KaVo EWL 4452 Operating Instructions Manual

Page 1
Operating Instructions
Frequency inverter type EWL 4452
1.000.3172
WHD Ge/Fk
03/01
KaVo Elektrotechnisches Werk GmbH
Wangener Straße 78 D-88299 Leutkirch Tel.: 0 7561 / 86-0 • Fax: 0 7561 / 86-371
STOP
START
Typ 4452
Page 2
Page 3
Table of contents
1
A 1 User information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
A 1.1 Meaning of the pictograms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
A 1.2 Important information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
A 1.3 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
A 1.4 Purpose and potential applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
A 1.5 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
A 2 Scope of delivery - Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
A 2.1 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
A 2.2 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
A 3 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
A 3.1 Rating plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
A 4 Description of functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
A 4.1 Three-phase asynchronous motor (ASM) . . . . . . . . . . . . . . . . . . . . . . . . . 10
A 4.2 Brushless DC motor without sensor (BLDC) . . . . . . . . . . . . . . . . . . . . . . . 10
A 4.3 Brushless DC motor with position sensors (BLDCS) . . . . . . . . . . . . . . . . . 10
A 4.4 Remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
A 4.5 Motor code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
A 4.6 Setpoint value selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
A 4.7 Motor emergency stop at mains failure . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
A 4.8 Speed sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
A 4.9 Counterclockwise operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
A 4.10 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
B 1 Assembly and installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
B 1.1 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
B 1.2 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
B 1.3 Wiring guidelines for compliance with the EMC standard . . . . . . . . . . . . . 17
B 1.4 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
B 2 Fast commissioning, the most important aspects in brief . . . . . . . . . . . . . . 21
B 2.1 Connecting the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
B 2.2 Establishing factory default . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
B 2.3 Setting motor parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
B 2.4 Setting remote control parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
B 2.5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
B 2.6 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
B 3 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
B 3.1 Commissioning parameters, examples . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
B 3.2 Examples of configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
B 3.3 Special functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
B 3.4 SP1 - Store and recall motor parameters . . . . . . . . . . . . . . . . . . . . . . . . . 29
B 3.5 SP2 - Test remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
B 3.6 SP3 - Reset parameter to factory default. . . . . . . . . . . . . . . . . . . . . . . . . . 30
B 3.7 SP4 - TKD test programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
B 3.8 Parameter list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
B 3.9 Description of the individual parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 33
B 3.10 Default parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
B 3.11 Display values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
B 3.12 Motor operating values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
B 3.13 Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
B 3.14 Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
B 3.15 Nominal motor values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
B 3.16 Device parameters, remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
B 4 Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
B 4.1 Hold function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
B 4.2 Error on motor control, can be influenced by operator . . . . . . . . . . . . . . . 52
B 4.3 Error on control, can be influenced by operator . . . . . . . . . . . . . . . . . . . . 52
B 4.4 Electronics error on motor control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
B 4.5 Electronics error on control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
B 4.6 Description of all errors and warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Customer settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Page 4
2
User information
A 1 User information A 1.1 Meaning of the pictograms
Situation which may lead to danger, damage to material or operating faults in the event of failure to follow the instructions.
Important information for operator and engineer.
Automatic mode Automatic sequence
Close, screw in, fasten, etc.
Open, slacken, loosen
+ more, higher
- less, lower
Continuous operation
Time, time sequence
Disconnect mains plug
A 1.2 Important information
The User Manual must be read by the user/operator prior to commissioning, in order to avoid incorrect operation and other damage. If further language versions are required, please request them from your
responsible KaVo agent. Duplication and distribution of the User Manual (UM) require prior consent from KaVo.
All technical data, information and properties of the product described in this UM correspond to the state on going to press.
Modications and improvements to the product on the basis of new technical developments are possible. This does not imply any right to retrofitting of existing devices. KaVo assumes no responsibility for damage arising through:
external influences (poor quality of the media or poor installation)
use of incorrect information
improper use
improperly performed repairs.
Repair and maintenance work - except for the activities described in this User Manual - may be performed only by qualified specialists.
In the event of modifications by third parties, the approvals shall become null and void. KaVo recommends using only original spare parts for operation and for repair.
For safety reasons, the inverter supplied has not been configured.
Since it is not known which motor will be connected, an incorrect configuration could damage or destroy the motor or the inverter. In order to configure the inverter, please read Section B2 Fast commissioning.
Page 5
User information
3
A 1.3 Precautions
Safe operation and protection of the device is ensured only by proper use, in accordance with the User Manual, with the tools approved for this purpose. The following should also be observed:
the work safety regulations,
the accident prevention regulations.
Before installation and commissioning of this device, please read this safety and warning information carefully and observe all warning signs mounted on the device.
The frequency inverter type 4452 controls dangerously rotating mechanical parts and generates dangerous electrical voltages. If these operating instructions are not followed, severe damage to property, injuries and even death may result.
Safe operation of this device depends on the proper installation, handling and operation of the device.
Only appropriately qualified personnel may put this device into operation, maintain it and work on it.
Connection, commissioning and rectification of faults may be performed only by specialists.
The device has no mains switch.When working on the open device, it must be completely disconnected from the mains beforehand.The device has no mains input fuses.
The capacitor of the DC voltage intermediate circuit remains charged with dangerously high voltage for some time even after the mains voltage has been switched off.It is essential to wait for two minutes after switching off the mains voltage before opening the device.
This device may start up automatically with certain settings after a mains failure.
This device may not be used as an “emergency stop mechanism”(see EN 60204).
The device may be used only for the purpose intended by the manufacturer.Unauthorized modifications and
the use of additional equipment not recommended by the manufacturer can cause fires, electric shocks and injuries.
Definitions ASM motor
3-phase asynchronous motor
BLDC- 3-phase brushless DC motor without position sensors Motor The inverter performs the position synthesis by measuring the motor voltage (e.m.f.).
BLDCS- 3-phase brushless DC motor with position sensors Motor
EEPROM Electrically Erasable Program Memory. In the EEPROM, all important alterable data (parame-
ters, calibration values) of the frequency inverter type 4452 are stored, and the data remain stored even during a voltage failure.
Danger In the context of this User Manual and of the warnings mounted on the device, this means
that death, serious injury or considerable damage to property may occur if the corresponding precautions are not taken.
Note In the context of this User Manual, a note constitutes important information which is of particu-
lar importance for the understanding and the operation of the device.
Combi display Combination display consisting of motor parameter memory, motor frequency or speed, motor
voltage and motor current. The motor parameter memory is displayed only with active motor code or after recall or storing of the motor parameters. With parameter P8, it is possible to switch between frequency display and speed display.
Microstep With microstep startup, the BLDC motor is operated as a synchronous motor with constant startup current. The output frequency is slowly increased from 0 Hz to the startup frequency, after
which the system switches to regulated motor running. The microstep startup permits startup of sensor-free BLDC motor with large centrifugal masses (e.g. vacuum pumps) for which the normal startup fails owing to the large mass moment of inertia.
Page 6
User information
Normal If no error occurs after switching on, the standard display appears on the LCD display state H1 and the LED H3 Operation (green) lights up. This machine state is called the normal
state. By repeatedly pressing the key
!(cancel, transfer), it is possible to exit the state and
return to it.
Configuration Configuration is the operating procedure for setting up the inverter for use, motor settings and
device-specific settings being implemented via the control panel. It is also possible to display different measured values.
Qualified are in the context of this User Manual persons who are familiar with the installation, assembly, personnel commissioning and operation of the product and with the possible dangers.
Standard With parameter P4-display, the value or the value combination (combi display) which display is displayed in the normal state can be selected. This is the standard display.
Caution In the context of the User Manual and of the warning signs mounted on the device, this
means that slight injury or damage to property may occur if the corresponding precautions are not taken.
Warning In the context of the User Manual and of the warning signs mounted on the device, this
means that death, serious injury and considerable damage to property may occur if the corre­sponding precautions are not taken.
A 1.4 Purpose and potential applications
KaVo EWL frequency inverters, type 4452, have been specially constructed for the operation of three-phase asynchronous motors (ASM) and brushless DC motors (BLDC), as used in spindles, e.g. for grinding, cutting and drilling units on machine tools. They can also be used for operating motors which are constructed from motor elements and serve, for example, as a drive for test stands or other physical equipment (e.g. vacuum pumps, centrifuges, optical systems etc.). Gentle operation of the motors is achieved by the pulse amplitude modulation (PAM) used.
