................................................................... 3-13
3.13.4.4.1 Multiple Line Messages............................................................................................................... 3-13
3.13.4.5 Data Separator .................................................................................................................................. 3-14
3.13.5 Understanding The Command Structure................................................................................................ 3-15
3.13.6 Program Message Syntax Summary...................................................................................................... 3-15
3.13.7 Status Reporting..................................................................................................................................... 3-16
3.13.7.1 Status Reporting Structure ................................................................................................................ 3-16
3.13.7.2 Standard Event Status Register ........................................................................................................ 3-16
3.13.7.3 QUEStionable Status Register .......................................................................................................... 3-18
3.13.7.4 Channel Status Register.................................................................................................................... 3-18
3.13.7.6 Status Byte Register.......................................................................................................................... 3-19
3.15 Analog Programming ................................................................................................................................. 3-21
1-1 Series EL Load ........................................................................................................................................... viii
2-1 Series EL, Front Panel Controls and Indicators .......................................................................................... 2-2
2-2 Series EL, Dual Model Front Panel Controls and Indicators....................................................................... 2-2
2-3 Series EL, Rear Panel Terminations and Connectors ................................................................................ 2-4
2-4 Series EL, Dual Models, Rear Panel Terminations and Connectors .......................................................... 2-4
2-5 Master Control Board Removal, Top View.................................................................................................. 2-7
2-6 Line Voltage Selection Jumper Orientation................................................................................................. 2-7
2-8 Local Sensing Jumpers............................................................................................................................... 2-10
2-10 EL Load, Outline Dimension Drawing ......................................................................................................... 2-14
2-11 EL Load, Dual-Channel, Outline Dimension Drawing ................................................................................. 2-16
3-1 Example of Remote Operation.................................................................................................................... 3-8
3-3 Tree Diagram of SCPI Commands Used with Series EL Electronic Load .................................................. 3-14
3-4 Status Reporting Structure.......................................................................................................................... 3-17
1-1 Model Parameters .......................................................................................................................................1-2
1-2 Series EL Specifications .............................................................................................................................1-5
2-1 Front Panel Functions .................................................................................................................................2-3
and Operation Event Register Bits .......................................................................................................... B-10
SERIES EL 020498vii
FIGURE 1-1. SERIES EL LOAD
viiiSERIES EL 070312
1.1SCOPE OF MANUAL
This manual contains instructions for the installation, operation and service of the Series EL
Electronic loads manufactured by KEPCO, Inc., Flushing, New York, U.S.A., and applies to
units with Firmware Version and Unit Revision number indicated on the Title page. Firmware
Version is obtained in the response to *IDN? query. The Unit Revision number is visible on the
side of the unit, directly behind the top left side of the front panel (looking from the front).
DANGEROUS AND LETHAL POTENTIALS AND CURRENTS
ARE PRESENT, BOTH WITHIN THIS ELECTRONIC LOAD, AND
AT THE OUTPUT!
Before proceeding to use the electronic load, read this manual very carefully. Caution must be used when working with, and making connections
to, this load. Use only wires with the proper current rating and proper voltage rating for high voltage connections.
1.2INTRODUCTION
The Series EL Electronic Loads (Figure 1-1) are modular, air-cooled, electronic loads. Typically
these loads are used to test DC power sources, such as batteries, power supplies, generators,
chargers, fuel cells etc.
SECTION 1 - INTRODUCTION
WARNING
Table 1-1 lists the rated power, voltage and current for Kepco’s Series EL electronic loads. For
example. Kepco Model 3K-600-90 Electronic Load uses 1000-volt devices allowing 600 volt
operation and is rated at a maximum current capability of 90 amperes and a power rating of
3000 Watts.
Model numbers with a D suffix indicate a dual-channel load. These models are comprised of two
identical independent loads within a single chassis.
1.3GENERAL DESCRIPTION
The Series EL load system is comprised of two elements—the load and a control source. The
load dissipates power from the UUT—i.e. the source of electrical energy being tested by the
load. The source of control is either the load front panel or an external computer or other device
that can communicate using the interface protocols for which the Series EL is configured.
The load is rack-mountable. Local front panel control allows mode selection and provides: mode
indications; display of load current, voltage and power measurements; control parameter adjustment; local/remote control status; fault indications; and power on/off control of the load.
The load has high-current rear panel LOAD Terminals used to connect the UUT to the load,
analog control and monitoring terminals, master/slave communications connections, USB 2.0
and RS-232 connectors for remote control, and a mains power connector with fuse. The load
can also be configured with optional Ethernet or GPIB interfaces.
Values of load current, voltage and power, as well as fault information can be reported to a computer for display and analysis. SCPI-compliant commands transmitted to the load set the load
operating parameters. Special commands allow the user to configure the load measurement
system and to perform diagnostic tests.
SERIES EL 0703121-1
Series EL electronic loads are designed for future expandability to accommodate increased
testing needs as user requirements grow. Any EL electronic load can be expanded to a full 5 kW
capability (with a commensurate increase in maximum current carrying capacity). Additionally,
the Series EL system can be expanded above the power/current limits defined in Table 1-1 by
adding up to 14 additional loads. These slave loads act in concert with a master load to increase
total power dissipation (and current handling).
TABLE 1-1. MODEL PARAMETERS
Operating LimitsOverload Protection
Model number
EL 1K-50-100, D
EL 1K-200-100, D
EL 1K-400-70, D
EL 1K-600-30, D
EL 2K-50-200, D
EL 2K-200-200, D
EL 2K-400-140, D
EL 2K-600-60, D
EL 3K-25-400D
EL 3K-50-300300050300315052.53150.005
EL 3K-200-300300020030031502103150.005
EL 3K-400-21030004002103150420220.50.015
EL 3K-600-90300060090315063094.50.056
EL 4K-50-500400050500420052.55250.002
EL 4K-200-500400020050042002105250.003
EL 4K-400-35040004003504200420367.50.009
EL 4K-600-15040006001504200630157.50.033
EL 5K-50-600500050600525052.56300.001
EL 5K-200-600500020060052502106300.002
EL 5K-400-420500040042052504204410.008
EL 5K-600-200500060020052506302100.028
NOTES:
(1)Temperature protection: Per FET safe junction temperature.
(2)Maximum operating power and current may be reduced if a) ambient temperature exceeds 25°C or b) operating conditions
(ambient temperature, available air flow, etc.) cause internal load temperature to exceed safe operating conditions for FETs
(temperature fault).
(3)Maximum permissible voltage across ±LOAD terminals. This voltage should never be exceeded, regardless of load power or
load on/off states. Applied voltage must always be positive: +LOAD with respect to –LOAD.
(4)Each FET is individually fused. A blown fuse is reported as a Fault.
(5)D indicates model is also available as a Dual model. Dual models (D suffix) contain two identical and independent channels
in a single chassis; specifications listed are per channel for dual models.
(6)EL 3K-25-400D only available as dual model,
(5)
(5)
(5)
(5)
(5)
(5)
(5)
(5)
(5)(6)
Rated
Power
(Watts)
100050100105052.51050.008
100020010010502101050.014
100040070105042073.50.046
100060030105063031.50.017
200050200210052.52100.004
200020020021002102100.007
200040014021004201470.023
2000600602100630630.083
300050400240052.54200.004
Rated
Vol tag e
(Volts)
Rated Current
Max (any Mode)
(Amperes)
Power
(Watts)
(2)
Vol tag e
(Volts)
(3)
(1)
Current
(Amps)
(2)(4)
Minimum On
Resistance
Short Mode
(Ohms)
1-2SERIES EL 070312
1.4OPERATING MODES
The load operates in one of six modes. Each mode is subject to independent limits for maximum
load current, power, voltage and frequency. Current draw does not occur until the load is turned
ON (engaged with) the Unit Under Test (UUT).
1.4.1CI (CONSTANT CURRENT).
The current drawn by the load from the UUT remains at a constant value defined by the user.
1.4.2CV (CONSTANT VOLTAGE)
The current drawn by the load from the UUT varies as required to cause the UUT voltage to
decrease to the voltage defined by the user. Operation in CV mode requires sufficient source
resistance in the UUT so voltage drops in the UUT allow the desired voltage control.
1.4.3CP (CONSTANT POWER)
The current drawn by the load from the UUT varies as required to cause a constant amount of
power defined by the user to be dissipated by the load, where power is defined as the product of
UUT voltage and current drawn by the load.
1.4.4CR (CONSTANT RESISTANCE)
The current drawn by the load from the UUT varies as required to cause a constant resistance
(UUT voltage divided by load current) defined by the user.
1.4.5CS (CONSTANT CONDUCTANCE)
The current drawn by the load from the UUT varies as required to cause a constant conductance (UUT current divided by load voltage) defined by the user.
1.4.6SHORT
The current drawn by the load is the maximum possible by the load; load resistance is minimum
ON (see Table 1-2). CAUTION: There is no user adjustment of the current in the SHORT
mode—use caution!
1.4.7OFF
No current is drawn by the load even when the load is turned ON.
1.5FEATURES
1.5.1LOCAL CONTROL
Three 4-digit, 7-segment LED displays and six individual LEDs on the front panel show operating status. A rotary encoder (CONTROL) allows the user to adjust the selected load parameter,
define the resolution of the rotary encoder and to select the operating mode. An illuminated
momentary pushbutton switch (LOAD) allows the user to alternately a) engage the load, allowing the source or Unit Under Test (UUT) to draw current and b) disengage the load, stopping
current flow. An integral indicator within the LOAD switch changes color to show the load connection status and indicate a fault condition if one exists.
SERIES EL 0703121-3
1.5.2REMOTE CONTROL
Remote control of the Series EL Electronic Load is accomplished from a remote device using
SCPI commands and either RS 232 or USB protocols. GPIB (G suffix) or LAN (E suffix) protocols are available as an option. The RS 232 and USB ports cannot be turned off, therefore the
Series EL can always be controlled via these ports. Digital commands expand the control available from the front panel, and include damping when required for square wave or pulse type
requirements, overvoltage, undervoltage, overcurrent and overpower protections.
1.5.3ANALOG PROGRAMMING
An analog input is provided via the 15-pin ANALOG CONTROL connector at the rear that allows
the user to use a 10V analog signal to control the voltage, current or power, depending on the
mode selected. See PAR 3.15 for details.
1.5.4DIGITAL CALIBRATION
Internal adjustments of the Series EL Electronic Load are automatic. Calibration can be performed remotely via one of the remote interfaces.
1.5.5DAMPING
Typical operation for an electronic load involves the flow of high currents. The combination of
high, rapidly changing currents and the inductance associated with connections to the load via
lead wires can cause unexpected results, such as very high voltage spikes, oscillation or severe
ringing (damped oscillations) at the source. To help reduce these issues, the Series EL offers
multiple forms and degrees of damping, allowing the best measurements possible. See PAR.
3.14 for details.
1.5.6BUILT-IN PROTECTION
•Overtemperature. Thermal management of the EL Series is accomplished by continually
monitoring the temperature of each individual power-dissipating MOSFET. If the temperature of a MOSFET begins to approach a dangerous level, then its power will be
reduced and the other MOSFETs will naturally increase their share via the control loops.
If the temperature of one or more of the MOSFETs exceeds safe operating limits, this
may cause either a reduction of the load maximum current/power handling ability or a
complete inability to use the load depending on the degree of overheating.
•The user can establish limits for overvoltage or undervoltage, overcurrent, or power
which can not be exceeded at the input. If the limits are exceeded, the unit disengages
from the UUT and a fault indication is displayed (see PAR. 3.3.1 for details).
1.5.7MASTER/SLAVE CONTROL
For configurations that require power or current in excess of the maximum available from a single unit, additional units can be added to the system to increase power/current capability, up to a
maximum of 14 additional units.
1-4SERIES EL 070312
1.6SPECIFICATIONS
Parameters unique to different models of Series EL loads are listed in Table 1-1. Specifications
common to all Series EL models are listed in Table 1-2.
TABLE 1-2. SERIES EL SPECIFICATIONS
SPECIFICATIONRATING/DESCRIPTIONCONDITION/COMMENT
MODE CHARACTERISTICS
Linearity vs. programming commandSee Table 1-3
Regulation
Resolution (via computer control)14 Bits5 – 100% of Full Scale
Current readback
(Current mode)
Parameter readback
(Current and Voltage)
(1)See Table 1-3
Computer Accuracy:±0.25%
Computer Resolution: ±15 Bits5 – 100% of Full Scale
Cooling Forced Air (400 CFM) Variable speed fans, cooling determined by load
Operating Temperature
Dimensions (load)19”W x 7”H x 24.5”DSee Figure 2-10.
Weight (load)88 lbs.
Storage Requirements–20 to +60°C, 15 to 80% RHRelatively dust free environment.
NOTES:
(1) Regulation specified after 15 minutes of operation at set power level. (2) Accuracy and regulation are valid from 5% to 100% of
the rated value. The accuracy (e.g., ±0.25% of a constant current setpoint) is ±0.25% of the full scale value and not the setpoint.
(3) For 240V configuration of dual-channel models, contact Kepco.
0°C to 40°C
120V is factory default; 240V requires internal
configuration
demand.
(3)
(see PAR 2.3.1)
(2)
SERIES EL 0703121-5
MODELinearity Vs. Programming CommandRegulation
Constant Current±0.25%±0.25%
Constant Power±2%±1%
Constant Voltage±0.25% (±1% for 50V models)±0.25%
Constant Resistance±1%±1%
Constant Conductance±1%±1%
(1) Regulation specified after 15 minutes of operation at set power level
1.7EQUIPMENT SUPPLIED
Equipment supplied with the unit is listed in Table 1-4.
