KEPCO BOP 5-20DL Operator's Manual

Page 1
MODEL
OPERATOR’S MANUAL
KEPCO INC.
ORDER NO. REV. NO.
BOP 5-20DL
BIPOLAR OPERATIONAL POWER SUPPLY
100W, 200W AND 400W
BOP 5-20DL
POWER SUPPLY
Page 2
Page 3
TABLE OF CONTENTS
SECTION PAGE
SECTION 1 - INTRODUCTION
1.1 Scope of Manual......................................................................................................................................... 1-1
1.2 General Description.................................................................................................................................... 1-1
1.3 Electrical Specifications, General............................................................................................................... 1-1
1.3.1 Static Specifications................................................................................................................................ 1-5
1.3.2 Dynamic Specifications........................................................................................................................... 1-6
1.4 Miscellaneous Features.............................................................................................................................. 1-6
1.4.1 Output Range.......................................................................................................................................... 1-6
1.4.2 Rear Programming Features................................................................................................................... 1-7
1.4.3 Output ON-OFF Port............................................................................................................................... 1-8
1.4.4 Load Reactance...................................................................................................................................... 1-10
1.4.5 Remote Turn-off...................................................................................................................................... 1-10
1.4.6 Circuit Breaker Shutdown Prevention (at Power Loss) Circuit................................................................ 1-10
1.4.7 References.............................................................................................................................................. 1-10
1.4.8 Series Or Parallel Operation ................................................................................................................... 1-10
1.4.9 Voltage Control Channel......................................................................................................................... 1-11
1.4.10 Mode Switch ............................................................................................................................................ 1-11
1.4.11 Current Control Channel ......................................................................................................................... 1-11
1.4.12 Bounding................................................................................................................................................. 1-11
1.4.13 Mode Lights............................................................................................................................................. 1-12
1.4.14 Remote Output ON-OFF LED................................................................................................................. 1-12
1.4.15 Standards................................................................................................................................................ 1-12
1.5 Mechanical Specifications .......................................................................................................................... 1-12
1.6 Equipment Supplied.................................................................................................................................... 1-12
Page 4
TABLE OF CONTENTS
SECTION PAGE
3.4.2 Remote Voltage Control Using Resistance (Decade Box) ..................................................................... 3-10
3.4.3 Remote Voltage Control Using D-C Signal Voltage................................................................................ 3-11
3.4.4 Using the BOP as a Voltage Amplifier.................................................................................................... 3-12
3.4.5 Remote Control of Current Limiting........................................................................................................ 3-14
3.5 Remote Control of Current Control Channel.............................................................................................. 3-15
3.5.1 Remote Current Control Using Resistance (Potentiometer)................................................................... 3-16
3.5.2 Remote Current Control Using Resistance (Decade Box)...................................................................... 3-16
3.5.3 Remote Current Control Using D-C Signal Voltage................................................................................ 3-17
3.5.4 Using the BOP as a Current Amplifier.................................................................................................... 3-18
3.5.5 Remote Control of Voltage Limiting........................................................................................................ 3-19
3.6 Series and Parallel Connection of BOP Power Supplies........................................................................... 3-20
3.6.1 Series Connection, Master/slave Operation........................................................................................... 3-21
3.6.2 Circuit Breaker Control Circuit................................................................................................................ 3-22
3.6.3 Parallel Connection, Master/Slave Operation......................................................................................... 3-23
3.7 Indicator And Flag Logic Circuit................................................................................................................. 3-27
3.8 Digital Control of BOP Power Supplies...................................................................................................... 3-28
SECTION 4 - INTERNAL ADJUSTMENTS AND CALIBRATION
4.1 General...................................................................................................................................................... 4-1
4.2 Equipment Required .................................................................................................................................. 4-1
4.2.1 Adjustment of (±) 10 Volt Calibration Controls (A1R31, A1R32)............................................................ 4-2
4.2.2 Uncommitted Amplifier “A” Zero Adjustment (A1R41)............................................................................ 4-3
4.2.3 Uncommitted Amplifier “B” Zero Adjustment (A1R42)............................................................................ 4-3
4.2.4 Adjustment of Ammeter Zero Control (A1R50)....................................................................................... 4-3
Page 5
LIST OF FIGURES
FIGURE TITLE PAGE
1-2 BOP Output Characteristic............................................. .. ........................................................................... 1-6
1-3 BOP Output WaveForm with Phase Shift................................................................................................... 1-7
1-4 Boundaries and Limits ................................................................................................................................ 1-11
1-5 Mechanical Outline Drawing, BOP 5-20DL................................................................................................. 2-15
2-1 BOP 5-20DL, Terminations and Controls, Front Panel............................................................................... 2-1
2-2 BOP Terminations and Controls, Rear Panel ............................................................................................. 2-3
2-3 A-C Source Voltage Selection .................................... .................................................. .............................. 2-3
2-4 Slide Installation on Full-rack Units............................................................................................................. 2-7
2-5 Load Connection Using Local Sensing at Rear Panel.................................................. .............................. 2-9
2-6 Load Connection Using Local Sensing at Front Panel ............................................................. .. ... ............. 2-9
2-7 Load Connection Using Remote Sensing at Rear Panel............................................................................ 2-10
2-8 Load Connection Using Remote Sensing at Front Panel ........................................................................... 2-10
3-1 Rear Programming Connector Terminals .......................................................... ... ...................................... 3-2
3-2 BOP Voltage Control Channel (Local Control, Local Sensing)................................................................... 3-4
3-3 BOP (±) Current Limiting Circuit (Local Control, Local Sensing) ................................................................ 3-6
3-4 BOP Current Control Channel (Local Control, Local Sensing) ................................................................... 3-7
3-5 BOP (±) Voltage Limiting Circuit (Local Control, Local Sensing) ................................................................ 3-8
3-6 Remote Potentiometer Control of D-C Output Voltage............................................................................... 3-9
3-7 Remote D-C Output Voltage Control Using Two-Terminal Resistance (Decade)....................................... 3-10
3-8 Digital Control of the D-C Output Voltage................................................................ ................................... 3-11
3-9 D-C Output Voltage Control with Non-inverting Configuration and High Impedance ±1V Signal Source... 3-12
3-10 Graphs Of Possible Input/output Waveshapes........................................................................................... 3-13
3-11 Basic Programming Circuit for Use of BOP as Bipolar Amplifier (Voltage Mode)....................................... 3-13
3-12 Programming Circuit for Driving Output Voltage with.................................................................................. 3-14
Page 6
LIST OF TABLES
TABLE TITLE PAGE
1-1 General Specifications ...............................................................................................................................1-2
1-2 Output Range and Output Impedance ....................................................................................................... 1-4
1-3 Static Specifications: Output Effects, Offsets, And Reference Specifications ............................................1-5
1-4 Dynamic Specifications for Nominal Resistive Load ..................................................................................1-6
1-5 Dynamic Specifications, in Current Mode for 2mH Inductive Load ............................................................1-6
1-6 Rear Programming Connector Terminal Functions ....................................................................................1-7
1-7 Output ON-OFF Port A2J211, Pin Assignments ............................ ............................................................1-9
1-8 Current Loop Bandwidth Reduction by Adding Compensation
Capacitor to Rear Programming Connector (Resistive Load) ................................................................1-10
1-9 Equipment Supplied ................................................................................................................................... 1-12
1-10 Accessories - Not Supplied ........................................................................................................................1-13
1-11 Safety Symbols ..........................................................................................................................................1-13
2-1 BOP Front Panel Terminations and Controls .................................................................. ... ... ... ..................2-1
2-2 BOP Rear Panel Terminations and Controls ..............................................................................................2-2
2-3 Chassis Slide Mounting Holes ....................................................................................................................2-6
4-1 Internal Calibration Controls .......................................................................................................................4-1
Page 7
Page 8
Page 9
SECTION 1 - INTRODUCTION
1.1 SCOPE OF MANUAL.
This manual contains instructions for the installation and opera tio n of th e BOP 5-20DL 100 Watt Bipolar Operational Power Supply manufactured by Kepco, Inc., Flushing, New York, U.S.A. The L suffix indicates that the unit is optimized to drive large inductive loads in a stable manner.
Not that throughout this manual E
O
represents the rated output voltage, 5V, and IO represents
the rated output current, 20A.
1.2 GENERAL DESCRIPTION.
Kepco Series BOP Bipolar Power Supplies are fully dissipative, linear stabilizers for laboratory and systems applications. The BOP is an all solid-state design, featuring IC operational amplifi­ers in the control circuit section and silicon power transistors mounted on special fan-cooled heat sinks in the complementary power stage.
