KEP BATCHtrol-II Operating Manual

BATCHtrol II
Software Versions 8.x & 12.x
Installation and Operating Manual
Description
The Batcher is a programmable, microprocessor based unit which provides batch control, monitors ow rate and controls the ow of processing liquids. Start/Stop controls can be used in conjunction with pre­warn and nal relays to provide valve actuation or pump control. An optional conguration offers stream­lined preset adjustments, remote Start, Stop & Reset, and weighted averaging.
Features
Pulse or Analog Input Display Batch, Rate or Grand Total Pulse Count Input up to 20 KHz 16 Point Linearization 8 Digit K-Factors for Rate and Total Security Lockout 2-Way RS232/422 Communications NEMA 4X/IP65 Front Panel Scalable 4-20 mA Output Scaled Pulse Output Optional Conguration Includes:
- Streamlined Preset Adjustment (Easy Preset)
- Remote Start, Stop and Reset
- Weighted Averaging
Kessler-Ellis Products Co.
BATCHtrol II
Application
The unit is normally used for batch control or inventory tracking. The display may be toggled between batch, rate, and grand total. A programmable K-factor makes keying-in engineering units easy. The unit accepts pulse, contact closures or analog inputs and provides two separate preset controls.
Principle of Operation
The batcher receives an input from a pulse producing owmeter through a sensor. The user programs the batcher to condition the incoming pulses signal and compute the batch ow and ow rate. A wide variety of different functions can then be performed based on the programmed congurations such as start/stop functions, totalizing, and/or ow rate monitoring. Several other inputs, outputs and functions are
available.
99392 05/21/08
BATCHtrol II Series Technical Manual
!
SAFETY INSTRUCTIONS
The following instructions must be observed.
This instrument was designed and is checked in accordance with
regulations in force EN 60950 (“Safety of information technology equipment, including electrical business equipment”).
A hazardous situation may occur if this instrument is not used for
its intended purpose or is used incorrectly. Please note operating instructions provided in this manual.
The instrument must be installed, operated and maintained by
personnel who have been properly trained. Personnel must read and understand this manual prior to installation and operation of the instrument.
The manufacturer assumes no liability for damage caused by incorrect use of the instrument or for modications or changes made to the
instrument.
Technical Improvements
The manufacturer reserves the right to modify technical data without
prior notice.
CONTENTS
1. INTRODUCTION
1-1 General Description ..................................................................................................1
1-2 Typical Application ....................................................................................................1
1-3 Principles of Operation .............................................................................................1
1-4 STD PRE and EZ PRE Operation Modes ................................................................3
1-5 Specications ...........................................................................................................4
1-6 Dimensions ...............................................................................................................5
2. INSTALLATION
2-1 Receipt of Equipment ...............................................................................................6
2-2 Return Shipment.......................................................................................................6
2-3 Panel Mounting.........................................................................................................6
2-4 Electrical Connections ..............................................................................................6
2-5 Wiring Connections and Diagrams ...........................................................................7
3. OPERATION
3-1 Front Panel Operation ..............................................................................................8
3-2 VER 8.7 Programming..............................................................................................9
3-3 VER 8.7 K-Factor Programming ...............................................................................9
3-4 Software Version 8.7 Programming Flow Chart .....................................................10
3-5 VER 12.0 Programming..........................................................................................11
3-6 VER 12.0 16 Point Linearization Notes .................................................................. 11
3-7 Software Version 12.0 16 Pt. Programming Flow Chart .........................................12
3-8 How to Program......................................................................................................13
3-9 Frequently Asked Questions About Setting Up The Batcher ..................................13
3-10 Setup Procedure For The Batcher ........................................................................14
3-11 Run Mode .............................................................................................................27
3-12 Internal Operation .................................................................................................29
4. INPUTS
4-1 Digital Pulse Inputs .................................................................................................30
4-2 Analog Inputs ..........................................................................................................30
4-3 DC Power Inputs ....................................................................................................32
4-4 AC Power Inputs .....................................................................................................32
5. OUTPUTS
5-1 Frequency Output ...................................................................................................32
5-2 Control Outputs ......................................................................................................33
