When IGBT-transistors G1 and G4 conduct, there is a positive voltage U
and when IGBT-transistors G2 and G3 conduct there is a negative voltage
Power is adjusted by changing the IGBT timings (PWM)
X9IGBT gates and emitters
X10IGBT gates and emitters
X11IGBT gates and emitters
X12IGBT gates and emitters
X13IGBT gates and emitters
X14IGBT gates and emitters
X15IGBT gates and emitters
X2
X1
Z001 connectors / signals
X16Primary choke
X17Primary choke
X18DC-link voltage (+)
X19DC-link voltage (+)
X20DC-link voltage (-)
X21DC-link voltage (-)
X29Chassis ground
X36Current transformer secondary
X37Current transformer secondary
X40Auxiliary transformer
X41Auxiliary transformer
H1-H4: Indicate the existence of the gate pulses.
H5, H6: Indicate that auxiliary voltages exist (+5V and +15V). If these Leds are not lit when the power source is
switched on, first thing to do is check if control card fuses are OK.
H7, H8: Indicate operation of the auxliary device connection. LED H8 indicates that there is data
communication taking place through the system bus when it is lit. LED H7 indicates that remote control unit is
connected when it is lit.
H9, H10: Indicate state of the microcontroller. In normal situation both leds should be lit.
22
Motor control card A002
X4
X3X1X2
Operating diagram
- WF-motor control
- Connection to the panel card P001
- Remote controller connection
- MIG gun connection
- Solenoid valve connection
-Fuse
- ID-Chip connection (MSF)
23
Motor control card A002 (A001 = MSF)
Connectors
A002 / X1 / KM
X1/1Connection to A001, X9/4
X1/4Connection to A001, X9/10
A001 / X1 / MSF
X1/1Bus +50V
X1/3Tacho +5V
X1/4Bus GND
X1/5Tacho GND
X1/6Tacho Signal
Err 2:Power source undervoltage ( new start up )
Err 3:Power source overvoltage ( new start up )
Err 4:Power source is overheated
Err 5:Water unit alarm
Err 11:Two units have the same address in the system bus
Err 12:Data error on communication (2)
Err 13:Member of a wrong FastMIG family connected
Err 14:Data communication problem between power source and auxiliary unit
Err 15:Power source program / updating method problem
Err 21:Power source´s control card +5 V aux. Voltage too low
Err 22:Power source´s control card +15 V aux. Voltage too low
Err 23:Temporarily power source overvoltage
Err 31:Power source calibration error. Welding only possible with default values.
Err 54:No data communication from power source. Perhaps faulty cable/connector.
Err 55:Welding forbidden (congiguration / system bus reserved)
Err 61:The water unit is not found. Cooling unit may be OFF.
Err 153:Overheating of liquid-cooled gun
Err 154:Wire feed motor overcurrent. Perhaps the wire liner is blocked or gun cable too curvy.
Err 155:Wire feed motor overload. Motor´s current is too close to the limit.
Err 161:Warning of the wire feed unit overheating
Err 162:Overloading of the wire feed motor
Err 171:Configuration of the equipment can not be found. Gun start wires cross-connected.
Err 172:Wrong configuration code has been supplied
Err 173:Operation is not activated with right configuration code
Err 184:Control cable not connected or faulty.
Err 185:Machine program update error. Wrong program or updating method.
Err 201:Usage of PMT-gun prevented
Err 221:Data error of the panel (1)
Err 222:Data error of the panel (2)
Err 223:Data error of the panel (3)
Err 224:Data error of the panel (4)
Err 225:Program updating problem.