The BOP has two bipolar control channels (volt age or cu rrent m ode), select a ble and individu ally controllable either from their front panel controls, or by remote signals. Each of the principal con­trol channels is protected by bipolar limit circuits. In these limit circuits the positive and negative current or voltage limit points can be manually set or remotely programmed simultaneously or individually. Automatic crossover between each principal control channel and it s associated limit channel is provided.
Page 10
TABLE 1-1. GENERAL SPECIFICATIONS
SPECIFICATION RATING/DESCRIPTION CONDITION/COMMENT
A-C Input Voltage Nominal 104V / 115V / 208V / 230V Internal setting, see Figure 2-3
Range 95-113V / 105-125V / 190-226V / 210-250V
Brown-out 93V / 103V / 186V / 206V
Frequency 50 / 60 Hz nominal, ±3Hz range
A-C Input Current 11.0A Nominal output power,
sourcing, @115V/ 60Hz
Active Input power 1050W Nominal output power,
sourcing, @115V/ 60Hz
Power Factor 0.83 Nominal output power,
sourcing, @115V/ 60Hz
Input Leakage Current (through earth-ground connection)
0.1mA rms 115V/ 60Hz
Insulation Coordination Input Installation Cat. 2, Overvoltage Cat. 2,
Pollution Deg. 2
For TN or TT power systems
Output Installation Cat. 2, Overvoltage Cat. 2,
Max. 500V between COMMON
Page 11
Output Power Source 100W (d-c or peak) For full operating temperature
range and full a-c input voltage range.
Sink 100W (d-c or peak) Internal dissipative sink.
Fully operation in all voltage­current quadrants.
Source/Sink Output Range- Main channel
Voltage Remote: -5V to +5V
Local: -5.25V to +5.25V
For remote, use programming signal in +10V to -10V range (with the default preamplifier). See “DC Transfer Factor” on page 1- 2 for tolerances
Current Remote: -20A to +20A
Local: -21A to +21A
Source/Sink Output Range- Limit channel
Voltage +0.05V to +6.2V, for positive limit
-0.05V to -6.2V, for negative limit
Remote or local. For remote programming of all limits, use programming signal in 0V to +10V range. ±2% Full scale tolerance
Current +0.05A to +22A, for positive limit
-0.05A to -22A, for negative limit
Static Specifications See Table 1-3 Output Impedance See Table 1-2 Analog Readback
Accuracy
Voltage 0.02% of rated output voltage (1mV) Zero to ±10V for zero to
± Rated output voltage or current
Current 0.1% of rated output current (20mA)
TABLE 1-1. GENERAL SPECIFICATIONS
SPECIFICATION RATING/DESCRIPTION CONDITION/COMMENT
Page 12
Protection Input overcurrent Always trips input circuit breaker
Heatsink
overtemperature
Always trips input circuit breaker
Input power loss Jumper on rear programming connector
offers choice whether or not to trip input cir-
cuit breaker
Series or Parallel connection of identical units
Type of
connection
Master-Slave Contact factory for more than 3-
units being connected in series or in parallel
Implementation Using external wiring, no standard cables
provided Front Panel See Figure 2-1 and Table 2-1 Rear Panel See Figure 2-2 and Tables 1-6 and 1-7 Provides access to rear
programming connector and Output ON-OFF port
Output Leakage Current (COMMON terminal to chassis-ground, with GND-network disconnected)
0.05mA rms / 5mA p-p Nominal output power, sourcing, @115V/ 60Hz
Temperature: Operating 0°C to +55°C
TABLE 1-1. GENERAL SPECIFICATIONS
SPECIFICATION RATING/DESCRIPTION CONDITION/COMMENT
Page 13
1.3.1 STATIC SPECIFICATIONS
The static specifications are listed in Table 1-3. The BOP output effects, in response to the t a bu­lated variations in the Influence Quantities, are given In Table 1-3 for the built-in input and feed­back resistor values of the voltage and current chan nel preamplifiers.
T ABLE 1-3. STATIC S PECIFICATIONS: OUTPUT EFFECTS, OFFSET S, AND
REFERENCE SPECIFICATIONS
INFLUENCE QUANTITY
OUTPUT EFFECTS
(1)
PREAMPLIFIER
(4)
OFFSETS
VOLTAGE MODE CURRENT MODE
REFERENCE
±10V
TYPICAL MAXIMUM TYPICAL MAXIMUM
)
SOURCE VOLTAGE (min-max):

0.001%

0.005% <5V <1nA <0.0005%
LOAD (no load-full load):

0.008% 0.5mA
1mA
——
<0.0005% TIME (8-hour drift): 0.005% 0.01% 0.01% 0.02% <20V <1nA 0.005% TEMPERATURE (per °C): 0.005% 0.01% 0.01% 0.02% <20V <1nA 0.005%
RIPPLE AND NOISE:
(2)
rms 1mV 3mV 0.01% 0.03%
p-p
(3)
10mV 30mV
0.1% 0.3%
——
(1) Output effects, expressed as a percentage, are referred to the maximum rated output voltage or current. (2) Measured with the common terminal grounded so that the common mode current does not flow through the load. (3) Peak-to-peak ripple Is measured over a 20 Hz to 10 MHz bandwidth. (4) To permit calculating of the effect of non-standard control current (less than the normal 1 mA) of non-standard gain
ratios.
E
ioIio
Page 14
1.3.2 DYNAMIC SPECIFICATIONS
Dynamic specifications are listed in Ta ble 1-5 for a nominal resistive load, and in Table 1-5 for a 2mH inductive load (current mode). The typical dynamic responses of the BOP output are tabu­lated in both the time domain (Output response to a step program) and in the frequency domain (bandwidth) for large and small signals.
1.4 MISCELLANEOUS FEATURES
TABLE 1-4. DYNAMIC SPECIFICATIONS FOR NOMINAL RESISTIVE LOAD
MODEL
3dB
BANDWIDTH
(KHz)
RISE AND FALL
TIME 10-90%
(S)
LARGE SIGNAL FRE­QUENCY RESPONSE
(KHz)
SLEW
RATE
REOVERY AT
STEP LOAD
(S)
Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current
BOP 5-20DL 3.5 10 125 50 3.5 10 0.08V/S0.9A/S 250 75
TABLE 1-5. DYNAMIC SPECIFICATIONS, IN CURRENT MODE FOR 2mH INDUCTIVE LOAD
MODEL
3dB BANDWIDTH
(Hz)
RISE & FALL TIME
10%-90%
msec)
BOP 5-20DL 140 2.5
Page 15
NOTE: The BOP is operating as a source if the direction of its output voltage is the same a s
the direction of its output current. The BOP is operating as a sink if the direction of its output voltage is opposite that of its output current. An illustrative case is shown in Fig­ure. 1-3, where the BOP is programmed to deliver a sine wave output and where the load produces a phase shift between the output voltage and current.’
FIGURE 1-3. BOP OUTPUT WAVEFORM WITH PHASE SHIFT
1.4.2 REAR PROGRAMMING FEATURES
E
o
I
o
SOURCE SOURCE
SINK SINK
(+) (-)
3043440
Page 16
8+Io Limit Input Refer to PAR. 3.3.2 32 –Eo Limit Input Refer to PAR. 3.3.4 34 Io Limit Input Refer to PAR. 3.3.2 10 Current Sensing Amp. Output Analog output voltage (0 to ±10V, 1 mA max) proportional
to the prevailing BOP output current for remote metering or monitoring.
20 Voltage Sensing Amp. Output Analog output voltage (0 to ±10V, 1 mA max) proportional
to the prevailing BOP output voltage.
21, 43, 44,
45, 46
Not Used.
12, 14 Reserved. (Not to be used). 16, 18 Current Mode Compensating Terminals Refer to PAR. 1.4.4 26, 36 Turn-off Signal Output Refer to PAR, 3.6.2
24 Circuit Breaker Control Refer to PAR, 3.6.2 41 Non-isolated Turn-off Signal Input Refer to PAR, 3.6.2
47/48,
49/50
Optically Isolated Turn-off Signal Input Refer to PAR, 3.6.2
17 Voltage Comparison Amp Input Analog input voltage of 0 to ±10V will produce 0 to ± full
TABLE 1-6. REAR PROGRAMMING CONNECTOR TERMINAL FUNCTIONS (CONTINUED)
TERMINAL (Figure 3-1
FUNCTION DESCRIPTION
Page 17
TABLE 1-7. OUTPUT ON-OFF PORT A2J211, PIN ASSIGNMENTS
PIN SIGNAL NAME FUNCTION
1---Not Used 2 ON-OFF_CTRL Optically isolated signal that controls output to be either ON (enabled)
or OFF (disabled). OFF: 0V to 0.4V or no connection (open circuit) at pin 2, referenced to pin 3. Turns OFF within 100S max (between 10% point of controlling signal and a) 10% point of output voltage for voltage mode with no load or b) 10% point of output current for current mode with short circuit. ON: 3.5V to 24V d-c at pin 2 referenced to pin 3; input current is 1mA ±0.3mA. Turns ON within 100S max (between 90% point of controlling signal and a) 90% point of output voltage for voltage mode with no load or b) 90% point of output current for current mode with
short circuit. 3 ISO_GND Return for ON-/OFF_CTRL and for /ON_OFF_FLAG signals. 4 /ON-OFF_FLAG Flags whether output set to ON or OFF. This isolated flag signal is the
collector of an optocoupler-transistor, with the emitter connected to pin
3. Optocoupler transistor is saturated when the output is ON (enabled).
Current through the transistor should not exceed 1.6mA and supply
voltage should not exceed 24V.
