KEP INTELLECT-69 Series, INT-69RT, INT-69T, INT-69R Installation & Operating Instructions Manual

Page 1
INTELLECT-69
INSTALLATION & OPERATING INSTRUCTIONS
MODELS
INT-69RT INT-69R INT-69T (with RS232 & RS422 Option)
V ersion V_41
KESSLER-ELLIS PRODUCTS CO.
10 Industrial Way East Eatontown, NJ 07724
http://www.kep.com
99318 10/2/98
Telephone: (732) 935-1320 T oll Free: (800) 631-2165 Fax: (732) 935-9344
Page 2
Proprietary Notice
The information contained in this publication is derived in part from proprietary and patent data. This information has been prepared for the expressed purpose of assisting operating and maintenance personnel in the efficient use of the instrument described herein. Publication of this information does not convey any rights to use or reproduce it or to use for any purpose other than in connection with the installation, operation and maintenance of the equipment described herein.
Copyright 1990
Printed in USA. All Rights Reserved.
!
WARNING!
This instrument contains electronic components that are susceptible to damage by static electricity. Proper handling* procedures must be observed during the removal, installation, or handling of internal circuit boards or devices.
*Handling Procedure
1. Power to unit must be removed.
2. Personnel must be grounded, via wrist strap or other safe, suitable means, before any printed circuit board or other internal device is installed, removed or adjusted.
3. Printed circuit boards must be transported in a conductive bag or other conductive container. Boards must not be removed from protective enclosure until the immediate time of installation. Removed boards must be placed immediately in protective container for transport, storage, or return to factory.
Comments This instrument is not unique in its content of ESD (electrostatic discharge) sensitive
components. Most modern electronic designs contain components that utilize metal oxide technology (NMOS, CMOS, etc.). Experience has proven that even small amounts of static electricity can damage or destroy these devices. Damaged components, even though they appear to function properly, may exhibit early failure.
Page 3
TABLE OF CONTENTS
SAFETY INSTRUCTIONS ...........................................................1
DESCRIPTION & SPECIFICATIONS ..........................................2
MOUNTING .................................................................................3
WIRING........................................................................................4
TYPICAL WIRING HOOKUPS.....................................................5
OPEN COLLECTOR & RELAY OPERATION .............................5
PROGRAMMING FLOWCHART .................................................6
DEFINITIONS .............................................................................. 7
FRONT PANEL OPERATIONS ...................................................10
PROGRAMMING .........................................................................10
SETTING PRESETS & PANEL LOCK.........................................15
RS 232/422 OPERATIONS .........................................................16
RS 232/422 WIRING....................................................................20
TROUBLESHOOTING GUIDE ....................................................21
WARRANTY ................................................................................22
DECODING PART NUMBER ......................................................22
Page 4
THIS PAGE IS BLANK
Page 5
SAFETY INSTRUCTIONS
!
The following instructions must be observed.
This instrument was designed and is checked in accordance with regulations in force EN 60950 (“Safety of information technology equipment, including electrical business equipment”). A hazardous situation may occur if this instrument is not used for its intended purpose or is used incorrectly. Please note operating instructions provided in this manual.
The instrument must be installed, operated and maintained by personnel who have been properly trained. Personnel must read and understand this manual prior to installation and operation of the instrument.
The us of an external line fuse is recommended. Add or replace the external fuse with the following specified type and rating only:
Input Power Recommended Fuse
115 VAC 100 mA slow blow fuse 230 V AC 50 mA slow blow fuse
12-24 VDC 250 mA slow blow fuse
Disconnect power supply before adding or replacing fuse!
The manufacturer assumes no liability for damage caused by incorrect use of the instrument or for modifications or changes made to the instrument.
Symbols Used On Unit
Number Symbol Publication Description
1 IEC 417, No. 5031 Direct current
2 IEC 417, No. 5172 Equipment protected throughout by
DOUBLE INSULATION or REINFORCED INSULATION (equivalent to Class II of IEC 536–see annex H)
3
!
ISO 3864, No. B.3.1 Caution (refer to accompanying documents)
Technical Improvements
• The manufacturer reserves the right to modify technical data without prior notice.
1
Page 6
DESCRIPTION & SPECIFICATIONS
Description:
Featuring 6 digits of bright, 7-segment LED displays, this unit is an integrating totalizer/ratemeter which ac­cepts analog signal inputs. The unit can be field programmed to accept 0-20mA, 4-20mA, 0-5V, 0­10V or 1-5V signals. An optional Square Law input is available for inputs that require square root extrac­tion. A 4-20mA output option is available to control strip recorders or other peripherals. Two assignable set points are standard for two stage shut off. The high and low scaling settings are programmable from the front panel. By pressing the "view" button, the unit will display: integrated total, rate, peak or valley. RS-422 or RS-232 serial communications are avail­able options for data communication with a host com­puter.
Specifications: Display: 6 digit, .55" high, LED. Input Power: 110, 220 VAC ± 15% or 12 to 24VDC.
Current: maximum 300 mA DC or 10.0 VA at rated AC voltage. Output Power: (AC powered units only) + 24VDC. @ 50 mA regulated ±5%
Temperature:
Operating: +41°F (5°C) to +130°F (+54°C). Storage: -40°F (-40°C) to +200°F (93°C). Memory: EEPROM stores data for ten years if power is lost. Reset: Front Panel: resets displayed values and control out­puts. Remote: 4-30 VDC positive edge, resets totalizer and control outputs. Control Outputs: Standard: Open collector sinks 250 mA from 30VDC when active. Optional: 2 each Form C SPDT 10Amp @ 120/240 VAC or 28 VDC. (Open collector outputs are also supplied with 10VDC provided at transistor outputs through relay coil. If greater than 2mA is used, relay will remain energized. Applying greater than 10 VDC may destroy unit. Transistor will sink 100mA in "ON" state.)
Input:
Standard: Linear 0-20mA, 4-20mA, 0-5V, 0-10V or 1­5V selectable from the front panel. Optional: Square Law 0-20mA, 4-20mA, 0-5V, 0-10V, or 1-5V, is available for inputs that require square root extraction.
Input Impedance: Current: 100; Voltage: 115K Calibration: The unit does all of the calibrations inter-
nally. There are no potentiometers to adjust and the unit never needs to be removed from the case.
