KEPCO BOP-GL 1KW Quick Start Guide

QUICK START GUIDE
KEPCO
BOP 1KW-GL POWER SUPPLY
This guide gives a brief introduction to the BOP 1KW­GL Power supply, shows simple load connections, and allows you to verify the power supply is working. The guide also shows you how to perform the most com­monly used functions.
ACCESSING MANUALS. First determine your
Firmware Version (see below), then download the BOP 1KW-GL Operator’s Manual from www.kepcopower.com/support/opmanls.htm#bop-gl
Refer to the BOP 1KW-GL Operator’s Manual for full specifications, installation considerations and oper­ating instructions. The BOP 1KW-GL Operator’s Manual also includes a full description of the digital interfaces and the SCPI command language.
BOP
1KW-GL
FIRMWARE VERSION. With no load connected and power off, use either the GPIB port or RS 232 port (see page 6) to accept remote commands.
If necessary, refer to “Reset Power-up” on page 8 and Figure 5 to configure the GPIB address (default is 6) or configure the RS 232 baud rate (default is
9600).
Apply power to the unit and send *IDN? query. The unit responds with a character string containing the following fields: <Manufacturer>,<Model Voltage­Current Calibration Date>,<Serial Number>, <Firm­ware Version> e.g., KEPCO, BOP1KW 20-50 09/30/ 2001,123456,4.01.
ACCESSING DRIVERS. Drivers are accessed from www.kepcopower.com/drivers/drivers-dl3.htm.
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Equipment Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Preliminary Operational Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Input Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Load Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Local Sensing (Factory Default). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Remote Sensing Select. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Analog I/O Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Trigger Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
GPIB Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
RS 232 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Power-up Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Turning The Power Supply On. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Reset Power-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Normal Power-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Power Supply Basics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Voltage and Current Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Setting Voltage or Current Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Voltage/Current Protect Limits (Limit Channel Software Limits). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Software Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Maximum/Minimum Protection Limits (Software-controlled). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Determining How the Unit Responds when Output is OFF (Load Type). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Configure Load Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Enabling/disabling Output Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Additional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
KEPCO, INC. 131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
093013 228-1699 REV 2 1
http://www.kepcopower.com email: hq@kepcopower.com

I — DESCRIPTION

The BOP 1KW-GL Series hereafter referred to as BOP-GL, are true 4-quadrant programmable voltage and current power supplies, meaning they are capa­ble of both sourcing and sinking power (see Figure
1).
The BOP-GL models have been optimized for exceptionally low current ripple and noise and improved stability (drift and temperature), making them ideal for driving inductive loads such as large magnets or motors. These bipolar power supplies pass smoothly through zero without switching to pro­vide true ± voltage and ± current. These BOP-GL power supplies use switch mode technology for low dissipation. A bi-directional, isolating, a-c input power factor correcting (PFC) circuit recuperates

TABLE 1. BOP-GL 1000 WATT MODEL PARAMETERS

d-c Output Range Closed Loop Gain
Model
1000 WATT MODELS
BOP 10-100GL ±10V d-c ±100A d-c 1.0 10.0
BOP 20-50GL ±20V d-c ±50A d-c 2.0 5.0
BOP 36-28GL ±36V d-c ±28A d-c 3.6 2.8
BOP 50-20GL ±50V d-c ±20A d-c 5.0 2.0
NOTE: When connecting active loads, the steady-state voltage of the active load must not exceed the maximum
voltage rating of the BOP. Otherwise the overvoltage protection will shut down the power supply.
E
O Max
energy sinked from an active load and sends it back into the line to maintain low dissipation.
These BOP power supplies can be controlled remotely by an analog ±10V input for the main chan­nel (voltage or current), and by a +1 to +10V input for the limit channels. They can also be controlled through one of the standard digital interfaces (GPIB or RS 232) to set voltage and current and the four protection limits (+voltage, –voltage, +current and – current.) Output voltage and current can be remotely monitored via the analog monitor signals present at the rear panel Analog I/O Port connector, or by using SCPI commands via either the RS 232 or GPIB ports.
.
I
O Max
Vol tag e
Channel
Current
Channel

