KeepRite N4A3, H4A3, C4A3, T4A3, N4A4 Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
R410A Split System Air Conditioner
Model Series: N4A3, H4A3, C4A3, T4A3 N4A4, H4A4, C4A4, T4A4
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product.
DANGER Immediate hazards which will result in severe personal injury or death.
WARNING Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION Hazards or unsafe practices which may result in minor personal injury or product or
property damage.
NOTE Used to highlight suggestions which will result in enhanced installation, reliability, or
operation.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
WARNING
!
The signal word CAUTION is used throughout this manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures on product labels.
WARNING
CAUTION
TABLE OF CONTENTS
Inspect New Unit 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Considerations 2. . . . . . . . . . . . . . . . . . . . . . . . . . .
Location 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clearances 2 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Support 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigeration System 4 − 8. . . . . . . . . . . . . . . . . . . . . . . .
Electrical Wiring 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Startup Procedure 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Charge 10. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sequence of Operation 10. . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
R410A Quick Reference Guide 13. . . . . . . . . . . . . . . . .
!
DEATH, PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death.
Installation or repairs made by unqualified per­sons could result in equipment malfunction, prop­erty damage, personal injury and/or death.
The information contained in this manual is in­tended for use by a qualified service technician fa­miliar with safety procedures and equipped with the proper tools and test instruments.
Installation must conform with local building codes and with the National Electrical Code NFPA70 current edition or Canadian Electrical Code Part 1 CSA C.22.1.
WARNING
421 01 5100 01 October 2006
INSTALLATION INSTRUCTIONS R410A Split System Air Conditioner
INSPECT NEW UNIT
After uncrating unit, inspect thoroughly for hidden dam­age. If damage is found, notify the transportation compa­ny immediately and file a concealed damage claim.
SAFETY CONSIDERATIONS
Consult a qualified installer, service agency, or the dealer/ distributor for information and assistance. The qualified installer must use factory authorized kits and accessories when modifying this product. Refer to the individual in­structions packaged with the kit or accessory when instal­ling.
The weight of the product requires careful and proper handling procedures when lifting or moving to avoid per­sonal injury. Use care to avoid contact with sharp or pointed edges.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use a heat sinking material such as a wet rag − during brazing operations. Keep a fire extinguisher available. Consult local codes and the Na­tional Electric Code (NEC) for special requirements.
Improper installation, adjustment, alteration, service or maintenance can void the warranty.
!
ELECTRICAL SHOCK HAZARD
Failure to turn off the main (remote) electrical dis­connect device could result in personal injury or death.
Before installing, modifying or servicing system, turn OFF the main (remote) electrical disconnect device. There may be more than one disconnect device.
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in proper­ty damage
R410A systems operate at higher pressures than R22 systems. When working with R410A sys­tems, use only service equipment and replace­ment components specifically rated or approved for R−410A service.
WARNING
CAUTION
LOCATION
Check local codes for regulations concerning zoning, noise, platforms, and other issues.
Locate unit away from fresh air intakes, vents, or bed­room windows. Noise may carry into the openings and disturb people inside.
Locate unit in a well drained area, or support unit high enough so that water runoff will not enter the unit.
Locate unit away from areas where heat, lint, or exhaust fumes will be discharged onto unit (as from dryer vents).
CLEARANCES
Nominal minimum clearances are 48 inches above unit for discharge air and 18 inches on each side of the coil for intake air. Clearance on any one side of the coil (normally between unit and structure) may be reduced to 6 inches. Nominal minimum clearances are based on a solid paral­lel object such as a wall or roof overhang.
The clearance may be reduced for a single object with small surface area, such as the end of a wall, outside cor­ner of a wall, fence section, post, etc. As a general rule, the minimum clearance from the unit should equal the width of the object. For example, a 6 inch fence post should be a minimum of 6 inches from the unit.
Do not install unit under roof overhangs unless gutters are present. A minimum vertical clearance of 48 inches is re­quired to the overhang.
Locate unit away from recessed or confined areas where recirculation of discharge air may occur (refer to CLEAR­ANCES section of this document).
Rooftop installation is acceptable providing the roof will support the unit and provisions are made for water drain­age and noise/vibration dampening.