Set Points: The two control set points can be set at any number from 0 to 59999. The set point outputs can be assigned to rate or total. The unit comes standard with two open collector control outputs. Two 5 Amp, Form C relays are optional. The outputs are programmable from .01 to 599.99 sec or latched until reset when assigned to the total and a hysteresis (alarm range) when assigned to the rate. Rate Display: Updates 5 times per second, Accurate to
4.5 digits. Set "low" greater than "high" for inverted display (LINEAR ONLY). Totalizer: Integrates from the rate reading and accu­mulates up to 6 digits of total count. The time base (hours, minutes or seconds) is field programmable from the front panel. Analog Out: The unit can be ordered with an optional 4-20mA output which is proportional to the rate display. The high and low settings are programmable from the front panel. Set "low" greater than "high" for inverted output. A sinking driver generates a corresponding linear current through the external devices. The output updates with each update of the rate. Accuracy is 50uA worst case. For rated accuracy, load must be con­nected to the analog output before unit is powered. Compliance voltage must be 3 to 30 VDC non inductive. (The unit can provide the DC source as long as the drop across the devices being driven does not exceed 21V). Programming: Decimal points, Scaling from 0 to 59999 units per selected time base, set points, input type, security lock code, and assigning outputs are all programmable from the front panel. Housing: Standard 1/8 DIN, high impact 94VO plastic case.
Shipping Weight: 2 lbs. Overvoltage Protection:
50 V
Overcurrent Protection:
50 mA
Resolution: 14.5 Bits Accuracy:
RANGE % FS ERROR % FS ERROR
(worst case) (typical)
4-20 mA 0.1% .05% 0-10 VDC 0.2% 0.1% 0-5 VDC .25% .15% 1-5 VDC .25% .15%
Square Law: (above 5% of bottom range) 0.1% (5V inputs .4%) Worst case over complete range: 2%
Temperature Stability: Will not drift more than 20 parts per million per °C from 5°C to 54°C
2
Page 7
HOW TO MOUNT:
MOUNTING
Slide the body of the unit through the rubber gasket. Insert the unit into the panel. Slide the brackets up the groove to press against the back of the panel, as shown in "FIG. A". Insert the screws into the rear of the brackets.
FIG. A
3.925
(99.7)
Tighten the screws evenly and alternately. A panel less than .1" may distort if the clamps are screwed too tightly. Do not over tighten! A normal level of torque is required. Maximum torque should be 3" pounds. The panel must be parallel to the bezel to assure proper seal. Unit seals to NEMA 4/ IP65 if properly mounted.
4.437
(112.7)
BEZEL
GASKET
.587
2.625
(66.68)
3.622 (92)
1.772 (45)
4.245
(107.8)
CUSTOMER PANEL Panel Thickness 0.062" (1.5) to 0.187" (4.7) max.
3
Page 8
!
WIRING
AC / DC CONNECTIONS: NOTE: Connect power only after other connec­tions are finished. Do not touch the live AC power terminals. The unit has been designed with an isolated AC input, therefore polarity is not a con­cern for the AC power. The chassis is plastic, therefore earth ground is not used. For DC opera­tion, connect +DC to terminal 10 and -DC to terminal 3.
This Product complies with requirements of the European Community Directive 89/336/EEC [Elec­tromagnetic Compatibility]. However, electrical noise or intense electromagnetic fields in the vicin­ity of the unit may disturb the microprocessor. Users should exercise care and should take proper precautions to avoid microprocessor disturbance.
Four common sources of noise are:
1) AC power line noise- The input power lines should not be common to power lines for motors, pumps, contactors, etc. If the unit cannot be con­nected to an electrically clean power source, an inductive load suppressing device (MOV as GE#V130LA1 or Resistor Capacitor as Paktron# .2uf/220 ohm @ 400V) can be installed. Although locating the suppressor across the AC supply at the unit should help, best results are obtained by connecting the suppressor across the leads of the "load" at the device causing the spikes.
2) Input line noise- The noise is carried on the input and DC ground lines. Make sure the input wires are not run into the unit in a bundle with power input lines. We recommend using shielded cable. Con­nect the shield to DC ground of the unit and "earth" at one point in the circuit preferably at the DC ground terminal of the unit.
3) Output lines- The unit has two open collector outputs and two optional relay outputs. When these outputs are used to run external relays or solenoids, spikes can be generated upon activa­tion. This noise can spread through the instrument causing operating problems. If the source is a D.C. operated device, a general purpose diode (IN4004) placed across the solenoid prevents electrical noise spikes. Connect the cathode (banded side) to the more positive side of the coil. If the source is an A.C. operated device, use a Resistor Capaci­tor or MOV across the coil.
4) 24 VDC output supply- Noise can be generated on the 24 VDC output supply if it is used to drive inductive loads or if the current draw exceeds 50mA. Insure that all inductive loads have a diode (such as IN4004) across the coil and that the current does not exceed 50mA.
RESET IN
1
ANALOG OUT (SINK)
2
SIGNAL GND (-DC)
3
(CURRENT) +I IN
4
(VOLTAGE) +V IN
5
NOT USED
6
+24V OUT
7
PRESET B COLLECTOR
8
PRESET A COLLECTOR
9
+D.C. IN
10
110 / 220 VAC
11
110 / 220 VAC
12
WIRING CONNECTIONS
13
COMMON
14
N.C.
15
N.O.
16
COMMON
17
N.C.
18
N.O.
RELAY A
RELAY B
4
13 14 15 15 17 18
1 2 3 4 5 6 7 8 9 10 11 12
REAR VIEW
Page 9
TYPICAL WIRING HOOKUPS
3-Wire 0-10V Transmitter2-Wire 4-20mA Transmitter
Flowmeter
(4-20mA T ransmitter)
4-Wire 4-20mA Transmitter
Power
Supply
Flowmeter
(4-20mA T ransmitter)
2-Wire 4-20mA Transmitter
with Multiple Devices
-
+
Flowmeter
(4-20mA T ransmitter)
-
Strip Chart
Recorder
•7 - +24V Out.•11 - AC In
•12 - AC In
..•11 - AC In
•12 - AC In
•7 - +24V Out.•11 - AC In
•12 - AC In
110 VAC 60/50 Hz
110 VAC 60/50 Hz
110 VAC 60/50 Hz
•3 - Signal GND (-DC)
•4 - I In + (Current)
.
