KEP SC-FI Operating Manual

SC-FI Series
Frequency to Current Signal Conditioner
99483 10/9/98
KESSLER-ELLIS PRODUCTS
10 Industrial Way East Eatontown, NJ 07724 800-631-2165 • 732-935-1320 Fax 732-935-9344
THIS PAGE IS BLANK
INDEX
DESCRIPTION ..................................................................................1
SPECIFICATIONS.............................................................................1
TYPICAL WIRING HOOKUP.............................................................1
INPUT & OUTPUT SETTINGS..........................................................2
"L" OPTION SPECIFICATIONS ........................................................3
"L" OPTION TYPICAL WIRING.........................................................3
"L" OPTION INPUT & OUTPUT SETTINGS .....................................4
DIMENSIONS....................................................................................5
WARRANTY ......................................................................................5
DECODING PART NUMBER ............................................................5
THIS PAGE IS BLANK
Description:
The SC-FI is a two wire frequency to analog converter that converts a pulse rate input into a 4-20 mA output signal proportional to frequency or rate.
The input pulse rate is amplified and filtered by the input signal conditioning circuitry. Two forms of input signal condi­tioning are provided, one for magnetic pickups and the other being an isolated pulse input.
The amplified frequency signal is then converted to an ana­log signal using a precision frequency to analog converter.
The output stage derives it’s power from the output current loop. The output stage converts the input signal into the desired output range. Multi-turn potentiometers provide for the necessary trimming of span and zero.
SPECIFICATIONS:
Operating Temperature
32° F (0°C) to 158°F (70°C)
High Level Pulse Input
Type: Opto-Isolated Logic 1: 4-30 VDC Logic 0: 0-1 VDC Frequency Range: 0-10 kHz Fault Protection: Reverse Polarity Protection
Over Voltage Protection Isolation Voltage: 500 V Fast Transient Immunity: 500 V Maximum Rise Time: No Limit Maximum Fall Time: No Limit
Magnetic Pickup Input
Differential Input Input Impedance: 10 k Frequency Response: 0-3500 Hz Trigger Sensitivity: 30 mV p-p Over Voltage Protection: ± 30 VDC
Frequency to Current Conversion
Range Selection: DIP Switch Selectable Available Ranges: 150 Hz, 300 Hz, 600 Hz, 1200 Hz,
2500 Hz, 5000 Hz, 10,000 Hz
Factory Default: 1000 Hz
SC-FI Signal Conditioner
Analog Output
Accuracy: ± 0.1% Span (@ 20° C) Output Type: Two Wire, Loop Powered Range: 4-20 mA (10 - 50 mA optional) Compliance Voltage: 10 to 40 VDC Loop Burden: < 10 VDC (less than 500 ) Trim Controls: Zero & Span, non-interacting
Span (20 mA) Trim Range: 50% to 100% of full scale Linearity: < ±0.1% Span Output Voltage Effect: < ± 0.002% Span/Volt Temperature Effect: < 200 PPM/C° Reverse Polarity Protected Noise Content: < 0.2% Span Response Time: 0.1 second (1 sec. jumper selectable) Over-current Limiting: 35 mA Output Loop Indicator: LED illuminates when output loop is
powered by proper polarity and blinks proportionally to the input frequency.
Mounting Styles
DIN Rail Mount: Plastic enclosure with a snap fastener for
fitting to DIN 46 277 and DIN EN 50 022 assembly rails.
NEMA 4X: 4.92" x 4.92" NEMA 4X Enclosure for wall
mounting.
Explosion Proof: Aluminum enclosure for:
Class I, Division 1, Groups B, C & D Class II, Division I, Groups E, F & G.
Typical Wiring Hookup Magnetic Pickup Hookup
1• Magnetic pickup
Turbine Meter with
Mag Pickup
2• Magnetic pickup 3• Shield (common) 4• Opto-isolator In + 5• Opto-isolator In –
+
DC POWER SUPPLY
+
ANALOG
4-20 mA DEVICE
6• Shield (common) 7• Output + 8• Output – 9• Do Not Use
High Level Pulse Hookup
Simplified Block Diagram
mV nput
-30V
Input
+ –
10k
10k
3.3k
V ref
F/V
Span
Zero
REED SWITCH PULSER
+
V/I
Loop Powered
4-20mA Output
+
DC POWER SUPPLY
+
ANALOG
4-20 mA DEVICE
1• Magnetic pickup 2• Magnetic pickup 3• Shield (common) 4• Opto-isolator In + 5• Opto-isolator In – 6• Shield (common)
7• Output + 8• Output – 9• Do Not Use
1
SC-FI Signal Conditioner
INPUT & OUTPUT SETTINGS
REMOVING THE CASE:
The case must be removed to change switch settings. To remove the case procede as follows:
Refer to FIGURE 1. Using finger tips, carefully pry the case away from the terminal blocks (as shown with dotted lines).
