KEP LEVELtrol II Operating Manual

LEVELtrol-II Installation & Operating Instructions
LEVELtrol-II
Flow Computer
Version 01.xx
99594 03/14/11
KESSLER-ELLIS PRODUCTS 10 Industrial Way East Eatontown, NJ 07724 800-631-2165 732-935-1320 Fax 732-935-9344
74
Proprietary Notice
The information contained in this publication is derived in part from proprietary and patent data. This information has been prepared for the expressed purpose of assisting operating and maintenance personnel in the efficient use of the instrument described herein. Publication of this information does not convey any rights to use or reproduce it or to use for any purpose other than in connection with the installation, operation and maintenance of the equipment described herein.
Copyright 1995
Printed in USA. All Rights Reserved.
!
WARNING!
This instrument contains electronic components that are susceptible to damage by static electricity. Proper handling* procedures must be observed during the removal, installation, or handling of internal circuit boards or devices.
*Handling Procedure
1. Power to unit must be removed.
2. Personnel must be grounded, via wrist strap or other safe, suitable means, before any printed circuit board or other internal device is installed, removed or adjusted.
3. Printed circuit boards must be transported in a conductive bag or other conductive container. Boards must not be removed from protective enclosure until the immediate time of installation. Removed boards must be placed immediately in protective container for transport, storage, or return to factory.
Comments This instrument is not unique in its content of ESD (electrostatic discharge) sensitive components. Most modern electronic
designs contain components that utilize metal oxide technology (NMOS, CMOS, etc.). Experience has proven that even small amounts of static electricity can damage or destroy these devices. Damaged components, even though they appear to function properly, may exhibit early failure.
SAFETY INSTRUCTIONS
!
The following instructions must be observed.
• This instrument was designed and is checked in accordance with regulations in force EN 60950 (“Safety of information technology equipment, including electrical business equipment”). A hazardous situation may occur if this instrument is not used for its intended purpose or is used incorrectly. Please note operating instructions provided in this manual.
• The instrument must be installed, operated and maintained by personnel who have been properly trained. Personnel must read and understand this manual prior to installation and operation of the instrument.
• This instrument is internally fused. Replace the internal fuse with the following specified type and rating only:
Input Power Recommended Fuse
1 15 VAC 160 mA slow blow fuse 230 VAC 80 mA slow blow fuse
12-24 VDC 800 mA slow blow fuse
Disconnect power supply before replacing fuse!
• The manufacturer assumes no liability for damage caused by incorrect use of the instrument or for modifications or changes made to the instrument.
Symbols Used On Unit
Number Symbol Publication Description
1 IEC 417, No. 5031 Direct current
2 IEC 417, No. 5172 Equipment protected throughout by DOUBLE
INSULATION or REINFORCED INSULATION (equivalent to Class II of IEC 536–see annex H)
3
!
ISO 3864, No. B.3.1 Caution (refer to accompanying documents)
Technical Improvements
• The manufacturer reserves the right to modify technical data without prior notice.
CONTENTS
1. Description...................................................................................................................1
1.1 Unit Description:..............................................................................................1
1.2 Unit Features: ................................................................................................. 1
1.3 Specifications:.................................................................................................2
2. Installation....................................................................................................................6
2.1 General Mounting Hints: .................................................................................6
2.2 Mounting Diagrams:........................................................................................6
3. Applications .................................................................................................................7
3.1 Tank Level/Volume ......................................................................................... 7
3.2 Corrected Tank Volume .................................................................................. 8
3.3 Total Mass in Tank..........................................................................................9
3.4 Batching Volume, Corrected Volume or Mass from Tank Level ................... 10
4 WIRING ...................................................................................................................... 11
4.1 Typical Batcher Wiring: ................................................................................. 11
4.2 Typical Level/Total Wiring:............................................................................11
4.3 Wiring In Hazardous Areas: ..........................................................................12
5. UNIT OPERATION .................................................................................................... 13
5.1 Front Panel Operation Concept for Run Mode ............................................. 13
5.2 General Operation ........................................................................................ 14
5.3 Level/Total Operation....................................................................................14
5.3.1 Password Protection for Level/Total mode ................................................ 14
5.3.2 Relay Operation in Level/Total mode.........................................................14
5.3.3 Pulse Output in Level/Total mode..............................................................14
5.3.4 Analog Output in Level/Total mode............................................................15
5.3.5 RS-232 Serial Port Operation in Level/Total mode.................................... 15
5.3.6 RS-485 Serial Port Operation in Level/Total mode.................................... 15
5.4 Batcher Operation.........................................................................................16
5.4.1 Batcher Configuration. ............................................................................... 16
5.4.2 Password Protection for Batcher Mode ..................................................... 17
5.4.3 Relay Operation in Batcher mode..............................................................17
5.4.4 Pulse Output in Batcher mode ................................................................... 17
5.4.5 Analog Output in Batcher mode.................................................................18
5.4.6 RS-232 Serial Port Operation in Batcher mode ........................................ 18
5.4.7 RS-485 Serial Port Operation in Batcher mode ......................................... 18
i
CONTENTS
6. PROGRAMMING.......................................................................................................19
6.1 Front Panel Operation Concept for Program Mode ...................................... 19
6.2 EZ Setup ....................................................................................................... 20
6.2.1 TOP LEVEL SETUP MENU...................................................................... 20
6.2.2 EZ Setup Submenu Groups.......................................................................20
6.3 Setup Menus................................................................................................. 22
6.3.1 Top Level Setup Menu............................................................................... 22
6.3.2 Submenu Groups......................................................................................22
6.4 Setup Sub-Menus ......................................................................................... 23
6.4.1 DO EZ SETUP? .........................................................................................23
6.4.2 SET INSTRUMENT TYPE ......................................................................... 23
6.4.3 SETUP INDICATORS (Vol) ...................................................................... 24
6.4.4 SETUP INDICATORS (Mass)....................................................................24
6.4.5 SETUP INDICATORS (Level)....................................................................25
6.4.6 SETUP INDICATORS (Temperature)........................................................25
6.4.7 SETUP TANK STYLE (Strapping Table) ................................................... 26
6.4.8 SETUP TANK STYLE (Vertical Cylindrical or Horizontal Cylindrical) ........ 27
6.4.9 SETUP TANK STYLE (Sphere) ................................................................. 27
6.4.10 SETUP PROCESS INPUTS (Level) ........................................................ 28