Err 241:EEPROM is faulty
Err 251:DLI data communication error(another unit in the bus is using same code=conflict)
Err 252:DLI data error (2)
Err 254:DLI data communication error(connection to other units has been interrupted(maybe bad connectors or cable
damages)
Err 255:DLI data communication error(program update problem, maybe a wrong program version etc)
Err 999:Unidentified error (systembus has sent an error message not identified by the panel)
27
Setup menu
MF 29 / 33
FastMig Basic (MF) SETUP menu
SF 51, 52, 53, 54
Normal MIG
1-MIG
FR-MIG
All MIG
processes
MMA
FastMig Synergi c (MSF) setup menu
28
Wire feed speed calibration / KM
• In factory set Wfs is adjusted in the range of 4... 100 without any unit
• LED light and feed roll symbol tells that the parameter to be set is Wfs
• After Wfs Calibration m/min unit is displayed
• Drive filler wire through the MIG gun and contact tip
• Enter to User Setup Me nu by pressing SETUP button ( appr 5 s )
• Select the Calibration me nu ( CAL ) with left side potentiometer
• Select "Enter" ( Ent ) with right side potentiometer
• Approve your selection by pressing briefly REMOTE / LOCAL key
• Select 'm/min' as calibration value of the quantity with right side potentiometer
• Approve selection by pressing briefly REMOTE / LOCAL key
• Set first Calibration point (e.g. 2.0 m/min ) with left side potentiomet e r
1. Press MIG gun trigger and let the wire run until it stops automatically
2. Measure the length of feeded wire with the accuracy of 1 cm
3. Enter wire length to the panel display ( cm ) with right side potentiometer
4. Approve your selection by pressing briefly REMOTE / LOCAL button
• Set second Calibration point (e.g. 18.0 m/min )
• Repeat steps 1 - 4 with left side potentiometer
• Message "Suc cES" in the display inform that calibration has ended successfully
• After Calibration panel returns to the operation mode
29
Wire feed speed calibration
If wire feeding speed is not correct (too slow or too fast), motor
control card A002 must be calibrated by following instruction:
• Set ‘MIN’ and ‘MAX’ -trimmers to middle position.
• Set ‘IR-comp’ -trimmer to clock vice maximum.
• Set wire feeding speed to maximum from the panel (Basic: 100, Synergic: 25,0
m/min). Adjust ‘MAX’ –trimmer until wire feeding speed is same than value adjusted
from the panel.
• Set wire feeding speed to minimum from the panel (Basic: 4, Synergic: 1,0
m/min). Adjust ‘MIN’ –trimmer until wire feeding speed is same than value adjusted
from the panel.
• Check/adjust minimum and maximum again until both are OK.
• If adjustment range is too small, decrease IR -compensation and adjust minimum
and maximum again.
R87
max.
IR
comp
R24
min
30
Structure
KM / KMS
Mains connector
and
varistors
Z001
Main circuit board
Z002
DC-link
Capasitor board
S001
Main
switch
R001
Shunt
resistor
A001
Control card
P001
Panel card
A002 (KM)
Wire feed
control card
Water cooler
Power
connector
31
Structure
KM / KMS
T002
Auxiliary
transformer
L002
Secondary
choke
Capacitors and
varistors
L001
Choke
Z003
Secondary
rectifier diodes
32
Structure
MF 29 / 33
Dura Torque wire feeding mechanism
Control cable connector
& wiring
Solenoid valve
Axle for wire reel coop
Welding gun
connection
Welding current connector
& copper bar
Dura Torque wire feeding mechanism
33
Structure
MSF 53 / 55 / 57
A001
Motor control
card
A002
ID-chip
card
34
IGBT testing
B1/4
B2/6
X14
G3
X12
G1
X10
G4
X8
G2
C1/3
E2/2
X15
E3
X13
E1
X6
X7
X11
E4
X9
E2
C2E1/1
X6
X7
C1
E2
X15
X14/G3
X11/
X10/G4
X13
X12/G1
X9
X8/G2
B1/4
B2/6
X14
G3
X12
G1
X10
G4
X8
G2
C1/3
E2/2
X15
E3
X13
E1
X6
X7
X11
E4
X9
E2
C2E1/1
GCE
2
/
3
/
1
2
C
B2/6
I
T
G
O
F
F
O
N
R
C
O
N
T
R
O
L
B
1
T
-
T
E
S
T
T
R
E
2
R
E
C2E1/1
B1/4
35
IGBT replacing
Mounting the IGBT to the heat sink
The tools and premises used in this work must be clean and free of dirt and dust. Even very
small particles (0,050mm) between the surfaces may increase the gap between heatsink and
module, causing overheating ans possible damage.
Heat transfer compound is to be spread in even layer of approximately 0,1 mm onto the module
base. Then the module should be immediately mounted on the heatsink, in order to minimize
the possibility of dirt getting between the components.
Firts, all the M5 type screws are tightened 0,5...2 NM. After a few minutes the module can be
tightened into the torque of 3 NM.
36
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.