KeepRite DLFCAB, DLFCHB, DLCCHR, DLFDAB, DLCDAR Installation Instruction

...
DLFCAB / DLCCAR / DLFCHB / DLCCHR DLFDAB / DLCDAR / DLFDHB / DLCDHR
High- Wall Ductless S plit Sys tem Sizes 09 - 36
Installation Instruction
NOTE: Read the entire instruction manual before starting the installation.
GENERAL 2.........................................
SYSTEM REQUIREMENTS 2...........................
Piping 2.........................................
DIMENSIONS- INDOOR 4.............................
DIMENSIONS- OUTDOOR 5...........................
CLEARANCES- INDOOR 8............................
CLEARANCES- OUTDOOR 8..........................
TABLE OF CONTENTS
PAGE
INSTALLATION GUIDE 9..............................
Install Mounting Plate 9.............................
Drill Hole in Wall for Interconnecting Piping, Drain
and Wiring 9.....................................
Piping Connections to Outdoor Unit 9.................
INSTALL ALL POWER, INTERCONNECTING WIRING AND
PIPING TO INDOOR UNIT 11..........................
SYSTEM VACUUM AND CHARGE 11...................
START- UP 13........................................
WIRING DIAGRAMS 14...............................
TROUBLESHOOTING 15..............................
The following parts are included in your indoor unit. Please contact your dealer if any parts are damaged or missing.
Tabl e 1—Pa rts L ist
Mounting Plate 1 Mounting Hardware 7 Remote Control 1 Remote Control Holder 1 Battery (1.5V) 2
Parts Qty
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start- up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and current editions of the National Electrical Code (NEC) NFPA 70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
!
Recognize safety information. This is the safety- alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety- alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be
.
a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start- up.
WARNING
CAUTION
GENERAL
These instructions cover the installation, start-up and servicing of outdoor and indoor units ductless systems.
SYSTEM REQUIREMENTS
Allow sufficient space for airflow and servicing unit. See Fig. 4 for minimum required distances between unit and walls or ceilings.
Piping
IMPORTANT: Both refrigerant lines must be insulated separately.
S Minimum refrigerant line length between the indoor and outdoor
units is 10 ft. (3 m).
S The following maximum lengths are allowed.
2
PIPING AND REFRIGERANT TABLES DLFCAB / DLCCAR / DLFCHB / DLCCHR
Table 2—Piping Information DLFCAB / DLCCAR / DLFCHB / DLCCHR
System Size 9K 12K 9K 12K 18K 24K 30K 36K
Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Min. Piping
Length
Standard
Piping Length
Max. Outdoor-
Indoor Height
Difference
Max. Piping
Length w/ No
Additional
Refrigerant
Charge
Max. Piping
Length
Gas Pipe
(size -
connection
type)
Liquid Pipe
(size -
connection
type)
System Size 9K 12K 9K 12K 18K 24K 30K 36K
Cooling
Only
Heat
Pump
ft 10 10 10 10 10 10 10 10
m 3 3 3 3 3 3 3 3
ft 25 25 25 25 25 25 25 25
m 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
ft 32.8 32.8 32.8 32.8 32.8 32.8 32.8 32.8
m 10 10 10 10 10 10 10 10
ft 25 25 25 25 25 25 25 25
m 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
ft 49.2 65.6 49.2 65.6 82 82 98.4 98.4
m 15 20 15 20 25 25 30 30
in 3/8 1/2 3/8 1/2 1/2 5/8 5/8 5/8
in 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Table 3— Refrigerant Information DLFCAB / DLCCAR / DLFCHB / DLCCHR
Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Refrigerant
Type
Charge
Amount
Additional
Refrigerant
Charge
(between Standard – Max Piping
Length)
Refrigerant
Type
Charge
Amount
Additional
Refrigerant
Charge
(between Standard – Max Piping
Length)
-- R410A R410A R410A R410A R410A R410A R410A R410A
Oz 42.3 47.6 45.9 47.6 56.4 81.1 84.66 84.7 Kg 1.2 1.35 1.3 1.35 1.6 2.3 2.4 2.4
Oz/ft 0.161 0.161 0.161 0.161 0.161 0.161 0.161 0.16
g/m 15 15 15 15 15 15 15 15
-- R410A R410A R410A R410A R410A R410A R410A R410A
Oz 42.3 47.6 45.9 47.6 56.4 77.6 84.66 91.7
kg 1.2 1.35 1.3 1.35 1.6 2.2 2.4 2.6
Oz/ft 0.215 0.215 0.215 0.215 0.161 0.538 0.538 0.54
g/m 20 20 20 20 15 50 50 50
3
PIPING AND REFRIGERANT TABLES DLFDAB / DLCDAR / DLFDHB / DLCDHR
Table 4— Piping Information DLFDAB / DLCDAR / DLFDHB / DLCDHR
System Size 9K 12K 9K 12K 18K 24K 30K* 36K*
Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Min. Piping
Length
Standard
Piping
Length
Max.
