KEP TP-554 Data sheet

TP-554 Series
Features
• Very bright LED display, height 14mm
• DIN housing, 96 x 48 mm
• Programmable operating curve, even non­linear, allowing the use of economical sensors
• Two relay outputs with two preset limit values
Te mperature/Process Monitor With or Without Alarms
Additional features:
• DIN housing 96 x 48 mm
• Character height: 14 mm
• Resolution 14 bits
• Simple menu-driven programming, and operation with 4 keys
• Electrical connections by means of plug-in screw terminals
•Voltage supply: 10-30 VDC or 90-260 VAC
• IP 65/NEMA4 (front)
• Auxiliary power supply output for transducer or sensor
10..30 VDC: 10 VDC ± 2%, 30mA
90..260 VAC: 24 VDC ± 15%, 50mA and 10 VDC ± 2%, 30mA
• Hum eliminator (50/60 Hz user selectable)
• Serial interface allows reading of the measured values and
set-up programming.
Specifications:
• Display range: -19.999..99.999
DIGITAL PANEL METERS
• Input ranges:
0..400 , 0..4000
Thermocouples
• Integrated operating curves for thermocouples(types B, C, D,
• Programmable input operating curve with up to 24 reference
•2 programmable limit values (TP551; unit without presets,
• Outputs: Two (2) SPDT relays (250 VAC / 3A)
• Programmable hysteresis (on, off, on/off)
• SET key to reset the outputs
• Inputs: thermocouple, millivolt, resistance thermometer with
0..100 mV, -100..+100 mV
E, G, J, K, L, N, R, S, T, U)
points
has only 2 buttons)
measurement on 2, 3 or 4 wires, RESET to reset the outputs, KEY terminal to lock the front keys.
Order Code
Example: TP554.010 0 00 Series:
TP551.012 = No Presets/Relays TP554.010 = 2 Presets/Relays
Operating Voltage:
0 = 90 to 260 VAC 3 = 10 to 30 VDC
Options:
00 = without interface 05 = RS232 06 = RS422 07 = RS485
Dimensions:
3.78 (96)
1.89 (48)
1.77 (45)
3.62 (92)
Wiring:
TB1
1 Relay 2 Com. (Opto-Emitter) 2 Relay 2 N.0. 3 Relay 2 N.C. (Opto-Collector) 4 Relay 1 Com. (Opto-Emitter) 5 Relay 2 N.0. 6 Relay 2 N.C. (Opto-Collector) 7 A.C. In (10-30 VDC) 8 A.C. In (Ground; 0 VDC)
TB3
RS232 RS485 RS422 1 GND – 2 RxD DO+/RI+ RI+ 3 TxD DO–/RI– RI– 4 – DO+ 5– DO–
1.77 x 3.62 (44.9 x 91.9)
0.61
(15.5)
0.16 (4)
0.26 (6.5)
2.64 (67.1)
Dimensions are in inches (mm)
TB2
1 Measuring input 1 (Sense) 2 Measuring input 2 (– Ref) 3 Sensor (+Ref) 4 Current output for 0 .. 4000 (+ Sense) 5 Current output for 0 .. 400 (+ Sense) 6 Keys locking 7 Reference ground Reset / Key 8 Reset 9 GND for DC Output (Pins 10 & 11) 10 +10 VDC Out (30 mA) 11 +24 VDC Out (50 mA) (AC units only)
Page 94 • Industrial Instruments • II-15 Kessler-Ellis Products • 800-631-2165