5-3 Optional Analog Output ..........................................................................................33
5-4 Optional RS232 / RS422 Serial Communications ..................................................34
CONTENTS
6. TROUBLE SHOOTING AND MAINTENANCE GUIDE
6-1 Warning Messages .................................................................................................34
6-2 Troubleshooting ......................................................................................................35
6-3 Removing The Case ...............................................................................................36
6-4 Maintenance ...........................................................................................................36
7. CALCULATING THE K FACTORS
7-1 General ...................................................................................................................36
7-2 Calculating the K Factors .......................................................................................37
7-3 Calculating 16 Point K Factors ...............................................................................39
8. SERIAL COMMUNICATIONS
8-1 Unit Code................................................................................................................40
8-2 Baud Rate...............................................................................................................40
8-3 Parity ......................................................................................................................40
8-4 RS232 Electrical Requirements..............................................................................40
8-5 RS232 Card Wiring.................................................................................................41
8-6 RS422 Electrical Requirements..............................................................................41
8-7 RS422 Card Wiring.................................................................................................42
8-8 Strobe Input Electrical Requirements .....................................................................42
8-9 Strobe Wiring ..........................................................................................................43
8-10 Serial Interface Operation.....................................................................................43
8-11 Strobe Address Operation ....................................................................................45
9. Programming Worksheet
.................................................................................................46
SECTION 1 INTRODUCTION
123456
Flowmeter
Computer
Solenoid Valve
Remote
Totalizer
Strip Chart
Recorder
Pulse Output
RS232 Output
Analog Output
1-1 General Description
Sections 1 through 8 of this manual describe the wiring, programming and functionality of the standard Batch controller. Section 9 de­scribes the wiring, programming and function­ality of Batch controllers with software version
8.7 (Option 6). Software version 8.7 incor­porates Remote Start, Stop & Reset with EZ PRE (easy preset). EZ PRE is a useful tool for applications that require frequent changes to the Preset amount.
1-3 Principles of Operation
Presets
When the start button is pushed, two relays
engage simultaneously to start ow. When
the prewarn number is reached, one re­lay drops out. When the preset number is reached, the other relay drops out. The user may enter the two numbers when setting up the batch counter. The prewarn is set a cer­tain number of counts less than the preset number. If the prewarn is set larger than the preset, the message “PREWRONG” will ap­pear on the display.
The Batch controller uses the following soft­ware versions: VER 8.7 (Basic unit; Remote Start, Stop
& Reset with EZ PRE “Easy Preset”)
VER 12.0 (Option 4; 16 point linearization)
1-2 Typical Application
The above application involves liquid ow.
The start button is pushed and the Batcher receives pulses from the owmeter. The puls­es are scaled by the K Factor and sent out via the pulsed output to an external counter. The Analog output is directed to a strip chart re­corder which gives a hardcopy of the rate. As the Prewarn is reached, the control valve par-
tially closes. When the nal Preset is reached
the valve shuts down completely. At any time
the ow can be suspended by hitting the stop
button. Through the serial communications, a computer keeps a record of the daily events.
Ratemeter
Accurate to 5 1/2 digits (±1 display digit). The ratemeter can be programmed to ac­cept almost any number of pulses per unit of measurement, sample from 2 to 24 seconds maximum, and auto range up to 6 digits of
signicant information. The ratemeter with a
K Factor of 1 displays the rate of pulses per second. Simply dial in the proper K Factor to display in minutes, hours or other units of measurement. Press the C button, while the unit is displaying the batch, to display the rate; ‘R’ is displayed on the left side of the display.
K Factor
The K Factor is used to convert the input puls­es or analog input into workable units. The 8 digit K Factor is a divider with a range of
0.00011 to 99999999 (the decimal point may be keyed into any position). Separate K Fac­tors may be entered into the count and rate sections of the Batcher. Thus, you may batch in gallons and display rate in liters per hour. The maximum factored count speed is 20000 Hz. The maximum factored rate is 7 digits.
16 Point Linearization (Optional) This option extends the accurate range by al­lowing users to dial in different K Factors for different input rates. This option may be used with digital or analog inputs. (See Section 7-3.)
1
1-3 Principles of Operation (continued)
Counter
The maximum count is 99999999. In the setup mode choose “RO” (Reset to Zero) for adding (count up) operation or “SP” (Set to Preset) for subtracting (count down) opera­tion. At any time, the display can be made
to ash the Grand Total by pressing the ENT
button while in the run mode. Activating the
CLR button while the Grand Total is ashing,
resets the Grand Total counter.