6.4.11 SETUP PROCESS INPUTS (Compensation Input).................................29
6.4.12 SET FLUID PROPERTIES ...................................................................... 30
6.4.13 SETUP OUTPUTS (Analog Output) ........................................................ 30
6.4.14 SETUP OUTPUTS (Pulse Output)...........................................................31
6.4.15 SETUP RELAYS (Relay 1) ...................................................................... 31
6.4.16 SETUP RELAYS (Relay 2) ...................................................................... 32
6.4.17 SETUP RELAYS (Relay 3 & 4)................................................................ 33
6.4.18 SETUP CONTROL INPUTS (LEVEL/TOTAL) ......................................... 34
6.4.19 SETUP CONTROL INPUTS (BATCH)..................................................... 34
6.4.20 SETUP REALTIME CLOCK (Time) .........................................................34
6.4.21 SETUP REALTIME CLOCK (Date)..........................................................35
6.4.22 SETUP SERIAL OUTPUT ....................................................................... 35
6.4.23 SET PRINT OUTPUT (Configure) ........................................................... 36
6.4.24 SET PRINT OUTPUT (Select_list)...........................................................36
6.4.25 SETUP PASSWORDS (Operator) ........................................................... 37
6.4.26 SETUP PASSWORDS (Supervisor) ........................................................37
6.4.27 SETUP NETWORK CARD ...................................................................... 37
ii
CONTENTS
7. Principle Of Operation ............................................................................................... 38
7.1 General Operation ........................................................................................ 38
7.2 Determining the liquid quantity for various Tank Geometries ...................... 38
7.3 Determining Liquid Level .............................................................................. 38
7.4Corrections for density in hydrostatic pressure
based level measurements............................................................................38
7.5 Computation of Corrected Volume in Tank and Mass in Tank ..................... 39
7.6 Calculating the Expansion Factor For a Fluid ............................................... 41
8. Test, Service and Maintenance ................................................................................. 42
8.1 Test Menus ................................................................................................... 42
8.1.1 TOP LEVEL TEST MENUS ...................................................................... 42
8.2 Test Sub-Menus............................................................................................43
8.2.1 Audit Trail Submenu Group ....................................................................... 43
8.2.2 Error History Submenu Group ................................................................... 43
8.2.3 Print System Setup Submenu Group.........................................................43
8.2.4 Keypad test Submenu Group.....................................................................44
8.2.5 Display test Submenu Group ..................................................................... 44
8.2.6 - 8.2.16 Calibration Submenu Group ......................................................... 45
8.2.17 Analog In Test Submenu Group .............................................................. 49
8.2.18 Analog out test Submenu Group..............................................................50
8.2.19 Pulse out test Submenu Group................................................................ 50
8.2.20 Relay test Submenu Group.....................................................................50
8.2.21 Control input test Submenu Group .......................................................... 50
8.2.22 Battery Voltage test Submenu Group ...................................................... 51
8.2.23 Data logger utility Submenu Group.......................................................... 51
8.3 Internal Fuse Replacement...........................................................................52
8.4 Installing New Software ................................................................................ 52
9. RS-232 Serial Port..................................................................................................... 53
9.1 RS-232 Port Description: .............................................................................. 53
9.2 Instrument Setup by PC’s over Serial Port ................................................... 53
9.3 Operation of Serial Communication Port with Printers..................................53
9.4 LEVELtrol-II RS-232 Port Pinout...................................................................53
iii
CONTENTS
10. RS-485 Serial Port (optional) ................................................................................... 54
10.1 RS-485 Port Description:............................................................................. 54
10.2 General........................................................................................................ 54
10.3 Operation of Serial Communication Port with PC ....................................... 54
10.4 LEVELtrol-II RS-485 Port Pinout ................................................................. 54
11. Instrument Setup Software (optional) ....................................................................... 55
11.1 System Requirements: ................................................................................ 55
11.2 Cable and Wiring Requirements: ................................................................. 55
11.3 Installation for Windows™ 3.1 or 3.11 ......................................................... 55
11.4 Using the Setup Software ............................................................................ 56
11.5 File Tab ........................................................................................................ 56
11.6 Setup Tab .................................................................................................... 56
11.7 View Tab ...................................................................................................... 57
11.8 Misc. Tab ..................................................................................................... 57
12. Glossary Of Terms ................................................................................................... 58
13. Diagnosis and Troubleshooting ................................................................................ 62
13.1 Response of LEVELtrol-II on Error or Alarm: .............................................. 62
13.2 Diagnosis Flow Chart and Troubleshooting................................................. 63
13.3 Error & Warning Messages: ........................................................................ 64
13.3.1 Sensor/Process Alarms ............................................................................ 64
13.3 Error & Warning Messages: (Continued) .................................................... 65
13.3.2 Self Test Alarms ........................................................................................ 65
Appendix A ..................................................................................................................... 66
Common Fluid Properties Table .......................................................................... 66
Appendix B
Setup Menus ....................................................................................................... 67
..................................................................................................................... 67
iv
LEVELtrol-II Installation & Operating Instructions
Unit Description
1. Description
1.1 Unit Description:
The LEVELtrol-II satisfies the requirements for a variety of level instrument needs. Multiple equations and instrument functions for a variety of tank shapes are available in a single unit with many advanced features.
The alphanumeric display shows measured and calculated parameters in easy to understand format. Single key direct access to measurements and display scrolling is supported.
The versatility of the LEVELtrol-II permits a wide measure of versatility within the instrument package. The various hardware inputs and outputs can be “soft” assigned to meet a variety of common application needs. The user “soft selects” the usage of each input/output while configuring the instrument. Consider the following illustrative examples.
The isolated analog output can be chosen to follow tank levels, volume , corrected volume, mass, temperature, or density by means of a menu selection. Most hardware features are assignable by this method.
Unit Features
The user can assign the standard RS-232 Serial Port for data logging, transaction printing, or for connection to a modem for remote reading.
An RS-485 Modbus RTU communication card provides multidrop capabilities.