OFF level: determined by (Vext) - (Rext) (Icoff) where:
Page 18
1.4.4 LOAD REACTANCE
The BOP 5-20DL power supply is optimized for driving large inductor loads (L suffix). Factory test were performed with loads up to 1H, however higher values are possible.
CAUTION: When driving heavy inductive loads with high currents, it is possible for the
BOP and the load to be damaged by an A-C input power loss which prevent s the load's stored energy from being dissipated inside the BOP. To avoid pos­sible damage observe the following:
Use UPS to supply the BOP.
• Set BOP output current and/or voltage to zero and turn off the BOP after the output current actually reaches a zero value.
• Use properly rated (voltage and current) bipolar transorbs or a properly rated bipolar crowbar element connected directly at the output of the BOP. An alternative is a Normally-Closed Contactor connected across the output of the BOP. These options may also be combined.
When driving an inductive load, if the system becomes unstable at the crossover between volt­age limit mode and current m ode, the BOP 5-20DL can be further optimized by reducing the current loop bandwidth. This can be accomplished by connecting a ceramic capacitor across pins 16 and 18 of the Rear Programming Connector (see Figure 3-1 and Table 1-6). Refer to
!
Page 19
1.4.9 VOLTAGE CONTROL CHANNEL
The Bipolar Voltage Amplifier, with a fixed gain (See Table 1-1 for gain value) is connected via the MODE switch to the Voltage Preamplifier (see Figure 3-2). If the VOLTAGE CONTROL switch is on, the BOP output voltage can be locally controlled by means of the (front panel) (±) 10 volts bias source, from (–) 100% (through zero) to (+) 100% of the rated value. The Voltage Preamplifier is provided with a Zero control and all its terminals are available at the Rear Pro­gramming Connector for rem o te co n tro l o f th e output voltage. Control methods are described in PAR. 3.4.
1.4.10 MODE SWITCH
The BOP is equipped with a front panel-mounted M ODE switch, which selects bipolar voltage or bipolar current control. See paragraph 1.4.14 for remote MODE control.
1.4.11 CURRENT CONTROL CHANNEL
The Bipolar Current Amplifier, with a fixed gain (See Table 1-2 for gain value) is connected via the MODE switch to the Current Preamplifier (see Figure 3-4). If the CURRENT CONTROL switch is on, the BOP output current can be locally controlled by means of the (front panel) (±) 10 volts bias source, from (–) 100% (through zero) to (+) 100% of the rated value. The Current Preamplifier is provided with a Zero control and all its terminals are available at the Rear Pro­gramming Connector for remote control of the output current. Control methods are described in PAR. 3.5.
Page 20
1.4.13 MODE LIGHTS
Four (4) front panel (LED type) indicator lamps monitor the prevailing operating mode of the BOP. For each operating condition (Voltage Mode, Current Mode, ± E
o
Limit, ± Io Limit) the cor­responding indicator lamp energizes. Simultaneous TTL flags are available on the Rear Pro­gramming Connector. See PAR. 3.7
1.4.14 REMOTE OUTP UT ON-OFF LED
This LED indicates the status of the output, in accordance with the signal received at the rear panel OUTPUT ON-OFF Port. The indicator is on for output on (enabled) and off for output off (disabled).
1.4.15 STANDARDS
BOP models are designed and tested in accordance with NEMA Standard for Stabilized Power Supplies, d-c output, Publication No. PY-1.1972.
1.5 MECHANICA L SPECIFICATIONS
See Mechanical Outline Drawing, Figure 1-5 for dimensions and finish. Two (2) digital meters, monitoring the ± d-c output voltage and the ± d-c output current, are provided. The full rack BOP 5-20DL model is 75 lbs. (34 kg) unpacked.
Page 21
1.7 ACCESSORIES
Accessories (not supplied) are listed in Table 1-10.
1.8 SAFETY
Service must be referred to authorized personnel. Using the power supply in a manner not specified by Kepco. Inc. may impair the protection provided by the power supply. Observe all safety precautions noted throughout this manual. Table 1-11 lists symbols used on the power
TABLE 1-10. ACCESSORIES - NOT SUPPLIED
ITEM
FUNCTION
KEPCO
PART NUMBER
Rear Programming Connector, Unwired
50-terminal printed circuit connector, unwired, for access to all rear programming connections and flag-signal outputs.
PC-12
Slides Ease of access to adjustments through top cover 110 QD
(Jonathan)
4886 Interface Card Allows remote programming of BOP via GPIB or RS 232 interface using
IEEE 488 and SCPI commands and queries. NOTE: Contact Kepco to disable ON-OFF Port before using this card.
BIT 4886
802E Interface Card Allows remote programming of BOP via Ethernet /LAN using web pages.
NOTE: Contact Kepco to disable ON-OFF Port before using this card.
BIT 802E
Page 22
Page 23
081915 15
FIGURE 1-5. MECHANICAL OUTLINE DRAWING,
BOP 5-20DL
ON−OFF
OUTPUT
PORT
ON−OFF
1-15/(1-16 Blank)
-14/(-15
Page 24
Page 25
SECTION 2 - INSTALLATION
2.1 UNPACKING AND INSPECTION.
This instrument has been thoroughly inspected and tested prior to packing and is ready for operation. After careful unpacking, inspect for shipping damage before attempting to operate. Perform the preliminary operational check as outlined in PAR.
2.13. If any indication of damage
is found, file an immediate claim with the responsible transport service.
2.2 TERMINATIONS, CONTROLS AND INDICATORS
a) Front Panel: Refer to Figure 2-1. See Table 2-1 for an explanation of terminations,
controls and indicators.
b) Rear Panel: Refer to Figure 2-2 and Table 2-2 for an explanation of terminations.
Page 26
7 CURRENT meter IO d-c digital output ammeter 8 CURRENT control Provides manual adjustment of BOP d-c output current when CURRENT
CONTROL switch set to ON.
9 CURRENT CONTROL
switch
Provides manual adjustment of BOP d-c output current when CURRENT CONTROL switch set to ON.
10 Io Mode indicator LED lamp, indicating current mode operation. 11 CURRENT PROGRAMMING
INPUT terminals
Programming input terminals for current control channel.
12 CURRENT LIMITS (+)
control
Control for manual adjustment of the positive (+) current limit.
13 CURRENT LIMIT indicator LED lamp, indicating current limiting operation. 14 CURRENT LIMITS (–)
control
Control for manual adjustment of the negative (–) current limit.
15 SENSE (Output) terminal Used for OUTPUT sense connection. 16 OUTPUT terminal Used to connect power supply to load (parallel with rear panel barrier strip
terminals).
17 GROUND terminal Ground terminal (parallel with rear panel barrier strip terminals)
TABLE 2-1. BOP FRONT PANEL TERMINATIONS AND CONTROLS (CONTINUED)
FIG.
INDEX NO.
NAME OF TERMINATION
OR CONTROL
FUNCTION
Page 27
FIGURE 2-2. BOP TERMINATIONS AND CONTROLS, REAR PANEL
2.3 A-C INPUT REQUIREMENTS
This power supply is shipped wired for operation on a single phase, nominal 115V a-c line. For
See
Table 2-2
for functions.
Page 28
2.5 PRELIMINARY CHECKOUT
NOTES: 1. The Rear Programming Connector supplied with the unit (PC-15) is prewired for
local control (see Simplified Schematic Diagram, Figure 3-29) and must be attached to the BOP. The PC-12 Rear Programming Connector is unwired and available as an accessory.
2. With either no signal or logic 0 at OUTPUT ON-OFF Port pins 2 and 3, output volt­age (in voltage mode) or output current (in current mode and a load connected) will have the preadjusted output value. See Table 1-1 and PAR. 4.2.5 for details.