TABLE 1-3. MODE CHARACTERISTICS
(1)
TABLE 1-4. EQUIPMENT SUPPLIED
ITEM
Source Power cable118-1234
Series EL Quick Start Guide *228-16871
EL Series (except Dual models) ±LOAD terminal hardware
Chassis slide mounting screws, 10-32 x 1/4 in. (installed in chassis slide
mounting holes; replace screws provided with chassis slides which must
be discarded)
Fuse 3A, SB (installed in fuseholder on rear panel.)141-0129
PART NUMBERQUANTITY
(Unicable 3850-761-BB/G)
101-0507
102-0182
103-0196
103-0197
101-0507
102-0182
103-0196
103-0197
102-0190
103-0201
103-0204
102-0188
101-05317
(Littelfuse 0313003.HXP)
1
2
2
2
4
4
4
4
8
1
2
1
1
1
* Series EL USB Driver Manual and Series EL Operator Manual are available for free download from the Kepco website
at www.kepcopower.com/support/opmanls.htm#e
Series EL Drivers are available for free download at www.kepcopower.com/drivers/drivers-dl3.htm#el
1-6SERIES EL 070312
1.8ACCESSORIES
Accessories for the Series EL Electronic Load are listed in Table 1-5.
1.9OPTIONS
The G option (suffix G added to model number) includes the GPIB interface. For single units the
GPIB interface is in addition to the standard RS 232 and USB interfaces. For dual units the
GPIB interface replaces the standard RS 232 and USB interfaces.
The E Option (suffix E added to model number) includes the Ethernet (LAN) interface in addition
to the standard RS 232 and USB interfaces.
Dual Channel models are identified by a D Suffix. These models contain two identical independent loads in one chassis.
1.10SAFETY
There are no
operator serviceable parts inside the case. Service must be referred to authorized
personnel. Using the load in a manner not specified by Kepco, Inc. may impair the protection
provided by the load. Observe all safety precautions noted throughout this manual. Table 1-6
lists symbols used on the electronic load or in this manual where applicable.
TABLE 1-5. ACCESSORIES
ITEMFUNCTION
RJ 22 Master/Slave cable, 1 ft.
(See Note.)
Fuse 1.5A, SBRequired for units configured to run from 240V a-c
Slides (pair)Allows the unit to slide out of a rack. see PAR. 2.5.2.)CS 06
Side Support bracketPair required. Used to provide side support for EL
NOTE: For units that use slide mounting, consult Kepco for longer cable lengths.
Daisy chains Series EL loads with the same voltage for
parallel configurations.
source power.
Load. Requires rear rail at 18-13/16 in. setback.
KEPCO
PART NUMBER
118-1245
141-0031
(LittelFuse
31301.5)
128-1775
TABLE 1-6. SAFETY SYMBOLS
SYMBOLMEANING
CAUTION: RISK OF ELECTRIC SHOCK.
CAUTION: REFER TO REFERENCED PROCEDURE.
!
WARNINGINDICATES THE POSSIBILITY OF BODILY INJURY OR DEATH.
CAUTIONINDICATES THE POSSIBILITY OF EQUIPMENT DAMAGE.
SERIES EL 0703121-7/1-8 Blank)
SECTION 2 - INSTALLATION
2.1UNPACKING AND INSPECTION
This instrument has been thoroughly inspected and tested prior to packing and is ready for
operation. After careful unpacking, inspect for shipping damage before attempting to operate.
Perform the preliminary operational check as outlined in PAR 2.5. If any indication of damage is
found, file an immediate claim with the responsible transport service.
2.2TERMINATIONS AND CONTROLS
2.2.1FRONT PANEL CONTROLS AND INDICATORS. Three 4-digit, 7-segment LED displays and
six individual LEDs on the front panel show operating status as shown in Figure 2-1 or Figure 2-
2. A rotary encoder (CONTROL) allows the user to: a) adjust the selected load parameter, b)
define the resolution of the rotary encoder, c) select the operating mode. A momentary pushbutton switch (LOAD) with integral LED indicator allows the user to alternately a) engage the load,
allowing the source or Unit Under Test (UUT) to draw current and b) disengage the load, stopping current flow. The LOAD LED indicator colors show the load connection status and indicate
a fault condition if one exists.
Figure 2-1 shows the front panel of standard units; Figure 2-2 shows the front panel of dualchannel units. Table 2-1 presents the functions of all front panel controls and indicators. Front
panel controls listed in Table 2-1 are duplicated for identical (but independent) channels A and B
of the dual-channel units, with the exception of the single POWER switch which applies to both
channels.
2.2.2REAR PANEL CONNECTIONS. Figure 2-3 shows the rear panel of standard single-channel
units; figure 2-4 shows the rear panel of dual-channel units. Table 2-2 presents the functions of
all rear panel connections. Rear panel connections listed in Table 2-2 are duplicated for identical
(but independent) channels A and B of the dual-channel units, with the exception of the single
power inlet connector and fuse which apply to both channels.
SERIES EL 0703122-1
NOTE: See Table 2-1 for callout descriptions.
FIGURE 2-1. SERIES EL, FRONT PANEL CONTROLS AND INDICATORS
NOTE: See Table 2-1 for callout descriptions.
FIGURE 2-2. SERIES EL, DUAL MODEL FRONT PANEL CONTROLS AND INDICATORS
2-2SERIES EL 070312
TABLE 2-1. FRONT PANEL FUNCTIONS
SEE
FIG. 2-1
OR 2-2
1AMPS displayDisplays the load test current in Amps (factory default setpoint (see NOTE): 0 Amps) or test current
3CI indicatorOn to indicate Constant Current Mode.
4CV indicatorOn to indicate Constant Voltage Mode (factory default setpoint (see NOTE): maximum load voltage).
5CP indicatorOn to indicate Constant Power Mode (factory default setpoint (see NOTE): 0 kilowatts.
6Power ON/OFF
7LAN indicatorGreen LED on when Ethernet control is active.
8LOCAL indicator Red LED on when front panel controls are active.
9CONTROL
10LOAD
11KW displayDisplays the power (Amps x Volts) being dissipated by the load in kilowatts. Also indicates resis-
12VOLTS displayDisplays test voltage from UUT applied to the load in Volts. May also display blinking FAL7 which
NOTE:
Factory defaults refer to setpoints for the measurement displayed. These factory default setpoints are designed to ensure that no
current is drawn from the UUT when the load is engaged without further adjustment of these parameters. The EL Series load maintains individual setpoints for each mode. These are stored in non-volatile memory, however the factory default setpoints can be
restored by issuing *RST command over a remote interface.
COMPONENTFUNCTION
setpoint in Amps. May also display blinking FAL7 to indicate Current Fault (sets input to OFF).
CAUTION: Short mode is selected when CR, CI, CV and CP indicators all blink.
On (blinking with other Mode indicators off) indicates Constant Conductance Mode; factory default
setpoint: 1mS (0.001 siemens, I/E).
switch
rotary encoder/
pushbutton
switch
momentary
pushbutton
switch/indicator
Rocker switch: press top half to turn power on, bottom half to turn power off. NOTE: Cycling power
switch from ON to OFF to ON resets fault conditions, but does not reset setpoints (sse NOTE).
When LOCAL is active, Four functions are available as follows:
a. Select Mode: Press and hold until Mode indicators and LOAD pushbutton indicator start blinking.
Release and rotate knob to select mode indicated by the CI, CR, CV and CP indicators (see Table 3-
1). LOAD indicator off while selecting mode. To make a selection either (1) press and hold knob until
indicators stop blinking, (2) wait one minute, or (3) press LOAD button to exit selection process.
b. Set Value: Rotate knob to adjust the level of the controlled parameter: current, voltage, resistance, conductance or power (see Table 3-1). Rotate clockwise to increase, counterclockwise to
decrease. Settings are stored and will be available at next power-up.
c. Select Digit: Momentarily press knob to select one digit (blinks). Convenience function allows
adjustment at desired resolution.
d. Show settings: When Mode is set to OFF, rotating CONTROL while LOAD switch is blinking
green and depressed displays Model number, Serial number, IP address, etc. (see PAR. 3.7).
Switch used to alternately enable (load engaged) or disable (load disengaged) the ability of the load
to draw current from the UUT. Indicator lights to show load status:
Green (steady): Standby - Ready to operate; load does not draw current from the UUT. Parameter
displays show voltage, current and power setpoints when CONTROL is momentarily depressed.
Green (blinking): Modes set to off (CR, CI, CV, CP all off), Load can not be engaged. Load configuration information is displayed.
Amber: Engaged - The load is able to draw current from the UUT, however current may or may not
be flowing depending on the setpoint settings. Parameter displays show actual voltage, current and
power.
Red (blinking): Fault - The load does not draw current from the UUT. The nature of the fault is
shown in the appropriate 7-segment display (see PAR.3.3.1) NOTE: The fault condition must be corrected before the load can be engaged; press LOAD switch to change indication to Standby (green)
after fault is corrected.
Off (not lit): Mode selection using CONTROL is in progress.
tance (in Ohms) or conductance (in Siemens) settings. May also display blinking FAL7 to indicate
Power Fault. May also display blinking HO7 to indicate the unit has started to fold back the output
because the internal temperature sensors have detected FET temperature in excess of 130°C.
either alternates with Undr to indicate Undervoltage Fault or alternates with QuEr to indicate Overvoltage Fault (either fault sets input to OFF).
SERIES EL 0703122-3
NOTE: See Table 2-2 for callout descriptions.
FIGURE 2-3. SERIES EL, REAR PANEL TERMINATIONS AND CONNECTORS
NOTE: See Table 2-2 for callout descriptions.
FIGURE 2-4. SERIES EL, DUAL MODELS, REAR PANEL TERMINATIONS AND CONNECTORS
POWER: IEC 60320-C13 line cord connector to connect
mains power (either 120 VAC 50/60 Hz or optional 240V AC
50/60 Hz). NOTE: changing mains power voltage requires
internal connector changes (see PAR. 2.3.1).
Ampere Slo Blow)
UUT Connections. (–) Negative and (+) Positive: High current connections to UUT. Connections to ±LOAD are typically
made using the supplied 3/8” low-resistance hardware (2
sets: bolt, nut and lockwasher).
+S and –S terminals used for remote sensing. Install Jumpers between – and -S and between + and +S for local sensing. Either local or remote sensing must be connected for
unit to operate. See 2.6.2.2 for details.
Analog programming connections. Used for analog programming input/output signals. See 2.6.4 for details.
Standard RS-522 connector. Connects from Master Out to
Slave In (SL-I or SL I/O) for multiple units in parallel (see Figure 2-9). See PAR. 3.16 for master/slave configurations. See
Table 1-5 to order RJ 22 master/slave cable.
Standard RS-232. Connects with a remote device using RS
232 protocols and SCPI commands (see Figure 2-3).
Connection to remote device for command, monitoring or
calibration. Use USB connector of master to communicate
with multiple loads in a master/slave configuration. (see Figure 2-7).
Standard RS-522 connector. Connects Slave to next slave
SL-O to SL-I (SL I/O to SL I/O on D models) if unit is a slave
in a parallel configuration using more than two units. Only
use Kepco cable (see Table 1-5) for master/slave connections (Figure 2-9).
Standard RS-522 connector. Connects Slave to next slave
SL-O to SL-I (SL I/O to SL I/O on D models) if unit is a slave
in a parallel configuration using more than two units. Only
use Kepco cable (see Table 1-5) for master/slave connections (Figure 2-9).
Optional. When installed, connects user GPIB card with EL
load using standard GPIB cable (not supplied).
2.3MAINS POWER REQUIREMENTS
The Electronic Load is delivered configured for operation from 120V a-c ±10%, 50/60 Hz. If the
load is to be operated from a 240V a-c ±10%, 50/60 Hz power source, or the input power range
needs to be changed from a previous selection, see PAR 2.3.1 to change mains power
CAUTION: The Series EL electronic loads do not have 120/240V automatic line voltage
switching. Applying 240V a-c to a load configured for 120V a-c will damage
the load.
SERIES EL 0703122-5
2.3.1CHANGING MAINS POWER VOLTAGE
The load can be operated from either 120V a-c, ±10%, 50/60 Hz or 240V a-c, ±10% 50/60 Hz.
To change from one mains operating voltage to the other requires repositioning of line voltage
selection jumpers located on the Master Control Board and must be done only by authorized
personnel. NOTE: Carefully tag and retain all attaching hardware for use during reassembly.
NOTE: Conversion of Dual Channel Models (D suffix) from 120V a-c to 240V a-c is not autho-
rized; please contact factory for assistance.
1.Disconnect all line voltage sources and UUT sources.
2.Open the load cabinet by removing the top cover as described below:
a. Loosen and remove five screws holding the top cover to the load on each side.
b. Loosen and remove four nuts holding the top cover to the load rear panel. The top
cover is held in place by four threaded studs.
c. Loosen and remove four screws holding the top cover to the load front panel. For ease
of removal, use a non-metallic support tool through the front panel vertical ventilation
slots to support the top cover as the screws are removed. With the screws removed,
the tool can be used to elevate the top cover above the front panel so it can be grasped
and removed from the load.
3.Refer to Figure 2-5 and remove the Master Control Board as follows:
a. Unplug 10-pin ribbon cable at top of Master Control Board.
b. Unplug 16-pin ribbon cable from Front Panel Display Board at top of chassis.
c. Unplug front and rear fan connectors from Master Control Board.
d. From outside of side panel, remove four Allen Head screws holding the Master Control
Board mounting plate to the load side panel.
e. To allow the transformer on the Master Control Board clearance it is necessary to
remove one Power FET Module (PFM) board (see Figure 2-5). Disconnect two PFM
board interconnection cables, then remove four groups of four screws (each with one
flat washer and one lockwasher) and two sets of brass nuts (each with one flat washer
and one lockwasher).
f.Raise Master Control Board assembly until the two small black mains voltage selection
jumpers are visible (see Figure 2-6). NOTE: It may be necessary to remove nut securing wire strap holding front fan connector wires to fully remove board.
4.Using long-nosed pliers, remove the jumpers and relocate them to the desired position (see
Figure 2-6). NOTE: Two jumpers used for 120V a-c operation, only one jumper used for
240V a-c operation.
5.Reassemble the load by reversing the above steps. CAUTION: When reinstalling the
PFM Board, it is important to torque all screws and nuts to 1.5Nm (13.8 in-lb).
6.Change the mains fuse to correspond to the type and rating suitable for the selected mains
voltage operation (see Figure 2-3).
2-6SERIES EL 070312
FIGURE 2-5. MASTER CONTROL BOARD REMOVAL, TOP VIEW
FIGURE 2-6. LINE VOLTAGE SELECTION JUMPER ORIENTATION
2.4COOLING
The power devices used within the electronic load are maintained within their operating temperature range by means of internal heat sink assemblies cooled by six cooling fans.