1.2 Unit Features:

The LEVELtrol-II offers the following features:
Multiple Tank Shapes
Level and Tank Volume Indicator
Batching by Level
Level Control, Tank Volume, Corrected Volume and Mass Calculations
Multiple Instrument Functions
Menu Selectable Hardware & Software Features
Two Line LCD or VFD Display
Isolated Outputs Standard
RS-232 Port Standard
DIN Enclosure with Two Piece Connectors
Windows™ Setup Software (Future)
Foreign Language Options (Future)
RS-485 Modbus RTU Option (Future)
1
LEVELtrol-II Installation & Operating Instructions

1.3 Specifications:

Specifications: Environmental
Indoor Use Altitude up to 2000m Operating Temperature: 0°C to +50°C
(-20°C to 55°C optional) Storage Temperature: -40°C to +85 C Maximum Relative Humidity : 80% for temperatures
up to 31°C decreasing linearly to 50% RH at
40°C Mains supply voltage fluctuations not to exceed ±10%
of the nominal voltage Transient overvoltage according to INSTALLATION
CATEGORY II (see UL 3101-1 Annex J) POLLUTION DEGREE 2 in accordance with
IEC 664 (see 3.7.3) Materials: UL, CSA, VDE approved
Approvals: CE Approved Light Industrial,
UL File #: E192404 CSA Pending
Display
Type: 2 lines of 20 characters Types: Backlit LCD or VFD ordering options Character Size: 0.3" nominal User selectable label descriptors and units of measure
Keypad
Keypad Type: Membrane Keypad Keypad Rating: Sealed to Nema 4 Number of keys: 16
Enclosure
Size: See Dimensions Depth behind panel: 6.5" including mating connector Type: DIN Materials: Plastic, UL94V-0, Flame retardant Bezel: Textured per matt finish Equipment Labels: Model, safety, and user wiring
Power Input
The factory equipped power option is internally fused. An internal line to line filter capacitor and MOV's are provided for added transient suppression.
Order Option 1: 110VAC: 85 to 127 Vrms, 50/60 Hz Order Option 2: 220VAC: 170 to 276 Vrms, 50/60 Hz Order Option 3: 12VDC: 10.5 to 16 VDC Order Option 4: 24VDC: 16 to 24 VDC
Level Input:
Analog Input:
Ranges
Voltage: 0-10 VDC, 0-5 VDC, 1-5 VDC
Current: 4-20 mA, 0-20 mA
Basic Measurement Resolution: 16 bit Update Level: 5 updates/sec minimum Automatic Fault detection: Signal over/under-range,
Current Loop Broken
Calibration: Self Calibration and Auto-zero
Continuously
Extended calibration: Learns Zero and Full Scale
of each range using special test mode.
Fault Protection:
Fast Transient: 500 V Protection
(Capacitive Clamp) Reverse Polarity: No ill effects Over-Voltage Limit: 50 VDC Over voltage
protection
Over-Current Protection: Internally current
limited Protected to 24 VDC.
Compensation Input
The compensation input is menu selectable for temperature, density or not used.
Operation: Ratiometric Accuracy: 0.01% FS Thermal Drift: Less than 100 ppm/C Basic Measurement Resolution: 16 bit Update Level: 1 update/sec minimum Automatic Fault detection:
Signal Over-range/under-range Current Loop Broken RTD short RTD open Fault mode to user defined default settings
Transient Protection: 500 V (Capacitive Clamp) Reverse Polarity: No ill effects Over-Voltage Limit (Voltage Input): 50 VDC
Available Input Ranges
Voltage: 0-10 VDC, 0-5 VDC, 1-5 VDC Current: 4-20 mA, 0-20 mA Resistance: 100 Ohms DIN RTD
100 Ohm DIN RTD (DIN 42-760, BS 1904):
Three Wire Lead Compensation Internal RTD linearization learns ice point
resistance
1 mA Excitation current with reverse polarity
protection
Temperature Resolution: 0.01 C
Control Inputs
Switch Inputs are menu selectable for Start, Stop, Reset, Lock, Alarm Acknowledge, Print or Not Used. Control Input Specifications
Input Scan Rate: 10 scans per second Logic 1: 4 - 30 VDC Logic 0: 0 - 0.8 VDC Transient Suppression: 500 V fast transient
(Capacitive Clamp) Input Impedance: 100 K Control Activation: Positive Edge or Pos. Level based on product definition
Excitation Voltage
24 VDC @ 100 mA (current limited) Note: Not available on DC powered units
Relay Outputs
The relay outputs are menu assignable to (Individually for each relay) Level, Total, Temperature, Density, Low Alarm, Hi Alarm, Prewarn Alarm, Preset Alarm or General purpose warning (security).
Number of relays: 4
Note: RS-232 Multidrop not available with
4 relay version. Contact Style: Form C contacts Contact Ratings: 250 VAC @ 5 amps
30 VDC @ 5 amps
Fast Transient Threshold: 1000 V
2
LEVELtrol-II Installation & Operating Instructions
Analog Output
The analog output is menu assignable to correspond to the Uncompensated Volume Level, Corrected Volume Level, Mass, Temperature, Density.
Type: Isolated Current Sourcing Isolated I/P/C: 500 V Available Ranges: 4-20 mA Resolution: 12 bit Accuracy: 0.05% FS at 20 Degrees C Update Level: 1 update/sec minimum Temperature Drift: Less than 200 ppm/C Maximum Load: 1000 ohms (at nominal line voltage) Compliance Effect: Less than .05% Span 60 Hz rejection: 40 dB minimum EMI: No effect at 3 V/M Calibration: Operator assisted Learn Mode Averaging:User entry of DSP Averaging constant to cause an smooth control action.
Isolated Pulse output
The isolated pulse output produces pulses based on the changing Uncompensated Volume Total, Compensated Volume Total or Mass Total.
Usage: Quantity entering or leaving tank Isolation I/O/P: 500 V Pulse Output Form: Open Collector Maximum On Current: 25 mA Maximum Off Voltage: 30 VDC Saturation Voltage: 1.0 VDC Maximum Off Current: 0.1 mA Pulse Duration: 18 msec or 100 msec Pulse output buffer: 8 bit
Fault Protection
Reverse polarity: Shunt Diode Transient Protection: 500 VDC
(Capacitive Clamp)
RS-232 Communication
Uses: Printing, Setup, Modem, Datalogging Baud Rates: 300, 600, 1200, 2400, 4800, 9600, 19200 Parity: None, Odd, Even Device ID: 0 to 99 Protocol: Proprietary, Contact factory for more information Chassis Connector Style: DB 9 Female connector
RS-485 Communication (optional)
Uses: Network Communications Baud Rates: 300, 600, 1200, 2400, 4800, 9600, 19200 Parity: None, Odd, Even Device ID: 0 to 255 Protocol: ModBus RTU Chassis Connector Style: DB 9 Female connector
Operating Mode
The LEVELtrol-II can be thought of as making a series of measurements of level, temperature/density sensors and then performing calculations to arrive at a result(s) which is then updated periodically on the display. The analog output, the pulse output, and the alarm relays are also updated. The cycle then repeats itself.
Step 1:Update the measurements of input signals
Raw Input Measurements are made at each input using equations based on input signal type selected. The system notes the “out of range” input signal as an alarm condition.
Step 2:Compute the Flowing Fluid Parameters
The temperature and density equations are computed as needed based on the instrument equations and input usage selected by the user.
Step 3 : Compute the Tank Level
The value is computed based on the level sensor input type selected and by installation details on the tank.
Step 4: Compute the Uncorrected Tank Volume