Outdoor-
Indoor
Height
Difference
Max. Piping
Length w/ No
Additional
Refrigerant
Charge
Max. Piping
Length
Gas Pipe
(size -
connection
type)
Liquid Pipe
(size -
connection
type)
Cooling
Only
Heat
Pump
NOTE: * Sizes 30 and 36 not available as Cooling Only.
ft 10 10 10 10 10 10 10 10
m 3 3 3 3 3 3 3 3
ft 25 25 25 25 25 25 25 25
m 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
ft 32.8 32.8 32.8 32.8 32.8 32.8 32.8 32.8
m 10 10 10 10 10 10 10 10
ft 25 25 25 25 25 25 25 25
m 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
ft 65.6 65.6 49.2 49.2 82 82 98.4 98.4
m 20 20 15 15 25 25 30 30
in 3/8 3/8 3/8 3/8 1/2 5/8 5/8 5/8
in 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Table 5—Refrigerant Information DLFDAB / DLCDAR / DLFDHB / DLCDHR
System Size 9K 12K 9K 12K 18K 24K 30K 36K*
Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Refrigerant
Type
Charge
Amount
Additional
Refrigerant
Charge
(between
Standard –
Max Piping
Length)
Refrigerant
Type
Charge
Amount
Additional
Refrigerant
Charge
(between Standard – Max Piping
Length)
-- R410A R410A R410A R410A R410A R410A
oz 26.5 31.8 24.7 30 35.3 56.45 kg 0.75 0.9 0.7 0.85 1 1.6
oz/ft 0.161 0.161 0.161 0.161 0.161 0.161
g/m 15 15 15 15 15 15
-- R410A R410A R410A R410A R410A R410A R410A R410A
oz 24.7 31.8 24.7 30 49.4 65.27 84.7 92 kg 0.7 0.9 0.7 0.85 1.4 1.85 2.4 3
oz/ft 0.215 0.215 0.215 0.215 0.215 0.538 0.54 1
g/m 20 20 20 20 20 50 50 50
4
All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively. Per caution note, only copper conductors with a minimum 300 volt rating and 2/64- - inch thick insulation must be used. The use of BX cable is not recommended.
Recommended Connection Method for Power Communication Wiring - Power and Communication W
The main power is supplied to the outdoor unit. The field supplied 14/3 power/communication wiring from the outdoor unit to indoor unit consists of four (4) wires and provides the power for the indoor unit. Two wires are high voltage AC power, one is communication wiring and the other is a ground wire.
Recommended Connection Method for Power Communication Wiring (To minimize communication interfer
ence)
Power Wiring:
The main power is supplied to the outdoor unit. The field supplied power wiring from the outdoor unit to indoor unit consists of three (3) wires and provides the power for the indoor unit. Two wires are high voltage AC power and one is a ground wire. To minimize voltage drop, the factory recommended wire size is 14/2 stranded with a ground.