Specifically, the following motor types can be operated:
- Asynchronous motors (ASM)
- Brushless DC motors without sensors (BLDC)
- Brushless DC motors with sensors (BLDCS) Switching to the various motor types is performed without hardware or software replacement but only by chang-
ing the operating parameters. An integrated load compensation offers high speed constancy and - through low idling currents - avoids unnec-
essary heating up of the connected motors. At the stop command, the connected motor is braked until it stops. The control and monitoring of the inverter are performed by several microprocessors. This ensures high reliabili-
ty and flexibility. A firmware update can be performed on a PC via a serial interface (RS232); contact KaVo-EWL in this context. The inverter can be completely remote-controlled. Various inputs and outputs are freely programmable. The inverter is cooled by an integrated fan.
4
Page 7
User information
5
A 1.5 Technical data
Operation Menu-controlled with plain text display with two lines of 16 characters each, four keys for
menu control, one start key, one stop key, indicator lamps for operation (green), overload (yel­low), fault (red) and start (green). All inverter parameters can be input and changed on the control panel.
Display all parameter settings and operating procedures can be displayed in plain text in various
languages on the LCD display
Dimensions approx. 134 mm wide, 350 mm high, 238 mm deep, as built-in switch cabinet housing
(incl. mounting bracket) Operating temperature 0 ... 40°C Humidity of the air: lower than 90 % relative humidity, non-condensating Weight approx. 7.2 kg Tests and standards TÜV tested according to EN 50178
EMC according to EN 61800-3 Ingress protection IP20 according to DIN 40050
Power unit
Electrical connection single-phase 200...240V~, 50/60 Hz Current consumption 16A~ Output power max. 2500 VAcontinuous operation Output voltage 3 * 220 V~ at 8 A Output current max. 8A~ per phase, continuous operation (< 1 minute: max. 12A~) Output frequency 30 ... 3000 Hz for ASM motors (180.000 min
-1
)
30 ... 2000 Hz for BLDC motors (120.000 min
-1
) Braking resistance internal 80 W
external (option): rated resistance 27 ... 100 ; power 150 ... 1000 W
Efficiency 93 % (at 2500 VA, cos phi motor 86 %)
Motor sensors
Motor temperature sensor PTC (cold conductor) according to DIN 44081 Initial resistance Rk < 550 Tripping resistance (warm): Ra >= 1350 Tripping temperature: depending on PTC, 90...130°C Operating voltage: 12V, via 2200 pullup resistance Recommended Type PTC: Siemens+Matsushita M1100 B59100-M90-A70 Recommended Type KTY: Semiconductor sensor KTY84, cut-out threshold configurable
Hall sensor connection, motor code and speed sensor (option): Ouptut voltage: 12V -10% Output current: max. 100mA Signal level: active low Switching current: Is = 15mA Pullup resistance: internal 3 time R = 2200
All connections at the 6-pin terminal X7 are based on the negative potential of the intermediate circuit volt­age, i.e. not isolated from the mains potential.
Page 8
User information
Remote control
The function of the programmable inputs and outputs is described under Description of function A4.4. Digital control inputs
FB_IN1 ... 6 opto-decoupled, Re = 10 k, unwired=low
U_low = 0...+5 V, U_high = +13...+35V, Ie = 2.4 mA at 24 V
Input protected up to max. ± 35V, minimum pulse width 60 ms. FB_C_IN Reference point of digital inputs Relay switching outputs
FB-REL1 ... 3 Contact type: normally open contact, max. 25V~, 1A, max. 30V-, 1A
min. switching current 1 mA at 24V (10 mA at 10 V))
The contact is open in the currentless state FB_REL4 Contact type: change-over contact, max. 25V~, 1A, max. 30V-, 1A
min. switching current 1 mA at 24V (10 mA at 10 V) FB-C-REL common connection of relays REL1 to REL4
Analogue inputs FB-AIN1 ... 2 Ue = 0...10V, Re 100k, Ie = 0.1mA at 10 V,
unwired 0V, input protected up to max. ± 40V Analogue outputs
FB-AOUT1 ... 2 Ua = 0...10V, Iout = max. 10mA
Output short-circuit-proof Frequency output
FB-OUT-FREQ 3 times output frequency of the inverter, pulse duty factor 50%
open collector, U_max = 24V, I_max = 30 mA Supply and auxiliary voltages
FB+10V Uout = 10V +-3%, Iout = max.15mA,
short-circuit-proof I_k = max. 40mA FB+24V (X4-18) +24V -15...+5%, I_a = 0...80mA,
short-circuit-proof I_k = max. 300mA FB-GND Earth reference point for FB+10V, FB+24V
analogue inputs and outputs and frequency output Earth Flange of X4 earth connection for screening the control lines,
connected internally to PE (protective conductor)
All connections to the 25-pole jack X4 are potentially isolated from the control and relative to the protective
conductor up to max. 60 V DC or 25V AC.The analogue connections and the reference voltage output are based on the operating voltage output FB-GND, and the digital inputs are independently electrically isolated, as are the relay outputs.
6
Page 9
Scope of delivery - Accessories
A 2 Scope of delivery - Accessories A 2.1 Scope of delivery
Frequency inverter type 4452 Mat. No. 0.641.7700
Mounting plate for mounting switch cabinet (mounted on the inverter)
Instructions for use and assembly
25-pin Sub-D plug with solder connection, Mat. No. 0.223.1634, and metallized housing, incl. screw union, Mat.
No. 1.000.2790. (Omitted in the case of delivery of the connection adapter accessory, Mat. No. 1.000.2811).
A 2.2 Accessories
Connection adapter for 25-pin Sub-D plug with screw connection, incl. metallized housing and screw union, Mat. No. 1.000.2811.
Mains cable with safety plug for Germany, length 2 m, Mat. No. 1.000.3263
STOP
START
Typ 4452
Gebrauchsanweisung
SF-Umrichter 4452
STOP
ST A R T
Typ 4452
7
Page 10
Controls
A 3 Controls
STOP
STAR
T
H3 H2 H5
H1
S6
S8S12 S11 S10 S9
LED Betrieb/ LED Warnung/ LED Störung/ Operation Warning Fault grün/green gelb/yellow rot/red
Abbruch, unten/ oben/ Enter, Eingabe Stop Weiterschaltung/ down up Abspeichern/ Cancel, transfer Enter, input, save
LED Start grün/green
LCD-Anzeige/ LCD-display 16 Zeichen x 2 Zeilen 16 characters x 2 lines
Start
8
Page 11
Controls
A 3.1 Rating plate
The device has been tested for conformity with the requirements of the European standards by the TÜV product service. EN 50178 : 1997 Report No.: 014 100 56 208
KaVo ELEKTROTECHNISCHES WERK GMBH D-88299 Leutkirch im Allgäu
S-No.
Type EWL 4452 No. 0.641.7700 230 V~ 50/60 Hz 16 A
Made in Germany
Hersteller/ manufacturer
Gerätetyp/ Device type
Seriennummer/ Serial number
Warnhinweis: Begleitpapiere beachten/ Warning: see accompanying documents
CE-Kennzeichnung/ CE mark
Stromaufnahme/ Current consumption
Max. mögl. Gerät-V er­sorgungsspannung (diese
Angabe ist länder­spezifisch und kann von der Abbildung abweichen) Max. possible device supply voltage (this is country-specific and may differ from the Figure)
TÜV-Zeichen/ TÜV symbol
9
Page 12
Description of functions
A 4 Description of functions
The max. output frequency is 3000 Hz (180 000 min-1) for ASM motors and 2000 Hz for DC motors. The max. output power is 2.5 kVA.
The frequency inverter type 4452 is suitable for the variable-frequency control of various motors, especially with high frequencies of up to 3 kHz, corresponding to 180,000 min
-1
. The output voltage is set via a pulse amplitude
modulation (PAM) with 120° blocks.
A 4.1 Three-phase asynchronous motor (ASM)
Three-phase asynchronous motors (ASM) are controlled by means of pulse amplitude modulation (PAM). The voltage/frequency table serves as a basis for determining the motor voltage. Various control procedures are available for compensating speed changes under load. Specifically, these are IR and load compensation, slip compensation and speed regulation.