Compute the uncorrected tank volume from the tank level measurement and known geometry of the tank.
Step 5: Compute the Corrected Tank Volume at
Reference Conditions or Mass in tank.
Step 6: Check Alarms
The alarm functions have been assigned to one of the above during the setup of the instrument. A comparison is now made by comparing the current value against the specified hi and low limits.
Step 7: Compute the Analog Output
This designated process value is now used to compute the analog output.
Step 8: Total Preset Comparisons
The total associated with a preset function is then compared against the corresponding preset value and any required control actions taken.
Step 9: Pulse Output Service-
The pulse output is next updated by scaling the total increment which has just been determined by the pulse output scaler and summing it to any residual pulse output amount.
Step 10: Update Display and Printer Output-
The instrument finally runs a task to update the various table entries associated with the front panel display and serial outputs.
3
LEVELtrol-II Installation & Operating Instructions
Setup Mode
The setup mode is password protected by means of a numeric lock out code established by the user. In addition, a secret, manufacturers numeric unlock entry sequence is available.
The system also provides a minimum implementation of an “audit trail” which tracks significant setup changes to the unit. This feature is increasingly being found of benefit to users or simply required by Weights and Measurement Officials in systems used in commerce, trade, or “custody transfer” applications.
A Worksheet is provided to assist the user in setting up the instrument. In addition, a software program is available (optional) which runs on a PC using a RS­232 Serial for connection to the instrument. Illustrative examples may be down loaded in this manner.
The setup mode has numerous subgrouping of parameters needed for the instrument functions. There is a well conceived hierarchy to the setup parameter list. Selections made at the beginning of the setup hide unnecessary items further down in the lists.
In the setup mode, the instrument activates the correct setup variables based on the instrument configuration, the equations, and the hardware selections made for the compensation transmitter type, the level transmitter type, and any enhancement options selected. All required setup parameters are enabled. All setup parameters not required are suppressed.
A help line prompt is provided for each entry. In addition a help message is available which may be accessed by depressing the “HELP” key.
Also note that in the setup mode are parameter selections which have preassigned industry standard values. The unit will assume these values unless they are modified by the user.
Maintenance Mode:
The Maintenance Mode of the LEVELtrol-II is the Test and Calibration Mode for the device. This mode provides a number of specialized utilities required for factory calibration, instrument checkout on start-up, and periodic calibration documentation.
A Supervisor or Manufacturers password is required to gain access to this specialized mode of operation. Start-up, quality, calibration, and maintenance personnel will find this mode of operation very useful. It is also useful for factory testing.
Many of these tests may be used during start-up of a new system. Inputs signals may be read, and output signals may be exercised to verify the electrical interconnects before the entire system is put on line.
The following action items may be performed in the Maintenance Mode:
Print Calibration/Maintenance Report Examine Audit Trail Examine Error History Perform Keypad Checkout Perform Display Checkout Perform Pulse Output Checkout Perform Control Input Checkout Perform Relay Output Checkout Perform Analog Input Checkout Perform Analog Output Checkout Calibrate Analog Inputs using the Learn Feature Calibrate Analog Output using the Learn Feature Battery Voltage Test Print Datalogger Contents
Note that a calibration of the analog input/output will advance the audit trail counters since it effects the accuracy of the system.
Most of the process input variables have available a “default” or emergency value which must be entered. These are the values that the unit assumes when a malfunction is determined to have occurred on the corresponding input.
It is possible to enter in a nominal constant value for temperature or density, or analog level inputs by placing the desired nominal value into both the lo and hi values. This is also a convenience when performing bench top tests without simulators.
4
LEVELtrol-II Installation & Operating Instructions
RS-232 Serial Port
The LEVELtrol-II has a general purpose RS-232 Port which may be used for any one of the following purposes:
Transaction Printing Data Logging Remote Metering by Modem (optional) Computer Communication Link Configuration by Computer Print System Setup Print Calibration/Malfunction History
Instrument Setup by PC’s over Serial Port
A Diskette program is optionally available with the instrument that enables the user to rapidly configure the LEVELtrol-II using an Personnel Computer. Included on the diskette are common instrument applications which may be used as a starting point for your application. This permits the user to have an excellent starting point and helps speed the user through the instrument setup.
Operation of Serial Communication Port with Printers
LEVELtrol-II’s RS-232 channel supports a number of operating modes. One of these modes is intended to support operation with a printer in applications requiring transaction printing, data logging and/or printing of calibration and maintenance reports.
In data logging, the user defines the items to be included in each data log as a print list. The user can also select when or how often he wishes a data log to be made. This is done during the setup of the instrument as either a time of day or as a time interval between logging.
The system setup and maintenance report lists all the instrument setup parameters and usage for the current instrument configuration. In addition, the Audit trail information is presented along with a status report listing any observed malfunctions which have not been corrected.
The user initiates the printing of this report at a designated point in the menu by pressing the print key on the front panel.
Operation of Serial Port with Modems (optional)
The LEVELtrol-II RS-232 channel supports a number of operating modes. One of these modes is intended to support operation with a modem in remote metering applications.
For transaction printing, the user defines the items to be included in the printed document. The user can also select what initiates the transaction print generated as part of the setup of the instrument. The transaction document may be initiated via a front panel key depression, a remote contact closure, or upon completion of a batch.
5

