O|L-F|REDCAST |RONSTF.AM
BO|
Installation
• Operation
• RepairParts
Theseinstructionsmustbeaffixedonoradjacenttotheboiler.DUNKIRKBOILERS
DUNKIRK,NEWYORK14048- 716366-5500
MEMBER: The llydronies Institute
I/2" NPT
TANKLESS
HEATER
, o i
F , t , t i
, t , * ,
3/4 _ NPT
_LOW UMIT
CONTROL ON
COIL PLATE
I/2" NPT
PRESSURETROL
PRESSURE GAUGE
COMBINATION
1-1/2" NPT
RETURN
2-I/2" NPT
SUPPLY
\
iq°p
5/4" ASNE
POP SAFETY
VALVE
i
T
27"
WATER
IJNE
i-i/2" NPT
i SKIM TAPPING
i
35
'L
_l
,-V2 ° NPTi
RETURN
LEFT SIDE
FRONT
REAR
EMPIRE OIL-FIRED STEAM BOILER RATINGS
BOILER MODEL NO.
With Without
Tankless Tankless
No.
9ec.
Coil Cotl
3ESt O0C 3ES100 3
3ES1.25C 3ES1,25 3
3ES1.35C 3ES1.35 3
4ES1,50C 4ES1,50 4
4ES1.75C 4ES1 75 4
4ES1.85C 4ES1.85 4
Input
*MBH
140
175
189
2!0
245
259
Nesting
Capacity
*MBH
118
145
156
177
204
215
* MBH = 1,000 BTUpet hour
BTUH = British Thermal Unit Per Hour
GPH _ Gallons per Hour Oil at 140,000 BTU per Gallon
** Heating Capacity is based on a 13% CO2 with a -,02' w.c, draft over fire, and a #1 smoke or less. The testing on the boilers
was done in accordance with lhe DOE. (Department of Energy) test procedure
NewYorkCityMEANumber134-98-E
Selectionofboilersizeshouldbe basedupon"Net1=8=RRatingbeing
equaltoorgreaterthanthesq.ft.of radiationalreadyinstalledinthe
building.
TheNetI=B=R Ratingsshownarebasedonanallowanceof1.333in
accordancewiththefactorsshownonthe 1=B=RStandardas publishedby
TheHydronicsInstitute.
Net
I=B-R
Rating
"MBH
89
109
117
133
153
161
Not I-S-R
Rating
Sq. Ft,
Radiation
371
454
488
554
638
671
*Tonldelm
Cell
Ratings
GPM*
2.75
3,10
3.25
3.50
3.85
4,00
Typl©al
Chimney
Size and
Height
8" x 8' x 15'
8" x 8' x 15'
8" x 8' x 15'
8' x 8' x 15'
8" x 8" x 15'
8" x 8' x 20'
Theseboilersmusthavea non-combustiblebaseifinstalledon acombustible
floor.Two-inchcladlitepadmaybeused.Theseboilersarelowpressure
sectionalcastironboilersconstructedandhydrostaticallytestedfora maximum
workingpressureof 15psiin accordancewithA.SME. (AmericanSocietyof
MechanicalEngineers)SectionIVStandardsfor castironheatingboilers.They
arecapacityratedinaccordancewiththecodeofthe1=B=R(Hydronics
Institute).
CIMF31SIONS- INCHES
A B C
16% 7 9
16½ 7 9
16% 7 9
20% 8 11
20% 8 11
20% 8 11
RulesforSafeInstallationandOperation
1. Readthe Owner'sManualforSafeOperationcarefully.Failuretofollow
therulesforsafeoperationandtheinstructionscancausea malfunctionof
the boilerand result in death,_rious bodily injury, and/or property
damage.
2. Checkyourlocalcodesandutilityrequirementsbeforeinstallation.The
installationmustbeinaccordancewiththeirdirectives,orfollowNFPA31
- InstallationofOilBurningEquipment,latestrevision.
3. Beforeservicing,allowboilertocool.Nwaysshutoffanyelectricityand
oiltoboilerwhenworkingonit.Thiswillpreventanyelectricalshocksor
burns.
4. Inspectoillineandconnectionsforleaks.
This boiler has been designed for residentialinstallations. If used for commercial
applications,alljurisdictionalrequirementsmustbe met.This mayrequirewiringandlor
pipingmodifications.Themanufactureris notresponsibleforany changesto the original
design.
5. Be certainoil burnernozzleis size required.Overfiringwill resultin
earlyfailureofthe boilersections.Thiswill causedangerousoperation.
