KEPCO BOP 200W, BOP 100-1, BOP 20-10, BOP 36-6, BOP 50-4 Operator's Manual

...
Page 1
OPERATOR’S MANUAL
BOP (M) (D) 100W, 200W, 400W
BIPOLAR POWER SUPPLY
100W: BOP 20-5, BOP 50-2, BOP 100-1
200W: BOP 20-10, BOP 36-6, BOP 50-4, BOP 72-3, BOP 100-2, BOP 200-1
400W: BOP 20-20, BOP 36-12, BOP 50-8, BOP 72-6, BOP 100-4
KEPCO INC.
An ISO 9001 Company.
MODEL
BOP 100W, 200W, 400W
POWER SUPPLY
IMPORTANT NOTES:
1) This manual is valid for the following Model and associated serial numbers:
MODEL SERIAL NO. REV. NO.
2) A Change Page may be included at the end of the manual. All applicable changes and revision number changes are documented with reference to the equipment serial num­bers. Before using this Instruction Manual, check your equipment serial number to identify your model. If in doubt, contact your nearest Kepco Representative, or the Kepco Docu­mentation Office in New York, (718) 461-7000, requesting the correct revision for your par­ticular model and serial number.
3) The contents of this manual are protected by copyright. Reproduction of any part can be made only with the specific written permission of Kepco, Inc.
Data subject to change without notice.
©2013, KEPCO, INC.
P/N 243-1308-r5a
KEPCO, INC. z 131-38 SANFORD AVENUE z FLUSHING, NY. 11355 U.S.A. z TEL (718) 461-7000 z FAX (718) 767-1102
KEPCO®
THE POWER SUPPLIER™
email: hq@kepcopower.com z World Wide Web: http://www.kepcopower.com
Page 2
Page 3
INSTRUCTION MANUAL CORRECTION
KEPCO®
THE POWER SUPPLIER™
LOAD REACTANCE, PARAGRAPH 1-10D, add the following:
There are two means of eliminating oscillation in the current loop operating with moderate inductive loads and moderate voltage and current:
1. Add capacitance in parallel with the output (inductive load). The value of capacitor can be from 0.1 uF to 1.0 uF depending on the value of the load inductance.
2. Add a series-connected resistor capacitor network in parallel with the output (inductive load). The value of resistor should be in the range of 100 to 500 Ohms and the value of capacitor should be 0.1 uF to 0.5 uF, depending on the load inductance value.
Both options are recommended when the BOP is used with very low frequency output into inductive loads.
NOTE:BOP 200W and 400W units may be converted to ML units in order to eliminate oscilla-
tion when dealing with a large range of inductive load values. This upgrade must be accomplished at the Kepco factory in Flushing New York and includes component changes and re-calibration of the unit. Please contact Kepco Sales for price and delivery schedule regarding this upgrade.
KEPCO MODELS: BOP 100W, BOP 200W, BOP 400W
When driving heavy inductive loads with high currents, it is possible for the BOP and the load to be damaged by an A-C input power loss which prevents the load's stored energy from being dissipated inside the BOP. To avoid possible damage observe the following:
Use UPS to supply the BOP.
Set BOP output current and/or voltage to zero and turn off the BOP after the output current actually reaches a zero value.
Use properly rated (voltage and current) bipolar transorbs or a properly rated bipolar crow­bar element connected directly at the output of the BOP. An alternative is an A-C Normally Closed Contactor connected directly at the output of the BOP. These options may also be combined.
BOP/093013
KEPCO, INC. z 131-38 SANFORD AVENUE z FLUSHING, NY. 11355 U.S.A. z TEL (718) 461-7000 z FAX (718) 767-1102
email: hq@kepcopower.com z World Wide Web: http://www.kepcopower.com
1
Page 4
AFTER PAR. 3-3 B) LOAD CONNECTION (I) and PAR. 3-3 C) LOAD CONNECTION (II) add the following:
Load connections to the BOP power supply are achieved via the OUTPUT and COMMON ter­minals located on either the front or the rear panel, but not both. Sense connections must be made from the same location (front or rear panel) as the output and common connections.
AFTER PAR. 3-3 D) A-C GROUND add the following:
The GROUND terminal is connected to CHASSIS of the unit and to the local EARTH-GROUND potential through the A-C power line cord. It can be used a) as a monitoring reference point, b) as a grounding point for the output of the unit, and c) for doubling the a-c power cord EARTH­GROUND connection if necessary by providing a separate connection to the local EARTH­GROUND point.
CAUTION: NEVER CONNECT THE BOP OUTPUT TERMINAL (OR THE LOAD TERMINAL TIED TO
THE OUTPUT TERMINAL) TO EARTH-GROUND. OTHERWISE, IF THE CONTROLLING DEVICE IS GROUNDED, THE BOP CAN BE DAMAGED BY THE OUTPUT LIMIT CUR­RENT FLOWING INSIDE THE BOP ALONG THE PROGRAMMING SIGNAL RETURN PATH.