Lockout
Unauthorized front panel changes can be pre­vented by entering a user selected, four digit code, in the “Lockout” mode. The status of the unit can be observed but “LOCK ON” ap­pears if changes are attempted. Entering the code again returns the unit to “LOCK OFF” status.
Analog Output (Optional) The Analog Output option is available on all units except those with Square Law inputs. Controlled by an Open Collector transistor, it gives a 4 to 20mA (or 0-20mA) output which corresponds to predened rate or total read­ings. In the Setup mode the user is prompted to set the low and high (4 to 20 mA) values and also decide if the analog signal will corre­spond to the ratemeter or totalizer.
Frequency out
The Batcher generates a pulse out for each factored count. An NPN transistor output (Pin
2), can drive external devices at rates of 10, 200, 2000 or 20000 counts per second as selected through the keypad menu. If the K Factor scaled inputs generate pulses faster than the output speed selected, an internal buffer will store up to 9,999 counts before “DATALOST” ashes on the screen. This in­dicates that the counts being totaled and the scaled outputs may be incorrect. Note that all counts stored in the internal buffer will be pulsed out at the selected frequency even if the counter is reset.
Outcard (Optional) RS232 or RS422 serial two way communica­tions are available. Up to 15 units can be linked together in parallel and addressed separately to transmit unit status or accept new set points in the standard ASCII format. Baud rates of 300, 600, 1200, 2400, 4800 or 9600 as well as choice of odd, even, space, or mark parity can be selected by keypad con­trol.
A sinking driver generates a linear current across the user’s external device (such as a strip chart recorder, PLC, computer, external meter, etc). The Batcher can supply the 24 VDC to power the current loop. (Connect pin 15 to 13, Pin 16 is now +24 VDC with respect to pin 12.) Connect Pin 16 to the + DC side of the external device and connect Pin 3 to -DC side of the external device.
2
1-4 STD PRE and EZ PRE Operation Modes
STD PRE and EZ PRE Operation Modes
Version 8.7 of the batcher software allows the user to choose between STD PRE (Standard Preset) and EZ PRE (Easy Preset) operation modes. STD PRE operation is well suited for batch amounts that do not change, since the program mode must be entered to change the preset and the batch count must be cleared before starting a new batch. EZ PRE has been designed for users who frequently change the batch amount. During EZ PRE operation, the preset can be viewed and changed without entering the program mode and another batch can be started without resetting the unit.
Note: Before a batch is started and after a batch is complete, the unit will continue to totalize all inputs.
Note: EZ PRE is not available on units with 16 Point Linearization.
Using STD PRE
Programming Select STD PRE - Go into the Program Mode and
select STD PRE in the PRE TYP sub menu.
Set the PRESET and PREWARN - Go into the
Program Mode and enter the desired values for the PRESET and the PREWARN.
Program the Counter - Go into the Program
Mode and set up the counter in the COUNT sub menu.
Operation Start a Batch - In the Run Mode, reset the total by
pressing “CLR”, then press “A” to start. When started, both relays energize and the counter begins to count. When the batch is complete, the relays drop out and the unit displays the amount that was batched (0 if in Set to Preset mode).
Stop a Batch - Press “B”, to temporarily stop
process by de-energizing the PRESET and PREWARN relays. Press start, “A”, to continue process.
Repeat a Batch - In the Run Mode, reset the total
and press the start button.
Change the Batch Size - Go to the Program
Mode and enter new PRESET and PREWARN values.
Using EZ PRE
Programming Select EZ PRE - Go into the Program Mode and
select EZ PRE in the PRE TYP sub menu.
Set the PRESET and PREWARN - Go into the
Program Mode and enter the desired values for the PRESET and the PREWARN.
Program the Counter - Go into the Program
Mode and set up the counter in the COUNT sub menu.
Operation Start a Batch - In the Run Mode, press “A” to
start. When started, both relays energize and the counter begins to total. When complete,
the relays drop out and the display ashes the
current PRESET value.
Stop a Batch - Press “B”, to temporarily stop
process by de-energizing the PRESET and PREWARN relays. Press start, “A”, to continue process.
Repeat a Batch - Press the start button. Change the Batch Size - With the current
PRESET ashing on the display, type a
new number using the keypad. This number becomes the PRESET.