-
+
•3 - Signal GND (-DC)
•4 - I In + (Current)
-
+
•3 - Signal GND (-DC)
•4 - I In + (Current)
.
+
Flowmeter
(0-10 V Transmitter)
2-Wire 4-20mA Transmitter
Flowmeter
(4-20mA Transmitter)
AC Supply
LOAD
LOAD
+
-
recommende
for inductive
recommende
signal
with Analog Output
Strip Chart
Recorder
+
-
­+
Relay Output
Neutral
MOV
loads
Diode
for inductive
loads
-
DC
Supply
•13 Common
•14 N.C.
•15 N.O.
•16 Common
•17 N.C.
•18 N.O.
+
•3 - Signal GND (-DC)
.
•5 - V In + (Voltage).•7 - +24V Out.•11 - AC In
-
+
•2 - Analog Out
•3 - Signal GND (-DC)
•4 - I In + (Current)
.
•7 - +24V Out.•11 - AC In
110 VAC
•12 - AC In
60/50 Hz
110 VAC
•12 - AC In
60/50 Hz
Relay A
Relay B
OPEN COLLECTOR & RELAY OPERATION
The open collector and relay outputs trigger when the total or rate (assignable; see programming step 2) equals the corresponding Preset (A or B). When the outputs are assigned to the "total", the opera­tor can assign a duration of time (.01 to 599.99 sec.) that the output will remain energized. If 0.00 is assigned, the output will latch until reset. If output A is set at a duration (other than 0.00), the totalizer will autorecycle when Preset A is reached. At this time, output B will de­energize (if it was energized). Preset A is the final preset and should be set higher than Preset B, when both outputs are assigned to the total. If output A is set at a duration other than 0.00 and Preset A is set less
than Preset B, Preset B will be ignored (provided that they are both assigned to total). The totalizer will never autorecycle at Preset B. When the outputs are assigned to the "rate", the outputs can be assigned a hysteresis (alarm range). The hysteresis is the number of units below the preset that the output will remain energized. EXAMPLE: Preset set @ 100; Hysteresis set @ 10. The output will energize when the rate equals 100 and de-energize when the rate falls below 90 (10 below Preset).
NOTE: If the input scaling is inverted, the control output functions are inverted (LINEAR ONLY).
5
Page 10
V41 & V_41 PROGRAMMING FLOWCHART
4-20
EE
EE
LLAAAAYYYYSSSS
AA
AA
AA
AA
TTEEEE
AA
AA
tt
YYYYSS
SS
AA
AA
AA
AA
YYYYSS
SS
BB
BB
CC
CC
LLCCCC
AA
AA
LL
CC
CC
ddeeee
ssssee
ee
pp
pp
DDEEEECCCC
SSSSEE
EE
SSSSEE
EE
CC
CC
tt
SSSSEEEECCCCSS
SS
pp
pp
tt
AA
AA
TTEEEE
tt
bbaaaa
dd
tt
PP
PP
SS
SS
TT
ttaaaallll
D
300
E
DDEEEECCCCttttffffaaaaCCCCtttt
NOTE:
SSTTAARRT
PRGM
input
ENTER
i i 0-20 e 0-5
PRGM
e 1-5 e 0-10
ENTER
LiNEAR
PRGM
S9RT
ENTER
RUN MODE
SEVERAL PROGRAMMING SELECTIONS WILL NOT APPEAR WITH "RATE ONLY" & "TOTAL ONLY" UNITS OPTIONS NOT ORDERED WILL NOT APPEAR IN PROGRAM SELECTIONS
T
RR
RR
PRGM
RR
RR
ENTER
HH
HH
XXXXX
ENTER
RR
BBBB RR
TT
HH
HH
XXXXX
BB
LL
ENTER
TT
PRGM
PRGM
ttttoooott
ENTER
dddduuuurrrr
PRGM
XXX.XX
ENTER
BBBB ttttoooott
PRGM
ENTERENTER
dddduuuurrrr BB
XXX.XX
oo
lllloo
ENTER
LL
LLLLLL gg
LLLLCCCC ppppgg
ENTER
oooodd
XXXXX
ENTER
RUN MODE
PRGM
This symbol indicates any key. Press this key to step through Menu choices
PRGM
Press this key to enter displayed value.
ENTER
uu
ttttuu
PRGM
ENTER
*
lllloooo
PRGM
TTTT lllloo
TTTT HHHHii
uuuutt
nnnnoooorr
oo
ii
rr
NNNNNNNNiiiiNNNNSS
hhhhoooouuuurrrrss
rrrrDD
ENTER
XXXXX
ENTER
XXXXX
ENTER
XXXXX
ENTER
XX.X
ENTER
SS
ss
oooouuuutttt lllloo
oooouuuutttt HHHHii
uuuunnnniiiitt
oo
ii
PRGM
bb
oo
oo
ENTER
uuuudd
ENTER
tt
1200 2400 9600
PRGM
XXXXX
XXXXX
XX
ENTER
ENTER
RUN MODE
* For Version V41,
(with space between V & 41) ,
RDEC
appears after
Lo Cut
rdeC
appears as shown
. In Version V_41
For best results, choose the highest resolution possible when
entering the "set lo", "set hi" and "lo cut" values.
Enter the proper decimal location at the "rdec" prompt.
For V41
EXAMPLE: To scale the unit from 0.00 to 100.00, enter 0 for "set
lo" and 10000 for "set hi", enter the decimal at "rdec".
The Version number is displayed at power up. NOTE: Model INT69T & units with RS232/RS422 option can only
be used with V_41.
ii
LLLLii
ENTER
TT
PRESS
"PRGM"
TO
ADVANCE
TO NEXT
SELECTION
ttttoooott
RRRRAAAATTTTEE
PPPPEEEEAAAACC uuuuaaaallllllllyy PPPPRRRREEEE AA
PPPPRRRREEEE BB
SSSSEEEETTTT lllloo
SSSSEEEETTTT HHHHii
EEEENNNNDD
PRGM
RUN MO
EE CC
yy AA BB
oo
ii
DD
PRGM
ttttDD
ENTER
ENTER
1111000000
11110000000000
111100
11
11
00 00 00
RUN MODE
6
Page 11
DEFINITIONS
input
- INPUT; This section of the program menu assigns the type of input the unit will be using (0-20 mA, 4-
20 mA, 0-5 V, 0-10 V, 1-5 V, Linear or square root extraction).
i 4-20
- I 4-20; This sets the unit for a current input of 4 to 20 mA.
i 0-20
- I 0-20; This sets the unit for a current input of 0 to 20 mA.