ALL INLET AND EXHAUST OPENINGS AT THE FRONT AND REAR OF THE ELECTRONIC
LOAD MUST BE KEPT CLEAR OF OBSTRUCTION TO ENSURE PROPER AIR ENTRY AND
EXHAUST.
SERIES EL 0703122-7
These units are zero-clearance stackable, i.e., no top or side ventilation is required when rack
mounting. However, If the unit is rack mounted, or installed within a confined space, care must
be taken that the ambient temperature, which is the temperature of the air immediately surrounding the load, does not rise above the specified limits (see Table 1-2).
2.5INSTALLATION
!
The load is very heavy (80 - 90 pounds). Exercise care when lifting,
mounting or otherwise handling this product. It is recommended that
two or more persons handle the electronic load.
2.5.1RACK MOUNTING
The unit is intended to be either used on a bench or mounted directly in a 19-inch wide rack.
These units are zero-clearance stackable, i.e., no top or side ventilation is required when rack
mounting (see cooling, PAR. 2.4). Optional slides (see Table 1-5) can be used. See Figure 2-10
for outline dimensions, see Figure 2-11 for outline dimensions of Dual-channel models.
Four front panel mounting holes are provided. When optional slides are not used, additional
support is required.
When at least 1/2U space is available at the bottom, either a bottom support platform (shelf) or
side support brackets can be used. Contact factory for proper bracket depending on rail setback.
WARNING!
For zero-clearance stacking, support must be provided at the rear; contact factory for details.
2.5.2SLIDE MOUNTING
!
Use of any chassis slide other than CS 06 is unauthorized and may
damage the unit and void the warranty.
Refer to the instructions supplied with Chassis Slide CS 06 for slide installation. Use of screws
other than those supplied with CS 06 or pre-installed in slide mounting holes will damage the
unit and void the warranty. Contact factory for non-standard mounting options.
!
Do not lean on fully extended load. Weight added to the fully extended
unit in excess of 35 lbs. can cause the slide to fail and the unit to fall.
When replacing a unit with slide mounting, disconnect load cables before pulling the unit out.
With the unit fully extended and supported, press release buttons on the two intermediate sections of the slide and remove the unit from the cabinet.
2.6WIRING INSTRUCTIONS
Interconnections between an a-c power source and the load, and between the load and the unit
under test are as critical as the interface between other types of electronic equipment. Figure 27 illustrates connections for a typical test setup.
Series EL is provided with a three-terminal IEC appliance coupler for connection of the mains
supply source, one terminal of which is dedicated for the protective earthing conductor; no other
CAUTION!
WARNING!
2-8SERIES EL 070312
ground or earth connection is required, although the chassis may be separately connected to
earth ground for noise or other reasons, such as user or site requirements.
2.6.1MAINS POWER
FIGURE 2-7. TYPICAL INTERCONNECTIONS
Mains power is connected at the rear panel of the Series EL Electronic Load (see Figure 2-3)
via the IEC 320-style recessed power inlet connector, which provides interface to the three-wire
safety line cord (supplied) via a polarized mating plug. (see PAR. 2.3 for mains power requirements).
It is recommended that the 1/4-inch bolt with wingnut and flat washers (supplied) at the top left
of the rear panel be connected to earth ground.
2.6.2UNIT UNDER TEST (UUT) TO LOAD CONNECTION
WARNING!
Loose test connections between the UUT and the Series EL load can
lead to load instability, erratic operation and possible equipment
damage. In addition, loose connections or insufficiently sized
conductors can become very hot and cause burns.
2.6.2.1POWER CONNECTIONS
Connections between the UUT and the Series EL Electronic Load are achieved via the (+) and
(–) LOAD terminals located on the rear panel.
The load is capable of drawing very high currents. Connections between the UUT and the load
should be of suitably large wire, sized to carry the maximum current. It is extremely important to
ensure all connections are tight and corrosion free. Regular inspection of these connections is
important. Inspection interval should be established based on frequency and type of use. Once
per week is recommended, however where cable movement or vibration is likely, more frequent
inspections are warranted.
SERIES EL 0703122-9
Use two wrenches to tighten the 3/8 in. (5/16 in. for Dual models) Bolt/Nut on the bus bars.
these hardware items are brass and could shear if overtightened: recommended maximum
torque is 20 lb-ft for the 3/8 in. hardware, 10 lb-ft for the 5/16 in. hardware used on Dual models.
The small resistance created by a loose joint can cause very destructive heating (e.g., a 1 milliohm joint with a current of 400 Amperes generates 160 watts).
Reversing the polarity at the LOAD terminals will cause immediate and
significant damage to the load and UUT!
2.6.2.2SENSE CONNECTIONS
Remote Sensing terminals (±S) are provided for connection to the UUT in order to compensate
for voltage drops on the power cables connected to the ±LOAD terminals. When remote sensing
is used, the readings shown on the front panel accurately reflect the output of the UUT.
To use remote sensing first remove the local sense jumpers (NOTE: Local sense jumpers can
be fabricated as needed using #18 AWG stranded wire) installed on the SENSE Terminal block.
Then connect wires (#24 AWG or 22 AWG) from +S to the positive output of the UUT, and from
–S to the negative output of the UUT. Twisting of sense wires is recommended.
If remote sensing is not used, the pre-installed local sensing jumpers must remain in place as
shown in Figure 2-8. Operating the unit with neither local nor remote sensing in place will result
in erroneous readings.
WARNING
Connect the Series EL Electronic Load to the UUT using cabling appropriate for the current and
voltage drawn during testing. Contact Kepco if assistance is needed in selecting the appropriate
wire size, length and physical configuration. Ensure all connectors are suitable for the currents
and that connections are tight. Connections should be re-checked on a regular basis (see PAR.
2.6) to ensure continued low-resistance connections.
CAUTION:When connecting the load to the UUT be very careful not to accidentally short
the UUT output in the process of connecting the wiring. Best practice is to make the connection to the UUT Positive (+) output connector the last connection.
NOTE:
1.LOCAL SENSING SHOWN.
2.FOR REMOTE SENSING, REMOVE JUMPERS
FROM ±S AND CONNECT ±S TERMINALS TO
CORRESPONDING ± OUTPUT TERMINALS AT
THE UNIT UNDER TEST.
FIGURE 2-8. LOCAL SENSING JUMPERS
DUAL CHANNEL MODELS
(D SUFFIX) ONLY
2-10SERIES EL 070312
2.6.2.3GROUNDING
It is recommended that the 1/4-inch bolt with wingnut and flat washers (supplied) at the top left
of the rear panel be connected to earth ground.
The LOAD Bus bars are isolated from the chassis and from the control circuits well into the 100s
of volts. The PGM (Program) input (ANALOG CONTROL connector, pin 1, pin 15 return) is isolated from the control circuits (and are therefore doubly isolated from the LOAD Bus) up into the
100s of volts. The I-Load output (ANALOG CONTROL connector, pin 2, pin 13 return) is independently isolated from the control circuits and therefore is double-isolated from all other external connections. Lastly, all of the Remote Interface inputs (RS-232, USB 2.0, RS-522), optional
LAN and GPIB) are optically isolated from the control circuits and are therefore doubly isolated
from all other circuits.
2.6.3PARALLEL MASTER/SLAVE CONFIGURATIONS
Up to 15 Series EL Electronic Loads may be paralleled for additional current and/or power handling capability. All units must have the same voltage rating. One load is designated as the Master, and the rest are designated as slaves. Master/slave communications are via proprietary
protocols using special cable(s) connected to the MSTR O (Master Out) and SLAVE I/O connectors on the rear panel (see Table 1-5). Connections are from MSTR O to SLAVE I/O, then for
subsequent slaves, from SLAVE I/O to SLAVE I/O of the next unit. Computer/load communications are via either the RS 232 or USB (or optional LAN or GPIB) interfaces, and are applied to
the master only. Figure 2-9 illustrates connections for a typical master/slave system.
In a Master-Slave configuration, two or more Loads operate in parallel to increase the total current and power capacity.
CAUTION: Loads in Master-Slave configuration are always operated in PARALLEL,
never in series. Each Load in the system must have exactly the same maximum voltage limit-otherwise the Load internal software will not allow the
Loads to configure as a Master-Slave system. Paralleling two Loads of
unequal voltage rating and applying a voltage greater than the limits of the
Load with the lower voltage rating can result in the destruction of the Load,
the connected source or both.
Typically Loads are stacked vertically to minimize the distance between the ± LOAD terminals. It
is essential to keep this cabling as short as possible due to the high currents flowing during
operation. One of the Loads is designated as the Master and the other as the Slave. Any Load
may be designated as the Master.
Master-Slave configuration is achieved by two interconnections at the Load rear panel (see Figure 2-9): First connect the ± LOAD terminals of master and all slaves in parallel using sufficiently
heavy cable to carry the maximum current expected to be drawn by any of the individual loads.
Next connect the UUT (Unit Under Test) to the ± LOAD terminals. Use of No. 6 (or larger) Welding Cable is recommended for flexibility, current carrying capacity and insulation.
For remote operation use the supplied RJ-22 Master-Slave communications bus cables (these
use miniature modular connectors - do not try to use conventional modular telephone cables).
Connect an RJ-22 bus cable from the MSTR O (Master Out) which is the upper most RJ-22
Jack, to the upper SLAVE I/O RJ-22 Jack on the slave. For more than one slave, connect lower
SLAVE I/O jack to the next unit’s upper SLAVE I/O jack, and so on. No terminations are needed
at the final slave in the daisy chain.
SERIES EL 0703122-11
NOTES:
1 Remove local sense jumpers between + and S+ and between – and S– on
Master only. (See Fig. 2-8.)
2. Connect all Electronic Loads to Earth (safety) Ground using ground stud with
wingnut at upper left corner of each rear panel.
FIGURE 2-9. TYPICAL MASTER/SLAVE INTERCONNECTIONS
2.6.4ANALOG CONTROL CONNECTIONS
The signal at the ANALOG CONTROL - PGM BNC connector (see Figure 2-3) is used for
remote analog programming of the load. For dual channel models (D suffix) this signal appears
at Pin 3 (pin 13 return) of the ANALOG CONTROL connector (see Figure 2-4). (NOTE: This signal is not provided on Model EL 3K-25-400DG). Applying 0 to10V adjusts the controlled param-
2-12SERIES EL 070312
eter (depending on mode selection) from 0 to full scale. See PAR. 3.15 for details. For Master/
Slave configurations, the remote analog signal must be applied to all parallel-connected units.
2.6.5CURRENT MONITOR CONNECTIONS
The signal at the ANALOG CONTROL - ILOAD BNC connector (see Figure 2-3) is an output
signal (ILOAD), 0 to 10V corresponding to 0 to full scale of the load’s rated current. For dual
channel models (D suffix) this signal appears at pin 1 (pin 15 return) of the ANALOG CONTROL
connector (see Figure 2-4). Monitor current using an external voltmeter connected to the BNC
connector or, for dual channel models, across pin 1 and pin 15 when the load is drawing current
from the UUT. For Master/Slave configurations, each ILOAD output reflects the current flowing
in that individual load.
2.7DIGITAL CONNECTIONS
When communicating with the Series EL via a computer interface, the Series EL responds to
IEEE 488.2 and SCPI (Standard Commands for Programmable Instruments) commands and
queries. Compatible IEEE 488.2 commands and queries are listed in Appendix A. The complete
list of SCPI commands designed for the Series EL Electronic Load are listed in Appendix B.
2.7.1STANDARD UNITS
If control via the USB or RS 232 computer interface is desired, the computer should be connected to the load via either the USB 2.0 type B connector or the RS-232 interface connector
located at the rear panel.
The currently active interface takes precedence. That is, with no other direction, the Series EL
communicates with the computer via the USB or RS-232 interface. The selection of the interface
depends on the last interface used.
For simple communications a terminal emulator program such as HyperTerminal provides the
necessary interface. No drivers are required when using the RS-232 interface, however If USB
communications are used, a special driver must be installed (the USB interface is not plug andplay). Refer to the Kepco website to download the Series EL USB Driver Installation Manual that
describes how to download and install the driver, as well as how to establish communications
between the Series EL load and the computer using a terminal emulator:
www.kepcopower.com/support/opmanls.com#e
NOTE: If using USB and HyperTerminal, it is advisable to first turn on the Series EL load and
then launch HyperTerminal as HyperTerminal may become dysfunctional (hung up) if
power is removed from the USB connection before HyperTerminal is closed or before
the connection is closed.
2.7.2G OPTION - GPIB INTERFACE
For G option units, connect the EL Load GPIB connector at the rear panel to the GPIB bus using
a standard GPIB cable (not supplied). NOTE: GPIB drivers are not available.
2.7.3E OPTION - ETHERNET INTERFACE
For E option units, connect a computer to the LAN connector at the rear panel using a standard
RJ 45 Ethernet cable (not supplied). The LAN interface uses a socket connection at Port 5025.