Display Batch Total or Rate - With the current
PRESET ashing, press “ENT” to place the
PRESET value in memory and use the “C” button to toggle between the Batch Total and the Rate.
3
1-5 Specications
Housing: High impact plastic case with NEMA 4X front panel.
Dimensions: See Section 1-5, Page 4.
Display: 8 Digit, 0.55” High, 15 Segment, Red Orange, LED.
Input Power: A: 110 VAC ± 15% or 12 to 27 VDC B: 220 VAC ± 15% or 12 to 27 VDC
NOTE: AC Inputs are internally fused with a
160mA slow blow fuse.
Current: Maximum 280 mA DC or 5.3 VA at rated AC voltage.
Output Power: (On AC powered units only): +12 VDC at 100 mA. Separate Isolated 12 VDC at 100 mA to allow ± 12 VDC or +24 VDC, regulated ± 5% worst case.
Temperature: Operating: +32°F (0° C) to +130 ° F (+54° C) Storage: -40°F (-40° C) to +200 ° F (+93° C)
(Extended operating temperature range available, consult factory)
Memory: EEPROM stores all program, display mode and count data for a minimum of 10 years if power is lost.
Reset Front push button: “CLR” resets displayed number and control output. Remote Input (Terminal 5): Open or 0 to 1 VDC (low), 3 to 30 VDC (high), 10K ohm input impedance to ground. Minimum pulse on / off time 5 msec.
Accuracy over full temperature range: Analog - Zero error: ±0.175% full scale max. Overall error: ±0.5% full scale max.
Digital - 100% (within specied voltage
ranges)
Pulse Inputs: 3A: Standard. High impedance pulse input. Open or 0 to 1 VDC (low), 3 to 30 VDC (high), 10K ohm input impedance. 20 KHz maximum speed (min. on / off 25 usec).
3B: Same as 3A except 4.7 K ohm pull up re­sistor to +5 VDC with respect to Terminal 12.
Analog Inputs: The current or voltage input is converted to a highly linear 0 to 10 KHz frequency. This fre­quency can then be scaled by 8 digit K-factors to display rate or count in the appropriate en­gineering units.
5A: 4-20 mA; 250 Ω input impedance. 5B: 0-20 mA; 250 Ω input impedance. 5C: 1-5 VDC; 15 KΩ input impedance. 5D: 0-5 VDC; 15 KΩ input impedance. 5E: 0-10 VDC; 15 KΩ input imped-
ance.
6A: Square Law: 4-20 mA; 250 Ω in-
put impedance.
4
1-5 Specications (continued)
PANEL
CUTOUT
2.50 -0, +0.02
(63.5 -0, +0.5)
7.375 -0, +0.04 (187.3 -0, +1)
7.375
(187.3)
(NOM.)
0.53
(13.5)
6.0
(152.4)
2.48 (63)
(NOM.)
(NOM.)
A B C D
1 2 3
4 5 6
7 8 9
CLR0SET
8.17
(207.5)
3.31 (84)
Factored Output: One pulse per each factored count Sinking (NPN Transistor) Open Collector sinks 250 mA maximum to 1 volt maximum from 30 VDC maximum Internal buffer: 9999 pulses Output speed: user selectable (see table below)
Speed (Hz) 10 200 2000 20000
Min. on/off (msec) 47.5 2.0 0.2 0.013
Analog output: (Not available with 4-20 mA, Square Law input type) 4-20 mA (or 0-20 mA) Sinking, (NPN transistor), Open Collector Compliance voltage: 3-24 VDC, non-inductive Accuracy: ±100 uA worst case Update Rate: Follows ratemeter
1-6 Dimensions
Control Outputs: SPDT Relays Contact rating: 10 A 120/240 VAC or 28 VDC.
NPN Transistor Output Open Collector sinks maximum of 100 mA from 10 VDC when active Note: 10 VDC is provided at transistor outputs through the relay coils. If current greater than 2 mA is drawn, the relay will remain energized. Applying greater than 10 VDC may destroy the unit. The transistor will sink 100 mA in the “ON” state with relays installed.
All Dimensions in inches (mm)
5
1-5 Dimensions (continued)
SECTION 2 INSTALLATION
2-1 Receipt of Equipment When the equipment is received, the outside packing case should be checked for damage incurred during shipment. If the packing case
is damaged, the local carrier should be notied
at once regarding his liability. A report should be submitted to the factory. Carefully remove the equipment from the pack­ing case and inspect for damaged or missing parts.
