Keeprite ThermoSaver Installation Manual

ThermoSaver
02/12/10
Hot Gas
TM
PRODUCT DATA, APPLICATION & INSTALLATION GUIDE
Bulletin K40-THERM-PDI-13
1069130
Supplement to Condensing Unit Installation & Maintenance Manual
Defrost System
For use on select Air, Remote or Water-cooled Condensing Units matched with Low, Medium or High Prole Evaporators
R22 - R404A 2-30 HP
-30°F to +34°F Room Temperatures
CONTENTS PAGE
Application Guideline..............................
ThermoSaver Operation Cycle...............
Wiring Diagrams.....................................
Installation..............................................
ThermoSaver Control Settings...............
Troubleshooting Guide...........................
Service Parts List...................................
Warranty.................................................
2
3,4
5-7
8
8,9
10
11
BACK
● Provides fast, efcient evaporator
defrosting.
● Complete factory pre-piping of all controls and valves.
● Utilizes existing liquid line as hot gas pipe.
● Reduces installation time and provides maximum savings during operation.
● Ensures maximum compressor
protection using large capacity suction accumulator and outlet pressure regulating valve.
APPLICATION GUIDELINE
K40-THERM-PDI-13
- 2 -
02/12/10
ThermoSaver Hot Gas Defrost systems provide for a fast defrost alternative over comparable electric defrost systems. They can be used on any freezer or cooler application ranging in room temperatures from –30°F to 34°F, with capacity ranges of 2 – 30HP , available as an Indoor Air Cooled, Outdoor Air Cooled, Remote or Water Cooled Condensing unit.
The basic piping, layout and design concept are cov­ered in pages 3 and 4 of this manual. These should be reviewed rst to understand the refrigerant ow and to identify the special defrost components used.
Important design points are:
1. Concept is similar to a “three-pipe” hot gas bypass system yet only uses two pipes (shares the liquid line and reduces eld piping and labour cost). The main difference is the third shared pipe does not need to be oversized. During the initial hot gas cycle Liquid is fed rst, then a mixture, only at the latter part of the cycle is it all hot gas. (so high pressure drops are not
realized)
2. The defrost is very fast - less than 10 minutes and uses pressure controls (not temperature) for ter­mination and fan delay functions. (results in faster response time)
3. The evaporator used must be included together with the Condensing Unit (i.e. sold/supplied as a com­plete system package) as it must be properly select­ed and piped with the correct defrosting components. Line runs and sizes need to be reviewed. (keep within 100 feet) Electric heat drain pans (using time –delay relay function) are recommended in place of hot gas loops.
4. This unique defrost system can be used with either one or multiple evaporators (regardless of the ap­plication, freezer or cooler) and all can be defrosted at once.
5. There does exist added suction pressure drop across the outlet pressure regulator (CPR) and suction
accumulator so for load calculation purposes do not
undersize (keep adequate added safety margin).
6. Excessive system refrigerant charges (from long runs, oversized evaps, oversized receivers) must be avoided. During the latter portion of the defrost cycle and post defrost refrigeration cycle, refrigerant will ood back to the suction accumulator. Keeping the overall system charge low will reduce the amount of oodback.
To ensure maximum design benets:
1. Review the line runs and sizes (use short and properly sized liquid lines -do not oversize).
2. Use minimal refrigerant charge. Use only enough to satisfy the condenser ooding valve (low ambient control), receiver seal, liquid line and evaporator charge requirements.
3. Field adjust these ve critical defrost components to proper initial settings: (a) Outlet Press Regulator (CPR) Valve- Must be set
to the lowest possible setting (approx 10-15°F above evap temp design) without compromis­ing post defrost pull-down time. This valve is not primarily set for motor compressor motor overload protection, it’s main purpose is to keep a pressure differential during the defrost .
(b) Defrost Termination Control- Must not be set too
high. Keep to lowest possible setting (as soon as ice and frost has melted and pressure then starts to rise). Higher settings result in longer defrosts (over 10 minutes) and excessive oodback.
(c) Fan Delay Control- Must not be set too low (as
will promote ooding of the evap resulting in in­creased amount of refrigerant ood back after the defrost)
(d) Timeclock - Fail safe Time should not be set
greater than 20 minutes. If the defrost is taking too long then an issue exists with the control settings or application. (This must be identied and re­solved.)
(e) Time –Delay (Hot gas cycle) – Must be set at
least for two minutes (up to 5 min) in order to (i) pump out all remaining refrigerant in the evapora­tor and (ii) Pre-heat the drain pan prior to the hot gas entering the coil. This timer setting must be longer than the compressor anti-short cycle set­ting (if equipped)
Important initial set points are covered on pages 8 and 9 in this manual and must be followed. Further adjustments can then be made to suit local eld conditions.
THERMOSAVER OPERATION
K40-THERM-PDI-13
- 3 -
02/12/10
The ThermoSaver defrost cycle system provides a quicker defrost period (up to three times faster) over the conventional electric defrost system. This minimizes the rise in box temperature during the defrost which reduces product deterioration and increases the system efciency. This results in lower running times and reduced energy costs. When using more than one evaporator on the same condensing unit, all the evaporators can be defrosted simultaneously. All ThermoSaver components are completely factory installed, pre-piped and pre-wired. An extra third pipe (hot gas line) is not required.