3. If the unit is in current mode with no load connected and either no signal or logic 0 is applied to OUTPUT ON-OFF Port pins 2 and 3, the unit will go into voltage limit, dis­playing the preadjusted limit value with the same polarity as the output current off­set. The front panel Volt age Limit indicator will go on and the Current Mode indicator will go off.
A simple operating check after unpacking, and before permanent installation, is advisable to ascertain whether the BOP has suffer ed damage in shipment. Refer to Figur es through 2-2 an d Tables 2-1 and 2-2 for the location and function of the operating controls and terminals. Proceed as follows:
1. Connect the BOP to a 115V a-c source, or refer to paragraph 2-4 for conversion to other a­c input voltages if required.
Page 29
5. Turn the VOLTAGE control (3) clockwise through its range, while observing the front panel VOLTAGE meter (4). The BOP output voltage should smoothly respond, from the maxi­mum negative output voltage, through zero, to the maximum positive output voltage of the BOP.
6. At the rear panel, disconnect the positive voltage connected between pins 2 and 3 of the OUTPUT ON-OFF port. Verify the front panel VOLTAGE meter shows zero Volts and the REMOTE OUTPUT ON-OFF indicator goes off.
7. At the front panel, turn a-c circuit breaker/POWER switch (1) to OFF.
8. Connect a short circuit between the OUTPUT (16) and the COMMON (18) termina ls on the front panel.
9. At the rear panel, reconnect the positive volt age betwe en pins 2 a nd 3 of the OUTPUT ON­OFF port.
10. Set the BOP front panel controls as follows: a) Set MODE switch (6), to CURRENT. b) Set CURRENT CONTROL sw itch (9), to ON, and rotate CURRENT control (8) to its
maximum counterclockwise position.
Page 30
2.6 INSTALLATION OF FULL-RACK BOP MODELS
NOTE: For all installations into confined spaces, care must be taken that the temperature
immediately surrounding the unit does not exceed the maximum specified ambient temperature (55° C).
Refer to the Mechanical Outline Drawing, Figure 1-5 for Full Rack models. Full-rack BOP mod­els are delivered with the Fixed Angle Brackets and the Chassis Side Support Bars installed. For bench operation, both of these components may be removed. The full-rack BOP unit may be installed into standard (19-inch) equipment racks, or onto any other flat surface after remov­ing the four (4) bottom aluminum feet. If chassis slides are not used, the BOP may be installed onto any flat surface by means of the provided plastic mounting inserts on the bottom of the BOP chassis.
NOTE: If slide installation (as described below) is not desired, other means of supporting the
unit in the rear must be provided (additional re ar bracke ts or a solid platform, for exam­ple) since the front angle brackets alone are not sufficient to support the full weight of the unit.
2.6.1 SLIDE INSTALLATION.
The Chassis Slide Support Bars of the BOP are pre-drilled to accept Jonathan Series 110 QD slides. The slides listed in Table 2-3 can be accommodated.
Page 31
Page 32
2.7.2 LOAD CONNECTION, REMOTE SENSING
The basic interconnections between the BOP and the load using remote sensing are shown in Figure 2-7 (using the rear panel) and Figure 2-8 (using the front panel). This is the recom­mended load connection for all applications requiring minimum load effect acr oss a remote load. A twisted or shielded pair of wires (No. 22 AWG minimum) are connected from the BOP sensing terminals to the load. For the BOP 5-20DL this remote error sensing technique will compensate for load wire voltage drops up to 0.25 volts per wire.
NOTE: Observe polarities: the COMMON sensing wire must go to the COMMON load wire,
the OUTPUT sensing wire must go to the OUTPUT load wire.
2.7.3 A-C GROUND
The metal cases of electronic equipment which are operated from the a-c power line must be kept at ground potential at all times. If the 3-wire line cord with 3-prong safety plug (supplied with this equipment) is used in combination with a properly grounded a c power outlet, this is taken care of automatically. If a non-grounded outlet is used, the case must be grounded sepa­rately. A separate GROUND terminal is provided for this purpose on the front panel as well as on the rear of the BOP.
The GROUND terminal is connected to chassis of the unit and to the local earth-ground poten­tial through the A-C power line cord. It can be used a) as a grounding point for the output of the unit, and b) for doubling the a-c power cord earth-ground connection if necessary by providing a
Page 33
FIGURE 2-5. LOAD CONNECTION USING LOCAL SENSING AT REAR PANEL
Page 34
Page 35
SECTION 3 - OPERATION
3.1 INTRODUCTION
BOP Bipolar Operational Power Supplies can be used in a great variety of applications. As a precision voltage or current source, the BOP output can be controlled locally by means of the front panel bipolar VOLTAGE and CURRENT controls or remotely by means of resistance or voltage signals or an optional digital interface (see PAR. 3.42). Independently adjustable or remotely programmable limit circuits for both output voltage and output current protect a sensi­tive load from any overvoltage or overcurrent.
NOTE: Before using the BOP in any application, please refer to Section 2 to get acquainted
with the operating controls, a-c power requirements and information on load connec­tions and grounding. Front panel components identified by index numbers in parenthe­ses are shown in Figure 2-1.
3.2 POWER SUPPLY BASICS
As a Bipolar Amplifier , the BOP output responds to such input signa ls as sine, square or trian gu­lar waves. A ±10 volt input signal will program the BOP output (voltage or current) through its rated output ranges. Built-in preamplifiers, for the voltage, as well as the current channel of the BOP, permit amplification of the control signals to the required amplitude and provide the inter­face with high, as well as low, impedance signal sources.
!
Page 36
Application and test set up diagrams on the following pages show the symbolic and simplified representation of the four programmable circuits of the BOP:
Voltage Control Channel: see Figure 3-2 and PAR. 3.3.1 for local control.
•(±) I
O
Limit Circuits: See Figure 3-3 and PAR. 3.3.2 for local control.
Current Control Channel: see Figure 3-4 and PAR. 3.3.3 for local control.
•(±) E
O
Limit Circuits: see Figure 3-5 and PAR. 3.3.4 for local control.
The complete simplified diagram is shown in Figure 3-29 at the end of this section. The four cir­cuits can be programmed separately as described in the examples in th is section, or one main channel and two limit channels can be used simultaneously as the application req uires. The two main bipolar voltage and current channels are manually selected by the front panel MODE switch.
The numbered terminals in the simplified diagrams of this section correspond to the terminals of the Rear Programming Connector (see Figure 3 -1 . The ter mina l de sig nated C (Comm on) corr e­sponds to terminals numbers 23, 25, 27, 29, 31 or 33 on the Rear Programming Connector
NOTE: BOP’S have front and rear output terminals. Only the front terminals are shown on all
subsequent simplified diagrams.
Page 37
3.2.1 EXTERNAL PROGRAMMING RESISTORS.
External programming resistors should be high-quality units, with low-temperature coefficients. Resistors should be selected carefully , since in most applications, the limitations for stability and drift are due not to the BOP, but to the programming resistors. Selection criteria for resistors are:
Temperature coefficient
Leakage (in values above 100k ohm)
Humidity effects
Drift with time
Self-heating (power dissipation)
Tolerance.
For variable resistors (potentiometers or rheostats) similar selection criteria apply. In addition, such specifications as listed below should be carefully considered if the application requires:
End resistance
Linearity
Page 38
3.2.5 EXTERNAL CURRENT MONITOR
Use signal I
O
Sensing Output at pin 10 of the Rear Programming Connector (see Figure 3-1) for external current monitoring. This signal is not buffered. Use a series 5K resistor in combina tion with a high impedance monitoring device, or an external high impedance buffer between the BOP and the monitoring device.
CAUTION: An accidental short-circuit at this terminal while the unit is in Current mode
or Current limit mode will damage the BOP power stage.
There is no overvoltage protection. This stage is prot ected against short-circuit by th e intrinsic protection of the op-amp generating this signal. This signal is used by the BIT card if it is installed.
3.3 LOCAL (FRONT PANEL) OUTPUT CONTROL
3.3.1 VOLTAGE MODE OPERATION WITH CURRENT LIMITING.
The BOP may be used as a stabilized (d-c) source of positive or negative voltage with output current limiting (for either polarity) pre-selected for the application at hand. The output must be enabled via a positive voltage applied between pins 2 and 3 of the OUTPUT ON-OFF port (see Table 1-7 and Figure 2-2 for details).
Figure 3-2 illustrates the voltage control circuit configured for local (front panel) control using
Page 39
Proceed as follows:
1. Determine the output voltage and current requirements of your load. Set the BOP MODE switch (8, Figure 2-1) to VOLTAGE and the VOLTAGE CONTROL switch (4) to ON.