Communication Wiring:
A separate shielded copper conductor only, with a minimum 300 volt rating and 2/64- inch thick insulation, must be used as the communication wire from the outdoor unit to the indoor unit. Please use a separate shielded 16GA stranded control wire.
and
iring:
and
wiring
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Wires should be sized based on NEC and local codes.
S Use copper conductors only with a minimum 300 volt
rating and 2/64 inch thick insulation.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring may
cause terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
S No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S Disconnecting means must be provided and shall be
located within sight and readily accessible from the air conditioner.
S Connecting cable with conduit shall be routed through
hole in the conduit panel.
CAUTION
CAUTION
Table 6—Electrical Data
DLFCAB - DLCCAR / DLFCHB - DLCCHR
System Size 9K 12K 9K 12K 18K 24K 30K 36K
Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
MCA A 12 17 9 9 16 20 20 24
MOCP A 20 25 15 15 25 30 30 40
Table 7—Electrical Data
DLFDAB - DLCDAR / DLFDHB - DLCDHR
System Size 9K 12K 9K 12K 18K 24K 30K 36K
Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
MCA A 17 20 9 9 16 15 20 24
MOCP A 25 30 15 15 25 25 30 40
5
DIMENSIONS - INDOOR
Fig. 1 - Indoor Unit Dimensions
Table 8—DLFCAB / DLCCAR / DLFCHB / DLCCHR
System Size 9K 12K 9K 12K 18K 24K 30K 36K Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Height (H) in 11.4 11.4 11.4 11.4 11.8 12.8 12.8 12.8 Width (W) in 33.3 33.3 33.3 33.3 38.2 42.4 53.1 53.1
Depth (D) in 8.2 8.2 8.2 8.2 8.8 9.7 10 10
Weight-Net lbs 23.2 23.2 22.1 22.1 27.6 34.2 41.9 41.9
Table 9—DLFDAB / DLCDAR / DLFDHB / DLCDHR
System Size 9K 12K 9K 12K 18K 24K 30K* 36K* Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Height (H) in 10.8 11.4 10.8 11.4 11.8 12.8 12.8 12.8 Width (W) in 31.1 33.3 31.1 33.3 38.2 42.4 53.1 53.1
Depth (D) in 7.9 8.2 7.9 8.2 8.8 9.7 10 10
Weight-Net lbs 19.8 22.1 19.8 23.2 29.8 37.5 41.9 41.9
A
B
C
D
E
F
D
E
H
Fig. 2 - Indoor Mounting Plate
Table 10—DLFCAB / DLCCAR / DLFCHB / DLCCHR
System Size 9K 12K 9K 12K 18K 24K 30K 36K Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
A in 4.7 4.7 4.7 4.7 4.0 8.1 13.8 13.8
B in 21.3 21.3 21.3 21.3 27.0 27.0 29.4 29.4 C in 7.3 7.3 7.3 7.3 7.2 7.3 10.0 10.0 D in 2.2 2.2 2.2 2.2 2.2 2.8 2.8 2.8
E in 1.4 1.4 1.4 1.4 1.5 1.7 1.6 1.6
F in 5.0 5.0 5.0 5.0 7.5 6.0 11.6 11.6 H in 3.3 3.3 3.3 3.3 5.5 3.1 3.5 3.5
Table 11—DLFDAB / DLCDAR / DLFDHB / DLCDHR
System Size 9K 12K 9K 12K 18K 24K 30K* 36K* Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
A in 6.6 4.7 6.6 4.7 4.0 8.1 13.8 13.8
B in 18.2 21.3 18.2 21.3 27.0 27.0 29.4 29.4 C in 6.3 7.3 6.3 7.3 7.2 7.3 10.0 10.0 D in 2.2 2.2 2.2 2.2 2.2 2.8 2.8 2.8
E in 2.1 1.4 2.1 1.4 1.5 1.7 1.6 1.6
F in 6.0 5.0 6.0 5.0 7.5 6.0 11.6 11.6 H in 3.5 3.3 3.5 3.3 5.5 3.1 3.5 3.5
NOTE: * Sizes 30 and 36 not available as Cooling Only.