Pry far enough to release the restraining clips on both sides of the case.
Press up on terminal block with thumbs. The assembly will pop out allowing it to be removed from case.
FIGURE 1:
4 5 6
1 2 3
OUTPUT ADJUSTMENTS:
The unit has two potentiometers for adjustment. The upper potentiometer controls the 20mA setpoint and the lower potentiometer controls the 4mA setpoint (see Figure 2). The 4mA output range can be adjusted from 3mA to 5mA. The 20mA output range can be trimmed from 50% to 100% of the selected range. To adjust the output, initially turn the 20ma adjust 20 turns CW for starting position. Input 0 frequency and adjust the 4 mA pot. Connect your maximum frequency and adjust the 20 mA pot.
FIGURE 2:
4 5 6
1 2 3
20 mA Adjust (CCW-Up, CW-Down)
4 mA Adjust (CCW-Down, CW-Up)
LED INDICATOR
7 8 9
INPUT FREQUENCY RANGE SETTINGS:
The appropriate range is selected by turning “ON” the corre­sponding switch.
Range: Switch # “ON” 0-150Hz 1
0-300Hz 2 0-600Hz 3 0-1200Hz 4* 0-2500Hz 5 0-5000Hz 6 0-10000Hz 7
* Factory Default. The unit is setup at the factory for the range 0-1000Hz.
7 8 9
RESPONSE TIME SETTING:
Switch #8 controls the output response time.
Switch #8 Response Time
OFF 0.1 second
ON 1 second
Turn switch #8 ON to provide damping of the output result­ing in a 1 second response time.
LED INDICATOR:
The SC-FI has a LED which indicates the status of the unit. The table below describes the 3 states for the LED.
LED STATUS: MEANING: OFF The unit is off. ON (constant) The unit is loop powered. BLINKING The unit is receiving an input fre-
quency. The LED will blink at a rate proportional to the input frequency. (The LED may appear to be constant at high input frequencies)
2
"L" Option SPECIFICATIONS
SC-FI Signal Conditioner
Description:
The SC-FI with option "L" is a two wire frequency to analog con­verter that converts a pulse rate input into a 4-20 mA output signal proportional to frequency or rate.
The SC-FI with option "L" is intended for use with lower full scale input frequencies. Full scale frequencies of 15 Hz to 2000 Hz are possible. The unit includes both a contact closure input and an opto-isolated input. Output response time is selectable 1 or 10 seconds.
The amplified frequency signal is then converted to an analog signal using a precision frequency to analog converter.
The output stage derives it’s power from the output current loop. The output stage converts the input signal into the desired output range. Multi-turn potentiometers provide for the necessary trim­ming of span and zero.
SPECIFICATIONS:
Operating Temperature
32° F (0°C) to 158°F (70°C)
High Level Pulse Input
Type: Opto-Isolated Logic 1: 4-30 VDC Logic 0: 0-1 VDC Frequency Range: 0-10 kHz Fault Protection: Reverse Polarity Protection
Over Voltage Protection Isolation Voltage: 500 V Fast Transient Immunity: 500 V Maximum Rise Time: No Limit Maximum Fall Time: No Limit
Contact Closure Input
Sensor Compatibility- Requires an isolated, contact closure Maximum Contact Voltage- 5 V Maximum Contact Current- 0.12 mA Nominal Pullup Resistance - 47 Kohm to 5 Vdc
Frequency Range - 0-100 Hz
Frequency to Current Conversion
Range Selection: DIP Switch Selectable Available Ranges: 30 Hz, 60 Hz, 120 Hz, 240 Hz,
480 Hz, 960 Hz, 1920 Hz
Factory Default: 100 Hz
Analog Output
Accuracy: ± 0.1% Span (@ 20° C) Output Type: Two Wire, Loop Powered Range: 4-20 mA (10 - 50 mA optional) Compliance Voltage: 10 to 40 VDC Loop Burden: < 10 VDC (less than 500 ) Trim Controls: Zero & Span, non-interacting
Span (20 mA) Trim Range: 50% to 100% of full scale Linearity: < ±0.1% Span Output Voltage Effect: < ± 0.002% Span/Volt Temperature Effect: < 200 PPM/C° Reverse Polarity Protected Noise Content: < 0.2% Span Response Time: 1 second (10 sec. jumper selectable) Over-current Limiting: 35 mA Output Loop Indicator: LED illuminates when output loop is
powered by proper polarity and blinks proportionally to the input frequency.
Mounting Styles
DIN Rail Mount: Plastic enclosure with a snap fastener for
fitting to DIN 46 277 and DIN EN 50 022 assembly rails.
NEMA 4X: 4.92" x 4.92" NEMA 4X Enclosure for wall
mounting.
Explosion Proof: Aluminum enclosure for:
Class I, Division 1, Groups B, C & D Class II, Division I, Groups E, F & G.