NOTE: Roof mounted units exposed to wind may require wind baffles. Consult the manufacturer for additional in­formation.
Inside corner locations on single story structures require evaluation. Large overhanging soffits may cause air recir­culation in a corner area even though recommended mini­mum clearances are maintained. As a guide, locate the unit far enough out so that half of the discharge grille is out from under the soffit.
When placing two or more units side−by−side, provide a minimum of 18 inches between units.
Provide minimum service clearance of 24 inches from control box corner and side service panel.
Refer to Figure 1.
2 421 01 5100 01
INSTALLATION INSTRUCTIONS R410A Split System Air Conditioner
Figure 1 Clearances (various examples)
24”
Service
Wall
6”
18”
Wall
6”
18”
18”
Wall
24”
Service
Wall
6”
18”
Wall
6”
24”
Service
18”
24”
Service
4”
18”
18”
4” wide fence
Wall
24”
Service
24”
Service
18”
18”
6”
6” Post
24”
Service
18”
421 01 5100 01 3
INSTALLATION INSTRUCTIONS R410A Split System Air Conditioner
UNIT SUPPORT
NOTE: Unit must be level 2 degrees ( inch rise or fall
per foot of run) or compressor may not function properly.
A. GROUND LEVEL INSTALLATION
The unit must be level and supported above grade by beams, platform, or a pad. Platform or pad can be of open or solid construction but should be of permanent materi­als such as concrete, bricks, blocks, steel, or pressure treated timbers approved for ground contact. Soil condi­tions must be considered so that the platform or pad does not shift or settle and leave the unit partially supported. Minimum pad dimensions are shown in Figure 2.
If beams or an open platform are used for support, it is recommended that the soil be treated or area be graveled to reduce the growth of grasses and weeds.
To minimize vibration or noise transmission, it is recom­mended that supports not be in contact with the building structure. However, slabs on grade constructions with an extended pad are normally acceptable.
B. ROOF TOP INSTALLATION
This type of installation is not recommended on wood frame structures where low noise levels are required.
Supporting structure or platform for the unit must be level. If installation is on a flat roof, locate unit minimum 6 inches above roof level.
Place the unit over one or more load bearing walls. If there are several units, mount them on platforms that are self supporting and span several load bearing walls. These suggestions are to minimize noise and vibration transmis­sion through the structure. If the structure is a home or apartment, avoid locating the unit over bedrooms or study.
NOTE: When unit is to be installed on a bonded guaran­teed roof, a release must be obtained from the building owner to free the installer from all liabilities.
C. FASTENING UNIT DOWN
If conditions or local codes require the unit be attached in place, remove the knockouts in the base pan and install tie down bolts through the holes (refer to Figure 2).
Contact local distributor for hurricane holddown details and the P.E. (Professional Engineer) certification, when required.
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in proper­ty damage.
Inadequate unit support may cause excessive vibration, noise, and/or stress on the refrigerant lines, leading to refrigerant line failure.
Figure 2 Tie Down Knockouts
A
Base Pan
Width x Depth
                
        
CAUTION
” dia. Tie Down Knockouts In Base Pan (2 places)
VIEW
FROM
TOP
Base Pan Width
Tie Down
Knockouts
A B C
Base
Pan
Depth
C
B
Minimum
Mounting Pad
Dimensions
REFRIGERATION SYSTEM
A. COMPONENT MATCHES
Check to see that the proper system components are in place, especially the indoor coil.
R410A outdoor units can only be used with R−410A spe- cific indoor coils. If there is a refrigerant mismatch, con­sult the indoor coil manufacturer to determine if a refrigerant conversion kit is available for the indoor coil.
This outdoor unit is designed for use only with indoor coils that utilize a hard shutoff TXV refrigerant metering de­vice. If any other type of metering device is installed on the indoor coil, consult the indoor coil manufacturer to de­termine if a hard shutoff TXV conversion kit is available.
4 421 01 5100 01
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product damage.
Indoor coil and outdoor unit must be listed as a certified combination (match) in the ARI Unitary Directory of Certified Products. Indoor coil must have R410A specific, hard shut off TXV refrigerant metering device.
CAUTION
Loading...
+ 9 hidden pages