6
DIMENSIONS - OUTDOOR
M
N
H
W
D
P
S
Fig. 3 - Outdoor Unit
Table 12—DLFCAB / DLCCAR / DLFCHB / DLCCHR
System Size 9K 12K 9K 12K 18K 24K 30K 36K Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Height (H) in 21.3 23.3 21.3 23.3 27.6 31.1 31.1 31.1 Width (W) in 33.4 33.4 33.4 33.4 37.6 38.6 38.6 38.6
Depth (D) in 12.6 12.6 12.6 12.6 15.6 16.8 16.8 16.8
M in 10.0 10.0 10.0 10.0 13.4 14.6 14.6 14.6 N in 30.0 30.0 30.0 30.0 35.0 36.2 36.2 36.2
P in 21.3 21.3 21.3 21.3 22.0 24.0 24.0 24.0
S in 11.3 11.3 11.3 11.3 14.3 15.6 15.6 15.6
NET Weight
Cooling
Only
NET Weight
Heat Pump
lbs 62.8 73.9 72.8 80.5 113.6 147.7 152.1 154.4
lbs 71.7 77.2 78.3 86 114.7 142.2 154.4 161
Table 13—DLFDAB / DLCDAR / DLFDHB / DLCDHR
System Size 9K 12K 9K 12K 18K 24K 30K* 36K*
Voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Height (H) in 21.3 21.3 21.3 21.3 27.6 27.6 Width (W) in 30.6 30.6 30.6 30.6 37.6 37.6
Depth (D) in 12.6 12.6 12.6 12.6 15.6 15.6
M in 10.1 10.1 10.1 10.1 13.4 13.4 14.6 14.6 N in 28.0 28.0 28.0 28.0 35.0 35.0 36.2 36.2
P in 20.0 20.0 20.0 20.0 22.0 22.0 24.0 24.0
S in 11.3 11.3 11.3 11.3 14.3 14.3 15.6 15.6
NET Weight
Cooling
Only
NET Weight
Heat Pump
lbs 59.5 63.9 66.2 70.6 90.4 103.6
lbs 62.8 67.3 65.0 69.5 95.9 110.3 154.4 161.0
NOTE: * Sizes 30 and 36 not available as Cooling Only.
7
CLEARANCES - INDOOR
"
5
(0.13m)
min.
CEILING
6" (0.15m) min.
(1.8m)
6'
FLOOR
Fig. 4 - Indoor Unit Clearances
5
"
(0.13m)
min.
CLEARANCES - OUTDOOR
A
D
UNIT
A 24 (609) B 24 (609) C 24 (609) D 4 (101) E 4 (101)
B
Fig. 5 - Outdoor Unit Clearances
Table 14—Outdoor Clearances
Air-inlet
E
C
Air-outlet
Minimum Value in. (mm)
8
INSTALLATION GUIDE
Ideal installation locations include:
Indoor
Unit
S A location where there are no obstacles near inlet and outlet area. S A location which can bear the weight of indoor unit. S Do not install indoor units near a direct source of heat such as
direct sunlight or a heating appliance.
S A location which provides appropriate clearances as outlined in
Fig. 4. Be sure to leave enough distance to allow access for routine maintenance. The installation site should be 72” or more above the floor.
S Select a place away from potential electronic interference. S Select a place where the filter can be easily removed.
Outdoor
S A location which is convenient to installation and not exposed to
S A location which can bear the weight of outdoor unit and where
S A location which provides appropriate clearances as outlined in
S Do not install the indoor or outdoor units in a location with
S Make sure the outdoor unit is installed in accordance with the
S See the refrigerant piping table for the maximum height
Unit
strong wind.
the outdoor unit can be mounted in a level position.
Fig. 4.
special environmental conditions.
installation instructions and is convenient for maintenance and repair.
difference between indoor and outdoor units and the maximum length of the connecting tubing.