A 4.2 Brushless DC motor without sensors (BLDC)
Brushless DC motors have a pemanent magnet rotor and a fixed three-phase winding. The winding is preferably designed as an air-gap winding with yoke, but a grooved version similar to an ASM motor is also possible. The motor is controlled as a function of the rotor position. The rotor position is simulated by the inverter by measuring the e.m.f. voltage from the three part-windings. No position sensors are required. In order to permit measurement of the e.m.f. voltage, the motor inductance may not be too large.
A 4.3 Brushless DC motor with position sensors (BLDCS)
The design of this motor is identical to that of the BLDC motor described above. For position detection, however, 3 additional Hall sensors are installed in the motor. This motor design is not supported in the basic version of the frequency inverter type 4452, and a firmware update is required for this purpose.
A 4.4 Remote control
The voltages at the remote control plug may be max. 60 V DC or 25V AC according to SELV (EN50178). All connections are potentially isolated from the control and with respect to the protective conductor. The remote control provides a large number of programmable inputs and outputs:
6 digital inputs opto-decoupled, PLC-compatible (24 V). The inputs IN1 ... IN4 are programmable with the parameters
P110-input IN1 ... P113-input IN4. The inputs IN5 and IN6 are reserved for the selection of the
fixed frequencies (see Section A4.6) 4 relay outputs
(potential-free max. 25 V~, 30 V- / 1 A) for outputting various status signals (see parameter
P120-relay REL1 ... P123-relay REL4)
2 analogue inputs (0 ... 10V) for the functions of speed setpoint default and torque default. The programming is performed with the parameters
P130-analogue-AIN1 and P131-analogue-AIN2.(see Section A4.6)
2 analogue outputs (0 ... 10V) for outputting various analogue signals. The programming is performed with the parameters
P132-analogue-AOU1 and P133-analogue -AOU2.
1 frequency output (open collector, max 24V) with 3 times the inverter output frequency.
10
Page 13
Description of functions
2 auxiliary voltages +24 V (max. 80 mA) for wiring of the digital inputs IN1...IN6 and of the relay outputs REL1...REL4 +10 V (max. 15 mA) as auxiliary supply from external potentiometers to the analogue inputs AIN1 and AIN2
The function of the outputs (4 relay and 2 analogue outputs) is predetermined directly by the corresponding parameters. In order that the inputs perform the function prescribed in the parameters, parameter
P7-select func. should be set to remote con. or parallel.
Ansteuerung ohne Fremdspannung Control without external voltage
FB-REL1
FB-REL2
FB-REL3
FB+24V
FB-GND
FB-C-REL
R1
2k
R2
2k
FB-C-IN
FB-IN6
FB-IN3
FB-IN4
FB-IN5
LED2
LED1
FB-REL4-OE
FB-REL4-S
FB-OUT-FREQ
LED3
R5
2k
R3
2k
R4
2k
LED5
LED4
_
2k
Umrichter 4452 / Inverter 4452 Fernbedienung / remote control
FB-IN1
FB-IN2
FB-AGND
FB-AOUT2
FB-AOUT1
X4 D-Sub 25
FB+10V
FB-AIN1
FB-AIN2
11
Page 14
Description of functions
Ansteuerung mit Fremdspannung Control with external voltage
FB-C-REL
FB-GND
FB+24V
FB-REL3
FB-REL2
FB-REL1
FB-IN5
FB-IN4
FB-IN3
FB-IN6
FB-C-IN
FB-REL4-OE
FB-REL4-S
FB-OUT-FREQ
_
2k
Umrichter 4452 / Inverter 4452 Fernbedienung / remote control
FB-AIN2
FB-AIN1
FB+10V
FB-AOUT1
FB-AOUT2
FB-AGND
FB-IN2
FB-IN1
X4 D-Sub 25
12
Page 15
Description of functions
A 4.5 Motor code
The frequency inverter type 4452 can adapt automatically to up to 8 different motors via three code inputs at X7. The code inputs can be predetermined directly via the motor plug or by a superior control.
The code inputs at X7 are based on motor potential, i.e. not isolated from the mains potential. In the case of a PLC control, a relay should be connected between PLC and inverter for the potential isolation.
By means of parameter
P102-motor coding, the coding is switched on and the number of motors used is
input. In parameter
P20-motor code, the current state of the coding inputs and of the assigned motor
memory is displayed. If the state of the coding inputs changes, the corresponding motor parameters are loaded from memories M1...M8 (see Section B 3.4 SP1 - store and recall motor parameters). The motor coding can be changed only when the motor is stationary. Only the coding inputs H1...H3 actually required are evaluated, and inputs not required are ignored. A motor coding of up to 4 motors can be used in the case of motors with speed sensor; motor coding of up to 8 motors cannot be used simultaneously with a speed sensor since the two functions share the input H1, see
P20-motor code.
Coding Coding Coding Code value Assigned input input input in motor H1 (X7.3) H2 (X7.4) H3 (X7.5) P20-motor code parameter memory
HHH C1 M1 HLH C2 M2 HHL C3 M3 HLL C4 M4 LHH C5 M5 LLH C6 M6 LHL C7 M7 LLL C8 M8
L = low voltage 0..4V (contact closed), H = high voltage, 8...12V (contact open)
Achtung: Anschlüsse sind nicht potentialgetrennt vom Leistungsteil Note: Connections are not potentially isolated from the power unit
X7.4
H2
X7.5
X7.6
H3
PGND (Masse Leistungsteil/ Power unit Ground)
Umrichter Typ EWL 4452/ Inverter type EWL 4452
X7.3
externer Anschluß/ external connection
H1
13
Page 16
Description of functions
A 4.6 Setpoint value selection
The frequency setpoint value (speed setpoint value) can be predetermined by various sources, and the mode of operation is shown in the following figure.
If parameter
P7-select func. is set to Panel, the speed setpoint value of P1-f-rated is used, and
the analogue setpoint value at AIN1 and the fixed frequencies have no function. If P7-select func. is set to
remote control, the setpoint value is used in the following sequence: fixed
frequency, then analogue input. If one of the parameters
P111 ... P113 is set to fixfreq.on, the corre-
sponding input IN2 ... IN4 must be actuated in order that the fixed frequency FF1 ... FF4 selected by IN5 and IN6 is active. Otherwise, the analogue input AIN1 is used, and parameter
P130-analogue AIN1 must be
set to
rated frequency.
If P7-select func. is set to parallel, the setpoint value selection is performed in the following sequence: fixed frequency, analogue input and control panel.
A 4.7 Emergency motor stop at mains failure
With parameter P58-emerg.stop, the inverter can be set so that a running motor is automatically braked in the event of failure or if the mains voltage falls below the threshold value of approx. 150 V. The inverter supplies itself from the motor voltage still present, and braking is performed with maximum power of the brake resistance. The motor generally cannot be braked to a stop since the motor voltage is no longer sufficient for supplying the inverter. If an emergency stop occurs as a result of a brief drop in mains voltage, the motor is braked to a stop. In order to start the motor again, the operator must first input a stop command followed by a start command.
A 4.8 Speed sensor
For the ASM motor, an external speed sensor can be connected and the number of pulses per revolution can be configured in the range 1...10 with
parameter P59-speedsensor. The measured actual speed is displayed in P14-f_motor. The speed sensor is used for detecting motor stoppage (f < 1Hz, see status signals P120-RELx...), for the catch circuit (see P50-motor start) and for the speed regulation (see
P70-control).
The speed sensor and the motor coding for up to 4 motors can be used simultaneously. Motor coding for up to 8 motors cannot be used simultaneously with a speed sensor since both functions share the input H1 (see
P20-motor code).
A 4.9 Counterclockwise operation
In standard operation, the inverter operates electrically clockwise. With one of the parameters P111-input IN2 to P113-input IN4, a digital input can be configured for counterclockwise operation. If the corresponding input is supplied with voltage, the direction of rotation changes to
counterclockwise. If the direction of
rotation is switched while the motor is running, the motor is first braked before it is powered up again in the altered direction of rotation.
00
Auswahl Festfrequenz IN5,6/ Selection of fixed frequency IN5,6
11
01
10
Umrechnung/ Conversion
U_e in f_soll/ V_e into f_rated
P104-Fest(fix)freq.FF1
P105-Fest(fix)freq.FF2 P106-Fest(fix)freq.FF3
P107-Fest(fix)freq.FF4
P135-f_fern(rem)_min
P136-f_fern(rem)_max
Sollwert von Bedienpanel/ Setpoint value of control panel
P1-f_soll(rated)
Analog-Eingang/ Analogue input AIN1 0 ... 10 V
P7-Betriebsart P7-select func.