6. Nevervent this boiler into an enclosedspace.Alwaysvent to the
outside.Neverventto anotherroomor insidea building.
7. Besurethereisadequateairsupplyforcompletecombustion.
8. Followa regutarserviceandmaintenancescheduleforefficientand
safeoperation.
9. Keepboilerareacleanandfreeofcombustiblematerial,gasolineand
otherflammablevaporsandliquids.
BeforeYouStart
Check to be sure you have the dght size boiler beforestartingthe
installation.See ratingand capacitytableon precedingpage.Checkthe
ratingplateontheboiler.
You mustsee that theboileris suppliedwiththe properoil,freshair for
combustion,and a suitableelectricalsupply.Also, the boiler must be
connectedto a suitableventingsystemand an adequatepipingsystem.
Finally,a thermostat,properlylocated,is neededforcontrolofthe heating
system.If youhaveanydoubtsas to thevariousrequirements,checkwith
local authorities and obtain professionalhelp where needed. THE
OPERATING INSTRUCTIONSand THE FINAL CHECKS AND
ADJUSTMENTSare vitalto the properandsafe operationof the heating
system.Takethetimeto besuretheyarealldone.
Thefollowingstepsareallnecessaryforproperinstallationandsafe
operationof yourboiler.
1. LOCATINGTHEBOILER
2. OILSUPPLYANDPIPING
3. FRESHAIR FORCOMBUSTION
4. PIPINGCONNECTIONS
5. CHIMNEY& VENTPIPECONNECTIONS
6. ELECTRICALWIRING
7. THERMOSTATLOCATION
8. CHECKING&ADJUSTING
9. MAINTENANCE
Locatingthe Boiler
If yourboileris partof a plannedheatingsystem,locateit as nearlyas
possiblewhereshownon yourplan.If boileris to be partof an existing
system,it is usuallybestto put it wherethe old onewas.If youplanto
changelocation,youwill needadditionalmaterialsaswellasan adequate
base.Thefollowingrulesapply:
1. The boilermustbelevelandlocatednearpiping.
2. Usea raisedbaseiff]oorcanbecomewetordamp.
3. Theventpipeconnectionshouldbeasshortaspossible.
4. Maintainclearancesforfiresafetyaswellasservicing.SeeFigure2for
minimumclearances.18"clearancemustbemaintainedatasidewhere
passageisrequiredforaccessto anothersidefor cleaning,servicing,
inspection,or replacementofanypartsthatnormallymayrequiresuch
attention.Boilersmustbe installedat least6"fromcombustiblematerial
onallsidesandabove.Allowat least24"frontclearancefor servicing.
Allowat least18"leftsideclearanceforservicingboilersequippedwith
atanklesscoil.
5. FRESHAIRfor combustionmustbeavailableatthefrontoftheboiler.
FRESHAIRfor ventilationmustbeavailabletothefrontANDrearof
theboiler.Airpassagesmustbefreeofobstructionsatalltimes.
Ventilatingandcombustionairmustenterboilerroomwithout
restrictions.
6. The floor suppo_ng the boiler must be non-combustible.If it is
combustible,placetheboileron 2" cladlitepad.Thepadmustbeunder
theentireboilertoprotectthefloor.
7. Besureinstallationisinaccordancewiththerequirementsofthelocal
authoritieshavingjurisdiction.Compliancewiththeseregulationsis
required.In theabsenceof localcodes,followNFPA31- Insbtlationof
OilBurningEquipment.
Q 6" MIN. 18" WITH COIL
• _
I_// . I BOILER
_" 6" MIN. "
I-----2, .,..------IFRO.T
6" MIN.
SeRVraceL_NeLL,.------e_.ec_rRic
F_LPtFE ] I I[ s_,rrc_
GENERAL PRINCIPAL REQUiREMEnTS FOR A TYPICAL INSTALLATION
m_
Fresh Air for Combustion
WARNING
Be sure to provide enough fresh airfor combustion. Enough air ensures
proper combustion and assures that no hazard will develop due to
the lackof oxygen.
You must providefor enough fresh air to assurepropercombustion.The fire
in the boiler uses oxygen. It must have a continuous supply. The air in a
house contains only enough oxygen to supply the burner for a short time.
Outside air must enter the house to replace that used by the burner. Study
foIIowingexampIes 1 and 2to determineyour fresh air requirements.
EXAMPLE 1:Boiler Located in Unconfined Space
If your boiler is in an open area (unpartitioned basement) ina conventional
house, the air that leaks through the cracks around doors and windows will
usually be adequate to provide air for combustion. The doors should not fit
tightly. Do not caulkthecracks aroundthe windows.