II — UNPACKING

This instrument has been thoroughly inspected and tested prior to packing and is ready for operation. After careful unpacking, inspect for shipping damage before attempting to operate. Perform the “Prelimi­nary Operational Check” on page 5. If any indication

TABLE 2. EQUIPMENT SUPPLIED

ITEM FUNCTION
Source Power Entry mating connector Mates with source power entry connector 142-0381 (Kepco) (IEC 320)
PAR/SER CONTROL - IN mating connector
Mating Connector, Trigger Mates with Trigger port. 142-0527 (Kepco)
Mating Connector, Analog I/O Port (15-pin DSUB Connector)
Mates with PAR/SER CONTROL - IN port to allow access to pins required for calibration
Mates with connector for Analog I/O port A2A5J6
of damage is found, file an immediate claim with the responsible transport service.

III — EQUIPMENT SUPPLIED

See Table 2.
PART NUMBER
142-0488 (Kepco)
SP2501 (CUI Stack)
Dsub 15 pin hood
Dsub 15 pin male
108-0374 (Tyco-Amp 207470-1) 142-0449 (Amphenol 17S-DA15P)
KEPCO, INC. 131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
2 228-1699 REV 2 093013

FIGURE 1. BOP-GL OUTPUT CHARACTERISTICS

KEPCO, INC. 131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
093013 228-1699 REV 2 3
http://www.kepcopower.com email: hq@kepcopower.com

IV — ACCESSORIES See Table 3.

TABLE 3. ACCESSORIES

ITEM FUNCTION
Mating Connector, Trigger Mates with Trigger port. 142-0527 (Kepco)
IEEE 1118 (BITBUS) Mating connector
IEEE 488 Cable, (1 meter long) Connects BOP-GL power supply to GPIB bus. SNC 488-1
IEEE 488 Cable, (2 meter long) Connects BOP-GL power supply to GPIB bus. SNC 488-2
IEEE 488 Cable, (4 meter longs)
Line Cord (250V, 20A) Provides connection to a-c mains via Nema 6-20P connector. 118-1087
Line Cord (250V, 20A) Provides connection to a-c mains via Nema L6-20P locking type con-
RS 232 Cable Kit Contains RJ11 to RJ45 Patch cord, RJ 45 Patch cord, two RS 232
RS 232 Adapter (Male pins) Allows RS 232 port to be connected to DTE equipment. (Supplied in
RS 232 Adapter (Female pins) Allows RS 232 port to be connected to a PC (personal computer). (Sup-
15-pin DSUB Connector Mating connector for Analog input connector A2A5J6
IDC 6-pin connector Mating connector for RS-232 PORT, connector A1J5 and PROTEC-
IDC 8-pin plug Mating connector for PAR/SER PROTECT PORT (IN and OUT) con-
Slides Allows easy withdrawal of unit from rack (Model CS 04 includes slides,
Heat Sink Provides adequate cooling for calibration sense resistors. 136-0451
Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco)
Connects BOP-GL power supply to GPIB bus. SNC 488-4
nector.
adapters, one with male pins to connect to DTE equipment and one with female pins to connect to a PC (personal computer), two RS 232 Loop Back test Connectors (one 6-pin and one 8-pin) to test RS 232 communication and aid in isolating RS 232 communication problems.
KIT 219-0436.)
plied in KIT 219-0436.)
Dsub 15 pin hood
Dsub 15 pin male
TION EXT. PORT, connector A2A5J7
nectors.
brackets, all mounting hardware and installation instructions.)
PART NUMBER
SP2501 (CUI Stack)
KMDLA-5P (Kycon Inc.)
118-1088
KIT 219-0436
142-0487
(L-COM RA098M)
142-0506
(L-COM RA098F)
108-0374
(Tyco-Amp 207470-1)
142-0449
(Amphenol 17S-DA15P)
142-0536
(Amphenol 5-555176-3)
142-0535
(Amphenol 5-555176-3)
CS 04