E 1-5
- E 1-5; This sets the unit for a voltage input of 1 to 5 volts.
E 0-5
- E 0-5; This sets the unit for a voltage input of 0 to 5 volts.
E 0-10
- E 0-10; This sets the unit for a voltage input of 0 to 10 volts.
LiNEAR
S9RT
RELAYS
A RATE
HYS A
A tot
DuR A
B RATE
HYS B
b tot
- LINEAR; This sets the unit for linear input.
- SQUARE ROOT; This sets the unit for square root extraction.
- RELAYS; This section of the program menu sets the control output variables (relays & open collec-
tor).
- OUTPUT A FOR RATE; This assigns the A output to the rate.
- HYSTERESIS FOR OUTPUT A; This value is the number of units below Preset A that the output will remain "ON". EXAMPLE: Preset A set at 100, Hys set at 10. Output A will activate (turn on) when the rate equals 100; Output A will deactivate (turn off) when the rate falls below 90 (10 below Preset A)
- OUTPUT A FOR TOTAL; This assigns the A output to the totalizer.
- OUTPUT A DURATION; This is the duration of time (.01 to 599.99 sec) that Output A will remain energized. If 0.00 is entered the output will latch until reset. If a value other than 0.00 is entered the unit will autorecycle at Preset A.
- OUTPUT B FOR RATE; This assigns the B output to the rate.
- HYSTERESIS FOR OUTPUT B; Same as HYS A.
- OUTPUT B FOR TOTAL; This assigns the B output to the totalizer.
DuR B
- OUTPUT B DURATION; This is the duration of time (.01 to 599.99 sec) that Output B will remain energized. If 0.00 is entered the output will latch until reset.
loc
- LOCK; This section of the program menu sets up the lockout type and code.
LC ALL
- LOCK ALL; When this is selected the lockout will lock the program as well as the Presets and reset
button. The presets can be viewed but not changed.
7
Page 12
lc pg
- LOCK PROGRAM; When this is selected the lockout will lock only the program. The Reset can be
activated and the presets can be viewed and changed.
code
- CODE; This is a 5-digit code which will be used to lock and unlock the front panel.
setup
- SETUP; This section of the program menu sets up the operating variables.
rdec
- RATE DECIMAL LOCATION; This allows the user to program a decimal point for the rate display.
set lo
SET Hi
lo cut
nor
SECS
NNiNs
hours
tdec
tfact
- SET LOW; This is the rate value for the lowest input (0 or 1 Volts; 4 mA). (i.e. 4 mA = 10 lbs/hr.)
- SET HIGH; This is the rate value for the highest input (5 or 10 Volts; 20 mA). (i.e. 20 mA = 500 lbs/
hr.)
- LOW CUT-OFF; This is the lowest rate value to be recognized. All rate readings below this value will
assume the "set lo" value.
- NORMALIZING FACTOR; This is an averaging factor (00.0 to 99.9). Higher settings provide more normalizing (averaging) for a more stable display. Derived from the equation: (OLD DATA x "NOR" + NEW DATA)
("NOR" + 1)
- SECONDS; This tells the unit that the High and Low input values are entered in units per second.
- MINUTES; This tells the unit that the High and Low input values are entered in units per minute.
- HOURS; This tells the unit that the High and Low input values are entered in units per hours.
- TOTALIZER DECIMAL LOCATION; This allows the user to enter a decimal for the totalizer display. This decimal is not a dummy decimal and will scale the totalizer display accordingly. (i.e. if the tdec is set in the tenths position (#####.#), 100 will be displayed as 100.0)
- TOTALIZER FACTOR; This factor divides the totalizer display by 1, 10, 100 or 1000.
opt
- OPTIONS; This section of the program menu is for setting up optional features (analog out, RS232/422 serial communications).
out lo
out hi
BAuD
9600
2400
1200
300
- OUT LOW; The displayed rate value at which the unit will output 4 mA (2 lbs./hr = 4 mA out).
- OUT HIGH; The displayed rate value at which the unit will output 20 mA (2000 lbs./hr = 20 mA out).
- BAUD RATE; The baud rate at which the RS232 or RS422 communications will operate.
- 9600 BAUD; This sets the communications at 9600 Baud.
- 2400 BAUD; This sets the communications at 2400 Baud.
- 1200 BAUD; This sets the communications at 1200 Baud.
- 300 BAUD; This sets the communications at 300 Baud.
8
Page 13
unit
- UNIT NUMBER; This assigns the unit an ID number from 1 to 99. This number is to be addressed
when the unit is to be on line. A unit with 0 assigned will never come on line.
P LiST
- PRINT LIST; This sets a list of data that will be transmitted whenever the strobe is activated.
total
- TOTAL COUNT; When this is added to the print list, the unit will transmit the total when the strobe is
activated.
RATE
- RATE; When this is added to the print list, the unit will transmit the present rate value when the strobe
is activated.
PEAK
- PEAK; When this is added to the print list, the unit will transmit the present peak value when the strobe
is activated.
uALLEY
PRE A
PRE B
set lo
set hi
END
PXXXXX
uXXXXX
- VALLEY; When this is added to the print list, the unit will transmit the present valley value when the
strobe is activated.
- PRESET A; When this is added to the print list, the unit will transmit the Preset A value when the
strobe is activated.
- PRESET B; When this is added to the print list, the unit will transmit the Preset B value when the
strobe is activated.
- SET LOW; When this is added to the print list, the unit will transmit the Set Low value when the
strobe is activated.
- SET HIGH; When this is added to the print list, the unit will transmit the Set High value when the
strobe is activated.
- END; This is the only exit from the P List. If END is not entered the unit will start at the beginning of the P List again.