SERIES EL 0703122-13
FIGURE 2-10. EL LOAD, OUTLINE DIMENSION DRAWING (SHEET 1 OF 2)
2-14SERIES EL 070312
T
H
K
E
P
O
E
C
O
L
N
O
T
A
R
D
O
L
V
O
K
L
W
T
S
L
L
C
O
A
P
N
C
W
E
P
A
R
M
S
C
P
U
S
P
O
P
L
I
E
R
T
M
C
C
C
V
K
R
I
E
P
C
O
E
L
E
C
T
R
O
N
I
C
L
O
A
D
O
O
F
N
F
R
M
R
S
2
S
-
T
S
3
2
L
-
O
S
L
-
I
T
H
E
E
R
N
E
T
D
A
O
G
L
I
O
L
A
N
A
M
G
P
+
D
+
S
A
R
O
-
L
-
+
D
A
O
L
-
z
z
H
H
0
0
6
6
/
/
0
0
5
5
C
C
A
A
V
V
0
0
4
2
2
1
U
S
B
B
P
I
G
FIGURE 2-10. EL LOAD, OUTLINE DIMENSION DRAWING (SHEET 2 OF 2)
SERIES EL 0703122-15
FIGURE 2-11. EL LOAD, DUAL-CHANNEL, OUTLINE DIMENSION DRAWING (SHEET 1 OF 2)
2-16SERIES EL 070312
T
H
K
E
P
O
E
C
O
L
N
O
T
A
R
D
O
L
C
O
L
N
O
T
A
R
D
O
L
V
O
K
L
W
T
S
L
L
C
O
A
P
N
C
V
O
K
L
W
T
S
L
C
L
O
A
P
N
C
W
E
P
A
R
M
S
C
P
U
S
P
O
P
L
I
E
R
T
M
C
C
C
R
V
A
M
P
S
C
C
R
V
K
I
E
P
C
O
E
L
E
C
T
R
O
N
I
C
L
O
A
D
C
I
O
O
F
N
F
L
G
O
O
R
L
T
A
N
N
O
A
C
B
E
S
N
E
S
+
D
A
O
L
-
L
G
O
O
R
L
T
A
N
N
O
A
C
A
E
S
N
E
S
C
C
A
A
V
V
0
5
3
1
2
1
C
O
N
T
R
B
L
O
S
3
2
L
R
S
A
O
O
R
/
V
S
M
E
I
T
A
N
L
C
O
N
A
T
R
L
O
U
2
-
S
B
FIGURE 2-11. EL LOAD, DUAL-CHANNEL, OUTLINE DIMENSION DRAWING (SHEET 2 OF 2)
SERIES EL 0703122-17/(2-18 Blank)
SECTION 3 - OPERATION
3.1GENERAL
This section contains general operating instructions for the Series EL Electronic Load. Refer to
Section 2 for a description of the controls, display and terminals. When loading sources of electrical energy be sure to use appropriate precautions where high-currents and potentially high
voltages may be present.
An electronic load can present an extremely low resistance to a source
of electrical energy. in some cases this may be the equivalent of
placing a short circuit at the source output. This may have disastrous
consequences if done unintentionally.
Be sure the load parameter settings are appropriate for the source
being tested.
3.2FACTORY DEFAULT SETTINGS
The unit is shipped with the following settings preset at the factory:
•Current set point 0 A
WARNING
•Voltage set point Load maximum voltage
•Power set point 0 kWatts
•Overvoltage limit5% above rated maximum
•Undervoltage limit0V (deactivated)
•Overcurrent limit5% above rated maximum
•Overpower limit5% above rated maximum
•Resistance set point 1,000 ohms
•Conductance set point 1 mS (0.001 siemens)
•System damping5
•Mode damping3
•Local control Fully enabled
•Load ON/OFF OFF
•SYST:COMM:ECHOOFF
SERIES EL 0703123-1
3.3TURNING THE UNIT ON
1. Connect the load to the UUT (Unit Under Test) (see PAR. 2.6.2)
2. Connect the load to mains power (see PAR. 2.6.1)
3. Connect the load to a computer system
4. Press the front panel POWER switch to ON. The LOAD switch lights green (steady). If it is
illuminated Red a Fault condition exists that must be corrected prior to using the load (see
PAR. 3.3.1).
5. Ensure the computer control system is turned on and communication with the Series EL
Electronic Load is established. Current status of the Series EL Electronic Load modules is
shown by front panel displays.
6. When the unit is first turned on, the LOAD setting and remote computer commands
(INPUT/OUTPUT) are initialized for zero current draw. Setpoints, mode, limits, and other settings remain from prior work. The load is shipped in CI mode and set for 0 Amperes.
7. When first initiating a load, it is advisable to make a “Test run” at a nominal load level (e.g.,
10% of the expected parameter setting). This allows the user to ensure all connections are
properly made and results are as expected when engaging the load.
3.3.1ERROR CONDITIONS
FAL 7 blinking in the AMPS or KW display indicates the associated parameter (current or power)
exceeded established limits.
• HI:Alternating with a voltage measurement in the VOLTS display indicates the estab-
lished voltage limits were exceeded at the remote sense point. (Note: the voltage
measurement continues to be displayed as long as the UUT is connected.)
• LO:Alternating with a voltage measurement in the VOLTS display indicates the UUT
voltage (at the remote sense point) dropped below the internally set low voltage
limit.
• HOT Indicates that the temperature of one or more of the power dissipating Power MOS-
FETs exceeded safe operating limits. (Note: this may cause either a reduction of
the load maximum current/power handling ability or a complete inability to use the
load depending on the degree of overheating.)
3.4SELECTING THE MODE AND SETPOINT
To select a mode and setpoint for the controlled parameter (current, power, voltage, resistance
or conductance) prior to drawing current from the UUT, verify that the LOAD pushbutton indicator is green (steady) and proceed as follows:
1. Depress and hold the CONTROL knob for 3 seconds. The LOAD pushbutton indicator goes
from green to off. Release the CONTROL knob. Rotating the CONTROL knob sequentially
selects the operating mode in the order: CV, CI, CP, CR, CS, SHORT and OFF (see Table 3-
1). To set the selected mode, press and hold CONTROL knob for 3 seconds; LOAD pushbutton indicator goes from off to green.
3-2SERIES EL 070312
2. After the operating mode is selected, set the CONTROL resolution by momentarily depressing the CONTROL knob (CONTROL knob must be depressed twice the first time it is used
after a mode selection). This causes one digit in the selected mode parameter display
(AMPS, VOLTS, KW) to blink while showing the setpoint. The blinking digit indicates the
CONTROL resolution setting for one click of rotation. Momentarily depressing the CONTROL knob again shifts the resolution selection to the next digit.
3. Rotate the CONTROL (clockwise to increase or counterclockwise to decrease) to adjust the
parameter setpoint. Once the setpoint is selected, the setpoint remains displayed momentarily and then the display returns to displaying the measured parameter value.
TABLE 3-1. MODE SELECTION AND ADJUSTMENTS
MODE
INDICATOR
Only CI on
(solid)
Only CR on
(solid
Only CR on
(blinking)
Only CV on
(solid)
Only CP on
(solid)
CI, CR, CV and
CP all blinking
CI, CR, CV and
CP all off
MODE
SELECTED
CI mode
(Constant Current).
CR mode
(Resistance)
CS mode
(Conductance)
CV mode
(Voltage)
CP mode
(Constant Power)
Short mode
(lowest ON resis-
tance possible).
OffModes off, no adjustment. Load will not engage, no setpoints are active and load will
3.5ENGAGING THE LOAD
1. After selecting the mode and setpoint (PAR 3.4), momentarily press the LOAD pushbutton to
engage the UUT, causing the load to draw current from the UUT at the level determined by
the setpoint. LOAD pushbutton illumination changes to amber and the front panel displays
show the measured parameters: voltage, current and power.
ADJUSTMENT
CONTROL sets constant current level in Amperes as viewed on AMPS display.
CONTROL sets resistance in Ohms as viewed on KW display.
CONTROL sets conductance in Siemens (= I in Amps / E in Volts) as viewed on KW
display.
CONTROL sets voltage in Volts as viewed on VOLTS display.
CONTROL sets constant power level in kilowatts as viewed on KW display.
Short mode; maximum current, no adjustment. USE CAUTION before selecting this
mode.
not conduct current. When modes are off, pressing LOAD switch causes LOAD indicator to blink green, then rotate CONTROL to show model and serial number. on front
panel displays (see PAR. 3.7).
2. Rotating CONTROL with the load engaged (LOAD indicator amber) causes the controlled
parameter to increase (clockwise) or decrease (counterclockwise) in steps at the resolution
selected in PAR 3.4, step 2 above. The VOLTS, AMPS and KW displays show the measured
parameters any time the load is engaged (LOAD indicator amber).
3.6DISENGAGING THE LOAD
With the load engaged (LOAD indicator amber), disengage the load from the UUT by momentarily depressing the LOAD pushbutton (illumination changes to steady green) causing the load
to stop drawing current from the UUT.
SERIES EL 0703123-3
3.7VIEWING CONFIGURATION INFORMATION
When the Mode is OFF (none of the mode LEDs are illuminated), momentarily depressing the
LOAD pushbutton (illumination changes to blinking green) allows configuration information to be
viewed. Rotating CONTROL clockwise sequences the VOLTS, AMPS and KW displays as follows (counterclockwise sequences in reverse order starting with Firmware Version).:
•Model Information (displayed as AMPS, VOLTS and KW in respective display).
•Serial Number (5n in AMPS display, serial no. in VOLTS and KW displays)
•IP Mode (SrCE in VOLTS display, USEr (static), dHcP in AMPS display). Refer to PAR.
B.72 for description of IP Modes. To change IP Mode from the front panel see PAR. 3.8.
•IP Address (1st octet = left 3 digits of AMPS, 2nd octet = right digit of AMPS, left 2 digits
of VOLTS, 3rd octet = right 2 digits of VOLTS, left digit of KW, 4th octet = right 3 digits of
KW display.) To change the static IP address from the front panel, see PAR. 3.9. IP
Address is 0.0.0.0 if ethernet option is not installed.
•Subnet Mask (same as IP address). To change the Subnet Mask from the front panel,
see PAR. 3.9.
•Mac Address. Displays the hex Mac address if the ethernet option is installed. Mac
Address is 0.0.0.0 and CR indicator blinks if ethernet option is not installed. Mac
Address can NOT be changed by the user.
•GPIB address (6PIb in AMPS, Addr in VOLTS and GPIB address in KW display). To
change the GPIB address from the front panel, see PAR. 3.10. GPIB address is 33 if
GPIB option is not installed.
•Firmware Version (UEr in AMPS display, Firmware Version in VOLTS display).
•back to Model.
To exit, momentarily depress LOAD pushbutton to restore OFF mode (none of the mode LEDs
are illuminated and the LOAD pushbutton illumination is steady green).
3.8CHANGING IP MODE
When the Mode is OFF (none of the mode LEDs are illuminated), momentarily depressing the
LOAD pushbutton (illumination changes to blinking green) allows configuration information to be
viewed.
NOTE: To abort process without changing the IP Mode, momentarily depress LOAD pushbut-
ton to restore OFF mode (none of the mode LEDs are illuminated and the LOAD pushbutton illumination is steady green).
1. Rotate CONTROL until AMPS display shows IP, VOLTS shows SrCE and KW shows IP
Mode currently selected
2. Momentarily depress CONTROL: the mode shown in KW display blinks.
3. Rotate CONTROL to change IP Mode: USEr (static) or dHcP, then momentarily depress
CONTROL to return to OFF mode (none of the mode LEDs are illuminated and the LOAD
pushbutton illumination is steady green).
3.9CHANGING STATIC IP ADDRESS OR SUBNET MASK
When the Mode is OFF (none of the mode LEDs are illuminated), momentarily depressing the
LOAD pushbutton (illumination changes to blinking green) allows configuration information to be
viewed.
3-4SERIES EL 070312
NOTE: To abort process without changing the address or mask, momentarily depress LOAD
pushbutton to restore OFF mode (none of the mode LEDs are illuminated and the
LOAD pushbutton illumination is steady green).
1. Rotate CONTROL until AMPS, VOLTS and KW show 12 digits (4 groups of 3, referred to as
octets) of IP address or Subnet Mask.
2. Momentarily depress CONTROL; the right three digits of KW display blink (this is the 4th
octet, the right-most three digits of the address). Rotate CONTROL to change digits in KW
display, then momentarily depress CONTROL.
3. The 3rd octet (right two digits of VOLTS display and left digit of KW display) now blinks.
Rotate CONTROL to change digits, then momentarily depress CONTROL.
4. The 2nd octet (right digit of AMPS display and left two digits of VOLTS display) now blinks.
Rotate CONTROL to change digits, then momentarily depress CONTROL.
5. The 1st octet (left three digits of AMPS display) now blinks. Rotate CONTROL to change digits, then momentarily depress CONTROL to return to OFF mode (none of the mode LEDs
are illuminated and the LOAD pushbutton illumination is steady green).
3.10CHANGING GPIB ADDRESS
When the Mode is OFF (none of the mode LEDs are illuminated), momentarily depressing the
LOAD pushbutton (illumination changes to blinking green) allows configuration information to be
viewed.
NOTE: To abort process without changing the GPIB address, momentarily depress LOAD
pushbutton to restore OFF mode (none of the mode LEDs are illuminated and the
LOAD pushbutton illumination is steady green).
1. Rotate CONTROL until AMPS display shows 6PIb, VOLTS shows Addr and KW shows
value of GPIB address.
2. Momentarily depress CONTROL: the address in KW display blinks.
3. Rotate CONTROL to change GPIB address, then momentarily depress CONTROL to return
to OFF mode (none of the mode LEDs are illuminated and the LOAD pushbutton illumination
is steady green).
3.11OPERATION OF MASTER/SLAVE CONFIGURATIONS.
Up to 15 Series EL Electronic Loads may be paralleled for additional current handling capability.
All units must have the same voltage rating. One load is designated as the Master, and the rest
are designated as slaves. Refer to PAR. 2.6.3 for connections.
A Master/Slave combination responds to an *IDN? query with the *IDN string from first the Master and then the Slave(s).
SERIES EL 0703123-5
3.11.1POWER UP
Turn on power to all loads connected as Master/Slave. The units will go through power-up and
reset cycles until all slaves are recognized (this may take a few minutes). NOTE: Power-up time
can be reduced by powering up the slaves 10 to 20 seconds before powering up the master.
•The LOAD button on each Slave Load turns green once the Load completes its diagnostic tests.
•The VOLTS display on the Slave(s) reads SLAU (Slave).
•The LOAD button on the Master Load turns green once the Master Load 1) completes its
diagnostic routine, 2) interrogates the Slave(s) for Master-Slave connection eligibility
and ratings, 3) establishes the overall Master-Slave Load configuration.
3.11.2LOCAL (FRONT PANEL) OPERATION
The Load can be operated from the Master front panel as described in the previous paragraphs
for a single unit. Only the Master Load front panel is active.
3.11.3REMOTE (COMPUTER) OPERATION
If a computer is connected to the Master Load of a master/slave configuration in terminal display
mode, the information shown in Figure 3-2 is displayed at startup (boot).The Master-Slave configuration responds to the SCPI command set described in Appendix A and B.
3.11.4INDICATIONS DURING MASTER/SLAVE OPERATION
The Master Load displays:
•AMPS: Total Current drawn by the Master/Slave configuration
•VOLTS: Voltage applied to each of the Loads
•KW: Total power in kW drawn by the Master/Slave configuration
Slave Load(s) display:
•AMPS: Current drawn by the individual Slave
•VOLTS: reads SLAU showing unit is a slave connected to Master.