2. Installation

LEVELtrol-II Installation & Operating Instructions
2. Installation
WARNING: In control applications, independent safety inter-
locks (liquid level switches) should be used to
!
prevent hazards which could result from a mal­functioning LEVELtrol II.
General Mounting Hints
Mounting Procedure

2.1 General Mounting Hints:

The LEVELtrol-II Flow Computer should be located in an area with a clean, dry atmosphere which is relatively free of shock and vibration. The unit is installed in a 5.43" (138mm) wide by 2.68" (68mm) high panel cutout. (see Mounting Dimensions) To mount the instrument, proceed as follows:
a. Prepare the panel opening. b. Slide the unit through the panel cutout until the it touches the panel. c. Install the screws (provided) in the mounting bracket and slip the bracket over
the rear of the case until it snaps in place.
d. Tighten the screws firmly to attach the bezel to the panel. 3 in. lb. of torque
must be applied and the bezel must be parallel to the panel.
Termination Connectors:
Minimum Wire Gauge: 22 AWG Maximum Wire Gauge: 14 AWG Voltage/current limits are limited by unit specifications.
Permanently Connected Equipment: UL 3101-1, Section 6.12.2.1 specifies that:
A switch or circuit breaker shall be included in the building installation;
It shall be in close proximity to the equipment and within easy reach of the OPERATOR;
It shall be marked as the disconnecting device for the equipment.
Ensure that the switch or circuit breaker chosen is suitable for the power requirements of the unit.

2.2 Mounting Diagrams: Standard Mounting Bezel Kit Mounting

LEVELtrol-II
Mounting Bracket
0.5
Dimensions
3.43 (87)
RATE TOTAL
START
1
GRAND6SCROLL7PRE 28DENS
STOP
Mounting Bracket
5.67 (144)
GPM
147.43 GAL
267395.749
PRINT
TEMP4PRE 13RATE2TOTAL
5
TIME
0
9
6.18 Dotted Line Shows Optional Bezel Kit
CLEAR•MENU
HELP
2.83 (72)
ENTER
0.28 (7.2)
0.4 (10)
6.15
(156)
(13)
LEVELtrol-II
Bezel Adaptor
Gasket
5.43
(138)
Panel
Cutout
2.68 (68)
Dimensions are in inches (mm)
6

3. Applications

LEVELtrol-II Installation & Operating Instructions
Tank Level/Volume
3.1 Tank Level/Volume
Measurements:
A level or hydrostatic pressure transmitter measures the liquid level in a tank. A temperature sensor can also be installed to correct for liquid thermal expansion or density effects.
Output Results:
• Display Results Level, Available Tank Volume, Gross Tank Volume
• Analog Output Level or Tank Volume
• Pulse Output Changes in Tank Volume
• Relay Outputs Level or Tank Volume Alarms
Applications:
The LEVELtrol-II can monitor actual liquid level and tank volume of a liquid. Alarms are provided via relays and datalogging is available via analog (4-20mA) and serial outputs.
Tank Level/ Volume Illustration
TOTAL
START
1
GRAND6SCROLL7PRE 28DENS
STOP
LEVEL
TEMP
PRE 1
3
2
PRINT
0
5
TIME
CLEAR•MENU
HELP
ENTER
4
9
Tank Discharge
P
DP Transmitter
7
LEVELtrol-II Installation & Operating Instructions
Corrected Tank Volume
3.2 Corrected Tank Volume
Measurements:
An ultrasonic level sensor measures the liquid level in a horizontal tank. A temperature sensor is installed to correct for liquid thermal expansion.
Calculations:
• Corrected Tank Volume is calculated using the level and temperature inputs as well as the liquid's thermal expansion coefficient stored in the LEVELtrol-II. Use the "SET FLUID PROPERTIES" submenu to define reference temperature and density values for standard conditions.
Output Results:
• Display Results
Level, Available Corrected Volume, Gross Corrected Volume, Temperature
• Analog Output
Tank Volume or Temperature or Density
• Pulse Output
Change in Tank Volume
• Relay Outputs
Level or Tank Volume Alarms
Corrected Liquid Volume Illustration
Applications:
Monitoring corrected volume of a liquid stored in a horizontal tank. Alarms are provided via relays and datalogging is available via analog (4-20mA) and serial outputs.
TEMP
PRE 1
LEVEL
TOTAL
START
STOP
2
1
GRAND6SCROLL7PRE 28DENS
3
PRINT
0
5
TIME
CLEAR•MENU
HELP
ENTER
4
9
Ultrasonic
Level Sensor
T
Temperature Transmitter
8
LEVELtrol-II Installation & Operating Instructions
Total Mass in Tank