- P; This will appear in the 6th (furthest to the left) digit when viewing the Peak. The peak value is the highest rate reading that the unit had displayed since the peak had been reset. The peak is not retained in memory when power is lost.
- U; This will appear in the 6th (furthest to the left) digit when viewing the Valley. The valley value is the lowest rate reading that the unit had displayed since the valley had been reset. The valley is not retained in memory when power is lost.
RXXXXX
- R; This will appear in the 6th (furthest to the left) digit when viewing the Rate.
9
Page 14
FRONT PANEL OPERATIONS
Press to RESET in operating mode; Press to "ENTER" in programming mode.
Press once to freeze display. Press any key to update display normally. Press rapidly (3 times within 5 seconds) to "enter" LOCK code for panel lock.
RST
ENTER LOCK PRE A PRE B VIEW PRGM
Press to view or change Preset A
A B C D
Press to view or change Preset B
E
PROGRAMMING
Press to alter­nately view Rate, Total, Peak & Valley.
Press to cycle through PRO­GRAM choices; Press to step through set up choices in program mode.
STEP
1
SETTING
INPUT
PRESS
PRGM
ENTER
ENTER
DISPLAY
iNPuT
i 4-20, i 0-20
E 1-5, E 0-5
E 0-10
LiNEAR
or
S9RT
or
REMARKS
This section of the menu is used to set up the type of signal the unit will be receiving.
Press the PRGM key to step through choices. Press the RST/ENTER key to enter the displayed choice.
This section will only appear on units with the square root extraction option. Press the PRGM key to toggle be­tween the choices and press the RST/ ENTER key to enter the desired choice.
10
Page 15
PRESS DISPLAY REMARKS
STEP
2
SETTING
RELAYS
NOTE: If relay outputs
are not used, set dur A & dur B at "0.0" to prevent the counters from resetting at the presets.
PRGM
PRGM
ENTER
ENTER
ENTER
ENTER
input
RELAYS
A RATE
or
A ToT
(IF TOT SELECTED)
DuR A
(hit any key to view or
change existing dur A
value XX.X)
(IF RATE SELECTED)
HYS A
(hit any key to view or
change existing HyS A
value XXXXX)
B RATE
or
B ToT
This section of the menu sets up the open collector outputs and/or relays.
Output A assigned to the rate or total. Press the PRGM key to toggle be­tween choices, press the RST/ENTER key to enter the displayed choice.
dur A = the duration of time (.01 to
599.99 sec) that output A will remain on or energized. When dur A is dis­played, hit any key to view or change dur A. Press the RST/ENTER key to enter displayed value. When dur A is set at 0.00,output A will latch until re­set; when dur A is set other than 0.00 the counter will autorecycle at Preset A.
Hys (hysteresis)= The number of units below the preset that the output will remain "ON". EXAMPLE: Preset set @ 100; HyS set @ 10. Output will activate (turn on) when rate = 100 and turn off when rate falls below 90 (10 below preset). Follow instructions for A RATE & A TOT.
ENTER
ENTER
(IF TOT SELECTED)
DuR B
(IF RATE SELECTED)
HYS B
11
Follow instructions for dur A
Follow instructions for hys A
Page 16
PRESS
DISPLAY REMARKS
STEP
3
SETTING
LOCK
STEP
4
SETTING
SETUP
PRGM
PRGM
PRGM
ENTER
ENTER
PRGM
PRGM
PRGM
PRGM
input
RELAYS
LoC
LC PG or LC ALL
CoDE
Press any key to view
or change the lock
code
input
RELAYS
LoC
SETuP
This section of the menu is used to set up the lockout type and code.
LC PG = Locks program but presets
are accessible. LC ALL= Locks program & presets. Press the PRGM button to toggle be­tween choices; Press RST/ENTER to enter displayed choice.
When CODE is displayed, press any key to view existing lock code. To change the code press the key under each digit to be changed. Press RST/ ENTER to enter displayed value.
This section of the menu is used to set up important operating variables.
ENTER
ENTER
ENTER
rDEC
RDEC= rate decimal location; Press the key under the digit with the desired location. Press the "E" key if a decimal is not desired. Press RST/ENTER to enter the displayed location.
SET Lo
Press any key to view
or change existing
value
SET LO= Rate value for the lowest input (0 or 1V; 4mA).(i.e. 4mA = 10 lbs/ hr.) Key in the desired low value and press RST/ENTER to enter displayed value.
SET Hi
Press any key to view
or change existing
value
SET HI= Rate value for the highest input (5 or 10V; 20mA).(i.e. 20mA = 500 lbs/hr.). Key in the desired high value and press RST/ENTER to enter displayed value.
CONTINUED ON NEXT PAGE
12
Page 17
STEP
4
CONT...
SETTING
SETUP
ENTER
DISPLAYPRESS
Lo CuT
Press any key to view
or change existing
value
REMARKS
LO CUT= Low cut-off; Lowest rate value to be recognized. All rate read­ings below the "cutoff" will assume the "set lo" value. Key in the desired value and press RST/ENTER to enter dis­played value.
PRGM
ENTER
ENTER
ENTER
NoR
Press any key to view
or change existing
value
NNiNS, HouRS
or
SECS
tdec
NOR= Normalizing (averaging) factor (00.0 to 99.9); Key in the desired value and press RST/ENTER to enter dis­played value. Higher settings provide more normalizing (averaging) for a more stable display.
This section tells the unit that the high & low setting are entered in units per Minutes, Hours or Seconds. Press the PRGM key to step through choices. Press RST/ENTER to enter displayed choice.
TDEC= Totalizer Decimal; Press the arrow keys to enter in the desired totalizer decimal. Press RST/ENTER to enter displayed choice. Entering a decimal will add resolution to the total. (i.e. tdec=#####.#; 100 will be dis­played as 100.0)
PRGM
ENTER
ENTER
tfact
Press any key to view
or change existing
value
1, 10, 100
or
1000
13
TFACT= Totalizer Factor; This factor allows you to divide the totalizer by 1, 10, 100, 1000
Press the PRGM key to step to the desired factor. Press RST/ENTER to enter displayed choice.