P111 ... P113 Festfreq. ein UND
Eingang INx high/ Fixed frequency on AND input INx high
Sollwert an Motorsteuerung/ Setpoint value on motor cont.
P130-Analog AIN1
Panel
Fernbed. remote
P10-f_soll_akt P10-f_rated-act
14
Page 17
Description of functions
A 4.10 Block diagram
=
~
Leistungsteil power PCB
~ ~
EMV-Filter EMC filter
Motorsteuerung und Regelung motor control
X6
FB-REL3
FB-REL4-OE
FB-REL4-S
FB-C-REL
X7
PTC
PGND
P+12V
H1
H2
H3
X1
N
L1
X2
W
V
PE
PE
U
X3
PE
Motor 3
Bediensteuerung panel control unit
Bedieneinheit control panel
FB+10V
X4
RXD-F
TXD-F
+7V-F
X5
RS232 9 pol. / 9 pin
FB-IN5
FB-IN4
FB-IN3
FB-IN2
FB-IN1
FB-C-IN
FB-IN6
FB-REL1
FB-REL2
FB-AGND
FB-AOUT2
FB-AOUT1
FB-AIN1
FB-AIN2
FB-OUT-FREQ
FB+24V
FB-GND
15
Page 18
Assembly/Installation
B 1 Assembly and Installation
Before the installation and commissioning of this device, please read the safety and warning information under Section A1 carefully.
B 1.1 Assembly
The frequency inverter type 4452 should be mounted as follows in the switch cabinet: Fasten the mounting plate to the back panel of the switch cabinet by means of four screws. Ensure good electrical contact with the protective conductor!
Information on cooling
The inverter is cooled by an integral fan.To ensure effective cooling, at least the following clearances must
be maintained around the inverter: End surfaces: 30 mm Longitudinal surfaces:10 mm
STOP
ST
AR
T
Typ 4452
10
mm
10
mm
100
mm
30 mm
133 mm
238 mm
30
mm
350 mm
STOP
ST
ART
T
yp 4452
325,2 mm
113 mm
16
Page 19
Assembly/Installation
B 1.2 Electrical Installation
When installing the inverter, the applicable safety regulations must be observed. Cut-out devices for
preventing unexpected start-up must be provided. A device for the electrical isolation of the inverter must be provided unless a mains cable with a plug is used.The inverter must be provided with 16 A power cut-outs with tripping characteristic B.
For connection of the mains and motor connections, unscrew the small sheet metal cover of the connection compartment (2 screws). Disconnect the protective conductor cable. The connection is performed as described below. After connection is complete, reconnect the protective conductor cable and screw back the sheet metal cover.
B 1.3 Wiring guidelines for compliance with the EMC standards
The inverter was tested according to EMC product standard EN 61800-3 (variable-speed electrical drives).
The above-mentioned EMC product standard can be complied with only by means of shielded motor and
control cables. It should be ensured that the cable shields rest over a large area of the inverter housing and are surrounded by the cable clips.A shielded mains cable is not required.
The control cables must be laid separately from (not parallel with) mains and motor cables.Shielded cables
and metallized plug housings should be used.
All devices in the mounting cabinet should be connected over a large area to a common earthing point via
short ear thing cables.
On installation of the inverter, valid safety provisions may on no account be infringed.
B 1.4 Electrical connections X1, X2, X3: Mains and motor connections
Mains voltage 200...240V~, 50/60 Hz Plug type: Spring terminal (max 2.5 mm
2
/ AWG 12)
W V U PEPEPE N L
Montage der geschirmten Leitung: Mounting of the screened cable:
Motor
ext. Bremswiderstand (opt.) ext. brake resistance (opt.)
Motorsensoren (opt.) Motor sensors (opt.)
Netz Mains
Fernbedienung Remote control
X2
X3
X1
17
Page 20
Assembly/Installation
Connection of a KaVo spindle
A KaVo spindle is connected according to the following table; on operation for the first time, check the direction of rotation specified on the spindle (arrow). Compliance with EMC guidelines is ensured only with the use of spindle types EMC 4060 – 4063 with shielded connecting cable.
Signal Inverter connection Shielded cable Unshielded cable
Type EMV 4060 – 4063 Type 4060 – 4063
Connection colour Connection colour Phase U X2.1 (U) 1 – blue 1 – blue Phase V X2.2 (V) 3 –yellow 3 – violet Phase W X2.3 (W) 4 – black 5 – black PTC (cold conductor) X7.1 B – brown 4 – brown PTC (cold conductor) X7.6 C – white/natural 2 – white Protective conductor X3 (PE) 2 – yellow/green 7 – yellow/green Shield Pull-relief terminal Housing - braided not present
--- Not connected A – green 6 – natural
X4: Remote control connection
Plug type: 25-pole D-Sub jack
Note: All connections of the 25-pole jack X4 are potentially isolated from the control and with respect to the conductive earth up to max. 60 V DC or 25V AC.
+7V-F
TXD-F
FB-AGND
FB-C-REL
FB-REL4-OE
FB-REL4-S
FB-REL3
FB-REL2
FB-GND
FB+24V
FB+10V
FB-OUT-FREQ
FB-REL1
RXD-F
FB-AOUT2
FB-IN3
FB-IN4
FB-IN5
FB-IN6
FB-AIN2
FB-AIN1
FB-C-IN
FB-AOUT1
FB-IN1
FB-IN2
13 12 11 10 9 8 7 6 5 4 3 2 1
25 24 23 22 21 20 19 18 17 16 15 14
18
Page 21
Assembly/Installation
X5: Connection of external control panel and PC (option)
Plug type: 9-pole D-Sub jack
X6: Connection of external brake resistance
Plug type: 3-pole pluggable spring terminal (max. 1.5 mm2/ AWG 14); from Phoenix, Combicon grid 5.08 mm
3
1
2
3
1
2
Brückenstecker zur Verwendung des internen Bremswiderstandes/ Bridge plug for use of the internal brake resistance
Anschluß externer Bremswiderstand/ Connection of external brake resistance
Externer Bremswiderstand : Brücke entfernen und R-Brems anschliessen External brake resistance: remove bridge and connect R-brake!
X6
X6
R-Brems/R-brake (20...650 Ohm, 150...1000W)
Interner Bremswiderstand : Brücke zwischen Pin 2 und Pin 3 Internal brake resistance: bridge between pin 2 and pin 3!
X6
+7V-B
CTS-B
GND-B
TXD-B
RXD-B
CTS-B
5 4 3 2 1
9 8 7 6
19
Page 22
Assembly/Installation
X7: Connection of the motor sensors
This connection is used for the motor temperature sensor, motor coding, speed sensor in the case of the ASM motor and position sensors in the case of the BLDSC motor.
Plug type: 6-pole pluggable spring terminal (max. 1.5 mm
2
/ AWG 16); from Phoenix, Mini-Combicon grid 3.81 mm
All connections to the 6-pole terminal X7 are based on the negative potential of the intermediate circuit voltage, i.e.are not isolated from the mains potential.
165432
X7
X7
X7
X7
X7
+12V / max. 50mA - Zur Versorgung der externen Sensoren " - For supplying the external sensors!
Achtung: Anschlüsse sind nicht potentialgetrennt vom Leistungsteil Note: Connections are not potentially isolated from the power unit!
H2
H3
H1
ASM-Motor: Drehsensor an H1, Motor-Codierung an H2, H3 " Speed sensor at H1, motor coding at H2, H3!
BLDC-Motor: Motor-Codierung an (Motor coding at) H2, H3 BLDCS-Motor: 3 Positionssensoren (position sensors) H1...3
PGND (Masse Leistungsteil) PTC/KTY und Hallsensoren PGND (Power unit ground) PTC/KTY and Hall sensors!
PTC/KTY Motortemperatur/motor temperature
X7
20
Page 23
Fast commissioning
B 2 Fast commissioning, the most important aspects in brief B 2.1 Connecting the inverter
First check whether the mains voltage corresponds to the rated voltage of the device. Connect the inverter to the mains voltage and to the motor, see Section B 1 Assembly and installation.
The LCD display shows the standard display (frequency, voltage and current) and one of the upper three light emitting diodes lights up.
B 2.2 Establishing factory default
The standard state of the inverter is the factory default state. The display shows
Warning W 15 undefined motor. See Section B 2.3.