2-2 Return Shipment Do not return assembly or part with out a Return Material Authorization. The RMA is obtained by calling your local distributor.
2-3 Panel Mounting The controller should be located in an area with a clean, dry atmosphere which is relatively free of shock and vibration. The Batcher is installed in a 7.365” (187 mm) wide by 2.495” (63.4 mm) high panel cutout. To mount the controller pro­ceed as follows: a. Prepare the panel opening. b. Slip the gasket (provided) over the rear of
the counter case and slide it forward until it engages the inner surface of the front be­zel.
c. Install the screws (provided) in the mounting
brackets and insert in the holes located on both sides of the Batcher.
d. Tighten the screws rmly to attach the coun-
ter bezel to the panel.
Full Size Panel Cutout Template
(copy before using)
2-4 Electrical Connections (Reference Figures 2-1 to 2-3) All connections are completed at terminal blocks located at the rear of the case. Make sure all power is disconnected before making any elec­trical connections. In cases where cables are
situated in areas with heavy electrical elds,
6
2-4 Electrical Connections (continued)
FLOWMETER
SHIELD
GROUND
SIGNAL
1 2 3
TB1
AMPLIFIER
TB2
3 2 1
4 - Input A
12 - Ground (-DC) 13 - +12 Volts Out
15 - Isolate -12 Volts 16 - Isolate +12 Volts 17 - AC In 18 - AC In
+24VDC
GROUND
1 10 VA C 60/50 Hz
!
FLOWMETER
ANALOG SIGNAL
4 - Input A
12 - Ground (-DC) 13 - +12 Volts Out
15 - Isolate -12 Volts 16 - Isolate +12 Volts 17 - AC In 18 - AC In
+24VDC
1 10 VA C 60/50 Hz
4 - Input A
12 - Ground (-DC) 13 - +12 Volts Out
15 - Isolate -12 Volts 16 - Isolate +12 Volts 17 - AC In 18 - AC In
1 10 VA C 60/50 Hz
Switch
Closure
NPN
Output
4 - Input A
12 - Ground (-DC) 13 - +12 Volts Out
15 - Isolate -12 Volts 16 - Isolate +12 Volts 17 - AC In 18 - AC In
1 10 VA C 60/50 Hz
Switch
Closure
PNP
Output
shielding is required for maximum noise im­munity. One end of the shielding should be connected to earth ground. Relays or induc­tive coils connected to or located in the im­mediate area should be arc suppressed with appropriate diodes, MOV’s or resistor capaci­tor networks.
Caution:
An external fuse is required
for DC powered units.
DC Power: Use a 0.5 Amp
Fuse inline with Term. 14
AC units are internally fused.
2-5 Wiring Connections and Diagrams
1 - Not Used
2 - Scaled Pulse Output O.C. 3 - Analog Output 4 - Input A (Pulse/Analog) 5 - Remote Stop/Reset Input 6 - Not Used 7 - Not Used 8 - Not Used 9 - Not Used 10 - Remote Start Input 11 - Ground (-DC), Input Common 12 - Ground (-DC), Input Common 13 - +12 Volts Out 14 - DC Power In (12 - 27 VDC) 15 - Isolate -12 Volts 16 - Isolate +12 Volts 17 - AC In 18 - AC In
19-Prewarn Transistor O.C. 20-Preset Transistor O.C.
2-5 Wiring Connections and Diagrams
All AC powered BT2 Models are equipped with an internal fuse. Use KEP part #14039 for replacement
Figure 2-2
Typical Digital Wiring Connections
All AC powered BT2 Models are equipped with an internal fuse. Use KEP part #14039 for replacement
Figure 2-3
Typical Digital NPN (Input 3B) Wiring
All AC powered BT2 Models are equipped with an internal fuse. Use KEP part #14039 for replacement
Figure 2-4
Typical Digital PNP (Input 3A) Wiring
R1-N.O R2-N.C. Preset R3-Common R4-N.O R5-N.C. Prewarn R6-Common
Figure 2-1 Terminal Block Connections
All AC powered BT2 Models are equipped with an internal fuse. Use KEP part #14039 for replacement
Figure 2-5
Typical Analog Wiring Connections
7
3-1 Front Panel Operation
STOP
D
START
RATE/TOTAL
MENU
CBA
ENT
0
7
4
1
2
3
6
5
8
9
CLR
START - Pressing “A”, starts the
A
process by energizing the PRESET and PREWARN relays. Press “CLR” to reset Batch Total before starting new batch.