Page 18
DISPLAYPRESS
REMARKS
STEP
5
SETTING OPTIONS
PRGM
PRGM
PRGM
PRGM
PRGM
ENTER
ENTER
input
RELAYS
LoC
SETuP
oPT
ouT Lo
Press any key to view
or change existing
value
ouT Hi
Press any key to view
or change existing
value
This section of the menu is for setting up the variables for any options which were ordered (Analog out or Serial communications).
OUT LO= The rate value represented by the 4 mA end of the 4-20 mA output Key in the desired value and press RST/ENTER to enter displayed value.
OUT HI= The rate value represented by the 20 mA end of the 4-20 mA output. Key in the desired value and press RST/ENTER to enter displayed value.
BAuD
Press any key to view
or change existing
BAUD = Baud rate for RS 232 or RS 422 communications option. Press any key to view existing value.
value
ENTER
9600, 1200,
2400 or 300
Press the PRGM key to view available baud rates; Press RST/ENTER to en­ter displayed value.
unit
Press any key to view
or change existing
ENTER
value
P LiST
Press any key to enter
print list
ToTAL
RATE PEAK
ENTER
OR
PRGM
uALLY
PRE A PRE B
set lo
set hi
END
THE PROGRAM SETUP IS COMPLETE! YOU ARE NOW READY TO SET THE PRESETS.
14
UNIT = Unit ID number. Key in the desired unit number (1-99) and press RST/ENTER to enter displayed value.
P LIST = Print list. Press RST/ENTER to add items to list; Press PRGM to remove items from list.
TOTAL = Total RATE = Rate PEAC = Peak UALLY = Valley PRE A = Preset A PRE B = Preset B SET LO = Low Input Value SET HI = High Input Value END = Press RST/ENTER to exit (end) print list; Press PRGM to recycle through list choices.
Page 19
SETTING THE PRESETS & PANEL LOCK
SETTING
THE
PRESETS
NOTE:
Presets can be set at any value form 0 to 59999.
SETTING
THE
LOCK
STATUS
Press LOCK 3 times within 5 seconds (If LOCK is pressed once, unit freezes display)
PRE A
PRE B
LOCK
LOCK
LOCK
DISPLAYPRESS
PRE A
Press any key to view
or change existing
value
PRE B
Press any key to view
or change existing
value
CoDE
Press any key to enter
the 5-digit lock code.
REMARKS
PRE A = Preset A (Final Preset); The set point at which output A will trigger. If the displayed value is not the de­sired preset, press the key(s) under the digit to be changed.
PRE B = Preset B (Prewarn); The set point at which output B will trigger. If the displayed value is not the desired preset, press the key(s) under the digit to be changed.
Key in the lock code (see program­ming step 3) by pressing the keys under the digits to be changed. Each time a key is pressed the digit will increment one. Press the RST/EN­TER key to enter the displayed code.
ENTER
LoC
or
UN LoC
After the code is entered the unit will display LOC (unit is locked) or UN LOC (unit is un-locked). This message will be displayed for approximately 3 sec­onds before the unit returns to the run mode. If an invalid code is entered, no message is displayed; try again.
15
Page 20
RS 232/422 OPERATIONS
This section applies to units which have the serial communications interface option. Up to 99 units can be linked together. Unit status can be accessed and many menu items can be entered through the serial port. Data is transmitted at selected baud rates using stan­dard eight bit ASCII characters and one “stop” bit. The unit does not check or transmit a parity bit.
UNIT I.D. (DEVICE #)
Each unit in the hookup must be assigned a unit number from 1 to 99. This can be entered through the front panel (see step 5 of the programming section). If “00” is assigned, the unit can not be brought on line through the serial port. The units will remain in an “off” high impedance state until addressed by the as­signed unit number. Once a unit is addressed, do not address another unit until the data has been sent and any data requested has been transmitted back.
BAUD RATE
The baud rate is the speed at which data is transmitted, expressed in bits per second. Baud rates of 300, 1200, 2400 or 9600 are available. Select the desired baud rate from the menu. (see step 5 of the programming section).
PRINT LIST
The serial interface card is equipped with a strobe line. When the strobe line is activated a user selectable set of data (print list) is transmitted. This transmission can be sent to a computer or printer. The print list consists of eight selectable items: COUNT, RATE, PEAK, VALLEY, PRE A, PRE B, LOW SET, HIGH SET. The list can be entered through the front panel (see step 5 of the programming section) or through the serial port (read on).
HELP
A help command has been installed for easy access of the command and data variables. When help is needed, type a “?” and press return (enter) whenever a unit is on line. The following list will be transmitted: D#XX: S Set E Exam R Reset G Lock L*List C*Count R*Rate P*Peak V*Valley A*PreA B*PreB L*Lo Set H*Hi Set J Lo Out K Hi Out N Norm D Unit E Input G Hy/DrA I Hy/DrB M Time T Baud W Lock X Meter Y A Typ Z B Typ O Code F RDec Q TDec U TFact The unit transmits the unit ID (D#XX) as well as the variables for the corresponding commands and data. A “*” indicates that the data is available for the print list.
16
Page 21
COMMANDS:
Each command consists of an instruction and an address. Each instruction and address is represented by a letter. The prefix of each command must be an instruction followed by an address (and address variable if appli­cable).
INSTRUCTIONS (1st letter of command):
[S] Set - Used to set the value or operating parameter of an address. (i.e. “SC 5000” will set the count at 5000)
[E] Examine - Used to examine the value or status of an address. (i.e. “ER” will examine the present rate reading)
[R] Reset - Used to reset the count & control output, peak or valley. (i.e. “RP” will reset the peak value)
[G] Lock - used to lock and unlock the unit. Type “G” followed by the “lock code” to lock and unlock the unit.
ADDRESSES (2nd letter of command):
[C]*Count [R]*Rate [P]*Peak [V]*Valley [A]*PreA [B]*PreB [L]*Lo Set [H]*Hi Set [J] Lo Out [K] Hi Out [N] Norm [D] Unit [E] Input [G] Dur A [I] Dur B [M] Time [T] Baud [W] Lock [X] Meter [Y] A Type [Z] B Type [O] Code [F] RDec [Q] TDec [U] TFact
[L]*List - Used to set the print list. (i.e. “LCRVA” will set the list for count, rate, valley and preset A. These values will be transmitted whenever the strobe is activated.)