2. With the POWER circuit breaker/switch (2) set to OFF, connect a short circuit across the out­put terminals and set POWER to ON again.
3. Adjust CURRENT LIMITS controls for –I (18) and +I (16) polarities as required, monitoring the output CURRENT meter (11) for the correct limiting value. Proceed as follows:
a. Turn VOLTAGE control (3) fully counterclockwise. b. Adjust –I CURRENT LIMITS control (18) as required. c. Turn VOLTAGE control (3) fully clockwise. d. Adjust the +I CURRENT LIMITS control (16) as required. e. Turn VOLTAGE control (3) to the center of its range. f. Set POWER circuit breaker/switch to OFF; remove the short circuit from the output and
reconnect the load.
Page 40
3.3.2 LOCAL CONTROL OF CURRENT LIMITING
Figure 3-3 shows the Current Limit ing circu it configured for local sensing and local (front panel) control.
+
22
28
C
+
10V
10V
POWER
STAGE
-
+
G A T E
-
+
+
-
8
34
1
+
+
-
+
-
+
-
(+)I o LIMIT-
AMP (EXT)
(+)I o LIMIT-
AMP (INT)
(-)I o LIMIT-
AMP (INT)
(-)I o LIMIT-
AMP (EXT)
(+)
I o LIMIT
CONTROL
BIAS
15V
(-)
I o LIMIT
CONTROL
(+)
I o LIMIT-
COMP AMP
(-)
I o LIMIT-
COMP AMP
DRIVER
COMMON
BOP
I o
LIMIT CHANNEL
PART OF REAR PROGRAMMING CONNECTOR
57.6K
57.6K
LOAD
-
+
S
R
COM
S
OUT
S
NOTES:
1. Local Sensing shown (links installed between COM and S and between OUT and S terminals).
2. On rear programming connector install jumpers between terminals (1) and (34) and between (34) and (8).
CURRENT
SENSE AMP
I o CAL
Page 41
FIGURE 3-4. BOP CURRENT CONTROL CHANNEL (LOCAL CONTROL, LOCAL SENSING)
BOP CURRENT
CONTROL CHANNEL
PART OF REAR PROGRAMMING CONNECTOR
22
C
+
+
28
CURRENT CONTROL
CURRENT
PROGRAMMING
INPUT
OFF
10V
10V
ON
10K
10K
13
15
4
NOTES:
1. Set MODE Switch to CURRENT.
2. Set CURRENT CONTROL switch to ON for local (front panel) control and OFF for remote control.
3. Local sensing shown. Remote sensing not recommended for Current control.
4. For inductive loads in excess of 0.5mH, the BOP output response may be optimized by placing a capacitor across terminals 16 and 18 of the Rear Programming Connector (
Io COMP AMP).
Io ZERO
POWER
STAGE
COMMON
ZERO
+
10K
PREAMP
"B"
­2
19
Io COMP
AMP
+
-
DRIVER
R
G
A T E
S
C
16 18
LOAD
3043683
COM
S
OUT
S
SIGNAL
GROUND
R
i
f
R
Page 42
3.3.4 LOCAL CONTROL OF VOLTAGE LIMITING
Figure 3-5 shows the Voltage Limiting circuit configured for local sensing and local (front panel) control. The circuit functions in a manner similar to the I
O
Limit circuit described previously (refer to PAR. 3.3.2), except that the voltage limit feedback is derived by means of a voltage divider across the BOP output.
In the local (front panel) control mode, as well as in the external control mode, a 0 to 10 vo lt sig­nal, applied at the inverting inputs of the ± E
O
Limit Comparison amplifiers, will control the volt­age limit point over the entire output current range of each BOP model. For the internal (front panel) control mode, the control signal is derived across both 10 volt reference sources, ap plied by means of the ± E
O
Limit controls to the internal ± EO Limit amplifiers and directed to the
respective inputs of the ± E
O
Limit Comparison amplifiers. In the internal control mode, both ±E
O
Limit Amplifiers (EXT) are biased off by the 15V bias source.
S
+
-
6
32
3
+
+
­+
BIAS
15V
(-)Eo LIMIT CONTROL
(+)Eo LIMIT-
COMP AMP
PART OF REAR PROGRAMMING CONNECTOR
NOTES:
1. Local Sensing shown (links installed between COM and S and between OUT and S terminals).
2. On Rear Programming Connector install jumpers between terminals (3) and (32) and between (32) and (6).
Page 43
3.4 REMOTE CONTROL OF VOLTAGE CHANNEL
Remote control of the voltage channel is accomplished by using an external configuration to substitute for the internal control voltage produced by the front panel VOLTAGE CONTROL.
3.4.1 REMOTE VOLTAGE CONTROL USI NG RESISTANCE (POTENTIOMETER)
When configured as shown in Figure 3-6, Preamp “A” with the built-in feedback and input resis­tors has a gain of one and the fixed gain of all BOP models is designed so that a d-c input signal of zero to (±)10 volts will control the BOP output through its specified range. When the front panel VOLT AGE CONTROL switch (4, Figure for 3/4 r ack, Figur e 2-1 for full ra ck) is set to OFF, operation is similar to local control described in PAR. 3.3.1, except that an external potentiome­ter is substituted for the front panel VOLTAGE control (3).
PART OF REAR PROGRAMMING CONNECTOR
28
C
+
VOLTAGE CONTROL
OFF
10V
ON
10K
10K
11
9
C
7
NOTES:
1. Set MODE Switch to VOLTAGE.
2. Remote Sensing shown. For local sensing disconnect wires between S terminals and load, then restore local sensing links.
5
ZERO
PREAMP
"A"
-
+
2.49K
OUT
S
10K
(EXT.)
(EXT.)
REMOTE
VOLTAGE
CONTROL
20K
REMOVE
SENSING LINK
R
i
R
i
f
R
Page 44
3.4.2 REMOTE VOLTAGE CONTROL USING RESISTANCE (DECADE BOX)
Two-terminal resistance control of the d-c voltage (for example, by means of a Decade Box (make-before-break type) or any variable resistance) can be exercised as shown in Figure 3-7.
The external switch (S1), connected across the (±) reference voltage, is used to pre-select either positive or negative output by setting it to the applic ab le re fe re n ce vo ltage pola rity.
PREAMP “A” functions here as an inverter. Its output can be expressed by the equation: E
O (PREAMP “A”)
= –E
ref
(Rf/Ri). where
R
f
= Decade Resistor.
R
i
= Ext. Input Resistor The BOP output voltage will vary linearly with the change in decade resistance. This programming system can be calibrated very accurately by setting the external Remote
Voltage Control (Decade) to zero, and adjusting for zero output volts using the screwdriver­adjusted E
O
ZERO control while monitoring the BOP output with a digital voltmeter. The maxi-
mum output voltage is calibrated by making all or part of R
i
a rheostat and adjusting it with the
Remote Voltage Control at maximum resistance, to the maximum BOP output voltage.
Page 45
3.4.3 REMOTE VOLTAGE CONTRO L USING D-C SIGNAL VOLTAGE
The BOP d-c output voltage can be controlled directly by a ±10V d-c signal, applied to the front panel Voltage Programming Input terminals. An interesting example of how this can be imple­mented is the use of a Kepco SN Digital Programmer to convert digital input to the analog ±10V d-c signal. The digital input to the SN programmer can be provided by a computer, or manually by means of a keyboard. Th e analog output fr om the SN is from zero to ± 10 volts and const i­tutes the input programming voltage for the BOP.
The connections between the SN Programmer and the BOP are illustrated in Figure 3-8. This programming system provides a resolution of 12-bits with a linearity of (±)1/2 LSB (0.0122%). The digital and the power supply grounds are isolated (optical isolation) to 1000 volts. Calibra­tion of the system is performed with the provide d controls on the SN Programmer.
PART OF REAR PROGRAMMING CONNECTOR
28
C
+
VOLTAGE CONTROL
OFF
10V
ON
10K
10K
11
9
C
7
NOTES:
1. Set MODE Switch to VOLTAGE.
2. Remote sensing shown (links removed). For local sensing disconnect leads beteen S terminals and load, then install links between COM and S terminals and between OUT and S terminals.