•KW: Power in kW drawn by the individual Slave.
3.11.5MASTER/SLAVE CONTROLS AND INDICATORS
Controls and indicators function as described for a single unit, however controls are only active
on the Master Load. Indicators on the Master Load are for Master/Slave configuration. Indicators on the Slave indicate individual Slave Load current and power and Slave status (VOLTS
display reads SLAU). Slave LOAD switch indicators show engaged (amber) or disengaged
(green) status of each slave. Fault indications are displayed on each slave, as well as the master.
Be sure to read and follow the operating instructions described for a single unit and observe all
Cautions and Warnings. A Master/Slave Load configuration is capable of extremely high power
and extremely high currents, thus suitable precautions should be taken when using the Load.
•Use optimal damping (see PAR. 3.14 for setup instructions to optimize damping settings), otherwise use factory default settings.
•Interconnect UUT and Load with cabling designed to minimize inductance. Remember
that rapidly-changing high-currents combined with inductance produces high-voltage
spikes (spikes that can easily damage equipment including the EL Load).
•To minimize spiking and current surges when using computer-controlled remote operation, the best sequence is:
1. Select Mode (e.g. MODE CURR).
2. Select very low value set point (e.g. CURR 0.2).
3. Engage Load (INPUT ON).
4. Slew Load to desired operating set point (e.g. CURR 105).
3.11.7MASTER/SLAVE DISCONNECT
Once units have been operated in a Master/Slave configuration, they must be reconfigured to
restore normal standalone operation. This may be accomplished either from the front panel, or
via a computer interface.
From front panel: Turn power off to all units, then remove all master/slave cables. Power up all
units, wait two minutes, then turn power off and then back on to all units.
From computer interface: After three seconds send DIAG:RST to the master unit. Disconnect
all master slave cables within 10 seconds or turn off all slaves within 10 seconds and then disconnect the slave cables. If power is not cycled on slaves, send CAL:SLAVEMODE 0 followed
by DIAG:RST to each slave. The DIAG:RST command sends back multiple lines of data with
the last line having ### at end to indicate the Reset is complete. The GPIB and Ethernet options
will be available approximately 2 seconds after receipt of the ###.
3.12OPERATION VIA COMPUTER INTERFACE
The computer interface (either USB, RS 232 optional GPIB or optional Ethernet) can be used to
operate the load from a remote location using a computer using IEEE 488.2 and SCPI commands. Refer to Appendices A and B, respectively, for a complete list of applicable commands
and queries. The commands INPut 1 (or ON) or OUTput 1 (or ON) are equivalent to using the
LOAD switch on the front panel to engage the load; the commands INPut 0 (or OFF) or OUTput
0 (or OFF) are used to disengage the load. Figure 3-1 illustrates the commands used to set the
load to operate at 100 Amperes from a 12.5-volt source in the Constant Current mode, engage
the load, then disengage the load.
The GPIB interface is a listener and a talker; it can send and receive commands. The factory
default GPIB address is 10; refer to.Appendix B, PAR. B.68 to change it.
SERIES EL 0703123-7
MODE CURRSets mode to current.
CURR 0.1Sets current level to low level.
INPUT ONCauses load to engage UUT and draw current. LOAD pushbutton illu-
mination changes from green to amber and VOLTS, AMPS and KW
displays show measured parameters.
CURR 100Sets current level to 100 amperes.
MEAS:CURR?Request that Series EL measure current. Unit responds with 100.0.
MEAS:VOLT?Request that Series EL measure voltage. Unit responds with 12.5.
INPUT OFFCauses load to disengage UUT and stop drawing current.
FIGURE 3-1. EXAMPLE OF REMOTE OPERATION
3.13SCPI PROGRAMMING
SCPI (Standard Commands for Programmable Instruments) is a programming language conforming to the protocols and standards established by IEEE 488.2 (reference document
ANSI/IEEE Std 488.2, IEEE Standard Codes, Formats, Protocols, and Common Commands). SCPI
commands are sent to the Series EL Electronic Load as ASCII output strings within the selected
programming language (PASCAL, C, BASIC, LABVIEW, etc.) in accordance with the interface
protocol used.
Different programming languages (e.g., BASIC, C, PASCAL, LABVIEW, etc.) have different
ways of representing data that is to be put on the control bus. It is up to the programmer to
determine how to output the character sequence required for the programming language used.
If the optional IEEE 488.2 (GPIB) interface is used, address information (GPIB address) must
be included before the command sequence.
3.13.1SCPI MESSAGES
There are two kinds of SCPI messages: program messages from controller to electronic load,
and response messages from the electronic load to the controller. Program messages consist of
one or more properly formatted commands/queries and instruct the electronic load to perform
an action; the controller may send a program message at any time. Response messages consist of formatted data; the data can contain information regarding operating parameters, electronic load state, status, or error conditions.
3.13.2COMMON COMMANDS/QUERIES
Common commands and queries are defined by the IEEE 488.2 standard to perform overall
electronic load functions (such as identification, status, or synchronization) unrelated to specific
electronic load operation (such as setting voltage/current). Common commands and queries are
preceded by an asterisk (*) and are defined and explained in Appendix A. Refer also to syntax
considerations (PARs 3.13.3.7 through 3.13.6).
KEPCO, EL 5K-600-200 03-15-2010,A104503,MCB #234 1.219 $ 2010/03/26 12:58:08 $
KEPCO, EL 5K-600-200 03-15-2010,A104503,MCB #234 1.219 $ 2010/03/26 12:58:08 $
MEL (chassis) Serial Number: A104503
Calibration Settings
Calibrated Fullscale Ranges
100V 105000 mV
200V 210000 mV
400V 419900 mV
800V 839800 mV
Cutoffs
Current : 0.200
Voltage : 0.200
Power : 0.003
Max volt limit : 660.0
Max curr limit : 210.0
Max powr limit : 5.250
Setpoint scaling factor: 10.90
Setpoint Calibration Factors
Voltage : 1.050
Current : 1.000
Power : 1.000
Resistance : 1.070
Conductance : 1.000
Fan temperature limits (C)
Lower : 40
Upper : 100
External FB Gain : 2.000
Master Delay : -2000 uSec
Load Calibration
Configuration Information
Note: These are factory
settings and are displayed
should diagnostic
information be required.
FIGURE 3-2. MASTER/SLAVE START-UP, COMPUTER DISPLAY (SHEET 1 OF 2)
SERIES EL 0703123-9
KEPCO, EL 5K-600-200 03-15-2010,A104503,MCB #234 1.219 $ 2010/03/26 12:58:08 $
Chassis Serial Number: A104503
Voltage range : 800V
Current range : 200.0
System damping : 5
PFM damping : 3
Overvoltage limit : 799.0
Undrvoltage limit : 0.000
Overcurrent limit : 600.0
Overpower limit : 6.000
System mode (startup): CURRent
User protection
settings (values
shown are for no
user protection).
Current EL Load
User Settings
Note: This same
information can be
displayed at any time
by entering the SCPI
command:
SYST:SETTING?
System mode (now) : CURRent
Setpoints
Voltage : 660.0
Current : 0.000
Power : 0.000
Resistance : 1000.
Conductance : 0.001
IP Mode : Static
IP Address : 0.0.0.0
User operating
parameter settings
(values shown are for
no current draw at
turn on). Note: Each
parameter is retained
by Mode and is
stored in non-volatile
memory.
Load Dialog During
Process of
recognizing Power
FET Modules found
By Master Control
Board.
Sub Net : 0.0.0.0
Gateway : 0.0.0.0
DNS Addr : 0.0.0.0
Querying Power FET Module 0 [FET Board # 257 in position 0< 0>]
Found Ser# 257 at position 0 of 1
Querying Power FET Module 1 [FET Board # 258 in position 1< 0>]
Found Ser# 258 at position 1 of 2
Querying Power FET Module 2 [FET Board # 259 in position 2< 0>]
Found Ser# 259 at position 2 of 3
Querying Power FET Module 3 [FET Board # 260 in position 3< 0>]
Found Ser# 260 at position 3 of 4
Querying Power FET Module 4 [FET Board # 261 in position 4< 0>]
Found Ser# 261 at position 4 of 5
Querying Power FET Module 5 [FET Board # 262 in position 5< 0>]
Found Ser# 262 at position 5 of 6
Testing for additional Power FET Modules and seeking possible
Querying Power FET Module 6
connections to slave Loads.
Querying Power FET Module 6
Querying Power FET Module 6 ZYX
Discover Slaves
9
Setting serial # 222 as slave #0
8
Discovering Slave Loads
found by Master Load
Load System overcurrent,
overvoltage, under voltage,
overpower Limits
(mA, mV, mV, mW)
Setting serial # 223 as slave #1
7654321
N MCB-Serial Amps Volts Kwatts Ilast Eng Md Setpt Iover Vover Vundr Pover
FIGURE 3-2. MASTER/SLAVE START-UP, COMPUTER DISPLAY (SHEET 2 OF 2)
3-10SERIES EL 070312
3.13.3SCPI SUBSYSTEM COMMAND/QUERY STRUCTURE
Subsystem commands/queries are related to specific electronic load functions (such as setting
voltage, current limit, etc.) Figure 3-3 is a tree diagram illustrating the structure of SCPI subsystem commands used in the EL Series Electronic Load with the “root” at the left side, and specific
commands forming the branches. The following paragraphs introduce the subsystems; subsystem commands are defined and explained in Appendix B.
3.13.3.1DIAGNOSTIC SUBSYSTEM
This subsystem is used to print the SCPI command set.
TABLE 3-2. REMOTE OPERATION COMMAND SUMMARY
CommandFunction
CONTROL COMMANDS. Terminate command with ? to display established mode.
MODE CURRentEnter Constant Current mode
MODE VOLTageEnter Constant Voltage mode
MODE POWerEnter Constant Power mode
MODE RESistanceEnter Constant Resistance mode
MODE CONDuctanceEnter Constant Conductance mode
MODE SHORtEnter Short mode
MODE OFFDisengage load and enable viewing of Model data.
INPut 1 or INPut ON
INPut 0 or INPut OFF (alternatively OUT 0)Disengage load (load OFF)
SET PARAMETER LEVEL COMMANDS. Terminate command with ? to display parameter level.
CURRent <NR2>Set Current level in Amperes
VOLTage <NR2>Set Voltage level in Volts
POWer <NR2>Set Power level in Watts
RESistance <NR2>Set Resistance level in Ohms
CONDuctance <NR2>Set Conductance level in Siemens
MEASUREMENT QUERIES.
MEASure:CURRent?Return Load current in Amperes
MEASure:VOLTage?Return Load voltage in Volts
MEASure:POWer?Return Load power in Kilowatts
MEASure:ALL?Return Load Power, Current and Voltage
PROTECTION COMMANDS. Terminate command with ? to display the protection setting for that mode.
Exceeding these user-defined protection levels disengages the UUT and displays fault indication (see
PAR. 3.3.1.)
CURRent:PROTection <NR2>Set maximum Current level in Amperes
VOLTage:PROTection:OVEr <NR2>Set maximum Voltage level in volts
VOLTage:PROTection:UNDer <NR2>Set minimum Voltage level in volts
POWer:PROTection <NR2>Set maximum load Power in watts
STATUS CLEAR COMMANDS. Trip error prevents INPut 1 or OUTPut 1 from engaging the load. See STATus:QUEStionable register for error definitions (see PAR. 3.13.7.3)
VOLTMETER RANGE COMMANDS. Terminate command with ? to display the range setting. The voltmeter range is determined by the lower of: the range setting below and the lowest range that includes the
current VOLT setting.
SYSTem:RANGe:VOLTage 100VSet Voltage measurement range 0 – 100V
SYSTem:RANGe:VOLTage 200VSet Voltage measurement range 0 – 200V
SYSTem:RANGe:VOLTage 400VSet Voltage measurement range 0 – 400V
SYSTem:RANGe:VOLTage 800VSet Voltage measurement range 0 – 800V
<NR2> = Numeric Values with or without a decimal point. Examples: 0.0156, 15.6, 156 or 1.56E+3 (scientific
notation: digits with decimal point and exponent).
NOTE:If commands that expect a boolean are entered without an argument, the argument is interpreted as 0.
3.13.3.2PROTECTION SUBSYSTEM
This subsystem establishes limits for voltage, current and power.
3.13.3.3[SOURCE:]MEASURE SUBSYSTEM
This query subsystem returns the voltage, current and power measured at the LOAD terminals.
These subsystems set the mode and establish setpoints for each mode. Also establish protection limits and the range of the front panel display (VOLTS, AMPS or KW, respectively) for each
mode.
These subsystems set the mode and establish setpoints for each mode.
3.13.3.7STATUS SUBSYSTEM
This subsystem programs the Series EL status register. The electronic load has two groups of
status registers: Operation and Questionable. Each group consists of three registers: Condition,
Enable, and Event.
3-12SERIES EL 070312
3.13.3.8SYSTEM SUBSYSTEM
This subsystem controls various system functions.
3.13.4PROGRAM MESSAGE STRUCTURE
SCPI program messages (commands from controller to load) consist of one or more message
units ending in a message terminator. The message terminator is not part of the syntax; it is
defined by the way your programming language indicates the end of a line: “newline” must be
defined as CR (0D
) followed by LF (0AH). The message unit is a keyword consisting of a single
H
command or query word followed by a message terminator (e.g., CURR?<newline> or
INPut<end-of-line>). The message unit may include a data parameter after the keyword separated by a space; the parameter is usually numeric (e.g., CURR 5<newline>), but may also be a
string (e.g., OUTP ON<newline>). The following subparagraphs explain each component of the
message structure.
Each command must use the full syntax shown in Appendix B. Each command must be a separate line.
3.13.4.1KEYWORD
Keywords are instructions recognized by a decoder within the EL Series, referred to as a
“parser.” Each keyword describes a command function; all keywords used by the EL Series are
listed in Figure 3-3.
Each keyword has a long form and a short form. For the long form the word is spelled out completely (e.g. STATUS, OUTPUT and VOLTAGE are long form keywords). For the short form only
the first three or four letters of the long form are used (e.g., STAT, OUTP and VOLT). Figure 3-3
shows the short form keywords; both short and long form keywords are found in Appendix B.