INDOOR UNIT INSTALLATION
INSTALL MOUNTING PLATE
1. Carefully remove the mounting plate from the unit box.
2. The mounting plate should be located horizontally and level on the wall. All minimum spacings shown in Fig. 2.
3. If the wall is block, brick, concrete or similar material, drill .2” (5 mm) diameter holes and insert anchors for the appropriate mounting screws.
4. Attach the mounting plate to the wall.
DRILL HOLE IN WALL FOR INTERCONNECTING PIPING, DRAIN AND WIRING
Refrigerant Line Routing
The refrigerant lines may be routed in any of the four directions showninFig.6.
For maximum serviceability, it is recommended to have refrigerant line flare connections and the drain connection on the outside of the wall that the fan coil is mounted on.
rear left.
left
rear right
right
Fig. 6 - Refrigerant Line Routing
rear left
A12585
If piping is going through the back:
1. Determine pipe hole position using the mounting plate as a template. Drill pipe hole diameter per chart below. The outside pipe hole is 1/2- in. (13 mm) min. lower than inside pipe hole, so it slants slightly downward. If piping is going to exit from the left rear, it is recommended to field-fabricate piping extensions to get the flare connections to the outside of the wall.
1/2 in. (13 mm)
Min.
INDOOR
Fig. 8 - Drill Holes
Table 15—Hole Diameter
Model Size
9K, 12K, 18K , 24K 2.2 (56)
30K & 36K 2.75 (70)
If piping is going through the right or left side:
1. Use a small saw blade to carefully remove the corresponding plastic covering on side panel and drill the appropriate size hole where the pipe is going through the wall. See Fig. 14.
2. Remove knockout (see Fig. 7).
NOTE: If required, a condensate pump is available for the application.
OUTDOOR
A07371
Hole Diameter
in. (mm)
OUTDOOR UNIT INSTALLATION
1. Use a rigid base to support unit in a level position.
2. Locate outdoor unit and connect piping and wiring.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Excessive torque can break flare nut depending on installation conditions.
Piping Connections to Outdoor
IMPORTANT: Use refrigeration grade tubing ONL Y. No other type of tubing may be used. Use of other types of tubing will void manufacturer’s warranty. Make sure there is enough piping to cover the required length between the outdoor and indoor unit. Only use piping suitable for high side pressure for both high side and low side connections.
CAUTION
Unit
left right
cut off the hole
Fig. 7 - Refrigerant Line Routing
9
Piping Guide:
S Do not open service valves or remove protective caps from
tubing ends until all the connections are made.
S Bend tubing with bending tools to avoid kinks and flat spots. S Keep the tubing free of dirt, sand, moisture, and other
contaminants to avoid damaging the refrigerant system.
S Avoid sags in the suction line to prevent the formation of oil traps.
Insulate each tube with minimum 3/8- in. (10 mm) wall thermal pipe insulation. Inserting the tubing into the insulation before making the connections saves time and improves installation quality.
1. Remove service valve cover if provided with unit.
2. Cut tubing with tubing cutter.
3. Install correct size flare nut onto tubing and make flare connection.
4. Apply a small amount of refrigerant oil to the flare connection on the tubing.
5. Properly align tubing in with service valve.
6. Tighten flare nut and finish installation using two wrenches asshowninFig.9.
Outdoor Unit Wiring
Connections
1. Mount outdoor power disconnect.
2. Run power wiring from main box to disconnect per NEC and local codes. Set outdoor unit in place.
3. Remove field wiring cover from unit by removing screws.
4. Connect conduit to the conduit panel. (See Fig. 11)
5. Properly connect both power supply and control lines to terminal block per the connection diagram.
6. Ground unit in accordance with NEC and local electrical codes.
7. Use lock nuts to secure conduit.
8. Reinstall field wiring cover.
Field Wiring Cover
Conduit Panel
Fig. 9 - Tighten Flare Nut
Strong
wind
Fig. 10 - High Wind Installation
A07354
A07350
lock nut
conduit
Finish
Fig. 11 - Field Wiring
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
S Be sure to comply with local codes while running wire
from indoor unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring may
cause terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
S No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S Disconnecting means must be provided and shall be
located within sight and readily accessible from the air conditioner.