5
ZERO
PREAMP
"A"
-
+
2.49K
OUT
S
KEPCO
REMOVE
SENSING LINK
DIGITAL
INPUT
R
i
f
R
Page 46
FIGURE 3-9. D-C OUTPUT VOLTAGE CONTROL WITH NON-INVERTING CONFIGURATION
AND HIGH IMPEDANCE ±1V SIGNAL SOURCE
3043884
BOP VOLTAGE
CONTROL CHANNEL
PART OF
REAR PROGRAMMING CONNECTOR
+
22
28
C
+
VOLTAGE
CONTROL
VOLTAGE
PROGRAMMING
INPUT
10V
OFF
10V
ON
10K
10K
11
9
C
7
POWER
STAGE
NOTES:
1. Set MODE Switch to VOLTAGE.
2. Remote sensing shown (links removed). For local sensing disconnect leads beteen S terminals and load, then install links between COM and S terminals and between OUT and S terminals.
3. Remove jumpers between terminals (7) and (9) and between (11) and (C) on Rear Programming Connector.
COMMON
5
Eo ZERO
-
17
+
Eo COMP
AMP
ZERO
PREAMP
"A"
-
+
2.49K
DRIVER
G A T E
COM
S
OUT
S
LOAD
SIGNAL
GROUND
REMOVE
SENSING LINK
REMOVE
SENSING LINK
HIGH
IMPEDANCE
BIPOLAR SOURCE
(EXT.)
R 3K (EXT.)
f
E
i
0
TO
±1V
R 2K (EXT.)
i
OUT
COM
Page 47
instead of the front panel Voltage Programming Input terminals (inverting).
Page 48
If the external programming source does not have sufficient amplitude to drive the BOP over its full output range, the gain of Preamp “A” must be changed from the built-in value to suit the application. To calculate the required components for the new gain requirement, the output equation for Preamp “A” in the inverting configuration is used:
E
O (PREAMP “A”)
= –Ei (Rf/Ri)
where E
O
(Preamp “A”) = ±2.5V, and the values of Rf and Ri depend on the available amplitude
of the programming source. If, for example, a ±1 volt source is available, the ratio R
f/Ri
must be
2.5, and the two resistor values can be 10K and 24.9K respectively. The built-in resistor (R
i
=
10K) can be retained, and only R
f
must be replaced with a 24.9K metal film (1/2 watt) resistor. The necessary connections are illustrated in Figure 3-12. Gain control can be exercised by mak­ing R
f
a rheostat instead of a fixed resistor.
PART OF REAR PROGRAMMING CONNECTOR
28
C
+
VOLTAGE
CONTROL
OFF
10V
ON
10K
11
9
C
7
NOTES:
1. Set MODE Switch to VOLTAGE.
2. Remote sensing shown (links removed). For local sensing disconnect leads between S terminals and load, then install links between COM and S terminals and between OUT and S terminals.
5
ZERO
PREAMP
"A"
-
+
2.49K
S
REMOVE
SENSING LINK
24.9K
f
R
i
R
Page 49
FIGURE 3-13. SYMMETRICAL REMOTE CONTROL OF THE CURRENT LIMITS
3043706
+
22
28
C
+
10V
10V
POWER
STAGE
-
+
G A T E
-
+
+
-
8
34
1
+
+
-
+
-
+
-
(+)I o LIMIT-
AMP (EXT)
(+)I o LIMIT-
AMP (INT)
(-)I o LIMIT-
AMP (INT)
(-)I o LIMIT-
AMP (EXT)
(+)
I o LIMIT
CONTROL
BIAS
15V
(-)
I o LIMIT
CONTROL
(+)
I o LIMIT-
COMP AMP
(-)
I o LIMIT-
COMP AMP
DRIVER
COMMON
BOP
I o
LIMIT CHANNEL
PART OF REAR PROGRAMMING CONNECTOR
57.6K
57.6K
LOAD
-
+
S
R
COM
S
OUT
S
NOTES:
1. Local Sensing shown (links installed between COM and S and between OUT and S terminals).
2. On rear programming connector install jumpers between terminals (8) and (34) and remove jumper between (1) and (34).
CURRENT
SENSE AMP
I o CAL
SIGNAL
GROUND
+
±I o LIMIT
CONTROL
0-10V
(EXT.)
1
PART OF REAR PROGRAMMING CONNECTO R
NOTES:
1. Local Sensing shown (links installed between COM and S and between OUT and S terminals).
Page 50
3.5.1 REMOTE CURRENT CONTROL USING RESISTANCE (POTENTIOMETER)
Similar to the local (front panel) control mode described in PAR. 3.3.3, the BOP output current can be controlled over the full output range by means of and external resistance in place of the front panel CURRENT CONTROL as shown in Figure 3-15. The control potential (zero to (±)10V) is applied via Preamp “B,” operating with unity gain, to the l
O
Comp. Amp which drives the Power Stage with a fixed gain as listed in Table 1-2. A d-c control signal from zero to (±)10V will, therefore, control the BOP output current through its specified range.
BOP CURRENT
PART OF REAR PROGRAMMING CONNECTOR
22
C
+
+
28
CURRENT CONTROL
CURRENT
PROGRAMMING
INPUT
OFF
10V
10V
ON
10K
10K
13
15
4
NOTES:
1. Set MODE Switch to CURRENT and CURRENT CONTROL switch to OFF.
2. Local sensing shown. Remote sensing not recommended for Current control.
3. For inductive loads in excess of 0.5mH, the BOP output response may be optimized by placing a capacitor across terminals (16) and (18) of the Rear Programming Connector (
Io COMP AMP).
Io ZERO
POWER
STAGE
ZERO
+
10K
PREAMP
"B"
­2
19
Io COMP
AMP
+
-
DRIVER
R
G A T E
S
C
16 18
LOAD
COM
OUT
S
SIGNAL
Ri
10K
(EXT.)
(EXT.)
REMOTE VOLTAGE CONTROL
20K
f
R
Page 51
3.5.3 REMOTE CURRENT CONTROL USING D-C SIGNAL VOLTAGE
See Figure 3-17 for remote current control using a d-c signal voltage. See Figure 3-18 for remote current co ntrol using a high impedance ±1V voltage. Preamplifier
“B” is used in the non-inverting configuration, so the output current will have the same polarity as the input programming signal.
BOP CURRENT
NOTES:
1. Set MODE Switch to CURRENT and CURRENT CONTROL switch to OFF.
2. Local sensing shown. Remote sensing not recommended for Current control.
3. For inductive loads in excess of 0.5mH, the BOP output response may be optimized by placing a capacitor across terminals (16) and (18) of the Rear Programming Connector (
Io COMP AMP).
Io ZERO
POWER
STAGE
ZERO
+
10K
PREAMP
"B"
­2
19
Io COMP
AMP
+
-
DRIVER
R
G
A T E
S
16 18
LOAD
COM
OUT
S
SIGNAL
10K
CURRENT
PROGRAMMING
INPUT
PART OF REAR PROGRAMMING CONNECTOR
DIGITAL
INPUT
ANALOG
OUTPUT
(0 TO ±10V)
KEPCO
SN
DIGITAL
PROGRAMMER
(ONE CHANNEL)
COM
OUT
22
C
+
28
+
ON
OFF
10V
10V
10K
CURRENT CONTROL
C
15
4
13
f
R
i
R
Page 52
3.5.4 USING THE BOP AS A CURRENT AMPLIFIER
See Figure 3-19 to configure the BOP as a current-stabilized bipolar amplifier. See Figure 3-20 to drive output current using a bipolar signal voltage less than ±10V. See Figure 3-21 to drive output current using a high impedance source.
NOTES:
1. Set MODE Switch to CURRENT and CURRENT CONTROL switch to OFF.
2. Local sensing shown. Remote sensing not recommended for Current control.
3. For inductive loads in excess of 0.5mH, the BOP output response may be optimized by placing a capacitor across terminals (16) and (18) of the Rear Programming Connector (
Io COMP AMP).
Io ZERO
POWER
STAGE
ZERO
+
10K
PREAMP
"B"
­2
19
Io COMP
AMP
+
-
DRIVER
R
G A T E
S
16 18
LOAD
COM
OUT
S
15
C
13
4
PART OF REAR PROGRAMMING CONNECTOR
+10V
BIPOLAR
PROGRAMMER
(EXTERNAL)
-10V
COM
CURRENT
PROGRAMMING
INPUT
C
28
22
OUT
+
10V
+
10V
CURRENT CONTROL
ON
OFF
10K
10K
f
R
i
R
Page 53
FIGURE 3-21. PROGRAMMING CIRCUIT FOR DRIVING OUTPUT CURRENT WITH
A HIGH IMPEDANCE SOURCE
3.5.5 REMOTE CONTROL OF VOLTAGE LIMITING
BOP CURRENT
CONTROL CHANNEL
NOTES:
1. Set MODE Switch to CURRENT and CURRENT CONTROL switch to OFF.
2. Local sensing shown. Remote sensing not recommended for Current control.
3. On Rear Programming Connector: remove jumper between terminals (15) and (C), add jumper between terminals (2) and (4).