3.3 Total Mass in Tank

Measurements:
Actual level is measured by the level sensor (ultrasonic sensor or DP transmitter). Temperature is measured by the temperature transmitter. A density transmitter can alternately be used for direct density measurements.
Calculations:
• The density is calculated using the reference density and the thermal expansion coefficient of the liquid (see "SET FLUID PROPERTIES" submenu).
• Total Mass in tank is computed for tank geometry.
Output Results:
• Display Results
Level, Total Available Mass in Tank, Total Gross Mass in Tank, Temperature, Density
• Analog Output
Level, Total, Temperature or Density
• Pulse Output
Change in Tank Mass
• Relay Outputs
Level, Total or Temperature Alarms
Liquid Mass Illustration
Applications:
Monitoring level and mass total of any liquid in a tank. Alarms are provided via relays and datalogging is available via analog (4-20mA) and serial outputs.
TEMP
PRE 1
LEVEL
TOTAL
START
STOP
2
1
GRAND6SCROLL7PRE 28DENS
3
PRINT
0
5
TIME
CLEAR•MENU
HELP
ENTER
4
9
Ultrasonic
Level Sensor
T
Temperature Transmitter
9
LEVELtrol-II Installation & Operating Instructions
Batching Volume, Corrected Volume or Mass from Tank Level

3.4 Batching Volume, Corrected Volume or Mass from Tank Level

Measurements:
A Level transmitter measures the liquid level in a tank. A temperature sensor can also be installed to correct for liquid thermal expansion (see
3.2 Corrected Volume).
Calculations:
• Fluid Density (if required)
• Actual Level in tank is computed from level signal, installation parameters and fluid properties.
• Tank Volume, Corrected Volume, Mass
• Compare quantity delivered to quantity requested.
Output Results:
Display Results
Level, Batch Total, Tank Total, Temperature, Density
Analog Output
Level, Total, Temperature or Density
Pulse Output
Amount delivered since start of batch (other uses available)
Relay Outputs
Batch Total, Level, or Temperature Alarms
Batching Illustration
Applications:
Batching and monitoring level and total quantity in tank of any liquid. Batching is accomplished via relays and datalogging is available via analog (4-20mA) and serial outputs.
PRINT
TEMP
PRE 1
LEVEL
TOTAL
START
STOP
2
1
GRAND6SCROLL7PRE 28DENS
4
3
9
0
5
TIME
CLEAR•MENU
HELP
ENTER
10
Temperature Transmitter
T
P
DP Transmitter
Solenoid Valve

4 WIRING

LEVELtrol-II Installation & Operating Instructions
Batcher Wiring

4.1 Typical Batcher Wiring:

(+) V
Signal
123456
MOV recommended
Level Sensor
Remote Counter
115 VAC
115 VAC SOLENOID VAL VE
1
DC OUTPUT
2
Iin +
3 4
COMMON
5
---------
6
RTD EXCIT +
7
RTD SENS RTD SENS -
StartStop
8 9
CNTR IN 1
10
CNTR IN 2
11
CNTR IN 3
12
COMMON 13 PULSE OUTPUT + 14
PULSE OUTPUT ­15
ANALOG OUTPUT + 16
ANALOG OUTPUT ­17 NC
18 COM 19
20 21 22
NO
NC
COM
NO
RLY1
RLY2
Vin +
+
Iin +
25 NC 26 27
28 29 30
LEVEL
IN
COMP
IN
SEE USER MANUAL
4-20 mA
COM RLY3 NO
NC COM RLY4 NO
Level / Total Wiring
115 VAC

4.2 Typical Level/Total Wiring:

(+) V
Level Sensor
100 Ohm DIN RTD
STRIP CHART
RECORDER
+
-
Signal
123456
Remote Counter
Alarm Relay 1
Alarm Relay 2
23
AC LINE
AC LINE24
1
DC OUTPUT 2
Iin +
3 4
COMMON 5
---------
6
RTD EXCIT + 7
RTD SENS
RTD SENS -
8 9
CNTR IN 1 10
CNTR IN 2 11
CNTR IN 3 12
COMMON 13 PULSE OUTPUT +
14
PULSE OUTPUT ­15
ANALOG OUTPUT + 16
ANALOG OUTPUT ­17 NC
{ {
18 COM 19
20 21 22
NO
NC
COM
NO
RLY1
RLY2
DC + DC -
+
25 NC 26 27
28 29 30
POWER IN
LEVEL
IN
Vin +
COMP
IN
Iin +
SEE USER MANUAL
4-20 mA
COM RLY3 NO
NC COM RLY4 NO
115 VAC
11
23
AC LINE
AC LINE24
DC + DC -
POWER IN
LEVELtrol-II Installation & Operating Instructions

4.3 Wiring In Hazardous Areas:

Examples using MLT787S+ Barrier (MTL4755ac for RTD)
Level Input
Temperature or Density Input (4-20mA Transmitter)
Flow Input
Hazardous Area Safe Area
4-20mA
Transmitter
Q/P
4-20
+ –
3 4
28V
Diode
2 1
Temperature/Density Input (4-20mA Transmitter)
Hazardous Area Safe Area
1
24V Out
2 3
4-20mA In
4
Common
24V Out
1
Temperature Input (RTD)
4-20mA
Temp. or Dens.
Transmitter
T/D
4-20
– +
4 3
Temperature Input (RTD)
Hazardous Area Safe Area
3-Wire RTD
1 2 3 4 5 6
28V
Diode
1 2
7 8 9 10 11 12 13 14 15 16 17
4
Common
8
4-20mA In
Common
4 5
RTD Excite (+)
6
RTD Sense (+)
7
RTD Sense (–)
8
12
LEVELtrol-II Installation & Operating Instructions