CAUTION: DO NOT CONNECT BOTH THE LOAD AND THE PROGRAMMING DEVICE RETURN
(COMMON) TO EARTH-GROUND POTENTIAL AND DO NOT USE THE PROGRAMMING RETURN TERMINAL AS A TAP POINT FOR THE LOAD RETURN. OTHERWISE, IF THE COMMON POWER CONNECTION BETWEEN THE BOP AND THE LOAD IS LOST, THE BOP CAN BE DAMAGED BY OUTPUT CURRENT FLOWING INSIDE THE BOP ALONG THE PROGRAMMING SIGNAL RETURN PATH.
CAUTION: DO NOT USE THE PROGRAMMING RETURN TERMINAL AS A TAP POINT FOR THE
LOAD RETURN BECAUSE THE BOP CAN BE DAMAGED BY OUTPUT CURRENT FLOWING INSIDE THE BOP ALONG THE PROGRAMMING SIGNAL RETURN PATH.
AFTER PAR. 3-3 E) D-C (SIGNAL) GROUND add the following:
The GROUNDING NETWORK terminal is tied to GROUND (CHASSIS) terminal through a series capacitor-resistor network. Connecting the GROUNDING NETWORK terminal to the COMMON terminal reduces common noise current flowing through the load and, if a BIT card is installed, it ensures that the dynamic swing of the output does not affect the digital section.
AFTER PAR. 3-3 J) EXTERNAL LEADS add the following:
K) EXTERNAL VOLTAGE MONITOR. Use signal E
Monitor Output at pin 20 of the PC12 pro-
O
gramming connector (see Figure 4-5) for external voltage monitoring. Caution should be exer­cised in handling this signal: use a series 5K resistor in combination with a high impedance monitoring device, or an external high impedance buffer between the BOP and the monitoring device. This signal is buffered by OPAMP IC23 (see Figure 6-4) which functions as a repeater for the signal coming from the RN3 matched pair divider connected at the output. There is no overvoltage protection. This stage is protected against short-circuit by the intrinsic protection of the OPAMP generating this signal. This signal is used by the BIT card if it is installed.
2
Page 5
L) EXTERNAL CURRENT MONITOR. Use signal IO Sensing Output at pin 10 of the PC12 pro­gramming connector (see Figure 4-5) for external current monitoring. This signal is not buff­ered. Use a series 5K resistor in combination with a high impedance monitoring device, or an external high impedance buffer between the BOP and the monitoring device. CAUTION: An
accidental short-circuit at this terminal while the unit is in Current mode or Current limit mode will damage the BOP power stage. There is no overvoltage protection. This stage is
protected against short-circuit by the intrinsic protection of the OPAMP generating this signal. This signal is used by the BIT card if it is installed.
DIGITAL CONTROL OF BOP POWER SUPPLIES, PARAGRAPH 3-46 add the following:
The SN and SNR Programmers and the BIT 488 cards described in this manual are older meth­ods of controlling BOP power supplies via digital means. Although these products still function as described, the recommended method of digital control is now the use of Kepco’s BIT 4886 16-bit plug-in card with resolution of 1/2
16
. This plug-in card provides talk-listen support for the IEEE 488.2 bus using SCPI commands. The BIT 4886 card allows a BOP to communicate as a stand-alone instrument, directly on the GPIB. The BIT 4886 card also allows the BOP to be pro­grammed over the RS232C bus using either SCPI or CIIL commands via either an RS232-C terminal, or from a PC using a terminal emulation program with a baud rate of 9600, no parity, eight data bits and one stop bit. The downloadable BIT 4886 driver supports digital calibration (no manual pots) and multiple control and read-back ranges, For more information refer to: www.kepcopower.com/bit.htm.
PERIODIC MAINTENANCE, PARAGRAPH 5-6, add the following:
To clean the unit, proceed as follows:
1. Disconnect the unit from mains power.
2. Using a damp, lint-free cloth, wipe the exterior of the unit to remove accumulated dirt.
3. Reconnect AC power to the unit.
MASTER/SLAVE PARALLEL CONNECTIONS, PARAGRAPH 3-44, add the following:
For two or more two parallel units, refer to Figure 3-27A, below. This configuration is more sta­ble and accurate than the simple configuration shown in Figure 3-27; it eliminates the parasitic voltage drop on the COM connection of the slaves.