An unconfinedspace isdefined as aspace whose volume isnot lessthan 50
cubic feet per 1,000Btu per hour of the total inputrating of all appliances
installedin that space.
EXAMPLE 2: Boiler Located in Confined Space
A, All Air from Inside the Building: The confined space shall be provided
with two permanent openings communicating directly with an additional
room(s) of sufficientvolume so that the combined volume of all spaces
meets the criteria for an unconfined space. The total input of all
combustion equipment installed in the combined space shall be
considered in making this determination. Each opening shall have a
minimumfree area of one square inch per 1,000Btu per hourof thetotal
inputratingofall combustionequipment inthe confinedspace, but not less
than 100 squareinches. One opening shall be within 12 inches ofthe top
andonewithin 12 inchesof the bottom of theenclosure.See Figure 4.
Example: Your boiler is rated at 100,000 Btu per hour. The water heater
is rated at 30,000 Btu per hour. The total is 130,000 Btu per hour. You
need two grilles, each with 130 square inchesof FREE opening. Metal
grilles have about 60% FREE area. To find the Iouveredarea needed,
multiply the FREE area required by 1.7 (130 x 1.7 = 221.0 sq. in.
Iouvered area). In thisexample twogrilles, each having an 8"x 30" (240
sq.in,) Iouvered area would be used. Fig. 4 shows the grille locations.
B. All Air from Outdoors: The confined space shall be provided with two
permanent openings, one commencing within 12 inches of the top and
one commencing within 12 inches of the bottom of the enclosure. The
openings shall communicate directly, or by ducts, with the outdoors or
spaces (crawlor attic)thatfreely communicatewith the outdoors.
1.When directly communicatingwith the outdoors, each opening shall have
a minimum free area of one squareinchper 4,000 Btu per hour of total
inputratingof all equipment in theenclosure.
2. When communicatingwith the outdoors through ve_cal ducts, each
opening shall have a minimumfree areaof one square inch per 4,000
Btu perhour of total input ratingof all equipmentin theenclosure.
NOTE
If you use a fireplaceor a kitchenor bathroomexhaustfan,you
shouldinstallan outsideairintake.Thesedeviceswill robthe boiler
andwaterheaterof combustionair.
3.Whencommunicatingwiththeoutdoorsthroughhorizontalducts,each
openingshall havea minimumfreearea of onesquareinchper
2,000 Btu per hour of totalinput ratingof all equipmentin the
enclosure.
4. Whenductsareused,theyshallbeof thesamecross-sectionalarea
asthe freeareaof theopeningstowhichtheyconnect.Theminimum
dimensionofrectangularairductsshal{benotlessthanthreeinches.
VENTILATING -'_--i
GRII.LE I
i I ' 1
i ,11 II ',
AIR GRILLE _
Fresh Air Duct Capacities for Ducts Supplying Fresh Air to
boiler in tightly constructed houses. British Thermal Units per
hour Input (Btuh)*.
Fresh Air
Duct Size
31/2"x 12"
8* x 8"
8" x 12"
8" x 16"
*Based on opening covered by IA" mesh screen, wood louvers, or mela{ louvers
1/4"Mesh
Screen Btuh
144,000
256,000
384,000
512,0O0
Wood
Louvers Stuh
36,000
64,000
96,000
128,000
FRESH
Metal
Louvers Btuh
108,000
!92,000
288,000
384,000
Boilers With Tankless Heater Coil
Boilersmaybefactorypackagedwithatanklessheatercoil.Theuseof this
coileliminatesthe needforahot waterstoragetank.Instantaneousheatingof
waterinthecoil willprovidea flowof hotwaterfor domesticuse- ifproper
watersupplylinecontrolsareused.
IMPORTANT
Donot usea tanklesscoilif yourwateris excessivelyhardwithlimeor
otherdepositswhichwillaccumulateinsidethecoil.
Forsummerrunningwithcoilyou needtofill boilerwithwaterandaddthe
L6006limitcontrolto the coil.Thiswill maintainwatertemperaturein the
boilerand bringtheburneronwhennecessary.
TANKLESSCOlL PIPING
PipingisshowninFigure7B.A temperingvalve(mixingvalve)is
recommended.
LowLimit(whenused)- 140° F
Thesesettingscanbechangedafteryouhavesomeideahowthe system
responds.If moredomestichotwateris required,the lowlimitsettingcan
alsoberaised.
_NT_pERE_ _OT WATER
¢OL_ WATE_ _N_ET
WLV_