S Connecting cable with conduit shall be routed through
hole in the conduit panel.
A12539
10
INSTALL ALL POWER, INTERCONNECTING WIRING, AND PIPING TO INDOOR UNIT
1. Run interconnecting piping and wiring from outdoor unit to indoor unit.
2. Pass interconnecting cable through hole in wall (outside to inside).
3. Lift indoor unit into position and route piping and drain through hole in wall (inside to outside). Fit interconnecting wiring into back side of indoor unit.
4. Hang indoor unit on upper hooks of wall mounting plate (as shown in Fig. 12 and Fig. 15).
left right
cut off the hole
Fig. 14 - Remove Knockouts
Fixing hook
Mounting
plate
Fig. 15 - Hang Indoor Unit
Mounting plate
A12408
A08283
Fig. 12 - Hanging Indoor Unit
5. Open front cover of indoor unit and remove field wiring ter­minal block cover (see Fig. 13).
Field Wiring
Cover
Interconnecting Cable
A08279
Fig. 13 - Field Wiring Cover
6. Pull interconnecting wire up from back of indoor unit and position in close to the terminal block on indoor unit.
7. Push bottom of indoor unit onto mounting plate to complete wall mount.
8. Connect wiring from outdoor unit per connection diagram (see Fig. 21).
NOTE: Polarity of power wires must match original connection on outdoor unit.
9. Replace field wiring cover and close front cover of indoor unit.
10. Connect refrigerant piping and drain line outside of indoor unit. Refer to Fig. 9 for proper installation of flare connections. Complete pipe insulation at flare connection then fasten piping and wiring to the wall as required. Completely seal the hole in the wall.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined below is followed. Always break a vacuum with dry nitrogen.
CAUTION
SYSTEM VACUUM AND CHARGE
Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D, connect manifold gage charge hose to a charge port of the low side service valve (see Fig. 16.)
2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage. (See Fig. 17)
4. Start vacuum pump
5. Evacuate using either deep vacuum or triple evacuation method.
6. After evacuation is complete, fully close the low side of manifold gage and stop operation of vacuum pump.
7. The factory charge contained in the outdoor unit is good for up to 25 ft. (8 m) of line length. For refrigerant lines longer than 25 ft (8 m), add 0.2 oz. per foot of extra piping up to the maximum allowable length.
8. Disconnect charge hose from charge connection of the low side service valve.
9. Fully open service valves B and A.
10. Securely tighten caps of service valves.
11
Outdoor Unit
t
Service Valve
Refrigerant
Low Side
A
High Side
B
Indoor Uni
C
D
A07360
Fig. 16 - Service Valve
Manifold Gage
500 microns
Low side valve
Charge hose
Low side valve
High side valve
Charge hose
Vacuum pump
A07361
Fig. 17 - Manifold
Deep Vacuum
Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 18)
5000 4500 4000 3500 3000
LEAK IN SYSTEM
2500 2000
MICRONS
1500 1000
500
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
Triple Evacuation
Method
The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercury vacuum and system does not contain any liquid water. Refer to Fig. 19 and proceed as follows:
1. Pump system down to 28 in. of mercury and allow pump to continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr. During this time, dry nitrogen will be able to diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 19. The system is then free of any contaminants and water vapor.
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM
A95425
Fig. 19 - Triple Evacuation Method
Final Tubing
Check
IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
01234567
MINUTES
Fig. 18 - Deep Vacuum Graph
A95424
12
START- UP
Tes t Operation
Perform test operation after completing gas leak and electrical safety check.
1. Push the “ON/OFF” button on Remote Control to begin testing.
NOTE: A protection feature prevents the air conditioner from being activated for approximately 3 minutes.