3
Page 6
PART OF
PC 12
28
C
22
10
TWIST
PART OF
PC 12
44
43
28
C
22
10V
+
+
10V
MASTER
(EXT.) R1A
(EXT.) R2A
NOTE 3
10V
+
+
10V
20K
20K
PART OF
OFF
ON
VOLTAGE
CONTROL
VOLTAGE
PROGRAMMING
INPUT
NOTE 3
(EXT.) R1B
(EXT.) R2B
OFF
ON
CURRENT CONTROL
PC 12
20K
20K
10K
10K
10K
7
9
11
C
CONTROL CHANNEL
C
PART
OF
PC 12
4
13
15
C
CONTROL CHANNEL
NOTES (MASTER):
10K
-
PREAMP
"A"
+
ZERO
-
17
Eo COMP
AMP
+
BOP VOLTAGE
NOTES (SLAVE 1):
1. MODE Switch position to: CURRENT
2. CURRENT CONTROL Switch to: OFF
3. R1 (A and B) and R2 (A and B) are matched pairs, 0.01% tolerance, metal film, 0.25W.
4. Remove PC 12 jumpers between pins 4 and 13 and between pins 15 to 27.
10K
-
PREAMP
"B"
+
ZERO
BOP CURRENT
1. For Voltage Mode (shown) set MODE Switch to VOLTAGE and VOLTAGE CONTROL Switch to ON.
2. For Current mode, set MODE Switch to CURRENT and CURRENT CONTROL Switch to ON.
3. If external control is needed, set the CONTROL switch to OFF and use either the corresponding VOLTAGE or CURRENT
5
PROGRAMMING INPUT or the appropriate PC 12 terminals.
DRIVER
G A T E
Io SENSING
Eo ZERO
2
AMP
19
-
+
COMMON
-
Io COMP
AMP
+
POWER
STAGE
Io ZERO
POWER
STAGE
G A T E
R
SCOM
DRIVER
R
OUT
OUT
COMS
S
REMOVE
LINKS
S
S
TWIST
LOAD
TWIST
DRIVER
R
S
OUT
COM
S
S
S
TWIST
GENERAL NOTES:
1. SYSTEM IS SET IN VOLTAGE MODE, LOCAL CONTROL, REMOTE SENSING.
2. FOR MASTER AND SLAVE(S) PIN C OF PC 12 CONNECTOR IS THE "C" POINT (COMMON), AND IS AVAILABLE AT PINS 23, 25, 27, 29, 31 AND 33 OF THE PC 12 CONNECTOR.
3043677
TWIST
PART OF
PC 12
44
43
28
C
22
SLAVE 1
(EXT.) R1A
20K
(EXT.) R2A
20K
NOTE 3
10V
+
+
10V
SLAVE 2
OFF
ON
NOTE 3
(EXT.) R1B
CURRENT CONTROL
20K
(EXT.) R2B
20K
10K
PART OF
PC 12
C
4
13
15
C
NOTES (SLAVE 2):
1. MODE Switch position to: CURRENT.
2. CURRENT CONTROL Switch to: OFF.
3. R1 (A and B) and R2 (A and B) are matched pairs, 0.01% tolerance, metal film, 0.25W.
4. Remove PC 12 jumpers between pins 4 and 13 and between pins 15 to 27.
10K
-
PREAMP
"B"
+
ZERO
BOP CURRENT
CONTROL CHANNEL
19
-
Io COMP
+
2
COMMON
AMP
Io ZERO
COMMON
POWER
STAGE
G A T E
FIGURE 3-27A. ALTERNATIVE MASTER/SLAVE PARALLEL CONNECTION (FOR MORE PRECISE AND
STABLE CONTROL) OF TWO OR MORE BOP POWER SUPPLIES
4
Page 7
Declaration of Conformity
Application of Council directives:
Standard to which Conformity is declared:
EN61010-1:2001 (Safety requirements for electrical equipment for measurement,
control and laboratory use - Part 1)
Manufacturer's Name and Address:
Importer's Name and Address:
Type of Equipment:
Model No.:
73/23/EEC (LVD) 93/68/EEC (CE mark)
KEPCO INC. 131-38 SANFORD AVENUE FLUSHING, N.Y. 11355 USA
P
O
C
E
V
I
T
A
T
N
E
S
E
R
P
E
R
Component Power Supply
[PRODUCT MODEL NUMBER]
Y
Year of Manufacture:
I, the undersigned, declare that the product specified above, when used in conjunction with the condi­tions of conformance set forth in the product instruction manual, complies with the requirements of the Low Voltage Directive 73/23/EEC, which forms the basis for application of the CE Mark to this product.
Place: KEPCO Inc.
131-38 Sanford Ave. Flushing, N.Y.11352 USA
Saul Kupferberg
(Full Name)
Date:
228-1348 DC-COMP/INST 062810 A
VP OF SALES
(position)
Page 8
Conditions of Conformance
When this product is used in applications governed by the requirements of the EEC, the following restric­tions and conditions apply:
1. For European applications, requiring compliance to the Low Voltage Directive, 73/23/EEC, this power supply is considered a component product, designed for "built in“ applications. Because it is incom­plete in construction, the end product enclosure must provide for compliance to any remaining electri­cal safety requirements and act as a fire enclosure. (EN61010-1:2010, Cl. 6, Cl. 7, Cl.8, and Cl. 9)
2. This power supply is designed for stationary installation, with mains power applied via a detachable power supply cord or via direct wiring to the source power terminal block.