4. For inductive loads in excess of 0.5mH, the BOP output response may be optimized by placing a capacitor across terminals (16) and (18) of the Rear Programming Connector (
Io COMP AMP).
Io ZERO
POWER
STAGE
COMMON
ZERO
+
PREAMP
"B"
­2
19
Io COMP
AMP
+
-
DRIVER
R
G A T E
S
16 18
LOAD
COM
S
OUT
S
SIGNAL
GROUND
15
C
13
4
10K
10K
CURRENT CONTROL
PART OF REAR PROGRAMMING CONNECTOR
HIGH Z
INPUT
SOURCE
0 TO ±10V
BIPOLAR
PROGRAMMER
(EXTERNAL)
3043705
22
C
COM
OUT
28
10V
+
10V
+
ON
OFF
CURRENT
PROGRAMMING
INPUT
Page 54
FIGURE 3-23. INDEPENDENT REMOTE CONTROL OF +EO AND –EO VOLTAGE LIMIT
3.6 SERIES AND PARALLEL CONNECTION OF BOP POWER SUPPLIES.
3043889
+
22
28
C
+
10V
10V
-
+
-
+
+
-
6
32
3
+
+
-
(+)Eo LIMIT-
AMP (EXT)
(+)Eo LIMIT-
AMP (INT)
(-)Eo LIMIT-
AMP (INT)
(-)Eo LIMIT-
AMP (EXT)
(+)Eo LIMIT
CONTROL
BIAS
15V
(-)Eo LIMIT CONTROL
COMMON
BOP Eo
LIMIT CHANNEL
PART OF REAR PROGRAMMING CONNECTOR
57.6K
57.6K
NOTES:
1. Remote sensing shown (links removed). For local sens ing disconnect leads between S terminals and load, then install links between COM and S terminals and between OUT and S terminals.
2. On Rear Programming Connector remove jumper between terminals (3) and (32) and between (32) and (6).
REMOVE
SENSING LINK
REMOVE
SENSING LINK
DRIVER
SIGNAL
GROUND
S
POWER
STAGE
COM
OUT
LOAD
S
+E o LIMIT
CONTROL
0-10V (EXT.)
-E o LIMIT
CONTROL
0-10V
(EXT.)
+ +
(-)Eo LIMIT-
COMP AMP
(+)Eo LIMIT­COMP AMP
+
-
­G
A T
E
Page 55
3.6.1 SERIES CONNECTION, MASTER/SLAVE OPERATION
Two or more BOP power supplies can be connected in series to increase output voltage. One series-connection limitation is the isolation limit of the BOP itself (500V); contact Kepco if more than three units is series are required. Figure 3-24 shows a master/slave connection of two BOP power supplies.
BOP VOLTAGE
PART OF REAR PROGRAMMING CONNECTOR
+
22
28
C
+
VOLTAGE CONTROL
VOLTAGE
PROGRAMMING
INPUT
10V
OFF
10V
ON
10K
10K
11
9
C
7
POWER
STAGE
NOTES (MASTER):
1. Set MODE Switch to VOLTAGE.
2. Set VOLTAGE CONTROL switch to ON.
3. Install sense link between OUT and S terminals.
4. Remove link between COM and S terminals.
5
Eo ZERO
-
17
+
Eo COMP
AMP
ZERO
PREAMP
"A"
-
+
2.49K
DRIVER
G A T E
COM
S
OUT
S
REMOVE
LINK
T
R
Page 56
new SLAVE, front panel VOLTAGE PROGRAMMING INPUT. Place the MODE switch on the BOP added to the series combination to VOLTAGE and the VOLTAGE CONTROL switch OFF.
1. Connect the BOP supplies as shown in Figure 3-24. Set the MO DE switches and the VOLT­AGE CONTROL switches as directed in the set-up diagram, Figure 3-24.
a. Load-wire size should be rated to at least the maximum load current and load-wire pairs
should be twisted or tied together to keep the indu ct ance a nd EMI as low as possible . For remote sensing, use #22 AWG twisted pair wires.
b. Use shielded cabl e for connecting the coupling resistor (R
T
). Connect shield to chassis-
ground. Either the positive or the negative output side of the system can be grounded.
c. The coupling resistor (R
T
) should be either a wirewound or a metal film component with a low temperature coefficient. For BOP 5-20DL this value is 2.49K (either 1/4 or 1/2 Watt). This value of R
T
will be able to drive the BOP Slave unit to its (±) maximum output voltage
as the BOP Master is controlled through its range.
d. Both BOP powe r supp lies shou ld be con nected to the power line using a common circuit
breaker. Alternatively, the BOP Circuit Breaker Control Circuit, as described in PAR.
3.6.2, can be used to interconnect both BOP’s in such a way that if one of them should fail, the other one is automatically shut down also.
2. Turn BOP‘s on and begin operation. The syst em as shown in Figure 3-24 operates in Volt-
Page 57
A manual, non-isolated turn-off is provid ed which, when implemented with an ex ternal switch contact as shown in Figure 3-25, will energize the diode in the first optocoupler (LC-1). thus providing the SCR turn-on.
If it is not
desired to trip the circuit breaker (CB101) upon a-c line power loss, it can be prevented by a jumper wire or an external switch across terminals 24 and 2 5 on the Rear Programming Connector. In this manner, Q1 is inhibited from providing a turn-on signal for Q2, thus avoiding triggering the SCR and tripping the circuit breaker.
+
+
DRIVER
COLLECTOR
SUPPLY
CR4
COM
LC1
+5V
FAST
TURN OFF
ON
Q2
PART OF
CB101
COMMON
LC2
TO
DRIVER
ASSEMBLY
(A3)
THERMO
SWITCH
ON A4
R4
Page 58
Figure 3-26 shows a simple parallel master/slave connection of no more than two BOP power supplies. The configuration shown in Fig ure 3-26 ca n be used for mast er/sla ve parallel con nec ­tion of two BOP power supplies (three are shown in Figure 3-27). The configuration shown in Figure 3-27 is more stable and accurate than that shown in Figure 3-26 since is includes com­pensation that eliminates the parasitic voltage drop on the COM connections of the slaves.
1. Connect the BOP supplies as shown in Figure 3-26 or 3-27. a. Set the MODE switches and the VOLTAGE and CURRENT CONTROL switches as
directed in the set-up diagram, Figure 3-26 or 3-27.
b. Load-wire size should be rated for at least the maximum load current and load-wire pairs
should be twisted or tied together to keep the inductance and EMI as low as possible. Use shielded cable for the drive signal connection between the BOP’s. Connect the shield to common ground. For remote sensing, use #22 AWG twisted pair wires.
c. Both BOP power supplies should be connected to the power line using a common circuit
breaker. Alterna tively, the BOP Circuit-Breaker Control Circuit, as described in PAR. 3.6.2 can be used to interconnect both BOPS in such a way, that if one of them should fail, the other one is automatically shut down also.
2. Following the set-up procedure as described above, turn BOP’s on and commence opera-
tion. The system as shown in the set-up diagram, Figure 3-26 or 3-27, operates in the Volt­age Mode, since the MASTER MODE switch is set to VOLTAGE. For operation in the
Page 59
POWER
STAGE
COMMON
NOTES (Master):
1. Set MODE switch to VOLTAGE.
2. Set VOLTAGE CONTROL switch to ON.
NOTES (SLAVE):
MASTER
PART OF REAR PROGRAMMING CONNECTOR
22
10
28
C
+
+
PREAMP
"A"
BOP VOLTAGE
CONTROL CHANNEL
10K
OFF
4
VOLTAGE
PROGRAMMING
INPUT
10K
VOLTAGE
CONTROL
ON
OFF
10V
10V
10K
11
C
7 9
2.49K
Eo ZERO
Eo COMP
AMP
ZERO
17
2.49K
5
G A
T
E
Io SENSING
AMP
DRIVER
S
R
COM
S
OUT
S
LOAD
TWIST
REMOVE
LINK
REMOVE
LINK
PART OF REAR PROGRAMMING CONNECTOR
(CHASSIS)
TWIST
Page 60
ON
OFF
MASTER
10
22
C
+
10V
28
+
10V
Eo ZERO
VOLTAGE
PROGRAMMING
INPUT
Io SENSING
AMP
BOP VOLTAGE
CONTROL CHANNEL
COMMON
S
Eo COMP
AMP
10K
VOLTAGE
CONTROL
10K
C
17
ZERO
PREAMP
"A"
11
7
9
2.49K
NOTES (MASTER):
1. For Voltage Mode (shown) set MODE Switch to VOLTAGE and VOLTAGE CONTROL Switch to ON.
2. For Current mode, set MODE Switch to CURRENT and CURRENT CONTROL Switch to ON.
3. If external control is needed, set the CONTROL switch to OFF and use either the corresponding VOLTAGE or CURRENT PROGRAMMING INPUT or the appropriate rear programming connector terminals.