Weighted Averaging
Version 8.7 of the batcher software includes weighted averaging of the rate display. Weighted averaging is not available on units with 16 Point Linearization.
Weighted averaging can be used to create a more
stable display when the rate input is uctuating.
A weight, “W”, from 00 to 99 is applied to the old rate data before the new rate data is sent to the display. The following equation is used:
Rate Display =
W = Weight (00-99)
(Old Data x W + New Data)
(W + 1)
B
C
D
ENT
CLR
STOP - Pressing “B”, will temporarily
stop the process by de-energizing the PRESET and PREWARN relays. Use START to continue the process from where it stopped.
RATE/TOTAL ­STD PRE mode Pressing “C” toggles between rate and total count displays. The rate display has an “R” on the left side of the screen. EZ PRE mode Pressing “C” toggles between rate, total count and preset displays in EZ PRE mode. The rate display has an “R” on the left side of the screen and the preset display has a “P” on the left side of the screen.
MENU - Pressing “D” takes the unit out of the Run Mode and into the Programming Mode (See Programming, Page 43 and
45). “D” is also used make to some programming selections.
ENT - With Total Count showing in the Run Mode (see “C” key), pressing “ENT” displays the Grand Total, which
begins ashing on the screen. Press
“ENT” again to return to the Count. In the Programming Mode, “ENT” is used to accept a selection (See Programming, Page 43 and 45).
CLR - When the count total is displayed, pressing “CLR” will reset the counter to 0 or to Preset A depending on how it was programmed. When the Grand Total is displayed, pressing “CLR” will reset it to
0. When the Preset or Program Mode values are displayed, pressing “CLR” will reset them to 0, so that new values can be entered.
If a weight of 00 is used, the new rate data will go directly to the display without being averaged. If a number other than 00 is entered for the weight, then the new data will be averaged with the old data before being sent to the display. Higher weight numbers will create a more stable rate display. Small rate changes will be more noticeable when lower weight numbers are used.
Programming Weighted Averaging
1. In the Program Mode, got to the RATE sub menu and program the K-FACTOR, the WINDOW, and the SIG FIG parameters.
2. When the display shows WEIGHTXX (XX represents the current WEIGHT value), either accept the current value and return to the Run Mode by pressing “ENT” or clear the current value by pressing “CLR”.
3. If the current value was cleared, the display shows WEIGHT00. Using the keypad, enter a new WEIGHT value from 00 to 99. Press “ENT” to accept the new value and return to the Run Mode.
Remote Start, Stop, and Reset
A 4 to 30 VDC positive pulse will activate these inputs. Remote Start, Stop, and Reset is not available on units ordered with the Control Input option 7A (4-20 mA In, 4-20 mA Out).
START (Pin 10): When activated, the unit will
START as described in Front Panel Operation.
STOP/RESET (Pin 5): When activated, the unit will
STOP (If the unit is started and the batch is not complete). A second pulse to pin 5 will reset the counter (When the unit is stopped or when the batch is complete). If pin 5 is held high (4 to 30
VDC), the display will ash “STOPPED” and any
start inputs will be inhibited.
8
3-2 VER 8.8 Programming
Overview:
This Section of the manual provides an outline of programming procedures for the batcher software version 8.7. Detailed descriptions and programming instructions for this unit are available in previous sections of this manual. Page number references
are included to help you nd related information in
this manual.
Programming Procedures:
Enter Program Mode - Press the MENU button,
“D”, in the Run Mode.
Choosing a Sub Menu - Once in the Program
Mode, continue pressing the “D” button until the desired Sub Menu is displayed. Press “ENT” to enter the selected Sub Menu.
Making a Selection - An arrow, “”, appearing over
only the “D” button indicates that “D” is used to change the selection. When an arrow appears over “B” and “D”, one must be selected.
Entering a Value - The keypad is used to enter a
number. Use the “D” button to enter a decimal. (Ex: 34.5 would be entered by pressing “3”, “4”, “D”, and “5”)
Accept a Value or Selection - Press “ENT” to ac-
cept the value and go to next step.