3. This power supply is considered a Class 1 (earthed) product, and as such depends upon proper con­nection to protective earth for safety from electric shock. (EN61010-1 Cl. 6.5.5)
4. This power supply is intended for use as part of equipment meant for test, measurement and labora­tory use, and is designed to operate from single phase, three wire power systems. This equipment must be installed within a suitably wired equipment rack, utilizing a three wire (grounded) mains con­nection. See wiring section of this manual for complete electrical wiring instructions. (EN61010-1 Cl.
6.5.5 and Cl.6.10.1)
5. This power supply has secondary output circuits that are considered hazardous, and which exceed 240 VA at a potential of 2V or more.
6. The output wiring terminals of this power supply has not been evaluated for field wiring and, therefore, must be properly configured by the end product manufacturer prior to use.
7. This power supply employs a supplementary circuit protector in the form of a circuit breaker mounted on the front panel. This circuit breaker protects the power supply itself from damage in the event of a fault condition. For complete circuit protection of the end product, as well as the building wiring, it is required that a primary circuit protection device be fitted to the branch circuit wiring. (EN61010­1:2010, Cl. 9.6)
8. Hazardous voltages are present within this power supply during normal operation. All operator adjust­ments to the product are made via externally accessible switches, controls and signal lines as speci­fied within the product operating instructions. There are no user or operator serviceable parts within the product enclosure. Refer all servicing to qualified and trained Kepco service technicians.
B 228-1351 COND/CONFORM 100913
Page 9
SAFETY INSTRUCTIONS
1. Installation, Operation and Service Precautions
This product is designed for use in accordance with EN 61010-1 and UL 3101 for Installation Category 2, Pollution Degree 2. Hazardous voltages are present within this product during normal operation. The product should never be operated with the cover removed unless equivalent protection of the operator from accidental contact with hazardous internal voltages is provided:
!
!
!
There are no operator serviceable parts or adjustments within the product enclosure. Refer all servicing to trained service technician.
Source power must be removed from the product prior to performing any servicing.
This product is factory-wired for the nominal a-c mains voltage indicated on the rat­ing nameplate located adjacent to the source power connection on the product's rear panel. To reconfigure the product input for other nominal mains voltages as listed herein, the product must be modified by a trained service technician.
2. Grounding
This product is a Class 1 device which utilizes protective earthing to ensure operator safety.
The PROTECTIVE EARTHING CONDUCTOR TERMINAL must be properly con-
!
nected prior to application of source power to the product (see instructions on instal­lation herein) in order to ensure safety from electric shock.
PROTECTIVE EARTHING CONDUCTOR TERMINAL - This symbol indicates the point on the product to which the protective earthing conductor must be attached.
EARTH (GROUND) TERMINAL - This symbol is used to indicate a point which is connected to the PROTECTIVE EARTHING TERMINAL. The component installer/ assembler must ensure that this point is connected to the PROTECTIVE EARTH­ING TERMINAL.
CHASSIS TERMINAL -This symbol indicates frame (chassis) connection, which is supplied as a point of convenience for performance purposes (see instructions on grounding herein). This is not to be confused with the protective earthing point, and may not be used in place of it.
3. Electric Shock Hazards
This product outputs hazardous voltage and energy levels as a function of normal operation. Operators must be trained in its use and exercise caution as well as common sense during use to prevent accidental shock.
This symbol appears adjacent to any external terminals at which hazardous voltage
!
228-1352 SAFETY - (COVER REMOVAL) 062810 C/(D BLANK)
levels as high as 500V d-c may exist in the course of normal or single fault condi­tions.
This symbol appears adjacent to any external terminals at which hazardous voltage levels in excess of 500V d-c may exist in the course of normal or single fault condi­tions.
Page 10
Page 11
Page 12
Page 13
Page 14
Page 15
Page 16
Page 17
Page 18
Page 19
Page 20
Page 21
Page 22
Page 23
Page 24
Page 25
Page 26
Page 27
Page 28
Page 29
Page 30
Page 31
Page 32
Page 33
Page 34
Page 35
Page 36
Page 37
Page 38
Page 39
Page 40
Page 41
Page 42
Page 43
Page 44
Page 45
Page 46
Page 47
Page 48
Page 49
Page 50
Page 51
Page 52
Page 53
Page 54
Page 55
Page 56
Page 57
Page 58
Page 59
Page 60
Page 61
Page 62
Page 63
Page 64
Page 65
Page 66
Page 67
Page 68
Page 69
Page 70
Loading...