2. Push MODE button, select COOLING, HEATING, FAN mode to check if all functions work correctly.
SYSTEM CHECKS
1. Conceal the tubing where possible.
2. Make sure that the drain tube slopes downward along its entire length.
3. Ensure all tubing and connections are properly insulated.
4. Fasten tubes to the outside wall, when possible.
5. Seal the hole through which the cables and tubing pass.
INDOOR UNIT
1. Do all Remote Control buttons function properly?
2. Do the display panel lights work properly?
3. Does the air deflection louver function properly?
4. Does the drain work?
OUTDOOR UNIT
1. Are there unusual noises or vibrations during operation?
Explain Following Items To Customer With The Aid Of The Owner’s Manual:
1. How to turn air conditioner on and off; selecting COOLING, HEATING and other operating modes; setting a desired temperature; setting the timer to automatically start and stop air conditioner operation; and all other features of the Remote Control and display panel.
2. How to remove and clean the air filter.
3. How to set air deflection louver.
4. Explain care and maintenance.
5. Present the Owner’s Manual and installation instructions to customer.
INSTALLATION AND MAINTENANCE OF FILTER
1. Grasp the front panel by its two ends and lift the panel and then remove the air filter.
2. Install a clean air filter along the arrow direction and close the panel.
Air filter
Auxiliary filter
A12541
Fig. 20 - Install Air Filter
13
Power to
Indoor Unit
Outdoor
Unit
Terminal
Block
Control to
Indoor Unit
Power to
Indoor Unit
Power to
Indoor Unit
Control to
Indoor Unit
Main Power
Supply
Power to
Indoor Unit
WIRING DIAGRAMS
DLF/DLC*09&12J 115-1-60 Connection Diagram
CONNECTING CABLE
OUTDOOR TO INDOOR
CAUTION
CAUTION
Atte nti on
Use Coppe r Conduc tor s O nly
Use Coppe r Conduc tor s O nly With Minimum 300 Volt,2/64"
With Minimum 300 Volt,2/64" Thick Insulation.
Main Power
Supply
Ground
Thick Insulation.
Utilisez seulement des
Utilisez seulement des conducteurs en cuivre d'un
conducteurs en cuivre d'un minimum de 3 00 volt d'une
minimum de 3 00 volt d'une isolationd' èpaisseur de 2/64".
isolationd' èpaisseur de 2/64".
Fig. 21 - 09K & 12K 115V Unit Wiring Diagrams
DLF/DLC*09&12K 208/230-1-60 Connection Diagram
CONNECTING CABLE
OUTDOOR TO INDOOR
CAUTION
Att ent ion
Use Copper Conductor s Only With Minimum 300 Volt, 2/64"
Ground
Thick Insula tion.
Utilisez seulement des conducteurs en cuivre d'un minimum de 300 volt d'une isolation d' èpaisseur de 2/64" .
Atte nti on
Power from
Outdoor
Unit
Power from
Outdoor
Control
from
Outdoor
Unit
Unit
Control
from
Outdoor
Unit
Power from
Outdoor
Unit
06-1-032/802CDVwoL06-1-032/802CDVwoL
Power from
Outdoor
DNG'1LS'2LDNG'1LS'2L
Ground
Unit
DNG'LS'NDNGNL'LS'N
Ground
06-1-511CDVwoL06-1-51106-1-51106-1-51106-1-511CDVwoL06-1-511
kcolBlanimreTtinUroodnIJ21&90*FLDkcolBlanimreTtinUroodtuOJ21&90*CLD
Indoor
Unit
Terminal
Block
L2 L1 GND
Main Power
Supply
208/230-1-60 208/230-1-60
Main Power
Supply
Ground
Fig. 22 - 09K & 12K 208/230V Unit Wiring Diagrams
DLF/DLC*18-36 208/230-1-60 Connection Diagram
CONNECTING CABLE
OUTDOOR TO INDOOR
CAUTION
CAUTION
Use Copper Conduct ors O nly
Use Copper Conduct ors O nly With Minimum 300 Volt,2/64"
With Minimum 300 Volt,2/64" Thick Insulation.