Typical Wiring Hookup (option "L") Contact Closure Hookup
Flowmeter with
Switch Closure Output
1• Not Used 2• Contact Closure In 3• Shield (common) 4• Opto-isolator In + 5• Opto-isolator In –
+
DC POWER SUPPLY
+
ANALOG
4-20 mA DEVICE
6• Shield (common) 7• Output + 8• Output – 9• Do Not Use
High Level Pulse Hookup
Simplified Block Diagram
+5V
47k
Contact Closure
Input
3-30V
Input
– +
3.3k
V ref
F/V
Span
Zero
REED SWITCH PULSER
+
V/I
Loop Powered
4-20mA Output
+
DC POWER SUPPLY
+
ANALOG
4-20 mA DEVICE
1• Magnetic pickup 2• Magnetic pickup 3• Shield (common) 4• Opto-isolator In + 5• Opto-isolator In – 6• Shield (common)
7• Output + 8• Output – 9• Do Not Use
3
SC-FI Signal Conditioner
"L" Option INPUT & OUTPUT SETTINGS
REMOVING THE CASE:
The case must be removed to change switch settings. To remove the case procede as follows:
Refer to FIGURE 1. Using finger tips, carefully pry the case away from the terminal blocks (as shown with dotted lines).
Pry far enough to release the restraining clips on both sides of the case.
Press up on terminal block with thumbs. The assembly will pop out allowing it to be removed from case.
FIGURE 1:
4 5 6
1 2 3
OUTPUT ADJUSTMENTS:
The unit has two potentiometers for adjustment. The upper potentiometer controls the 20mA setpoint and the lower potentiometer controls the 4mA setpoint (see Figure 2). The 4mA output range can be adjusted from 3mA to 5mA. The 20mA output range can be trimmed from 50% to 100% of the selected range. To adjust the output, initially turn the 20ma adjust 20 turns CW for starting position. Input 0 frequency and adjust the 4 mA pot. Connect your maximum frequency and adjust the 20 mA pot.
FIGURE 2:
4 5 6
1 2 3
20 mA Adjust (CCW-Up, CW-Down)
4 mA Adjust (CCW-Down, CW-Up)
LED INDICATOR
7 8 9
INPUT FREQUENCY RANGE SETTINGS:
The appropriate range is selected by turning “ON” the corre­sponding switch.
Range: Switch # “ON” 0-30Hz 1
0-60Hz 2 0-120Hz 3* 0-240Hz 4 0-480Hz 5 0-960Hz 6 0-1920Hz 7
* Factory Default. The unit is setup at the factory for the range 0-100Hz.
7 8 9
RESPONSE TIME SETTING:
Switch #8 controls the output response time.
Switch #8 Response Time
OFF 1 second
ON 10 second
Turn switch #8 ON to provide damping of the output result­ing in a 10 second response time.
LED INDICATOR:
The MS660 has a LED which indicates the status of the unit. The table below describes the 3 states for the LED.
LED STATUS: MEANING: OFF The unit is off. ON (constant) The unit is loop powered. BLINKING The unit is receiving an input fre-
quency. The LED will blink at a rate proportional to the input frequency. (The LED may appear to be constant at high input frequencies)
4
Dimensions
SC-FI Signal Conditioner
DIN Rail Mount
WARRANTY
This product is warranted against defects in materials and workmanship for a period of two (2) years from the date of shipment to Buyer.
.89
(22.5)
Mounting holes molded directly under cover screws. Max. screw head .29" (Typ. 4 places)
4.21
(107)
PANEL INSTALLED
1.40 (35.5)
2.95 (75)
NEMA4X
To access terminals, remove
4.21
(107)
4.92
(125)
TOP VIEW
cover and 4 panel screws.
4.92
(125)
.43
(11)
Explosion Proof Enclosure
3/4” NPT (2) HLS. (feed thru hubs)
.18 (5)
SIDE VIEW
3.88 (98.5)
2.95 (75)
1.93 (49)
The Warranty is limited to repair or replace­ment of the defective unit at the option of the manufacturer. This warranty is void if the prod­uct has been altered, misused, dismantled, or otherwise abused.
ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, ARE EXCLUDED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WAR­RANTIES OF MERCHANTABILITY AND FIT­NESS FOR A PARTICULAR PURPOSE.
Kessler - Ellis Products Co.
10 Industrial Way East
Eatontown, NJ 07724
(732) 935 - 1320
Toll Free 800 - 631 - 2165
Fax (732) - 935 - 9344
http://www.kep.com
5.06
(129)
7.125 (181)
5.44
(138)
4.06
(103.2)
2 MTG LUGS
0.31 DIA.
Decoding Part Number Example SC-FI D ET Series
FI= Frequency to Current
Mounting:
B= Nema 4X C= Explosion Proof D= DIN Rail
Options:
ET= Extended Temp (-20° to 85° C) L = Low Count Speed for Contact Closure Inputs 50 = 10-50 mA output
Accessories: (add to end of part number)
DR-4= 4" DIN Rail
5