G
A T E
DRIVER
5
R
POWER
STAGE
SCOM
OUT
S
LOAD
TWIST
REMOVE
LINKS
NOTES (SLAVE 1):
1. MODE Switch position to: CURRENT
2. CURRENT CONTROL Switch to: OFF
3. R1 (A and B) and R2 (A and B) are matched pairs, 0.01% tolerance, metal film, 0.25W.
4. Remove rear programming connector jumpers between pins 4 and 13 and between pins 15 to 27.
OFF
43
44
10K
4
C
2.49K
19
Io COMP
AMP
DRIVER
G A T E
+
-
-
+
-
+
TWIST
-
PART OF
REAR
PROGRAMMING
CONNECTOR
NOTE 3
(EXT.) R2B
20K
(EXT.) R1B
20K
(EXT.) R2A
20K
(EXT.) R1A
20K
PART OF REAR
PROGRAMMING
CONNECTOR
PART OF REAR
PROGRAMMING CONNECTOR
TWIST
Page 61
3.7 INDICATOR AND FLAG LOGIC CIRCUIT
Digital Logic Circuits (IC15, IC16, IC17) as shown in Figure 3-28 are used in the BOP to drive the front panel LEDs which indicate the prevailing operating mode:
E
O
LIMIT MODE (DS101)
I
O
LIMIT MODE (DS102)
E
O
MODE (DS103)
I
O
MODE (DS104)
REMOTE (DS105)
Together with these visual front panel indicators , TTL-compa tible status flags ar e provided at the Rear Programming Connector for the above BOP operating modes. All status flags available on the rear programming connector indicate a logic ”0” If the BOP is operating in the indicated operating mode, and a logic “1” if it is not.
5
4
6
1
DS101
Eo LIMIT
DS102
Io LIMIT
+5V
RN1
FLAG
Eo LIMIT
"1"
30
LAMP
DRIVERS
IC17
+5V
"0"
"1"
PART OF REAR PROGRAMMING CONNECTOR
FROM
Eo/
Io LIMIT
COMPARATORS
Page 62
The logic status signals shown in Figure 3-28 are valid for the BOP operating in voltage mode (E
O
MODE) and local mode (not driven by the GP lB interface). The BOP 5-20DL uses the front panel REMOTE ON-OFF indicator shows the output on-off status as determined by signals applied to the OUTPUT ON-OFF Port.
3.8 DIGITAL CONTROL OF BOP POWER SUPPLIES.
The BOP 5-20DL is configured with a remote output ON-OFF POR T which inte rfaces electrically and mechanically with the digital control assembly used by a BIT Interface card which must be installed for digital control. If digital control is required, contact Kepco to disable the output ON­OFF PORT and allow installation of the optional BIT interface card. Digital control options avail­able are via either GPIB and RS 232 using a BIT 4886 Interface Card, or ethernet/LAN using a BIT 802E Interface card. Both cards are compliant with IEEE 488 and SCPI commands and queries. For more details, see www.kepcopower.com/bit.htm.
Page 63
081915 29
FIGURE 3-29. SIMPLIFIED SCHEMATIC DIAGRAM,
BOP 5-20DL
I
I
I
I
I
I
I
I
I
I
I
I
I
I
-I
I
I
I
3-29/(3-30 Blank)
-28/(-29
Page 64
Page 65
SECTION 4 - INTERNAL ADJUSTMENTS AND CALIBRATION
4.1 GENERAL
This section contains the procedures for all internal adjustments and calibrations. All internal adjustment controls are illustrated In Figure 4-1 and listed in Table 4-1. Table 4-1
explains the purpose of each control and references the applicable adjustment procedure. NOTE: These controls are factory ca librated. Re-calibration is necessary only if components,
related to the circuitry involving these controls have to be replaced.
TABLE 4-1. INTERNAL CALIBRATION CONTROLS
REFERENCE
DESIGNATION
(SEE FIGURE 4-1)
CONTROL NAME PURPOSE
ADJUSTMENT
PROCEDURE
A1R31, A1R32 ±10V CA L. Reference Voltage Calibration PAR. 4.2.1
A1R41
PREAMP ’A” ZERO Uncommitted Amplifier “A“ Zero Adjustment PAR. 4.2.2
A1R42
PREAMP ’B” ZERO Uncommitted Amplifier “B“ Zero Adjustment PAR. 4.2.3
A1R50
AMMETER ZERO Sensing Amp. Offset Adjustment PAR. 4.2.4
A1R81
(1)
Eo COMP AMP ZERO Voltage Channel Zero Adjustment PAR. 4.2.6
Page 66
Page 67
4.2.2 UNCOMMITTED AMPLIFIER “A” ZERO ADJUSTMENT (A1R41)
1. Without a load connected at the output, set MODE switch to VOLTAGE and VOLTAGE CON­TROL switch to OFF.
2. Place a short circuit across the front panel VOLTAGE PROGRAMMING INPUT terminals.
3. Connect a Digital Voltmeter (DVM) to Rear Programming connector pin 5, referenced to pin 29 (signal common).
4. Locate the PREAM P “A” ZERO control (see Figur e 4-2, A1R41), then turn the BOP on and adjust control for 0V ±0.1mV, as read on DVM.
4.2.3 UNCOMMITTED AMPLIFIER “B” ZERO ADJUSTMENT (A1R42)
1. Without a load connected at the output, set MODE switch to VOLTAGE and VOLTAGE CON­TROL switch to OFF.
2. Place a short circuit across the front panel CURRENT PROGRAMMING INPUT terminals.
3. Connect a Digital Voltmeter (DVM) to Rear Programming connector pin 2, referenced to pin 29 (signal common).
4. Locate the PREAM P “B” ZERO control (see Figur e 4-2, A1R42), then turn the BOP on and
Page 68
4.2.5 ADJUSTMENT OF IO-OFF ZERO (A1A1R13) AND EO-OFF ZERO (A1A1R16)
1. At rear panel, disconnect positive voltage between pins 2 and 3 of the OUTPUT ON-OFF port (if present) (2, Figure
2-2) to turn the output OFF (refer to Table 1-7 for detailed signal
requirements).
2. Connect prec ision shunt resistor across the BOP OUTPUT and COMMON te rminals. Con­nect DVM to the shunt’s sensing terminals for output current measurements.
3. Set MODE switch to CURRENT and CURRENT CONTROL switch to OFF, then turn the BOP on.
4. Adjust IO-OFF ZERO (A1A1R13) potentiometer (see Figure 4-2) for 0A ±(0.01% of IOnom) as read on the DVM connected to the shunt. (For BOP 5-20DL IOnom is 20A and adjustment tolerance is ±2mA.)
5. Turn off the BOP and remove the shunt resistor from the output. Connect the DVM to the output sensing terminal of the BOP (OUT S and COM S).
6. Set MODE switch to VOLTAGE and VOLTAGE CONTROL switch to OFF, then turn the BOP on.
7. Adjust EO-OFF ZERO (A1A1R16) for 0V ±(0.01% of EOnom) as read on DVM. (For BOP 5­20DL E
O
nom is 5V and adjustment tolerance is ±0.5mV.)
Page 69
4.2.7 CURRENT CHANNEL ZERO ADJUSTMENT (A1R83)
1. At rear panel, apply positive voltage between pins 2 and 3 (return) of the OUTPUT ON-OFF port (2, Figure
2-2) to enable (turn on) the output. Refer to Table 1-7 for signal requirements.
2. With the unit turned off, connect a precision current measuring shunt, rated for the unit's nominal output current (20A for BOP 5-20DL) to the output.
3. Connect DVM to the shunt's sensing terminals.
4. Set MODE switch to CURRENT and CURRE NT CONTROL switch to OFF.
5. Place a short circuit across the front panel CURRENT PROGRAMMING INPUT terminals.
6. Locate the Io COMP AMP ZERO control (see Figure 4-2, A1R83), then turn on BOP and adjust control for 0A ±(0.005% of IOnom), as read on DVM. For BOP 5-20D L, IOnom is 20A and the adjustment range is ±1mA.
4.2.8 CALIBRATION OF IO FULL SCALE OUTPUT CURRENT (A3R316) AND FRONT PANEL AMMETER (A7AR3B)
1. Turn BOP off and remove the cover (see Figure 4-2).
2. Connect either a precision ammeter or a precision current-measuring shunt resistor to the
Page 70
Loading...