REFRIGERATION
L M
Suction
Accumulator
Condenser
C
D
Compressor
This signicantly reduces the overall installation time and cost. Factory installed standard components include the evaporator distributor nozzle, thermostatic expansion valve (TXV), liquid line solenoid valve, hot gas solenoid valve, liquid check valves, three way solenoid valve, defrost regulating valve, suction accumulator, defrost termination / fan delay pressure controls and drain pan heater and timeclock. Room thermostat and suction lter are optional to be eld installed.
The following diagrams explain the ThermoSaver operation during both refrigeration and defrost cycles.
N
H
Filter
Evaporator
FB
Boil Out
Drier
Receiver
A - Room Thermostat B - Liquid Line Solenoid Valve C - Dual Hi / Lo Pressure Control
D - Three Way Hot Gas Solenoid Valve * E - Liquid Line Check Valve
* On larger (15 HP & up) systems, a separate N/O and N/C solenoid valve is used in place of 3-way valve
As the box temperature rises, the room thermostat (A) energizes the liquid line solenoid valve (B). This allows refrigerant to enter the evaporator, build up pressure, cause the low pressure control (C) to energize the compressor contactor and start the compressor. The compressor’s hot discharge gas is piped out to the condenser through the de-energized 3-Way valve (D). or seperate N/O and N/C solenoid valves. The hot refrigerant gas is condensed by the condenser. The liquid then ows to the receiver through the opened check valve (E) and on through the coiled liquid line within the suction accumulator (this performs the function as a suction to liquid heat-exchanger). The subcooled liquid then ows through the liquid line solenoid valve (energized/open) and on to the TXV (F) (Thermostatic expansion valve).
E
F - Thermostatic Expansion Valve H - Defrost Regulating Valve I - Timeclock
Heat Exchanger
I
LEGEND
The refrigerant is then directed through the distributor at a lower pressure and ows into the evaporator. The refrigerant liquid / vapour mixture is then boiled by the warmer box air from the evaporator fan. The refrigerant vapour then ows though a defrost regulating valve (H) preventing a motor overload from high suction pressures and enters the suction accumulator and on to the com­pressor.
The cycle continues until the room temperature is satis­ed. This de-energizes the liquid line solenoid, initiating a pumpdown cycle that reduces the suction pressure to the cut-out setting on the low pressure control which de-ener­gizes the compressor.
A
J - Drain Pan Heater K - Hot Gas Solenoid Valve L - Three Way Hi Pressure Control M - Defrost Termination Pressure Control N - Fan Delay Pressure Control
K
J
THERMOSAVER OPERATION
K40-THERM-PDI-13
- 4 -
02/12/10
DEFROST
C
Condenser
D
Compressor
L M
Suction
Accumulator
H
N
Evaporator
Filter
FB
Boil Out
Drier
Receiver
A - Room Thermostat B - Liquid Line Solenoid Valve C - Dual Hi / Lo Pressure Control
D - Three Way Hot Gas Solenoid Valve* E - Liquid Line Check Valve
* On larger (15 HP & up) systems, a separate N/O and N/C solenoid valve is used in place of 3-way valve
E
F - Thermostatic Expansion Valve H - Outlet Pressure Regulator I - Timeclock
Heat Exchanger
I
LEGEND
Third
K
A
J - Drain Pan Heater K - Hot Gas Solenoid Valve L - Three Way Hi Pressure Control M - Defrost Termination Pressure Control N - Fan Delay Pressure Control
Pipe
J
The refrigeration cycle results in frost formation on the surface of the evaporator. This frost will eventually build up to the point where it will restrict the air ow causing a loss of refrigeration capacity. To prevent this, a timeclock (I), usually set to repeat every 6 or 8 hours, initiates a defrost cycle which melts the frost.
The clock de-energizes (closes) the liquid line solenoid valve which causes the compressor to pumpdown and shut off from the low pressure control. The clock also energizes the drain pan heater (J) in the evaporator and timer relay which after a two or more minute delay ener­gizes (opens) the 3-way valve and hot gas solenoid valve (K) which then builds up pressure in the evaporator causing the low pressure control to close and start the compressor.
The hot discharge gas from the compressor ows through the 3-way valve forcing all the liquid left in the liquid line into the evaporator. If pressure builds up too high the 3-way valve safety pressure control (L) will de-energize the solenoid valve and allow pressure to relieve through the condenser.
Pressures within the evaporator will increase during the defrost. The outlet pressure regulator (H) maintains a de­sired pressure differential in the system, as well as reduc­ing the amount of liquid refrigerant back to the accumulator. The regulator also minimizes any high suction pressure avoiding compressor motor overloads.
Once all the frost has melted the pressure will con­tinue to rise until the defrost termination pressure control (M) energizes the timeclock’s internal sole­noid terminating the defrost cycle. The 3-way valve, hot gas valve solenoids are then de-energized. The liquid line solenoid valve opens and the compressor continues to run. The evaporator fans do not start up until the pressure in the evaporator is low enough to close the Fan delay control (N). By delaying the fans this allows any moisture left on the coil to drain away or freeze. As soon as the evaporator fans are energized the system will then resume back to the refrigeration cycle.
The cycle continues until the room temperature is satised. This de-energizes the liquid line solenoid, initiating a pumpdown cycle that reduces the suction pressure to the cut-out setting on the low pressure control which de-energizes the compressor.
Loading...
+ 8 hidden pages