5. UNIT OPERATION

5.1 Front Panel Operation Concept for Run Mode

The LEVELtrol-II is fully programmable through the front panel. Please review the following usage summary before attempting to use the instru­ment.
TEMP
PRE 1
LEVEL
TOTAL
START
1
GRAND6SCROLL7PRE 28DENS
STOP
3
2
PRINT
0
5
TIME
CLEAR•MENU
HELP
ENTER
4
9
How To Use On-Line Help
How To Use Function Keys
How To Enter Presets
How To Create a Scroll List
How To Use The Print Key
How To Use Special Batching Keys
HELP
On-line help is provided to assist the operator in using this product. The help is available during RUN and SETUP modes simply by pressing the HELP key. The HELP key is used to enter decimals when entering numeric values.
FUNCTION KEYS
In the RUN mode, several keys have a special, direct access feature, to display an item of interest (i.e. LEVEL, TOTAL, PRE 1, etc.). Press the key to view your choice. Press the SCROLL key to return to scrolling display.
PRESET KEYS
In the RUN mode, PRE 1 & PRE 2 keys are used to view and/or change the preset setpoints. To view the Presets, simply press the desired Preset key once. Rapidly press the Preset keys three times, then press the Clear key for direct editing of the preset setpoints. The access for changing the presets can be locked.
SCROLL
Rapidly press the Scroll key twice to setup a display list. Press the CLEAR key to remove old scroll list. Press the function key for the item you wish to add Use the ∆ ∇ keys to assign the line.
PRINT
The PRINT key is used to print on demand. When the PRINT key is pressed, a user defined list of data (TOTAL, LEVEL, PRE 1, etc.) is sent to the RS-232 port. A timed message of "PRINTING" will be displayed to acknowledge the print request.
SPECIAL BATCHING KEYS
The START and STOP keys are used only when batching to start and stop batches. The CLEAR key will clear the batch total. All other keys work the same in both Level/Total mode and Batch mode. The Start and Stop keys operation are set by the control input settings. The Start options are: START or RESET/START. The Stop options are: STOP or STOP/RESET.
How To Use The Menu Key
How To Acknowledge Alarms
MENU KEY
The MENU key is used to enter the Setup and Test modes. Press the MENU key to enter the Setup and Test modes. (See section 6 for Setup mode, section 8 for Test mode). The MENU key is used as "escape" in Setup and Test Programming. Pressing the MENU key wile programming in the Sub-Menu groups will backup the display to that Sub-Menu group heading. Pressing the MENU key while viewing the Sub-Menu groups will backup the display to the Top Level Menu.
ACKNOWLEDGING ALARMS
Most alarm messages are self-clearing. Press the ENTER key to acknowledge and clear alarms.
NOTE: Some keys and functions are password protected. Enter the password to
gain access. The passwords are factory set as follows:
Operator = 0 Supervisor = 2000
13
LEVELtrol-II Installation & Operating Instructions
General Operation
Level/Total Operation
Password Protection
(Level/Total mode)

5.2 General Operation

The unit can display: Level, Available Total, Gross Total, Temperature, Density, Presets and Time of Day. The Temperature and/or Density can be displayed even if you are using the Volumetric Flow Equation (a Temperature or Density sensor must be installed). The unit can perform Volume, Mass or Corrected Volume equations using a temperature or density sensor (these equations can be computed without Temp/Dens sensors by using user defined default values). The unit can be programmed to perform Level or Batching functions (see section 6.3, SELECT INSTRUMENT Submenu).

5.3 Level/Total Operation

The Level/Total mode is used primarily to monitor and control level and tank volume. The relays can be used to trigger level, tank volume, temperature or density alarms. Analog, pulse and communication outputs are also provided.

5.3.1 Password Protection for Level/Total mode

After an Operator and/or Supervisor Password is entered in the setup mode (see section 6.3, SETUP PASSWORD submenu), the unit will be locked. The unit will prompt the user for the password when trying to perform the following functions:
Enter Menu Edit Preset 1 (PRE 1 Key) (if operator access is set to "none") Edit Preset 2 (PRE 2 Key) (if operator access is set to "none")
Relay Operation
(Level/Total mode)
The Supervisor password should be reserved for supervisors. The Supervisor password will allow access to restricted areas of the Setup and Test menus.
A control input can also be configured as a jumper hardware lockout.

5.3.2 Relay Operation in Level/Total mode

Four relays are available for control and/or alarm output functions. The relays can be assigned to trip according to level, total, temperature or density readings. The relays can be programmed for low or high alarms. Preset 1 (RLY1) and Preset 2 (RLY2) are easily accessible by pressing the PRE 1 or PRE 2 key on the front panel. Preset 3 and Preset 4 are accessible only through the setup menu.
NOTE: Choose relay operations that will fail safe for your process. Also
use suitable safety interlocks (level switches) to prevent overfilling containers.
Pulse Output
(Level/Total mode)

5.3.3 Pulse Output in Level/Total mode

The isolated pulse output (open collector) is menu is assigned to follow changes in the Volume Total, Corrected Volume Total or Mass Total. The pulse output duration can be set for 10mS (100Hz max) or 100mS (10Hz max). A pulse output scale factor (pulse value) can be set to scale the pulse output. The pulse output is ideal for connecting to remote totalizers or other devices such as a PLC. See section 1.3 for electrical specifications. Pulse outputs can be used to indicate approximate delivery totals received or delivered.
14
LEVELtrol-II Installation & Operating Instructions
Analog Output
(Level/Total mode)
RS-232 Serial Port
(Level/Total mode)

5.3.4 Analog Output in Level/Total mode

The analog output is menu assignable to correspond to the Level, Volume, Corrected Volume, Mass, Temperature, Density. The analog output is ideal for "trend" tracking using strip chart recorders or other devices.