If the inverter is to be controlled via remote control, see Section B 2.4 Remote control parameters. If the inverter was already in operation and is to be configured for another application,
first establish the factory default: Menu:
Special functions / SP3- reset parameter / all parameters
Keys Display
2 x ! Special functions Enter " SP1 ­2 x
# SP3 - reset parameter
Enter " Reset parameter - motor parameter top # (1) Reset parameter - remote control top # Reset parameter - all parameters Enter " P1 - P150 init. YES? Enter " Function: All parameters to factory setting
! and $ Stop
simultaneously Function: reset inverter (1) If you wish to bring only the parameters of the motor or the remote control to the factory default, select the
corresponding menu option with the keys
# and %.
For special applications, the inverter can be preconfigured by KaVo before delivery. This is evident from the fact that the parameter sheet (last sheet of these instructions) has been completed and the inverter shows the stan­dard display (
0 Hz 0V 0,0 A) in the normal state.
21
Page 24
Fast commissioning
B 2.3 Setting motor parameters
If you wish to set up the inverter for a KaVo spindle, call up the default parameters for the corresponding spindle: Menu:
Special functions / SP1- motor parameter / factory setting / KAVO Type xxxx
Keys Display
2x ! Special functions Enter " SP1 ­Enter
" Motor parameter - recall
3 x # Motor parameter - factory setting Enter " Factory setting - factory default Select
# and % spindle Factory setting - KAVO Type xxxx (e.g. type 4060 for spindles type 4060 – 4063)
Enter
" Function: Motor parameters are being recalled
! and $ Stop
simultaneously Function: Reset inverter If you wish to set up the inverter for another motor, or the spindle is not present in the list under factory setting,
see Section B 3.1 Commissioning parameters, examples. Start the motor with the Start key
& and check the motor running. If necessary, individual parameters
should be changed slightly; the individual parameters are described from Section B 3.9. Stop the motor with the Stop key
$.
B 2.4 Setting remote control parameters
If you wish to control the inverter via the remote control interface X4, additionally set the parameters P104 - P136 and
P7-select func. See Section B 3.1 Commissioning parameters, examples and from
Section B 3.9 Description of the individual parameters.
B 2.5 Operation
Operation concept for frequency inverter 4452
Parametrierung Configuration
Sonderfunktionen Special functions
oder or
oder or
Wert ändern Change value
Werteingabe
Value input
Normalzustand* Normal state*
Sollwert-Direkteingabe Direct setpoint input
Normalzustand Normal state
speichern und zurück Save and back
Abbruch, ohne speichern Cancel without saving
Netz-Ein oder RESET Mains on or RESET
*im Fehlerfall Fehleranzeige
sonst Standardanzeige
oder or
speichern Save
Abbruch, ohne speichern Cancel without saving
oder or
Parameternummer ändern Change parameter number
Standardanzeige Standard display
zur Normalanzeige to normal display
zur Fehleranzeige to error display
siehe unter A 7.3 see under A 7.3
wenn Fehler: if error:
*In case of error, error display, other­wise standard display
22
Page 25
Fast commissioning
After the inverter has been switched on (mains on), the device tests various hardware components. The standard display appears on the LCD display H1, and LED Operation H3 (green) lights up. If an error occurs, LED H5 (red) lights up, see Section B 4 Error messages.
Meaning of the status displays:
H3 - LED Operation (green) - The inverter is ready for operation, the
motor can be started or is running, no fault is present.
H2 - LED Warning (yellow) - The inverter has detected that a limit has
been exceeded (e.g. motor current limit, temperature too high), the motor can be started or is running.
H5 - LED Fault (red) - The inverter has detected an error and is not
ready for operation, the motor cannot be started. Afault can be reset only by switching off or reset (see Section B 4 Error mes­sages).
Only the following functions are available:
With the ! key (cancel, transfer), you can select between
1. Normal state (Standard display or error display)
2. Configuration (Display of parameter P1)
3. Special functions
B 2.6 Reset
If a serious error occurs (LED H5 Fault lights up red), a reset must be triggered in order to fetch the device from this state.
There are three possibilities for triggering a reset:
1. Key combination ! (cancel, transfer), Stop $
First press the ! key and keep depressed, then press the Stop key $ and keep both keys depressed for about one second.
2. Reset via remote control
Configure digital input with one of the parameters P111-input IN2 to P113-input IN4 to reset and then trigger a reset via an external voltage pulse (see configuration).
3. Switch off device
Wait until the error display (LED H5 red) goes out and then switch on the device again. With a reset a total initialization is triggered and the inverter is in the normal state and is ready for operation. If
the error occurs again, the error display does of course reappear.
STOP
START
H1
H3 H2 H5
23
Page 26
Configuration
B 3 Configuration
All inverter-relevant data are accessible in the form of parameters P1 ... P150.
The configuration in turn is divided into
Default parameters
Superior parameters on which further settings are dependent (P1 .. P9) (speed setpoint value, display settings, operating language, mode...)
Display values
Pure display values which cannot be changed (P10 ... P39) (voltage, current and frequency values)
Motor operating parameters
Motor-specific parameters for adapting the motor to the inverters (P41 ... P99)
Device parameters
Inverter-specific parameters which can be changed (P100 ... P150) (braking resistance, remote control)
The parameter number can be selected with the keys
% and #. If a parameter is to be changed, the Enter key
" is pressed. The value can now be changed within the permissible range. After the Enter key " has been
pressed, the value is adopted by the control and is stored. If the old value is to be retained, the
! key (cancel,
transfer) is pressed. If a parameter cannot be changed (e.g. pure display values), an eye symbol (oo) appears in the first position of
the second line in the LCD display H1. This also applies to parameters which can be changed only when the motor is stationary.
If a parameter is displayed from the hold memory in the error state, a fault symbol . appears in the first position of the second line in the LCD display H1. This applies to the standard display (see
P4-display) and
the parameters P10 to P19 (see under Error messages, hold function). If a parameter is not used, depending on the mode or other parameters, it is faded out. It is thus not displayed
and also cannot be changed.
24
Page 27
Configuration
Overview of the various parameter memories Explanation: SPxx -Special functions, see Section B 3.3
automatische Speicherung Automatic storage
Parameter reset (SP31...SP33,) SP141
Motorparameter speichern Store motor parameter
Motorparameter laden Recall motor parameter
KaVo
Typ(e)4060
M1 . . . M8
P1 P3 . . . . P38
P40 . . . . . . . . . P96
P100 . . . . P136
P150
Parameterspeicher Parameter memory
Speicher für Werkseinstellung Memory for factory setting
Speicher für Motorparameter Memory for motor parameters
Motorparameter für vordefinierte Spindeln Motor parameters for predefined spindles
SP11
SP12
P100 . . P137 P150
P1 . . P38
P41 . . . . . P96
autom. Laden bei Netz ein Automatic recall at mains on
EEPROM nichtflüchtiger
Speicher Nonvolatile memory
Motorparameter Werkseinstellung
motor parameter factory setting
KaVo Typ(e) xxxx (SP 142)
Diese Parameter können über das Bedienpanel an­gezeigt und ver­ändert werden, außerdem werden sie für die Motor­steuerung und Regelung benutzt
These parameters can be displayed and changed by the control panel; they are also used for motor control and regulation
siehe/see Kap./Sec. B3.4 Kap./Sec.B3.6
siehe/see Kap./Sec. B3.4
siehe/see Kap./Sec. B3.4
25
Page 28
Configuration
B 3.1 Commissioning parameters, examples
In order to start from a defined initial state, the factory setting must first be restored, which can be achieved with the following menu option:
Special functions / SP3 - Reset parameter / Motor parameter.
The safety inquiry should be confirmed with the Enter key
".
For fast commissioning of the inverter, at least the following parameters must be set; for optimization, further parameters can be adapted. [Factory settings in square brackets]
To ensure that the parameters marked with * are displayed, parameter
P3-para level should be set
to
parameter.
