AMP-1-N
Features
• NAMUR Compatible Sensitivity.
•100 mA Current Sinking Output.
•11 to 26 VDC Power Supply Range.
• Easy Mount Metal Housing.
• Screw Terminal Hookup.
Preamplifier & Signal Conditioners
For NAMUR Sensors
Description
The KEP AMP-1-N powers and conditions the low
level signals from NAMUR pickups, sensing gear teeth
movement or flow, and provides a high level pulse
output suitable to drive any KEP ratemeter, counter or
controller.
Application
AMP-1-N
Specifications
Environmental
Operating temperature:32° to 140° F (0° to 60° C)
Storage temperature: -40° to +85° C
Humidity: 0 - 95% non-condensing
Power Input
Power requirement: 11-26VDC; 30mA maximum
Sensor Supply: 8VDC ± 1 VDC
Input Characteristics
Input impedance: 1000 ohm nominal
Input frequency : 0 - 10kHz
Input current: High: > 3mA
Low: < 1 mA
Output Characteristics
Output Type: Open collector with internal
2700 ohm pull-up resistor to
supply voltage.
Max. sink current: 100mA sink to 1V or less
Turbine Meter with
NAMUR Pickup
8 1 4 2 3 5
RST
A B C D
ENTER LOCK PRE A PRE B VIEW PRGM
Totalizer
E
Approvals:
CE approved; Light Industrial
Fast transient: 500V (capacitive clamp)
EMI: No effects at 3V/m
ESD: 8kV (case grounded)
Kessler-Ellis Products Co. 10 Industrial Way East, Eatontown, NJ 07724
Toll Free: 800-631-2165 • Phone: 732-935-1320 • Fax: 732-935-9344
99987 02/08/05
Installation
The AMP-1-N is mounted in a rugged 2" x 3" metal
housing with screw terminals for easy installation.
When installing the AMP-1-N the metal case housing
must be grounded.
All input and output connections should be run with
shielded cable. Connect cable shield to shield terminal of
AMP-1-N (TBI pin 1). The signal line from the NAMUR
pickup to the AMP-1-N must be less than 100 ft. in length,
shielded and separated from relays, solenoids or other
sources of electrical noise.
Sample Hookup :
Dimensions:
.67
(17)
.15
(3.8)
1.4
(35.6)
3.00
(76.2)
2.2
(55.9)
NAMUR
PICKUP
1 NC
2 INPUT
3 8 VDC
GEAR OR
TURBINE
WARRANTY
This product is warranted against defects in
materials and workmanship for a period of two
(2) years from the date of shipment to Buyer.
The Warranty is limited to repair or replacement of the defective unit at the option of the
manufacturer. This warranty is void if the product has been altered, misused, dismantled, or
otherwise abused.
TB1
AMP -1-N: Standard unit
TB2
3 OUTPUT
2 GND
1 11-26 VDC
@ 30 mA
SIMPLY ORDER:
ALL OTHER WARRANTIES, EXPRESSED
OR IMPLIED, ARE EXCLUDED, INCLUDING
BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
KESSLER-ELLIS PRODUCTS
10 Industrial Way East
Eatontown, NJ 07724
800-631-2165 732-935-1320
Fax 732-935-9344