Exit Program Mode - Program or skip each step
of one of the menus to return to the Run Mode. Pressing “ENT” allows a step to be skipped with­out changing its value.
Key to Programming Flow Chart:
Display - This box represents the unit’s dis-
play. In the Run Mode, the ow rate, the batch
total, or the grand total will be displayed.
XX Current Value - The number that is currently
programmed for that step. It must be cleared (CLR button) before entering a new value.
00 No Value - Indicates that programmed value
for that step has been cleared, and a new number may be entered.
Keypad - Use the front panel keypad to enter
a value or select a decimal point location for this step.
3-3 VER 8.8 K-Factor Programming
(See Programming Flow Chart, Page 10)
The average sensor K-Factor is usually provided in
pulses per unit volume, and will have to be modied before entering it into the instrument. On most ow-
meters, the average sensor K-Factor is stamped on the nameplate or provided on its documenta­tion. (see section 7 for Calculating K-Factors, for a complete example)
Count K-Factor:
The Count K-Factor must be modied to allow for
the decimal point location chosen in the ”DEC LOC“ step.
Sensor K-Factor
DPF
DPF - The Decimal Point Factor is a divider to com­pensate for the displayed decimal point.
DPF Table DPF Decimal
1 XXXXXX. 10 XXXXX.X 100 XXXX.XX
1000 XXX.XXX 10000 XX.XXXX 100000 X.XXXXX
Rate K-Factor: The Rate K-Factor must be determined to dis-
play the rate in the desired time unit. The oating decimal point displayed by the Rate Meter oats according to the signicant gure setting used in
the SIG FIG step.
Sensor K-Factor
Where: TF - The Time Factor is a divider to adjust the
time units that the Rate Meter shows.
TF Table TF Time Units Rate Display
1 Seconds Units per Second 60 Minutes Units per Minute 3600 Hours Units per Hour 86400 Days Units per Day
(For information on entering a K-Factor on a unit with 16 Point Linearization, see 16 Point Linear- ization Notes, page 11)
= Count K-Factor
= Rate K-Factor
TF
9
ENT
D
RATE
D
ENT
K-FACTO R
XXXX
CLR
WINDOWXX
CLR
S I GF I G X X
CLR
WE IGHTXX
LOCKOUT
ENT
D
SECUR XX
CLR
CODE
XXXX
CLR
UNIT X X
CLR
ALG OU T
OUTFREQ
ENT
D
ENT
D
D
ANLG RT↓ANLG CT
ENT
SE T LO W
XXXX
CLR
SET HIGH
D
2000 ↓200
ENT
20000
10
0
ENT
WINDOW00
ENT
S I G F I G 0 0
ENT
SECUR 00
ENT
0
UNIT 00
ENT
0
ENT
PLSE R
ENT
D
B
BAUDRATE
D
1200↓ 2400
600↓ 300
4800↓ 9600
COUNT
ENT
D
K-FACTO R
XXXX
CLR
R0 SP
ENT
D
B
D.E.C. . .L.O.C.
8 7 6 54 3 2 1
ENT
0
ENT
PRESET
ENT
D
XXXX
CLR
PREWARN
D
XXXX
CLR
ENT
PRE TYP
ENT
D
D
EZ PR E↓STD PRE
ENT
0
ENT
0
ENT
MENU
D
Run Mode
- On a Standard unit (Without 16 Point Linearization), the Count and/or the Rate must be programmed for basic operation.
§ - Sub menu will always appear, but feature may not be included in the unit. (Check Model Number).
Page
2, 24
§ Page
2, 23
§ Page 2, 21
Page 2, 19
Page 1, 17
Page 2, 15
Page 15
Page 1, 14
Page 1, 14
OUTCARD
CLR
XXXX
CLR
WEIGHT0 0
ENT
ENT
0
ENT
ENT
PARITY
D
ODD↓ MARK
ENT
EVEN
SPA CE
Software Version 8.8 Programming Flow Chart
10
3-5 VER 12.0 Programming
(Unit with 16 Point Linearization)
Overview:
This Section of the manual provides an outline of programming procedures for the software ver­sion 12.0. Detailed descriptions and programming instructions for this unit are available in the following sections of this manual. Page number references
are included to help you nd related information in
this manual.
3-6 VER 12.0 16 Point Linearization Notes (See Programming Flow Chart, Page 12)
A K-Factor and a Frequency must be entered for at least three points on a unit with Linearization.