Power to
Indoor Unit
Control to
Indoor Unit
Power to
Indoor Unit
Main Power
Supply
Main Power
Supply
Ground
Thick Insulation.
Utili sez se ule me nt d es
Utili sez se ule me nt d es conduct eurs en c uivre d' un
conduct eurs en c uivre d' un minimum de 300 voltd'une
minimum de 300 voltd'une isolat ion d' è paiss eur de 2/6 4".
isolat ion d' è paiss eur de 2/6 4".
Fig. 23 - 18K & 36K 208/230V Unit Wiring Diagrams
NOTE: Polarity of power wires must match original connection on outdoor unit.
Attention
Attention
Power from
Outdoor
Unit
Control
from
Outdoor
Unit
Power from
Outdoor
Unit
DNG'1LS'2LDNG2L1L'1LS'2L
Ground
06-1-032/802CDVwoL06-1-032/80206-1-032/80206-1-032/80206-1-032/802CDVwoL06-1-032/802
kcolBlanimreTtinUroodnI63-81*FLDkcolBlanimreTtinUroodtuO63-81*CLD
14
TROUBLESHOOTING
This unit has on- board diagnostics. Error codes appear on the LED display on the front panel of the indoor unit in place of the temperature display. Error codes are also displayed on the outdoor unit microprocessor board with colored LED lights. The table below explains the error codes for both units.
Table 16—Diagnostic Codes
Display of lamp (the times of blinking)
Malfunction Display of
indoor unit
Anti-freezingprotection E2 2 3 BlockorLow pressure of refrigerant system E3 3 9 Compressor exhaust high temperature protection E4 4 7 AC over-current protection E5 5 5
Communication failure between indoor unit and outdoor unit E6 6 O/U
Anti-high temperature protection
No feedback of indoor fan motor H6 11 Jumper cap malfunction protection C5 15 Indoor unit and outdoor unit doesn't match LP 19 16 Outdoor DC fan motor malfunction L3 23 14 Power protection L9 20 9
Gathering refrigerant Fo 1 1
Indoor ambient sensor open or short circuit F1 1
Indoor tube sensor open or short circuit F2 2 Outdoor ambient sensor open or short circuit F3 3 6 Outdoor tube sensor open or short circuit F4 4 5 Exhaust sensor open or short circuit F5 5 7 Overload limit / drop frequency F6 6 3 Over current limit / drop frequency F8 8 1 High exhaust temperature limit / drop frequency F9 9 2 Refrigerant leakage protection F0 10 9 Anti-freezing limit / drop frequency FH 2 2 4 Defrosting H1 1 2 Compressor overload protection H3 3 8 IPM protection H5 5 4 Module temperature is too high H5 5 10 PFC protection HC 6 14 Loading EEPROM malfunction EE 15 11 High PN voltage protection PH 11 13 Low PN voltage protection PL 21 12 4-way valve reversal abnormal U7 20 DRED1 / DRED2 / DRED3 d1/d2/d3 Compressor Min frequence in test state P0 Compressor rated frequence in test state P1 Compressor maximum frequence in test state P2 Compressor intermediate frequence in test state P3 Compressor is running(normal) 1 The temperature for turning on the unit is reached (normal) 8
Frequency limiting (module temperature) EU 6 6 11 Frequency limiting (power) LU 24 13
E8 8 6 H4 4 6
Indoor Outdoor
R C H Y R G
Notes: R(Indoor)--Running C--Cooling H--Heating Y--Yellow R(Outdoor)--Red G--Green
O/U--OFF or Unblink The display difference between Fo and F0 is 'o' is the bottom part of figure 8
15
Copyright 2015 International Comfort Products Lewisburg, TN 37091 USA
Manufacturer reserves the right to change, at any time, specifications and designs without notic e and without obligations.
Edition Date: 06/15
Catalog No:42101942000
Replaces: NEW
16
Loading...