3.13.4.2KEYWORD SEPARATOR
If a command has two or more keywords, adjacent keywords must be separated by a colon (:)
which acts as the keyword separator (e.g., SOUR:MEAS:VOLT).
3.13.4.3QUERY INDICATOR
The question mark (?) following a keyword is a query indicator. This changes the command into
a query. If there is more than one keyword in the command, the query indicator follows the last
keyword. (e.g., VOLT? and MEAS:CURR?).
3.13.4.4DATA
Some commands require data to accompany the keyword either in the form of a numeric value
or character string. Data always follows the last keyword of a command or query (e.g.,
SOUR:VOLT:LEV 100 or LOCK OFF.
3.13.4.4.1 MULTIPLE LINE MESSAGES
Some commands return multiple lines of data via the serial or USB port. Each line is separated
by a CR LF sequence. The GPIB and LAN interfaces change the line terminators of multiple line
messages to “CR,” (CR comma). Each line is a different data element. The longest multiple line
message contains 120,000 bytes of information (DIAG:TREE?).
SERIES EL 0703123-13
3.13.4.5DATA SEPARATOR
Data must be separated from the last keyword by a space (e.g., SOUR:VOLT:LEV 100 or
LOCK OFF).
3.13.4.6MESSAGE TERMINATOR
The message terminator defines the end of a message. One message terminator is permitted:
• new line (<NL>) is defined as CR (Carriage Return, 0D
NOTE: The examples shown in this manual assume a message terminator will be added at the
ROOT : (colon)
LOCK subsystem
LOCK
STATus subsystem
STAT
:CHAN?
:OPER
:NTR
:PTR
:QUES
DIAGnostic subsystem
DIAG
:RES
:TREE
) followed by LF (Line Feed, 0AH)
H
end of each message. Where a message terminator is shown it is represented as
<NL> meaning CR (0D
:COND?
:ENAB
:ENAB?
[:EVEN]?
:CSUM?
:ENAB
:ENAB?
[:EVEN]?
:COND?
:ENAB
:ENAB?
[:EVEN]?
:COND?
:ENAB
:ENAB?
[:EVEN]?
:DISP
:SEP
:SEP?
) followed by LF (0AH).
H
[SOURce:] subsystem
[SOUR:]
INP
:PROT
:CLE
INP?
OUTP
:PROT
:CLE
OUTP?
MEAS
:ALL
:ALL2
:CURR
:POW
:VOLT
COND
[:LEV]
[:IMM]
[:AMPL]
[:AMPL?]
:TRAN
:TRAN?
CURR
[:LEV]
[:IMM]
[:AMPL]
[:AMPL?]
:PROT[:LEV]
:STAT 0
:STAT?
:PROT[:LEV]?
:TRAN
:TRAN?
[SOUR:]
POW
[:LEV]
[:IMM]
[:AMPL]
[:AMPL?]
:PROT
:PROT?
:STAT 0
:STAT?
:PROT[:LEV]?
RES
[:LEV]
[:IMM]
[:AMPL]
[:AMPL?]
:TRAN
:TRAN?
VOLT
[:LEV]
[:IMM]
[:AMPL]
[:AMPL?]
:PROT
[:LEV]
:OVE
STAT 0
STAT?
:OVE?
:UND
STAT 0
STAT?
:UND?
:PROT[:LEV]?
:TRAN
:TRAN?
SYSTem subsystem
COMM
[:GPIB]:ADDR
[:GPIB]:ADDR?
:ECHO
:ECHO?
:LAN
:IPAD
:IPAD?
:MAC?
:MODE
:MODE?
:SUBN
:SUBN?
DAMP
DAMP?
ERR?
EXT
EXT?
FAN
FAN?
PFM
PFM?
:LIST?
:STAT?
MODE
MODE?
RAMP
RAMP?
RANG
:CURR
:CURR?
:POW
:POW?
:VOLT
:VOLT?
REPLY
REPLY?
SERN?
SETT?
VERS?
FIGURE 3-3. TREE DIAGRAM OF SCPI COMMANDS USED WITH SERIES EL ELECTRONIC LOAD
3-14SERIES EL 070312
3.13.5UNDERSTANDING THE COMMAND STRUCTURE
Understanding the command structure requires an understanding of the subsystem command
tree illustrated in Figure 3-3. The “root” is located at the top left corner of the diagram. The
parser goes to the root if:
•a message terminator is recognized by the parser
•a root specifier is recognized by the parser
Optionalkeywords are enclosed in brackets [ ] for identification; optional keywords can be omitted and the electronic load will respond as if they were included in the message. The root level
keyword [SOURce] is an optional keyword. Starting at the root, there are various branches or
paths corresponding to the subsystems. The root keywords for the EL Series
:INPut, :OUTPut, [:SOURce], :PROTection, :STATus, and :SYSTem. Because the [SOURce]
keyword is optional, the parser moves the path to the next level, so that VOLTage, CURRent,
and MEASure commands are at the root level.
Each time the parser encounters a keyword separator, the parser moves to the next indented
level of the tree diagram. As an example, the STATus branch is a root level branch that has
three sub-branches: OPERation, CHANnel, and QUEStionable.
A command must contain the short form (the part of the command in capital letters in appendix
B) or the full command. Commands and values are not case sensitive.
Command strings must be sent as a single message at all times. it is possible to send multiple
command/query strings by separating the commands with a CR. If multiple commands and/or
queries are sent this way, each response must be separated by a CR.
are :MEASure,
Commands that change a setting must be preceded or followed by a query. This response must
be accepted by the host prior to sending a new command. Example: volt 10\rvolt?\r\n changes
the voltage setpoint of the EL load (\r is CR and \n is NL).
3.13.6PROGRAM MESSAGE SYNTAX SUMMARY
•Common commands begin with an asterisk (*).
•Queries end with a question mark (?).
•Program messages consist of a root keyword and, in some cases, one or more message
units separated by a colon (:) followed by a message terminator. Several message units
of a program message may be separated by a semicolon (;) without repeating the root
keyword.
•UPPER case letters in mnemonics are mandatory (short form). Lower case letters may
either be omitted, or must be specified completely (long form)
e.g., PROTection (long form) has the same effect as PROT (short form).
•Commands/queries may be given in upper/lower case (long form)
e.g., SoUrCe is allowed.
•Text shown between brackets [ ] is optional.
e.g., :[SOUR:]VOLT[:LEV][:AMPL]? has the same effect as :VOLT?
SERIES EL 0703123-15
3.13.7STATUS REPORTING
The status reporting of the EL Series Electronic Load follows the SCPI and IEEE 488.2 requirements.
3.13.7.1STATUS REPORTING STRUCTURE
The status reporting of the EL uses multiple status register sets, illustrated in Figure 3-4. These
register sets are Channel Status, Channel Summary, Questionable, Operation, Standard Event
and Status Byte/Service Request registers. All registers are 16-bit registers except the Standard
Event and Status Byte/Service Request registers which are 8 bits. The Channel Status, Operation Status and Questionable registers all have condition registers which are associated with
two related registers: an event register which holds unlatched events reported in real-time by
the instrument and is cleared by reading the register, and an enable register which allows the
contents of the event register to be passed through to set the associated condition register.
3.13.7.2STANDARD EVENT STATUS REGISTER
The Standard Event registers contains bits (condition register) is as follows:
•0 - OPC — Operation Complete
•1 - Not Used — always zero.
•2 - QYE — Query Error
•3 - DDE — Device Dependent Error
•4 - EXE — Execution Error
•5 - CME — Command Error
•6 - Not Used — always zero.
•7 - PON — Power On since this bit last read
3-16SERIES EL 070312
FIGURE 3-4. STATUS REPORTING STRUCTURE
SERIES EL 0703123-17
3.13.7.3QUESTIONABLE STATUS REGISTER
The QUEStionable condition register (see Figure 3-4) contains status bits representing unusual
operation such as inconsistent sensor readings or unusual but non-fault conditions.
•0 - Voltage Fault (VF) — 1 indicates the Voltage Fault
•1 - Overcurrent (OC) — 1 indicates overcurrent condition has been detected.
•2 - Not Used — always zero.
•3 - Overpower (OP) — 1 indicates power has exceeded the rated maximum.
•4 - Overtemperature (OT) — 1 indicates overtemperature condition has been detected.
•5 - 7 - Not Used — always zero.
•8 - Not Used — always zero.
•9 - Not Used — always zero.
•10 - Not Used — always zero.
•11 - Not Used — always zero.
•12 - Overvoltage (OV) — 1 indicates overvoltage condition has been detected.
The Channel Summary registers (see Figure 3-4), store the OR’ed output of each Channel status register.
•0 - MASTER
•1 - SLAVE 1
through
•14 - SLAVE 14
•15 - Not Used — always zero.
3.13.7.6STATUS BYTE REGISTER
The Status Byte registers (see Figure 3-4), essentially determine which lower-level summary
conditions can generate a Service Request.
•0 - 1 - Not Used — always zero.
•2 - CSUM — Channel Summary, logical OR of enabled channels in the Channel Sum-
mary registers.
•3 - QUES — Questionable Status, logical OR of enabled conditions in the Questionable
Status registers
•4 - MAV — Message Available, set if an error message is available in the Message
Queue.
•5 -ESB — Event Status Summary, set if an enabled standard event occurs.
•6 - MSS — Master Status Summary.
•7 - OPER — Operation Status Summary, set if an Operation event occurs.
3.14DAMPING
Typical operation for an electronic load involves the flow of high currents. Often these currents
flow through long interconnections. The combination of high, rapidly changing currents and the
inductance associated with connections to the load can cause unexpected results, such as very
high voltage spikes, oscillation or severe ringing (damped oscillations) at the source.
To help reduce these issues, the Series EL offers multiple forms and degrees of damping to
allow the best measurements possible.
There are two forms of damping in the Series EL load: 1) System Damping, which dampens the
response of the main control loop and 2) Mode Damping that dampens effects at the Power FET
Modules by modifying the individual FET loop characteristics. Increased system damping
reduces the tendency for oscillation and reduces response time to high speed transients.
Increased Mode damping decreases the loop's response time to transients. These two damping
functions have a great deal of interplay. For best results, follow the guidelines of PAR. 3.14.1.
3.14.1DAMPING ADJUSTMENTS
The factory default settings for damping sets the overall system damping at maximum and the
Power FET Module damping at mid-level. It should be noted that once changed, these damping
settings are stored in non-volatile memory; the new values are retained until changed again. For
most applications the factory settings should provide optimum damping, however, if you have a
SERIES EL 0703123-19
special situation, damping adjustments are best made using a test set up as shown in Figure 3-
5.
Figure 3-6 shows various waveforms that may appear at the current monitor output (I-Load)
when the load is connected to a high current source and the current drawn from the source
changes rapidly following a square wave (or pulse) source connected to the E-Load input. Figure 3-6 shows the effects of changing both the System Damping and the Mode Damping. The
exact waveforms that will be seen are highly dependent on the nature of the source, the interconnecting cables and the various damping setting.
FIGURE 3-5. DAMPING MEASUREMENT SETUP
Damping adjustments are made using the SCPI Commands found in Appendix B via either the
RS 232 or USB remote interface.
•System Damping. Use SYST:DAMP command (see PAR. B.79).
•Mode Damping. Use SYST:PFM:DAMP (see PAR. B.86).
When modifying the damping settings, a good approach is to start with SYSTem:DAMPing 5
(the factory default) and adjust the Mode Damping from 3 to 2 or 4 while observing the results
on an oscilloscope connected to the I-MON terminals (Figure 3-5). Once the impact of the Mode
Damping adjustments are understood, a change in System Damping may be warranted.
A test plan should anticipate potential conditions that may cause an under-damped response to
transitions. Some basic steps taken at setup may help minimize problems:
•Where possible, use short cables between the source (UUT) and the load.
•Maximize the size of the cables to minimize both resistance and inductance.
3-20SERIES EL 070312
•Twist the positive and negative cables together to provide as much cancelation of inductance as possible.
•When using batteries, ensure they are fully charged when possible. Many styles of batteries (especially lead-acid batteries) have a tendency to oscillate when excited by fast
rise-time transients. The sudden change in current causes the battery plates to warp
slightly, thus changing capacitance which interacts with the inductance of the cables.
FIGURE 3-6. DAMPING WAVEFORMS
3.15ANALOG PROGRAMMING
The Analog PGM input is summed with the digital setpoint value. Applying a positive voltage to
the Analog PGM input increases the digitally determined setpoint, and applying a negative voltage to the Analog PGM input decreases the digitally determined setpoint.
Because the analog signal is summed with the digital setpoint, it must produce a result that is
either 0 or positive, since the load can not control current in the negative direction.
For example, for the EL 5K-400-400 in CI Mode, if the digital setpoint is zero, a 0 to10V signal
applied to the PGM input adjusts the controlled parameter (current) from 0 to full scale (400A).
However, if the digital setpoint is set to 200A, ±5V applied to the Analog PGM input allows current from 0A (-5V) to 400A (+5V).
The effect of the analog signal varies depending on mode selected (limited to CI, CP or CV) and
the range (see Table 3-3).
For Master/Slave configurations, the analog programming signal must be simultaneously
applied to all parallel-connected units.
SERIES EL 0703123-21
TABLE 3-3. ANALOG PROGRAMMING CONTROL VOLTAGE SCALE
MODE
Constant Current (CI)Not Applicable60 Amperes/Volt
Constant
Power
(CP)
Constant
Voltage
(CV)
NOTE: Default voltage measurement setting for CP and CV mode is auto-
range. Use SCPI commands to change ranges (see APPENDIX B).
3.16OPERATOR MAINTENANCE
No scheduled maintenance is required, other than to keep the high current connections tight
and to ensure all airways are clear of obstructions that could cause the load to overheat during
operation at higher power. Calibration Verification should be performed yearly or as required.
