KEP PMT-555 Data sheet

PMT-555 Series
Features
• Large keys allow easy operation and programming
• Key lock input
• Programmable 24 point linearization
• Integration function (totalizer) for the integration (sum calculation) of the measured
values (e.g. throughput measurement =>Fill­up level) with own scaling and programmable input threshold
• RS-232, RS-422, RS-485 Option
Process Monitor and Totalizer from Analog Inputs
COUNTERS/RATEMETERS
•2 setpoints with programmable hysteresis and 2 relays or optocoupler outputs
• Current or voltage input
Description:
The PMT-555 process monitor/totalizer is ideal for applications that require an LED process/totalizer display from voltage or current inputs. The unit can accept 4-20mA, 0-20mA, 0-10V, 2-10V or -10 - +10V
signals. Two assignable set points are standard.
Specifications:
Supply voltage: 10 to 30 V DC, galvanically
isolated with reverse polarity protection 90 to 260 V AC 50/60 Hz
mains hum suppression Power consumption: max. 2 W/6 VA Display: 5-digit , red 7-segment LED‘s
height 14 mm Measuring rate: 1 measurement/second Data backup: EEPROM Housing: housing for control panel 96
x 48 mm acc. to DIN 43 700;
RAL 7021, dark grey Ambient temperature: –10 to +50°C EMC: according to EC EMC
directive 89/36/EEC Interference emissions: EN 50081-2/EN 55 011
Class B Interference resistance: EN 6100-6-2 Protection: IP65 (front) Weight: app. 190 g
• 10 VDC and/or 24 VDC output power supply
Current input: 0-20 mA, 4- 20 mA
voltage drop max. 2 V limit 50 mA
Voltage input: 0-10 V, 2-10 V, (-)10 - (+)10 V
limit ±30 V input resistance > 1 M
Control inputs: High: 4-30 V DC
Low: 0-2 V DC Resolution: 14 bits Accuracy: < 0.1 % ±1 digit at 20 °C, automatic null balance DC output: 10 V DC ± 2%, 30 mA(DC
powered units)
10 V DC ±2%, 30 mA and
24 V DC ±15%, 50 mA (AC
powered units) Outputs: 2 Form C Relays
max. 300 V DC/250 V AC
current: max. 3 A, min. 30 mA
DC
or optocoupler output, NPN
30 V, 15 mA
Kessler-Ellis Products • 800-631-2165 II-15 • Industrial Instruments • Page 65
Wiring Connections
Rear View
TB1 Measurment Inputs
COUNTERS/RATEMETERS
TB2 Supply Voltage and Outputs
TB3 Serial Interface
Dimensions
3.78 (96)
1.89 (48)
1.77 (45)
3.62 (92)
1.77 x 3.62 (44.9 x 91.9)
0.61
(15.5)
0.16 (4)
0.26 (6.5)
2.64 (67.1)
Dimensions are in inches (mm)
Order Code
Example: PMT555.01 0 00 Series:
PMT-555 = Process Monitor & Totalizer
w/ 2 Presets/Relays
Operating Voltage:
0 = 90 to 260 VAC 3 = 10 to 30 VDC
Options:
00 = without interface 05 = RS232 06 = RS422 07 = RS485
Page 66 • Industrial Instruments • II-15 Kessler-Ellis Products • 800-631-2165
Loading...