5.3.5 RS-232 Serial Port Operation in Level/Total mode

The RS-232 serial port can be used for programming (using the optional Setup Disk) or for communicating to printers and computers in the Operating Mode (Run Mode).
PC Communications:
The Setup Disk also allows the user to query the unit for operating status such as Level, Tank Total, Temperature, Density, Presets, etc.
Operation of RS-232 Serial Port with Printers:
Transaction Printing For transaction printing, the user defines the items to be included in the printed document (see SET PRINT OUTPUT, Select_list). The transaction document can be initiated by pressing the PRINT key or by a remote contact closure.
Data Logging to Printer In data logging, the user defines the items to be included in each data log (see SET PRINTER OUTPUT, Select_list). The user can also select when (time of day) or how often (print interval) the data log is to be made (see section 6.3.19 SET PRINT OUTPUT, Configure).
System Setup and Maintenance Report The system setup and maintenance report lists all of the instrument setup parameters and usages for the current instrument configuration. The audit trail information and a status report is also printed. This report is initiated in the Test menu (see PRINT SYSTEM SETUP).

5.3.6 RS-485 Serial Port Operation in Level/Total mode

The RS-485 serial port can be used for accessing level, total quantity, temperature, density and alarm status information. The port can also be used for changing presets and acknowledging alarms.
15
LEVELtrol-II Installation & Operating Instructions
Batcher Operation
Batcher Configuration

5.4 Batcher Operation

The Batcher mode is used primarily to dispense batches of fluid based on changes in tank volume as indicated by tank level. The main difference between the Batch mode and Level/Total mode is the relay operation. The Batch mode allows the operator to "START" the batch transfer via the front panel or remote input. Once started, the relays (RLY1 & RLY2) will energize and send power to a flow control device (i.e. solenoid valve or pump). The level sensor will send a signal to the unit and total comparisons will begin. When the Prewarn value (PRE 2) is reached, Relay 2 will drop out (this is ideal for flow slow down). When the Batch amount (PRE 1) is reached, Relay 1 will drop out and the Batch is complete.
Several messages will be displayed during normal batch operation (i.e. Batch Fill, Batch Stopped).

5.4.1 Batcher Configuration.

When the unit is programmed for the batch mode, several batch operation choices are available. These choices include: Up or Down Counting, Batch Into or Out of the Tank, Batch Overrun Correction feature, Start or Reset/Start, and Stop or Stop/Reset.
BATCH OVERRUN
The batch overrun is used for batch applications that have slow responding valves and a consistent batching flowrate. When the Batch Overrun is set, the unit will compensate for batch overruns by computing an averaged overrun value from the last four batches. This average is used to internally adjust the batch setpoint to minimize overrun.
START, RESET/START and STOP, STOP/RESET
When configuring the control inputs, Control Input1 can be set for START or RESET/START. When set for START, the unit will start batching when a signal is applied to Control Input1 or the front panel Start key is pressed. A separate Reset signal must be used to clear the previous batch total. When set for RESET/START, the unit will automatically reset then start when a signal is applied to Control Input1 or the front panel Start key is pressed (provided that the previous batch was completed). If a previous batch was stopped during a batch cycle, the unit will Restart from where it was stopped. Control Input 2 can be set for STOP or STOP/RESET. When set for STOP, the unit will stop batching when a signal is applied to Control Input 2 or the front panel Stop key is pressed. A separate Reset signal must be used to clear the batch total. When set for STOP/RESET, a running batch will stop when a signal is applied to Control Input 2 or the front panel Stop key is pressed. If the unit is Stopped or after a completed batch, the unit will reset when a signal is applied to Control Input 2 or the front panel Stop key is pressed. NOTE: Applying a voltage level to Control Input 2 will inhibit or override
all Start inputs in either mode.
16
LEVELtrol-II Installation & Operating Instructions
Password Protection
(Batch mode)
Relay Operation
(Batch mode)

5.4.2 Password Protection for Batcher Mode

After an Operator and/or Supervisor Password is entered in the setup mode (see section 6.3, SETUP PASSWORD submenu), the unit will be locked. The unit will prompt the user for the password when trying to enter the menu. The unit will also prompt the user to enter the password if this access has been limited.
The Supervisor password should be reserved for supervisors. The Supervisor password will allow access to restricted areas of the Setup and Test menus.
The passwords are factory set as follows:
Operator = 0 Supervisor = 2000
A control input can also be configured as a jumper hardware lockout.

5.4.3 Relay Operation in Batcher mode

Four relays are available for batch control and/or alarm outputs. Preset 1 (RLY1) is reserved for batch amount, Preset 2 (RLY2) is usually reserved for prewarn. (see section 5.4 Batcher Operation for Relay 1 & Relay 2 functions) Preset 1 (RLY1) and Preset 2 (RLY2) are easily accessible by pressing the PRE 1 or PRE 2 key on the front panel. Preset 3 and Preset 4 are accessible only through the setup menu. Relays 3 and 4 can be assigned to trip according to level, temperature, density, overrun or alarm. When level, temperature or density is selected the relays can be programmed as low or high alarms. Overrun can be used to detect minor leakage around valves in some applications.
Pulse Output
(Batch mode)
NOTE: Choose relay operations that will fail safe for your process. Also
use suitable safety interlocks (level switches) to prevent overfilling containers.

5.4.4 Pulse Output in Batcher mode

The isolated pulse output (open collector) is assigned to produce pulses on changing Volume, Corrected Volume or Mass as indicated by the pulse output usage and the compensation equation selected. The pulse output duration can be set for 10mS (100Hz max) or 100mS (10Hz max). A pulse output scale factor (pulse value) can be set to scale the pulse output. The pulse output is ideal for connecting to remote totalizers or other devices such as a PLC. It may be used to keep track of deliveries, the amount sent to/from a tank or for a combination of these. See section
1.3 for electrical specifications.
17
Loading...
+ 51 hidden pages