Operating language and display preselection
P5-language Selection of the operating language [English] P4-display Selection of the standard display
*
P8-speed displ Selection of the speed display in Hz or min
-1
Motor operating parameters
Three-phase asynchronous motors (ASM): Parameters which must be input: *
P90-motortype Motor type ASM
*
P91-f_mot_nom Rated motor frequency according to rating plate
*
P92-V_mot_nom Rated motor voltage according to rating plate
*
P93-I_mot_nom Rated motor current according to rating plate
*
P94-cos phi Cosine phi under nominal load [85%]
*
P96-no. of poles Number of motor poles [2]
*
P85-motor prot. Protection of the motor from excess temperature
Brushless DC motors without position sensors (BLDC): Parameters which must be input: *
P90-motortype Motor type BLDC
*
P91-f_mot_nom Rated motor frequency according to rating plate
*
P92-V_mot_nom Rated motor voltage according to rating plate
*
P93-I_mot_nom Rated motor current according to rating plate
*
P94-cos phi Cosine phi under nominal load [85%]
*
P96-no. of poles Number of motor poles [2]
*
P85-motor prot. Protection of the motor from excess temperature
Brushless DC motors with position sensors (BLDCS): This motor is not supported in the standard version of the inverter.
For optimization, it may be necessary to set further parameters P41 ... P84. (See Section B3.12)
Device parameters
*P100 - P101 If an external braking resistance is used, P100 and P101 should be set *P104 - P136 If the remote control interface (X4) is used, the corresponding parameters should be
set here
Basic parameters
P1-f_rated desired speed setpoint value (operating speed)
*
P7-select func. Selection of the control on the control panel or remote control [Panel].
26
Page 29
Configuration
B 3.2 Examples of parameters ASM motor
Speed range up to 60 000 min-1, 230V~, 5A~, cos phi 80 %, motor protection with PTC
P90-motortype ASM
P91-f_mot_nom 1000 Hz P92-V_mot_nom 230 V P93-I_mot_nom 5 A P94-cos phi 80%
P96-no. of poles 2 P85-motor prot. PTC
BLDC motor
Speed range up to 60 000 min-1, 220V~ 5 A~ (max 8A~), no centrifugal mass, normal startup
P90-motortype BLDC
P91-f_mot_nom 1000 Hz P92-v_mot_nom 220 V P93-I_mot_nom 5 A
P96-no. of poles 2
P44-I_limit 8 A
P85-motor prot. no sensor
BLDC motor
Speed range up to 60 000 min-1, 220V~, 5A~, large centrifugal mass (0.004 kgm2), microstep startup with start ramp
P90-motortype BLDC
P91-f_mot_nom 1000 Hz P92-V_mot_nom 220 V P93-I_mot_nom 5 A
P96-no. of poles 2
P51-t_start 4.0 sec P52-I_start 5 A P53-f_start 5 Hz
P85-motor prot. no sensor
Normal state
In the normal state, the standard display is output to H1 (LCD panel). During configuration, the standard display can be selected under
P4-display if the inverter is in an error
state, at this point the error number is displayed in the 1st line and a short text relating to the cause of the error is displayed in the 2nd line. In the event of an error, it is possible to switch back and forth between the error dis­play and the standard display by means of the Enter key
".
B 3.3 Special functions
Under special functions, it is possible to establish the default state and to select various utility and test programs which serve as troubleshooting programs and repair aids for the customer and the Technical Customer Service (TKD).
Contrast setting for LCD display
The contrast of the LCD display H1 can be set as follows: Menu:
Special functions / % and #
Keys Display Function
1 x ! P 1-x.. 1 x ! keep depressed Special functions additionally # Special functions Increase contrast additionally
% Special functions Reduce contrast
27
Page 30
Configuration
Operation of the special functions:
First select the menu option Special functions with key ! and call up with Enter key ". With the keys % and #, select the desired menu entry and call up with the Enter key ". Select further submenus with the keys
% and # and call up with Enter key ". Each special program can be exited with the Cancel key ! or
you can jump back one level.
Further spindles, if present
!
Control keys!
(occupied memories only!)
(occupied memories only!)
ENTER, selection, exit with saving!
Cancel, exit without saving
SP1
motor parameter
SP14
SP12
SP11
SP13
recall
store
delete
factory setting
SP142
SP143
SP141
Kavo type 4060
factory default
SP100
SP100
SP100
memory M1 ... M8
memory M1 ... M8
memory M1 ... M8
Up, increase value, exit memory entry
Down, decrease value, previous memory entry!
SP121
overwrite ?
SP22
SP0
SP4
SP3
TKD-test progr.
Reset Parameter
SP32
SP31
SP33
SP23
SP24
SP21
Test remote ctrl
SP2
Special functions
Standard display
Normal state
Configuration
Parameter valueParameters P1...P150
Aout: 2 0...10V
0...10VAout: 1
SP300
SP300
SP300
motor Parameter
remote control
all parameters
Display 0=off, 1=on
REL: R1 R2 R3 R4
Display L=low, H=high
D.IN 1 2 3 4 5 6
digital input
relay output
analog input
analog output
P104-P137 init. | Yes?
P40 - P96 init. | Yes?
P1 - P150 init. | Yes?
AIN1: x.xxx V | AIN2: x.xxx V
28
Page 31
Configuration
B 3.4 SP1 - Storing and recalling motor parameters
All motor-dependent parameters (P41 ... P96) can be stored in separate memories or recalled therefrom, 8 memory locations M1...M8 being available. The corresponding functions are accessible via the menus Special functions - motor parameters. See diagram in Section B 3. First select the menu option Special functions with key
! and call up with Enter key ". Select the menu entry
Motor parameters with the keys
% and # and call up with Enter key ". Each special program can be exited
with the Cancel key
!, the system jumping back in each case to the next highest menu level.
SP11 -
Special functions - motor parameter - recall - memory M1...M8
The selected memory is loaded into the parameters P41 ... P96; these parameters are used for motor control. Only occupied memories can be recalled. If no memory is occupied, the recall function is not available.
SP12 -
Special functions - motor parameter - store - memory M1...M8
The parameters P41 ... P96 are stored. If a memory is already occupied, you will be asked whether the memory is to be overwritten (SP121); the memory is overwritten using the Enter key
" and the function is aborted with-
out storing when the Cancel key
! is used.
SP13 -
Special functions - motor parameter - delete - memory M1...M8
The memory is deleted. Only occupied memories can be deleted. If no memory is occupied, the delete function is not available.
SP14 -
Special functions - motor parameter - factory setting
With this menu option, all motor-dependent parameters P41 ... P96 can be set to the factory setting or to various predefined motors.
SP141 -
Special functions - motor parameter - factory setting - factory default
With this function, motor parameters P41 ... P96 are set to the factory setting. The configuration of the inverter P1 ... P8 and the configuration of the braking resistance and of the remote control P100 ... P150 remain unchanged.
SP142 -
Special functions - motor parameter - factory setting- KaVo type xxxx
With this function, the motor parameters P41 ... P96 are preset to values for specific KaVo spnidles. Depending on use and operating point, the corresponding parameters must be adapted.
B 3.5 SP2 - Test remote control
These functions serve for checking the function of the remote control at X4. SP21 -
Special functions - test remote ctrl - digital input
The state of the 6 inputs read in by the inverter is displayed, L representing low input voltage (0 V) and H high input voltage (24 V).
SP22 -
Special functions - test remote ctrl - relay output
With this menu, the switching function of the relays can be checked. First, all 4 relays are switched on. The relay can be selected (Rx flashes) with the keys
% and #, and the corresponding relay can be switched with the
Enter key
". The switching state is displayed as 0 (contact open) and 1 (contact closed).
SP23 -
Special functions - test remote ctrl - analogue input
The voltages read in by the inverter at the inputs AIN1 and AIN2 are displayed. SP24 -
Special functions - test remote ctrl - analogue output
With this menu, the functioning of the outputs AOUT1 and AOUT2 can be checked. First, the desired output is selected with the keys
% and # and confirmed with the Enter key ". Now, the out-
put voltage can be set with the keys
% and #, confirmation with the Enter key " being unnecessary.
29
Page 32
Configuration
B 3.6 SP3 - Reset parameter to factory default
SP31 - Special functions - reset paramter - motor parameter With this function, the motor parameters P41 ... P96 are set to the factory setting. After confirmation of the safety inquiry (SP300) with the Enter key
", the function is performed. The other parameters remain unchanged.
SP32 -
Special functions - reset parameter - remote control
With this function, the parameters for the remote control P104 ... P137 are set to the factory setting, rendering the remote control inactive. After confirmation of the safety inquiry (SP300) with the Enter key
", the function is
performed. The other parameters remain unchanged. SP33 -
Special functions - reset parameter - all parameters
With this function, all parameters P1 ... P150 are set to the factory setting. After confirmation of the safety inquiry (SP300) with the Enter key
", the function is performed. Stored motor parameters in the memories M1 ... M6
are retained.