17
Page 22
POSSIBLE COMMANDS:
Each command must be followed by a carriage return for execution.
DXX: (device “unit ID” #)- Unit XX will come “on
line” and stay “on line” until another device is addressed.
SD XX: (set device “unit ID”#)- sets unit ID # at
requested value
ED: (examine device)- Unit will transmit the present
device (unit ID) number (i.e. d = 000000XX).
SC XXXXXX: (set count)- Sets count at requested
value.
EC: (examine count)- Unit will transmit the present
count value ( i.e. c=00XXXXXX).
RC: (reset count)- Resets the counter and control
output .
ER: (examine rate)- Unit will transmit the present
rate value (i.e. r= 000XXXXX).
RR: (reset rate)- Resets the normalization EP: (examine peak)- Unit will transmit the present
peak value (i.e. p= 000XXXXX).
RP: (reset peak)- Unit will reset the peak. EV: (examine valley)- Unit will transmit the present
valley value (i.e. v=000XXXXX).
RV: (reset valley)- Resets the valley. SA XXXXX: (set preset A)- Sets preset A at re-
quested value.
EA: (examine preset A)- Unit will transmit present
preset A value (i.e. a=000XXXXX).
SB XXXXX: (set preset B)- Sets preset B at re-
quested value.
EB: (examine B)- Unit will transmit present preset
B value (i.e. b = 000XXXXX).
SL XXXXX: (set “Low”)- Sets “set low” at re-
quested value.
EL: (examine “Low”)- Unit will transmit present “set
low” value (i.e. l = 000XXXXX).
SH XXXXX: (set “High”)- Sets “set high” at re-
quested value.
EH: (examine “High”)- Unit will transmit present
“set high” value. (i.e. h = 000XXXXX)
SJ XXXXX: (set “low out”)- Sets “out low” at
requested value. Only available with ANA­LOG OUT option.
EJ: (examine “low out”)- Unit will transmit present
“out low” value. (i.e. j = 000XXXXX)
SK XXXXX: (set “high out”)- Sets “out high” at
requested value. Only available with ANA­LOG OUT option
EK: (examine “high out”)- Unit will transmit present
“out high” value. (i.e. k = 000XXXXX)
SN XX.X: (set norm)- Sets “norm” at requested
value. Must be a 3-digit number with decimal.
EN: (examine norm)- Unit will transmit present
“norm” value (i.e. n = 000XX.X).
SE i 4-20, i 0-20, e 0-5, e 1-5 or e 0-10: (set input)-
sets input to one of the 4 available types. Enter type exactly as it appears on the display.
EE: (examine input)- Unit will transmit input type
(i.e. e 0-10).
SG XXXXX: (set dur A or hys A)- Sets dur A or hys
A at requested value. (dur A when A is assigned to total; hys A when A assigned to rate).
EG: (examine dur A or hys A)- Unit will transmit
present dur A or hys A value (i.e.g = 000XXXXX)
SI XXXXX: (set dur B or hys B)- Sets dur B or hys
B at requested value. (dur B when B is assigned to total; hys B when B assigned to rate).
EI: (examine dur B or hys B)- Unit will transmit
present dur B or hys B value (i.e.I = 000XXXXX)
SM secs, mins or hours: (set time base)- Sets
time base to desired setting.
EM: (examine time base)- Unit will transmit present
time base (i.e. secs).
ST XXXX: (set baud)- Sets baud at desired rate
(9600, 2400, 1200 or 300).
ET: (examine baud)- Unit will transmit present
baud rate (i.e. 9600).
EW: (examine lock type)- unit will transmit present
lock type (i.e. lc pg).
SX linear or sqrt: (set meter type)- Sets meter
input for linear or square root extraction. Only available with square law option.
EX: (examine meter type)- Unit will transmit present
meter type (i.e. linear).
SY A tot or A rate: ( set A type)- Assigns control
output A to rate or total.
EY: (examine A type)- Unit will transmit present A
type (i.e. a tot).
SZ B tot or B rate: ( set B type)- Assigns control
output B to rate or total.
EZ: (examine B type)- Unit will transmit present B
type (i.e. b tot).
18
Page 23
SO XXXXX: (set lock code)- Sets lock code at
requested value.
EO: (examine code)- Unit will transmit present
code (i.e. o=000XXXXX).
SF X: (set rate decimal location)- Sets rate decimal
at requested location (0 to 4).
EF: (examine rate decimal location)- Unit will trans-
mit the present rate decimal location (i.e. f = 0000000X).
G XXXXXX: (lock unit)- Locks and unlocks unit.
(XXXXX = code)
SQ X: (set totalizer decimal location)- Sets total-
izer decimal at requested location (0 to 4)
EQ: (examine totalizer decimal location)- Unit will
transmit present total decimal location (i.e. Q = 0000000X).
SU XXXX: (set totalizer scale factor)- Sets totalizer
scale factor at requested value. This factor divides the totalizer by 1, 10, 100 or 1000. (i.e. SUXXX100 sets the divider at 100 where "X" represents the required space characters.
EU: (examine totalizer scale factor )- Unit will
transmit present total scale factor (i.e. U = XXX100 where "X" represents the space characters).
L CRPVABLH: (list)- The list can consist of any
combination of the eight available options. Any address with a "*" next to it can be listed.
When the unit is active (on line) it will operate in an echo back mode so that data sent from the terminal will be transmitted back for verifi­cation. When the unit is "on line", use the proper serial transmit commands to request data or set a new value. Be sure to send only one command at a time followed by a carriage return to insure proper operation. If an error is made, a correction can be made by back spacing and retyping correct data before the return (enter) is sent. Once a return (enter) is sent, the unit begins processing the data and will transmit the requested data on a non­priority basis over the data transmit line. The unit will not transmit data if the Printer Busy line is activated (high). When the Printer Busy line is activated all transmissions are halted until the line goes low or open. There should be a pause after data is requested to insure that all data has been transmitted before making an­other request or addressing another unit. If transmission has not started within two sec­onds after data is requested, it can be as­sumed that there is a problem. The unit transmits a carriage return and line feed after each data value. The unit will stay "on line" until another unit is addressed.