V — SAFETY See Table 4

TABLE 4. SAFETY SYMBOLS

SYMBOL MEANING
CAUTION: RISK OF ELECTRIC SHOCK.
CAUTION: REFER TO REFERENCED PROCEDURE.
!
WARNING INDICATES THE POSSIBILITY OF BODILY INJURY OR DEATH.
CAUTION INDICATES THE POSSIBILITY OF EQUIPMENT DAMAGE.
KEPCO, INC. 131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
4 228-1699 REV 2 093013
http://www.kepcopower.com email: hq@kepcopower.com

VI — PRELIMINARY OPERATIONAL CHECK

A simple operational check after unpacking and before equipment installation is advisable to ascer­tain whether the power supply has suffered damage resulting from shipping.
1. With POWER switch set to off position, connect the power supply to source power (see “Input Connections” below).
2. Verify that the power-up switches at the top cover are set to the factory default positions shown in Figure 5. This establishes GPIB address 6, stand­alone operation, Voltage mode, Analog Input enabled and internal ±current limits enabled and set to maximum.
NOTE: The unit is shipped with load type set to
Active (for inductive loads). To change the load type refer to the “Reset Power-up” on page 8. The logic for Remote on/off input at pin 2 of the Trigger port is set to high (1) or open circuit for output on, low (0) or short circuit for output off.
3. Connect a twisted wire pair (either #24 or #22 AWG) to the mating connector for the Analog I/O port pins 11 and 10. Connect +10V d-c ±0.1mV to pin 11, referenced to pin 10, then install the mat­ing connector on the Analog I/O port at the rear panel.
!
4. Connect the power supply to source power. With no load connected, set POWER switch to the ON position.
5. Each time the unit is turned on an internal self­test is performed. If the unit passes, it initializes with the power-up settings established in step 2 and the front panel POWER/FAULT/LIMIT light is green (power good), the DIGITAL CONTROL light is not lit (analog input enabled) and the VOLT­AGE/CURRENT light is green (voltage mode), MASTER/SLAVE light is green (standalone or master configuration) and the OUTPUT ON light is lit (output enabled). If the front panel POWER/ FAULT/LIMIT light is red, the unit has failed self­test; contact Kepco for further instructions. If the unit beeps, or the MASTER/SLAVE or VOLTAGE/ CURRENT light blinks, refer to the BOP-GL Oper­ator Manual for troubleshooting.
6. Connect a digital voltmeter (DVM) with resolution and accuracy of 0.01% or better to the OUT S and COM S terminals at the rear panel terminal block.
7. Verify DVM voltage reading matches the nominal voltage of the unit within 0.01% of rated maximum voltage.
CAUTION:
DO NOT repeatedly toggle the POWER circuit breaker/switch as this may damage the unit.

VII — INSTALLATION

Install units either on a bench or in a 19 inch-wide rack. For rack mounting: first remove four feet; rack must provide support at the rear. Optional slides may be used. Leave the front and rear panels clear of obstructions to ensure adequate cooling.

INPUT CONNECTIONS. Source power is con­nected to the power supply via three-wire input power using the source power mating connector supplied (see Table 3). This power supply operates from single phase a-c mains power (or between two phases of 3-phase a-c mains power), 230V, 50/60Hz nominal (range: 176 - 264V, 47-63Hz) without any need for range selection. The user must provide a properly sized and rated mains lead (line cord) and service with a current rating compatible with the required input current. Line cords available as accessories are listed in Table 3. Plug the source power connector into the source power inlet connec­tor at the rear panel.

KEPCO, INC. 131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
093013 228-1699 REV 2 5

LOAD CONNECTIONS.

CAUTION:
!
Before connecting a load, verify that power up switch settings (see “Power-up Settings” on page 8) are compatible with your load.
Power connections require wires that are properly rated for the nominal output current of the unit. Con­nect the load to the OUTPUT and COMMON power terminals on the rear panel (see Figure 3). OUT S and COM S terminal of the Monitor and Sensing Ter­minal block are for connection of remote sensing leads (after removing the factory-installed local sensing links). NOTE: Output Sense lines must be
connected for proper operation, either locally, or at the load (remote). Also use OUT S and COM S
to monitor voltage at the load using external equip­ment such as a DVM, oscilloscope, etc. Use OUT
Loading...
+ 11 hidden pages