RANGE
(SEE NOTE)
100 Volts6 KWatts/Volt
200 Volts12 KWatts/Volt
400 Volts24 KWatts/Volt
800 Volts48 KWatts/Volt
100 Volts10 Volts/Volt
200 Volts20 Volts/Volt
400 Volts40 Volts/Volt
800 Volts80 Volts/Volt
ANALOG CONTROL
The exterior of the load should be cleaned periodically, as is necessary, using a soft cloth dampened with a mild, non-abrasive, water-soluble detergent, and then rinsed with a water-dampened soft cloth.
3-22SERIES EL 070312
APPENDIX A - IEEE 488.2 COMMAND/QUERY DEFINITIONS
A.1INTRODUCTION
This appendix defines the IEEE 488.2 commands and queries used with the Series EL Electronic
Load. These commands and queries are preceded by an asterisk (*) and are defined and explained
in PARs. A-1 through A.13, arranged in alphabetical order. Table A-1 provides a quick reference of
all IEEE 488.2 commands and queries supported in the Series EL Electronic Load. NOTE: Message terminator requires CR and LF (see PAR. 3.13.5).
COMMANDPAR.COMMANDPAR.
*CLSA.2*RSTA.9
*ESE, ?A.3, A.4*SRE, ?A.10, A.11
*ESR?A.5*STB?A.12
*IDN?A.3*WAIA.13
*OPC, ?A.7, A.8
TABLE A-1. IEEE 488.2 COMMAND/QUERY INDEX
A.2*CLS — CLEAR STATUS COMMAND
*CLS
Syntax:*CLS
Description: Clears status data. Clears the following registers without affecting the corresponding Enable Regis-
ters: Standard Event Status Register (ESR), Operation Status Event Register, Questionable Status
Event Register, and Status Byte Register (STB). Also clears the Error Queue.
A.3*ESE — STANDARD EVENT STATUS ENABLE COMMAND *ESE
Syntax:*ESE <integer> where <integer> = positive whole number: 0 to 255 per Table A-2.
Default Value: 0
Description: This command programs the standard Event Status Enable register bits. The contents function
as a mask to determine which events of the Event Status Register (ESR) are allowed to set the ESB
(Event Summary Bit) of the Status Byte Register. Enables the Standard events to be summarized in
the Status Byte register (1 = set = enable function, 0 = reset = disable function). All of the enabled
events of the standard Event Status Enable register are logically ORed to cause ESB (bit 5) of the Status Byte Register to be set (1 = set = enable, 0 = reset = disable)
A.4*ESE? — STANDARD EVENT STATUS ENABLE QUERY *ESE?
Syntax:*ESE? Return value: Integer> value per Table A-2.
Description: Returns the mask stored in the Standard Event Status Enable Register. Contents of Standard
Event Status Enable register (*ESE) determine which bits of Standard Event Status register (*ESR)
are enabled, allowing them to be summarized in the Status Byte register (*STB). All of the enabled
events of the Standard Event Status Enable Register are logically ORed to cause ESB (bit 5) of the
Status Byte Register to be set (1 = set = enable function, 0 = reset = disable function).
A.5*ESR? — EVENT STATUS REGISTER QUERY *ESR?
Syntax:*ESR?
Return value: <integer> (Value = contents of Event Status register as defined in Table A-2.)
Description: Causes the power supply to return the contents of the Standard Event Status register. After it
has been read, the register is cleared. The Standard Event Status register bit configuration is
defined in Table A-2 (1 = set, 0 = reset). The error bits listed in Table A-2 are also related to error
codes produced during parsing of messages and to errors in the load (see PAR. B.81).
•Any 1xx type error sets the Command error bit (5).
•Any 2xx type error sets the Execution error bit (4).
•Any 3xx type error sets the Device error bit (3).
•Any 4xx type error sets the Query error bit (2).
A.6*IDN? — IDENTIFICATION QUERY *IDN?
Syntax:*IDN?
Return value: Character string
Description: Identifies the instrument. This query requests identification. The electronic load returns a string (see
example below) which contains the manufacturer name, the model, the serial number and the firmware level. The character string contains the following fields: <Manufacturer>, <Model> <Warranty
Date>,<Serial Number>,MCB (Main Control Board) Serial number> <Firmware> $ <Date> where:
<Manufacturer> = KEPCO, <Model> =EL model (see Table 1-1), <Firmware = MCB Firmware revision
no.> and <Date> = Date and Time of MCB Firmware compilation.
KEPCO, EL 5K-600-200 03-15-2010,A104503,MCB #234 1.219 $ 2010/03/26 12:58:08 $
A.7*OPC — OPERATION COMPLETE COMMAND *OPC
Syntax:*OPC
Description: Causes load to set status bit 0 (Operation Complete) when pending operations are complete
This command sets Standard Event Status Register bit 0 to “1” when all previous commands have
been executed and changes in output level have been completed. This command does not prevent
processing of subsequent commands, but bit 0 will not be set until all pending operations are completed. (1 = set = enable function, 0 = reset = disable function).
A.8*OPC? — OPERATION COMPLETE QUERY *OPC?
Syntax:*OPC?
Return value: <1> (ASCII) placed in output queue when load has completed operation.
Description: Indicates when pending operations have been completed.When all pending operations are com-
plete (all previous commands have been executed and changes in output level have been completed)
a “1” is placed in the Output Queue. Subsequent commands are inhibited until the pending operations
are completed. *OPC? is intended to be used at the end of a command line so that the application program can monitor the bus for data until it receives the “1” from the Output Queue.
A-2SERIES EL 070312
A.9*RST — RESET COMMAND
Syntax:*RST
Description: Causes system reset of EL Load. *RST causes the unit to be reset as follows.
•VOLT:PROT:OVE Overvoltage protection set to rated overvoltage protection limit of the
Load.
•VOLT:PROT:UND Undervoltage protection set to 0.
•CURR:PROT Current Protection set to rated overcurrent protection limit of the load. or
load system when in Master/slave operation.
•POW:PROT Power protection set to rated overpower protection of the load or load system when in master/slave operation.
•CURR Current set to 0.
•VOLT Voltage set to maximum voltage of load.
•POW Power set to 0.
•RES Resistance set to 1000 ohms.
•COND Conductance set to .001.
•INP Input set to off.
•MODE Mode set to current.
*RST
•SYST:REPLY set to off.
No other features are affected by *RST command.
A.10 *SRE — SERVICE REQUEST ENABLE COMMAND *SRE
Syntax:*SRE <integer> where <integer> = value from 0 - 255 per Table A-3, except bit 6 cannot be pro-
grammed.
Description: Sets the condition of the Service Request Enable register. The Service Request Enable register
determines which events of the Status Byte Register are summed into the MSS (Master Status Summary) and RQS (Request for Service) bits. RQS is the service request bit that is cleared by a serial
poll, while MSS is not cleared when read. A “1” (1 = set = enable, 0 = reset = disable) in any Service
Request Enable register bit position enables the corresponding Status Byte bit to set the RQS and
MSS bits. All the enabled Service Request Enable register bits then are logically ORed to cause Bit 6
of the Status Byte Register (MSS/RQS) to be set.
TABLE A-3. SERVICE REQUEST ENABLE AND STATUS BYTE REGISTER BITS
ESBEvent Status Byte summary
CONDITIONOPER
BIT 7 6543210
VALUE1286432168421
MSS
RQS
ESBMAVQUES CSUMNUNU
MAVMessage available
MSSMaster Status Summary
NU(Not Used)
OPER Operation Status Summary
QUESQUEStionable Status Summary
RQSRequest for Service
SERIES EL 070312A-3
A.11 *SRE? — SERVICE REQUEST ENABLE QUERY *SRE?
Syntax:*SRE?Response: <integer> = value from 0 - 255 per Table A-3.
Description: Reads the Service Enable Register. Used to determine which events of the Status Byte Register are
programmed to cause the power supply to generate a service request (1 = set = function enabled, 0 =
reset = function disabled). Related Commands: *SRE, *STB?
A.12 *STB? — STATUS BYTE REGISTER QUERY *STB?
Syntax:*STB?Response: <integer> value from 0 to 255 per Table A-3.
Description: Reads Status Byte Register without clearing it. This Query reads the Status Byte Register (bit 6 =
MSS) without clearing it (1 = set = function enabled, 0 = reset = function disabled). The register is
cleared only when subsequent action clears all set bits. MSS is set when the power supply has one or
more reasons for requesting service. (A serial poll also reads the Status Byte Register, except that bit
6 = RQS, not MSS; and RQS will be reset.)
A.13 *WAI — WAIT COMMAND *WAI
Syntax:*WAI
Description:Causes the load to wait until all previously issued commands and queries are complete before execut-
ing subsequent commands or queries. This command can be used to guarantee sequential execution
of commands and queries. When all pending operations are complete (all previous commands have
been executed, the WAI command is completed and execution of subsequent commands can continue.
A-4SERIES EL 070312
APPENDIX B - SCPI COMMAND/QUERY DEFINITIONS
B.1INTRODUCTION
This appendix defines the SCPI subsystem commands and queries used with the Series EL
Electronic Load. Subsystem commands are defined in PAR. B.9 through B.100, arranged alphabetically in groups as they appear in the tree diagram, Figure 3-3. Table B-1 provides a quick
reference of all SCPI subsystem commands and queries used in the EL Load. NOTE: Message
terminator requires CR and LF (see PAR. 3.13.5).
The following conventions are used throughout this Appendix.
< > Items in these brackets are parameter abbreviations. Parameters may be numbers or text
<NR1> Simple numbers (without a decimal point) from 0 - 255. Examples: 156, 0 or 1
<NR2 > Numeric Values with or without a decimal point. Examples: 0.0156, 15.6, 156 or 1.56E+3 (scientific
notation: digits with decimal point and exponent)
<txt>Text data. For example, operating modes: CURRent, VOLTage, POWer, RESistance, CONDuctance,
SHORt
<bool>Boolean Data. Examples: 0, 1, OFF or ON. NOTE: If a command expecting a boolean argument is
sent with no argument, the argument is assumed to be 0 (e.g., INPut and INPut 0 are identical).
[ ] Optional keywords are shown in square brackets. For example [SOURce:]INPut:[STATe] <bool>
means SOURce and STATe: may be omitted thus the command is reduced to INP <bool>.
B.3DIAGnostic:RESet COMMAND DIAG:RES
Syntax:Short Form: DIAG:RES Long Form: DIAGnostic:RESet
Description: Allows user to change operation of *RST from SCPI to PPM mode. PPM mode is provided to pro-
vide backward compatibility with earlier versions of EL Load Firmware.
*RST in PPM mode causes a full reboot of the EL load. During the reboot, data is sent by the EL load
to the host interface (similar to that shown in Figure 3-2). The data must be received in order for the EL
load to function normally (this can be as many as 50,000 characters, taking minutes to complete). Wait
at least 200 milliseconds after all data is received before sending any commands to the load. *RST
sets the voltage protection level to 600, Current protection to 600 (or the total current of the system
when slaves are connected), and power protection to 5000 (or 600 multiplied by the total current of
system when slaves are connected). *RST also resets damping to the factory default levels of 5 and 3,
sets SYST:COMM:ECHO to on (see PAR. B.70), and sets SYST:REPLY to off; it does not affect any
set points.
B.4DIAGnostic:TREE:DISPlay COMMAND DIAG:TREE:DISP
Syntax:Short Form: DIAG:TREE:DISP Long Form: DIAGnostic:TREE:DISPlay
Description: Produces text file showing the SCPI command set accessible to the user. The text file is
arranged in columns and can be imported into a spreadsheet application such as Excel for easy viewing. The column separator is determined by DIAG:TREE:SEP command
Syntax:Short Form: DIAG:TREE:SEP? Long Form: DIAGnostic:TREE:SEParator?
Returns <NR1> defines the column separator
Description: Returns the number corresponding to the selected column separator when producing a text
file of the command set using DIAG:TREE:DISP command.
B-2SERIES EL 070312
B.7LOCK COMMAND
Syntax:Short Form: LOCK <lock state> Long Form: LOCK <lock state>
where <lock state> = OFF, EMERgency or LOCKed
Description: Controls functionality of front panel controls. When set to OFF, all front panel controls are fully
functional. When set to EMER, the front panel LOAD switch can only turn the load to the off state; all
other front panel controls except for the POWER switch are disabled. When set to LOCK, all front
panel controls except for the POWER switch are disabled.
LOCK
B.8LOCK? QUERY LOCK?
Syntax:Short Form: LOCK? Long Form: LOCK?
Returns: <lock state> = OFF, EMERgency or LOCKed
Description: Indicates state of front panel controls.
Long Form: [SOURce:]CURRent:PROTection[:LEVel] <NR2>
where: <NR2> = current protection setpoint
Description: Establishes current protection setpoint. Current protection setpoint is stored in non-volatile mem-
ory; value is restored upon power-up. This is a user-defined value which, if exceeded during operation, causes a FAULT condition, forcing the load to disengage.
Long Form: [SOURce:]VOLTage:PROTection:UNDer:STATe[:LEVel]?
where <bool> = 1 (undervoltage protection error occurred)
0 (undervoltage protection error has not occurred)
Description: Indicates whether an undervoltage protection error has occurred (1) or not (0).
B.50 STATus:CHANnel[:EVENt]? QUERY STAT:CHAN?
Syntax:Short Form: STAT:CHAN[:EVEN]? Long Form: STATus:CHANnel[:EVENt]?
Returns: <16 bits> = the value of the Channel event register.
Description: Returns value of Channel event register. Each PFM within a chassis has three Channel registers
associated with it. Bits in the Event register are set whenever the associated condition occurs, and are
cleared only upon an explicit command, thus latching any conditions that occur. See Table B-2 for bit
assignments.
TABLE B-2. CHANNEL STATUS CONDITION,
ENABLE, AND EVENT REGISTER BITS
CONDITIONNUPSOVNUOT OP NU OC VF
BIT14-1513125 - 1143210
VAL UE
16384-
8192 409632-2048168421
32768
NU - NOT USED
OCOVERCURRENT
OPOVERPOWER
OTOVERTEMPERATURE
OV OVERVOLTAGE
PS PROTECTION SHUTDOWN
VF VOLTAGE FAULT
Syntax:Short Form: STAT:CHAN:COND? Long Form: STATus:CHANnel:CONDition?
Returns: <16 bits> = the value of the Channel condition register.
Description: Returns the value of the Channel Condition Register. Each PFM within a chassis has three Chan-
nel registers associated with it. The Condition register reflects the instantaneous state of that PFM.