SERIAL INTERFACE OPERATION:
Data is received and transmitted over stan­dard EIA RS232 or RS422 levels. Each ten bit character is made up of a start bit, eight bit ASCII code and a stop bit. The input impedance of RS232 is 3K to 7K worst case. The terminal addressing the unit must be capable of driving all loads in the loop. The input impedance of RS422 is much higher and there should be no problem driving as many as 99 units. The transmit line remains in a high impedance "off" state until addressed. Only one unit is to be on line at a time!!! More than one unit on line could damage the unit or destroy the transmitted data.
RS232/RS422 - PC INTERFACE:
The following BASIC program is for setting up RS232/RS422 on serial port (#1) at 300 baud. Run this program after connecting the serial interface connections.
10 SCREEN 0,0:WIDTH 80 20 CLS:CLOSE 30 OPEN "COM1:300,n,8,1,CS,DS,CD" AS #1 40 ON ERROR GOTO 110 50 B$=INKEY$ 60 IF B$< >"" THEN PRINT #1,B$; 70 IF EOF (1) THEN 50 80 A$=INPUT$ (LOC(1),#1) 90 PRINT A$; 100 GOTO 50 110 RESUME
19
Page 24
RS232 / RS422 WIRING
COMPUTER HOOKUP: RS 232: When connecting the unit to a
computer with RS 232 communication, only three connections are needed. These con­nections are: Receive data, Transmit data and Ground. The connections should be made as follows:
DB-9 CONNECTOR COMPUTER Transmit data (pin 2) Receive data Receive data (pin 3) Transmit data Ground (pin 5) Ground
RS 232
RECEIVE PIN (3)
TRANSMIT PIN (2)
GROUND PIN (5)
RS 422: When connecting the unit to a com­puter with RS 422, five connections are needed. These connections are: Receive data A (+), Receive data B (-), Transmit data A (+), Transmit data B (-) and Ground. The connections should be made as follows:
DB-9 CONNECTOR COMPUTER Trans. data A(+) (pin 2) Rec. data A(+) Trans. data B(-) (pin 7) Rec. data B(-) Rec. data A(+) (pin 3) Trans. data A(+) Rec. data B(-) (pin 8) Trans. data B(-) Ground (pin 5) Ground
RS 422
RECEIVE A(+)PIN (3) RECEIVE B(-)PIN (8)
TRANSMIT A(+)PIN (2) TRANSMIT B(-) PIN (7)
GROUND PIN (5)
PRINTER HOOKUP:
When connecting the unit to a printer, you must first program the desired baud rate, parity and strobe list with a computer. After the unit is programmed it can be connected to the printer. Connect the transmit line(s) of the unit to the receive line(s) of the printer and be sure that both devices have common grounds. When the strobe line is triggered the unit will transmit the selected strobe list which you had previously programmed.
DB - 9 CONNECTOR
1- Printer busy: 3 to 30 VDC, Level activated. 2- Transmit A(+) (RS422); Transmit (RS232) 3- Receive A(+) (RS422); Receive (RS232) 4- Not Used
6789
5- Ground 6- Strobe: 3 to 30 VDC Positive Edge
12345
7- Transmit B(-) (RS422 Only) 8- Receive B(-) (RS422 Only) 9- Not Used
RS 422
STROBE PIN (6)
PRINTER BUSY PIN (1)
TRANSMIT B (-)PIN (7)
TRANSMIT A (+) PIN (2) GROUND PIN (5)
RS 232
STROBE PIN (6) PRINTER BUSY PIN (1)
TRANSMIT PIN (2) GROUND PIN (5)
20
Page 25
TROUBLESHOOTING GUIDE
PROBLEM POSSIBLE CAUSES SOLUTIONS
Power is applied to unit but the display does not light.
Unit works but occasionally the display freezes or skips counts.
Input signal is connected but the unit does not totalize or rate.
1. AC or DC power wiring is incorrect.
1. Line noise is effecting the processor due to a current spike or surge.
1. Input wiring is incorrect
2. High and low scaling set­tings are incorrect.
3. Transmitting device is de­fective.
4. Unit is defective.
1. Recheck power wiring.
1. Use a different power sup­ply or install a surge sup­pressor.
1. Recheck input wiring.
2. Recheck high and low scal­ing settings.
3. Replace transmitting de­vice.
4. To confirm set meter for 0­10V input, low @ 0; high @
10. Apply a 0-10V signal to the voltage input (pin 5). When viewing the rate the meter should display the voltage value that is applied. If not call factory for an RMA#.
Display reading is inaccurate.
Ratemeter works properly but totalizer is incorrect.
1. Input wiring is incorrect.
1. Time base is incorrect.
1. Be sure that voltage sig­nals are connected to volt­age input (pin 5) and cur­rent signals are connected to current input (pin 4).
1. Recheck time base setting in setup section of the pro­gram menu.
IF YOU HAVE ANY OTHER PROBLEMS, PLEASE CALL THE FACTOR Y.
21
Page 26
We hope you will be pleased with our product. If you have any questions concerning our
warranty, repair, modification or returned goods process, please contact your local distributor.
WARRANTY
This product is warranted against defects in materials and workmanship for a period of
two (2) years from the date of shipment to Buyer.
The Warranty is limited to repair or replacment of the defective unit at the option of the manufacturer. This warranty is void if the product has been altered, misused, dismantled, or otherwise abused.
ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, ARE EXCLUDED, INCLUD­ING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
Kessler - Ellis Products Co.
10 Industrial Way East
Eatontown, NJ 07724
(732) 935- 1320
Toll Free 800 - 631 - 2165
Fax (732) - 935- 9344
DECODING PART NUMBER SAMPLE: INT69RT A L 1 C1
Series
INT69RT= Ratemeter / Totalizer INT69R= Ratemeter Only INT69T= Totalizer Only
Operating Voltage
A= 110 VAC ± 15% or 12 to 24 VDC B= 220 VAC ± 15% or 12 to 24 VDC
Inputs
L= Linear (standard) S= Square Law (optional)
Control outputs
1= 2 - Open Collector Outputs (standard) 2= 2 - 10 Amp Form C Relays (optional)
Options
A= Analog Output (4-20 mA) C1= RS 232 communications C2= RS 422 communications
Accessories
Separate non keyboard panel order # 34235 Separate keyboard panel order # 34237
Loading...