B 3.7 SP4 - TKD test programs
Various test programs for the KaVo Technical Customer Service are included under this menu option.
30
Page 33
Configuration
B 3.8 Parameter list
This list includes all displayable and alterable parameters. In the column Change display, the following abbreviations are used:
N = not alterable, S = alterable only when motor stationary, I = always alterable, even when motor running M = display and alterability dependent on
P90-motortype,
P = display only if P3-param level is set to parameter * = display dependent on other parameters
Par. Indication Description Value range, Unit Factory Change No. in display physical value setting display
Basic parameters:
P1 f_rated Frequency setpoint value control panel 30... 3000 Hz 50 I P3 Para level Parameter level Operation, configuration - Operation I P4 Display Standard display Combi display, various values - Combidisp.I P5 Language Language of the menu texts numerical, German, English - German I P6 F_norm Standardization factor for P24 0.01... 500.00 - 1.00 I P P7 Select func.Operation local, remote control panel,remote control,parallel- Panel I P P8 Speed displ Selection Speed display in Hz, in min-1 - in Hz I P
Display values
P10 f_rated_act Current frequency setpoint value 0...3000 Hz - N
P11 I_limit_act Current current limit 0.5....12 A~ - N
P12 f_rated_int Frequency setpoint value after integrator 0...3000 Hz - N P13 f_out_act Actual inverter frequency 0..3000 Hz - N P14 f_motor Actual motor frequency 0...3000 Hz - N P15 V_motor Output voltage 0..250 V~ - N P16 V_DC circ Intermediate circuit voltage 0..350 V- - N P17 I_mot_app Apparent motor current 0..12 A~ - N P18 I_mot_real Real motor power 0..12 A~ - N P19 P_real Real power 0..2000 W - N P20 motor code Motor coding and motor memory 1..8 - - N P24 Norm value Standardized display value 0...1500000 - - N P25 t_action Operating hours counter 0... 65000 h 0 N P26 t_reset Switch-on time from reset 0... 65000 min 0 N P30 1st error Last error - - 0 N P31 2nd error Penultimate error - - 0 N P32 3rd error Third-last error - - 0 N P33 4th error Fourth-last error - - 0 N P34 5th error Fifth-last error - - 0 N P36 Inverter Inverter type - - Type 4452 N P37 SW panel Firmware version of panel - - - N P38 SW mot cont Firmware version of motor control - - - N
Motor parameters: Motor operating values
P41 f_mot_min Min. motor frequency 30... 100 Hz 50 S P M P42 f_mot_max Max. motor frequency f_mot_nom, 101 ... 3000 Hz f_nom S P P43 V_mot_max Max. motor voltage phase-phase V_mot_nom, 1 ...250 V~ V_nom S P P44 I_limit Current limitation (phase current) 1.5 * I_mot_nom, 0,5...12 A~ 1,5*I_nom I P P46 t_rise Ramp time for run-up 0.5... 400 s 5 I P P47 t_fall Ramp time for fall-down 0.5... 400 s 5 I P P48 t_stop Ramp time for stop DC brake, t_fall,0.,5..400 s t_fall I P P50 Motor start Start option, catch circuit Normal, catch circuit - Normal I P M P51 t_start Start time for microstep operation without ramp, 0.5 ... 100 s without ramp I P M P52 I_start Startup current microstep oper. BLDC 0.4 ... 12 A~ 0.4 I P M * P53 f_start Startup frequency microstep operation 1 ... 30 Hz 5 S PM P54 t_off Inverter switch-off time, startup 200 ... 1000 µs 600 S P M P55 t_DC_brake DC brake time DC brake off, 0.1... 120 s 2 I P M P56 I_DC_brake DC brake current DC brake 0.1 ... 12 A- 1 I P M * P57 I_DC_stop DC stop current (at stop) off, 0.1 ... 3 A- off I P P58 emerg. stop Select emergency stop at mains failure inactive, on at mains failure - inactive I P P59 speedsensor Number of pulses at speed senor no speed sensor, 1...10 I/U no sensor S P M
31
Page 34
Configuration
Par. Indication Description Value range, Unit Factory Change No. in display physical value setting display
U/f characteristic (ASM motor)
P60 V_boost Startup voltage at f=0 3%V_nom, 1...50 V~ 3%V_nom I P M P61 f1 1st characteristic point frequency f_nom, 30... 3000 Hz f_nom I P M P62 V1 1st characteristic point voltage V_nom , 1... 250 V~ V_nom I P M P63 f2 2nd characteristic point frequency f_nom, 30... 3000 Hz f_nom I P M P64 V2 2nd characteristic point voltage V_nom, 1... 250 V~ V_nom I P M P65 f3 3rd characteristic point frequency f_nom, 30... 3000 Hz f_nom I P M P66 V3 3rd characteristic point voltage V_nom, 1... 250 V~ V_nom I P M
Control
P70 control Control principle speed control U/f,I*R,slip, speed - U/f-Tab.I PM P71 I*R factor I*R compensation gain factor off, 0.1 ... 30 V/A off I P M * P72 loadcomp Load compensation gain factor off, 0.1 ... 40 %/A~ off I P M * P73 komp-t_filt I*R and load compensation. Filter time 1 ... 1000 ms 20 I P M * P75 slipkomp Slip compensation gain factor off, 0.1 ... 10.0 %/A~ off I P M * P76 slip-t_filt Slip compensation filter time 1... 1000 ms 20 I P M * P77 I-limtr-KP Current limitation P-component 2 ... 200 % 40 I P P78 I-limtr-t_n Current limitation I-component reset time 1 ... 999, without I-part ms 10 I P P79 V-contr-KP Voltage control V_WR P-component 5...100 % 20 I P P80 V-contr-t_n Voltage control I-component reset time 5 ... 999, without I-part ms 10 I P P81 N-contr-KP Speed control P-component 5 ... 500 % 50 I P M * P82 N-contr-t_n Speed control I-component reset time 5 ... 999, without I-part ms 250 I P M * P83 N-contr-t_v Speed control D-component derivative time without D-part, 1...300 ms 30 I P M * P84 N-contr-t_filSpeed control T1-element for D-component 1 ... 300 ms 200 I P M *
Monitoring
P85 motor prot. Monitoring motor temperature off, PTC, KTY - PTC I P P86 R_protect Resistance value for sensor KTY 500...4000 W 1200 I P *
Rated motor data (according to rating plate)
P90 motortype Motor design ASM, BLDC, BLDCS - no motor S P P91 f_mot_nom Rated motor frequency 30 ... 3000 Hz 50 S P P92 V_mot_nom Rated motor voltage 0 ... 250 V~ 30 S P P93 I_mot_nom Rated motor current 0.5 ... 8.0 A~ 1.0 S P P94 cos phi Cosine phi at nominal load 20 ... 100 % 85 S P P96 no.of poles Number of poles 2, 4, 6, 8 - 2 S P
Device parameters: ext. brake resistance
P100 R_ext_brake Resistance of external brake resistor internal, 27 ... 100 ohm internal S P P101 P_ext_brake Power of external brake resistor 150 ... 1000 W 150 S P *
Motor coding
P102 motorcoding Motor coding, number of motors off, 2...4 motors off S P
Fixed frequencies
P104 fixfreq.FF1 Fixed frequency FF1 (select with IN5,IN6) 30 ... 3000 Hz 100 I P P105 fixfreq.FF2 Fixed frequency FF2 30 ... 3000 Hz 100 I P P106 fixfreq.FF3 Fixed frequency FF3 30 ... 3000 Hz 100 I P P107 fixfreq.FF4 Fixed frequency FF4 30 ... 3000 Hz 100 I P
Remote control:
P110 input IN1 Function digital input IN1 off, start/stop, start pulse - off S P P111 input IN2 Function digital input IN2 off, stop, reset, FF, left - off S P P112 input IN3 Function digital input IN3 see input DE2 - off S P P113 input IN4 Function digital input IN4 see input DE2 - off S P P120 relay REL1 Function relay output REL1 off, various status signals - f_rated.I P P121 relay REL2 Function relay output REL2 see relay REL1 - overload I P P122 relay REL3 Function relay output REL3 see relay REL1 - standstill I P P123 relay REL4 Function relay output REL4 see relay REL1 - failure I P P125 I_warning var. current limit for relay output 0.4...12 A~ 0.4 I P P130 analog AIN1 Function analogue input AIN1 off, rated frequency - off S P P131 analog AIN2 Function analogue input AIN2 off, torque - off S P P132 analog Aou1 Function analogue output AOUT1 off, various values - I_mot_real S P P133 analog Aou2 Function analogue output AOUT2 off, various values - f_mot S P P135 f_rem_min min. rated freq. of analogue input 0.. 3000 Hz 0 I P P136 f_rem_max max. rated freq. of analogue input 0.. 3000 Hz 3000 I P P137 f_stop_ana Stop via analogue signal off,1... 3000 Hz off I P P150
End End mark - - -
32
Page 35
Configuration
B 3.9 Description of the individual parameters
The square brackets [ ] behind the entries indicate the numerical value; this is displayed numerically in the oper­ating language (see
P5-Language). If a natural language (German, English ...) is chosen, the corresponding
text appears instead.