Bits in the Event register are set whenever the associated condition occurs, and are cleared only upon
an STAT:CHAN:COND 0 command, thus latching any conditions that occur. See Table B-2 for bit
assignments.
Where <NR1> = 16 bits = the value of the Channel enable register.
Description: Sets the Channel Enable Register to determine which bits are allowed to set the channel event
register. Each PFM within a chassis has three Channel registers associated with it. The Enable register selects which of the latched bits in the Event register can propagate to higher-level indicators. See
Table B-2 for bit assignments.
Description: Indicates changes in conditions monitored by Operational Event Register. Returns the value of
the Operation Event register. The Operation Event register is a read-only register which holds
(latches) all events that occur. Reading the Operation Event register clears it.
CME COMMAND ERROR
DDE DEVID DEPENDENT ERROR
EXE EXECUTION ERROR
NU - NOT USED
OPC OPERATION COMPLETE
PON POWER ON SINCE THIS BIT LAST READ
QYE QUERY ERROR
Description: Returns the value of the Operation Condition Register. The Operation Condition Register contains
unlatched real-time information about the operating conditions of the load. Bit set to 1 = function
enabled (active, true); bit reset to 0 = function disabled (inactive, false).
Description: Sets Operation Enable Register. The Operation Enable Register is a mask for enabling specific bits
in the Operation Event Register which will cause the operation summary bit (bit 7) of the Status Byte
register to be set. Bit set to 1 = function enabled (active, true); bit reset to 0 = function disabled (inactive, false). The operation summary bit is the logical OR of all the enabled bits in the Operation Event
register.
Return Value: <NR1> =16 bits = actual Questionable register value
Description: Indicates questionable events that occurred since previous STAT:QUES? query. Returns the
value of the Questionable Event register. The Questionable Event register is a read-only register
which holds (latches) all events. Reading the Questionable Event register clears it.
Return Value: <NR1> =16 bits = actual Questionable condition register value
Description: Returns the value of the Questionable Condition Register. The Questionable Condition Register
contains unlatched real-time information about questionable conditions of the electronic load. Bit set to
1 = condition (active, true); bit reset to 0 = condition (inactive, false). (See example, PAR. B.61.)
determines which conditions are allowed to set the Questionable Condition Register; it is a mask for
enabling
(bit 3) of the Status Byte register to be set. The questionable summary bit is the logical OR of all the
enabled bits in the Questionable Event register. Bit set to 1 = function enabled (active, true); bit reset
to 0 = function disabled (inactive, false)
specific bits in the Questionable Event register that can cause the questionable summary bit
Syntax:Short Form: STAT:QUES:ENAB? Long Form: STATus:QUESionable:ENABle?
Return Value: <NR1> =16 bits = actual Questionable enable register value
Description: Reads Questionable Condition Enable Register. Electronic load returns value of Questionable
Condition Enable Register, indicating which conditions are being monitored. Bit set to 1 = function
enabled (active, true); bit reset to 0 = function disabled (inactive, false)
.
B.68 SYSTem:COMMunicate[:GPIB]:ADDRess COMMAND
Syntax:Short Form: SYST:COMM[:GPIB]:ADDR <NR1>
Long Form: SYSTem:COMMunicate[:GPIB]:ADDRess <NR1>
Where: <NR1> = numbers from 1 to 30 comprising the GPIB Address. Factory default GPIB address
is 10.
Description: Sets the GPIB Address to be used during communication over the GPIB interface. After setting
the address, the EL Load must be power cycled (turned off, then on) in order for the new GPIB
address to take effect. Command is not valid from the GPIB interface.
SYST:COMM[:GPIB]:ADDR
B.69 SYSTem:COMMunicate[:GPIB]:ADDRess? QUERY
SYST:COMM[:GPIB]:ADDR?
Syntax:Short Form: SYST:COMM[:GPIB]:ADDR?
Long Form: SYSTem:COMMunicate[:GPIB]:ADDRess?
Returns: <NR1> = number from 1 to 30 comprising the GPIB Address
Description: Returns the GPIB Address used during communication over the GPIB interface. Command is
Long Form: SYSTem:COMMunication:LAN:MODE [FIXed | DCHP]
Description: Determines method used to obtain IP address for LAN communication.
SYST:COMM:LAN:MODE:FIX (default) configures the LAN port to use a static (fixed) IP address
entered from the front panel. SYST:COMM:LAN:MODE DCHP configures the LAN port for the standard DCHP hub required interface; uses IP address in the 192.168.x.x range compatible with most
default hub configurations.
Long Form: SYSTem:COMMunication:LAN:SUBNetmask <a.b.c.d>
Where: <a, b, c, d> = numbers from 0 to 255 comprising the Subnet Mask
Description: Sets the Subnet Mask to be used during LAN communication.
B-12SERIES EL 070312
B.78 SYSTem:COMMunicate:LAN:SUBNetmask? QUERY
Syntax:Short Form: SYST:COMM:LAN:SUBN?
Long Form: SYSTem:COMMunication:LAN:SUBNetmask?
Returns: <a.b.c.d> = numbers from 0 to 255 comprising the Subnet Mask
Description: Returns the Subnet Mask used during LAN communication.
SYST:COMM:LAN:SUBN?
B.79 SYSTem:DAMPing COMMAND SYST:DAMP
Syntax:Short Form: SYST:DAMP x Long Form: SYSTem:DAMPing x
Where x = integer from 0 (minimum damping) to 7 (maximum damping)
Description: Inserts capacitance required to damp oscillation. Increased damping reduces the tendency for
oscillation and reduces response time to high speed transients. Units are shipped from the factory set
to 4. See PAR. 3.14 for details. Older units only accept settings from 0 to 5. This can be determined
by sending SYST:DAMP 6 and then SYST:DAMP? - if the query returns 6, the unit will accept a maximum of 7; if the query returns 5, the maximum setting is 5.
B.80 SYSTem:DAMPing? QUERY SYST:DAMP?
Syntax:Short Form: SYST:DAMP? Long Form: SYSTem:DAMPing?
Returns x where x = integer from 0 (minimum damping) to 7 (maximum damping)
Description: Returns the damping setting established by SYST:DAMP (PAR. B.79). See PAR. 3.14 for an
explanation of damping. See PAR. B.79 to determine whether the unit will accept a maximum setting
of 5 or 7.
B.81 SYSTem:ERRor? QUERY SYST:ERR?
Syntax:Short Form: SYST:ERR? Long Form: SYSTem:ERRor?
Description: Returns next entry from the error message queue. Responds with the most recent error message
in a queue of up to 10 possible messages and clears each error message as it is sent. Issuing *CLS
clears all error messages in the queue.
Error Message
Command Error Generic -100
Invalid Separator-103
Illegal Parameter Value-224
Invalid Unit Number-241
Queue Overflow-350
No Error-0
Code
B.82 SYSTem:EXTernal COMMAND SYST:EXT
Syntax:Short Form: SYST:EXT <x> Long Form: SYSTem:EXTernal <x>
where <bool> = 0 or OFF for disable, 1 or ON for enable
Description: Enables or disables external analog programming.
B.83 SYSTem:EXTernal? QUERY SYST:EXT?
Syntax:Short Form: SYST:EXT? Long Form: SYSTem:EXTernal?
Returns: <bool> = 0 (disabled) or 1 (enabled)
Description: Indicates whether external analog programming is enabled or disabled.
SERIES EL 070312B-13
B.84 SYSTem:FAN COMMAND SYST:FAN
Syntax:Short Form: SYST:FAN <NR1> Long Form: SYSTem:FAN <NR1>
Where <NR1> = integer, either 0 or 100
Description: SYST:FAN 0 sets fan to off. SYST:FAN 100 sets fan to on.
B.85 SYSTem:FAN? QUERY SYST:FAN?
Syntax:Short Form: SYST:FAN? Long Form: SYSTem:FAN?
Returns <NR1> = 0 or 100
Description: Indicates fan status: 0 = off, 100 = on.
26 C 24 C 24 C 21 C
26 C 25 C 23 C 21 C
26 C 25 C 24 C 22 C
27 C 25 C 24 C 23 C
27 C 25 C 24 C 21 C
27 C 25 C 24 C 21 C
Below is a response to SYST:PFM:STAT? for a 2 PFM Load when the load is drawing 52 Amperes.
Note that these are not highly accurate current measurements but rather are intended to show system
status such as the distribution of current (and therefore power) between the FETs. In the example
below, the top row is the second set of FETs and the bottom row is the first row of FETs. The Currents
are for FETs in each of the four positions as viewed from the front.
104 C 114 C 110 C 104 C
98 C 106 C 100 C 101 C
94 C 93 C 100 C FUSE 91 C
87 C 82 C 86 C 82 C
74 C 76 C 76 C 71 C
SERIES EL 070312B-15
B.90 SYSTem:RANGe:CURRent COMMAND SYST:RANG:CURR
Syntax:Short Form: SYST:RANG:CURR <txt> Long Form: SYSTem:RANGe:CURRent <txt>
Where <txt> = HIGH (HIGH = factory default) or LOW
Description: Establishes range for remote interface current readback and front panel AMPS display. LOW
changes the current range to 1/10 of full scale. If the unit is 200A at full scale, entering
SYST:RANG:LO, changes the ammeter range to 0 - 20A full scale.
B.91 SYSTem:RANGe:CURRent? QUERY SYST:RANG:CURR?
Syntax:Short Form: SYST:RANG:CURR? Long Form: SYSTem:RANGe:CURRent?
Returns: <txt> = HIGH or LOW
Description: Indicates the range for remote interface current readback and front panel AMPS display.
B.92 SYSTem:RANGe:POWer COMMAND SYST:RANG:POW
Syntax:Short Form: SYST:RANG:POW <txt> Long Form: SYSTem:RANGe:POWer <txt>
Where <txt> = HIGH or LOW (LOW = factory default)
Description: Selects one of two power ranges, low (default) or high for remote interface power readback
and KW meter on front panel. The power ranges are a function of the full scale ammeter range.
For example, for a 5 kW load (600A, 50V), the instrument inherently has a 600A full scale range. So
at, for example, the 100V voltmeter range, the dynamic range of power measurement is: (0 - 100V)
x 600A = 0 - 60,000 Watts, much higher than needed. Therefore, when the voltage is high and the
current is low, SYST:RANG:POW LOW restricts the ammeter to 1/10th of full scale and thus, in this
example, limits the maximum power reading to 6,000 Watts.
B.93 SYSTem:RANGe:POWer? QUERY SYST:RANG:POW?
Syntax:Short Form: SYST:RANG:POW? Long Form: SYSTem:RANGe:POWer?
Returns: <txt> = HIGH or LOW (LOW = factory default)
Description: Indicates one of two power ranges, low (1/10 full scale) or high for remote interface power
readback and KW meter on front panel.
B.94 SYSTem:RANGe:VOLTage COMMAND SYST:RANG:VOLT
Syntax:Short Form: SYST:RANG:VOLT <Vrange> Long Form: SYSTem:RANGe:VOLTage <Vrange>
where <Vrange> = 100V, 200V, 400V or 800V
Description: Establishes full scale voltage range of remote interface voltage readback and VOLTS display
on front panel. This setting is saved in non-volatile memory and is retained for subsequent power-up.
B.95 SYSTem:RANGe:VOLTage? QUERY SYST:RANG:VOLT?
Syntax:Short Form: SYST:RANG:VOLT? Long Form: SYSTem:RANGe:VOLTage?
Returns: <Vrange> = 100V, 200V, 400V or 800V
Description: Indicates full scale voltage range for remote interface voltage readback and VOLTS display on
front panel.
B.96 SYSTem:REPLY COMMAND SYST:REPLY
Syntax:Short Form: SYST:REPLY <bool> Long Form: SYSTem:REPLY <bool>
Where <bool> = 0 or OFF = replies off or 1 (or ON) = replies ON
Description: Turns reporting of error messages on (1) or off (0). Turns on/off reporting of error messages gener-
ated when SCPI parser analyses SCPI commands. When set to 0, If command is understood, the EL
load provides the normal or expected response. When set to 1, if command is understood, the EL load
provides the normal or expected response, followed by OK. If the command is not understood, the EL
Load responds with “##” and the appropriate error message is added to the error queue. (see PAR.
B.81 for details).
B-16SERIES EL 070312
B.97 SYSTem:REPLY? QUERY
Syntax:Short Form: SYST:REPLY? Long Form: SYSTem:REPLY?
Returns: <bool> = 0 or 1
Description: Indicates whether error message reporting is on (1) or off (0).
Caution: When the GPIB/LAN interface is installed, SYST:REPLY must be on (1). Turning
SYST:REPLY off (0) will cause all commands to take approximately 1 second to complete, and the
responses to queries will have multiple CR LF pairs in front of the actual response.
SYST:REPLY?
B.98 SYSTem:SERNumber? QUERY SYST:SERN?
Syntax:Short Form: SYST:SERN? Long Form: SYSTem:SERNumber?
Returns: <NR3> where <NR3> = unit serial number
Description: Returns unit serial number.
B.99 SYSTem:SETTings? QUERY SYST:SETT?
Syntax:Short Form: SYST:SETT? Long Form: SYSTem:SETTings?
Returns: <txt> where <txt> = system settings (see below).
Description: Display system settings (see sample response shown below).
Chassis Serial Number: A999104
Voltage range: 400V
Current range: 595.5
System damping: 5
PFM damping: 3
Overvoltage limit: 799.0
Undrvoltage limit: 0.000
Overcurrent limit: 600.0
Overpower limit: 6.000
Max volt limit: 220.0
Max curr limit: 630.0
Max powr limit: 5.250
System mode (startup): CURRent
System mode (now): CURRent
Setpoints
Voltage : 220.0
Current : 0.000
Power : 0.000
Resistance : 1000.
Conductance : 0.255
Fan temperature limits (C)
Lower: 40
Upper: 70
IP Mode : Static
IP Address: 0.0.0.0
Sub Net : 0.0.0.0
Gateway : 0.0.0.0
DNS Addr : 0.0.0.0
B.100 SYSTem:VERSion? QUERY SYST:VERS?
Syntax:Short Form: SYST:VERS? Long Form: SYSTem:VERSion?