Linearization K-Factor: The K-Factor for each
Linearization point must be modied to allow for the
display decimal point location chosen in the “DEC LOC” step of the “DEV TYP” menu. Modify each K-Factor using the following equation:
Programming Procedures:
Enter Program Mode - Press the MENU button,
“D”, in the Run Mode.
Choosing a Sub Menu - Once in the Program
Mode, continue pressing the “D” button until the desired Sub Menu is displayed. Press “ENT” to enter the selected Sub Menu.
Making a Selection - An arrow, “”, appearing over
only the “D” button indicates that “D” is used to change the selection. When an arrow appears over “B” and “D”, one must be selected.
Entering a Value - The keypad is used to enter a
number. Use the “D” button to enter a decimal. (Ex: 34.5 would be entered by pressing “3”, “4”, “D”, and “5”)
Accept a Value or Selection - Press “ENT” to ac-
cept the value and go to next step.
Exit Program Mode - Program or skip each step
of one of the menus to return to the Run Mode. Pressing “ENT” allows a step to be skipped with­out changing its value. (Note: “B” or “D” must be
pressed on the rst step in the DEV TYP menu)
K-Factor
DPF
DPF - The Decimal Point Factor is a divider to compensate for the displayed decimal point.
= Linearization K-Factor
DPF Table Desired Total Decimal Location: DPF
XXXXXX. 1 XXXXX.X 10 XXXX.XX 100 XXX.XXX 1000 XX.XXXX 10000 X.XXXXX 100000 Example: for X.X, DPF = 10
Calculating K-Factors and Frequencies: If a Linearization table is not available, the K-Factor and the frequency for each point can be calculated using the Test Mode on the unit. Refer to Section 7-3.2, Test Mode Operation and K-Factor Calculation, on page 37.
Key to Programming Flow Chart:
Display - This box represents the unit’s dis-
play. In the Run Mode, the ow rate, the batch
total, or the grand total will be displayed.
XX Current Value - The number that is currently
programmed for that step. It must be cleared (CLR button) before entering a new value.
00 No Value - Indicates that programmed value
for that step has been cleared, and a new number may be entered.
Keypad - Use the front panel keypad to enter
a value or select a decimal point location for this step.
Entering K-Factors and Frequencies: Refer to Section 7-3, Calculating 16 Point K-Factors, on page 37 and the programming step listing on page
25.
11
OUTCARD
ENT
D
LOCKOUT
ENT
D
UNIT X X
CLR
ALG OU T
OUTFREQ
ENT
D
ENT
D
D
ANLG RT↓ANLG CT
ENT
SE T LO W
XXXX
CLR
SET HIGH
XXXX
CLR
D
2000 ↓200
ENT
20000
10
UNIT 00
ENT
0
ENT
0
ENT
PLSE R
ENT
D
B
BAUDRATE
D
1200↓ 2400
ENT
600↓ 300
4800↓ 9600
PARITY
D
ODD↓ MARK
ENT
EVEN
SPA CE
PRESET
ENT
D
XXXX
CLR
PREWARN
D
XXXX
CLR
ENT
DEV TYP
ENT
D
0
ENT
0
ENT
MENU
D
Run Mode
Software Version 12.0 16 Point Linearization Programming Flow Chart
RT CNT
R0 SP
ENT
D
B
D.E.C. . .L.O.C.
8 7 6 54 3 2 1
ENT
D
B
WINDOWXX
CLR
S I GF I G X X
CLR
WINDOW00
ENT
S I G F I G 0 0
ENT
16 POINT
ENT
D
D
MINUTE S↓ HOURS
ENT
SECONDS
T EST
POINT 00
1
POINT 01
ENT
F XX
CLR
F 00
ENT
K XX
CLR
K 00
ENT
ENT
CLR
To Exit
Increment to next point (Ex. POINT 02, POINT 03, Etc.
- At least three points in the 16 Point Linearization sub menu must be programmed for basic operations.
Enter a Point # of “0” at any point to exit the 16 Point settupeep all data entered up to that point.
§ - Sub menu will always appear, but feature may not be included in the unit. (Check Model Number).
Do not use PL. Select SER.
CODE
XXXX
CLR
0
ENT
3-7
12
Loading...
+ 35 hidden pages