B 3.10 Basic parameters
P1-f_rated
Rated frequency value (speed preselection) for the motor (input on control panel). By means of parameter
P8-speed displ, this parameter can be changed from frequency display to speed
display. The number of motor poles
P96-no. of poles is taken into account. Here, only values between
the min. frequency P41-f-mot-min and the max. frequency P42-f-mot-max can be set. Minimum value: 30 Hz Maximum value: 3000 Hz Factory setting: 50 Hz
P3-para level
Indicates the operating state Values: [0]
Operation - only basic and display values (P1...P39) are accessible.
[1]
Parameter - all parameters P1 to P150 are accessible
Factory setting: [0]
Operation
P4-display
Selection of the standard display in the normal state Values: [0]
Combi display - Combination display consisting of actual motor values
P14-f_motor, P15-V_motor and P17-i_mot app
[1] f_out_act - Inverter output frequency (P13-f_out_act) [2]
V_motor - Voltage at motor (P15-V_motor)
[3]
I_mot_app - Apparent current through motor (P17-I_mot_app)
[4]
I_mot_real - Real current through motor (P18-I_mot_real)
[5]
V circ - Voltage at intermediate circuit (P16-V_circ)
[6]
P_real - Real power (P19-P_real)
[7]
Norm_value - Standard factor * output frequency (P6-F_norm * P13-f_off_act)
Factory setting: [0]
Combi display
P5-language
Selection of the language which is to be used for operation Values: [0]
numerical - only numerical display without text information
[1]
German
[2] English
Factory setting: [1] German
P6-F_norm
Determination of the factor for the standard value display (norm_value = P6-F_norm * P13-f_off_act). This factor is evaluated only if
P4-display is set to norm_value. With the standard value display, the out-
put frequency can be converted into a process variable via the standard factor and can be displayed. Adisplay in, e.g. m/s can thus be shown. Minimum value: 0.01 Maximum value: 500.00 Factory setting: 1.00
33
Page 36
Configuration
P7-Select func
Selection of the source from which the inverter is to be operated with start/stop, setpoint speed value and torque limitation. The digital and analogue output values are always output independently of the setting.
Values: [0]
Panel
-Operation is via the control panel. The digital and analogue levels at the remote control X4 are not taken into account. [1]
Remote control.
Start
&, Stop $ and P1-f_rated of the control panel are disabled. The parameters
P104 ... P136 for remote control should be set accordingly. [2]
Parallel
-Start/Stop can be operated in parallel by the remote control and via the control panel. If Start/Stop is configured via the remote control, the keys Start
& and Stop $ on the control
panel are active only as long as they are kept depressed. Alternatively, the parameter
P1-f_rated, the analogue input AIN1 or a fixed frequency is used as the setpoint speed
value, depending on figuration. The parameters P104 ... P136 should be set accordingly. (See Section A4.6)
Factory setting: [0]
Panel
P8-Speed displ
Selection of the display for rated and actual motor speeds, in Hz or in min-1, the conversion of the frequency into the speed is performed by the following formula: Speed = frequency * 60 / number of poles/2 of the motor (
P96-no. of poles).
The parameters of the rated values
P1-f_rated, P10-f_rated_act, P12-f_rated_int, the actual
motor speed
P14-f_motor and the fixed frequencies P104-fixfreq.FF1 ... P107- fixfreq.FF4
of the remote control and the frequency limits for the analogue setpoint value input P135-f_rem_min,
P136-f_rem_max are effected.
Values: [1]
in Hz - the display is in Hz
[2]
in min-1 - the display is in min
-1
(revolutions per minute)
Factory setting: [1]
in Hz
B 3.11 Display values
P10-f_rated_act
(display value) The valid rated speed value can originate from various sources depending on configuration (panel, remote con­trol analogue input, remote control fixed frequency input). The currently valid value, i.e. the value transmitted to the motor control, is displayed for the user via parameter P10. By means of parameter
P8-speed displ, this parameter can be changed from frequency display to speed
display, the number of motor poles
P96-no. of poles being taken into account.
P11-I_limit_act (display value)
The valid torque limitation may originate from two sources depending on configuration (panel
P48-I_limit or
remote control AIN2). The currently valid value, i.e. the value transmitted to the motor control, is displayed for the user via the parameter P11.
P12-f_rated_int (display value) f_rated_int is the setpoint speed value present after the ramp integrator, and this value may be limited to
the maximum output frequency
P42-f_mot_max (see error description No.13)
By means of parameter
P8-speed displ, this parameter can be changed from frequency to speed display,
the number of motor poles
P96-no. of poles being taken into account.
The value is updated every 500 ms.
P13-f_out_act (display value) f_out_ist is the current output frequency of the inverter (inverter frequency).
The value is updated every 500 ms.
34
Page 37
Configuration
P14-f_motor (display value) f_motor is the current motor frequency and differs from the inverter frequency (P13) only in the case of an
ASM motor if the control (
P70-control) is set to slip or speed control. In all other cases and for BLDC and
BLDCS motors this parameter is the same as the output frequency (
P13-f_out_act).
By means of parameter
P8-speed displ, this parameter can be changed from frequency display to speed
display, the number of motor poles
P96-no. of poles being taken into account.
The value is updated every 100 ms.
P15-V_motor (display value) V_motor is the current motor voltage between two phases and is measured using a real-time converter.
The value is updated every 250 ms.
P16-V_DC_circ (display value) V_DC_circ is the current intermediate circuit voltage.
The value is updated every 500 ms.
P17-I_mot_app (display value) I_mot_app is the current apparent motor voltage in phase U and is measured using a real-time converter. The
value is updated every 500 ms.
P18-I_mot_real (display value) I_mot_real is the current real motor current in a phase.
The value is updated every 250 ms.
P19-P_real (display value) P_real is the current inverter output power, corresponding to the real power consumed by the motor.
The value is updated every 500 ms.
P20-motor code (display value) Motor code is the current motor coding which is present at X7.4 and X7.5. In addition, the currently used
motor parameter memory M1...M6 is displayed. If the parameters from the memory have been changed, the dis­play of the memory is not present. Example:
C2 - memory M2motor coding value 2, memory M2 used.
The value is updated every 50 ms.
P24-norm value (display value)
Standard value is
P13-f_out_act * P6-F_norm.
The value is updated every 500 ms.
P25-t_action (display value) t_action shows the total operating hours of the device in hours.
The value is read in from the EEPROM.
P26-t_reset (display value) t_reset shows the time since the last reset after an error in minutes.
The value is read in from the EEPROM.
P30-1st error (display value) 1st error shows the error number of the last error which occurred.
The value is read in from the EEPROM.
P31-2nd error (display value) 2nd error shows the error number of the penultimate error which occurred.
The value is read in from the EEPROM.
P32-3rd error (display value) 3rd error shows the error number of the third-last error which occurred.
The value is read in from the EEPROM.
35
Page 38
Configuration
P33-4th error (display value) 4th error shows the error number of the fourth-last error which occurred.
The value is read in from the EEPROM.
P34-5th error (display value) 5th error shows the error number of the fifth-last error which occurred.
The value is read in from the EEPROM.
P36-Inverter (display value) Inverter shows the inverter type (KaVo type 4452).
P37-SW panel (display value) SW panel shows the software version and the date of the operating software.
P38-SW mot.cont (display value) SW mot.cont shows the software version and the date of the motor control software.
B 3.12 Motor operating values
These parameter values are displayed depending on the chosen motor type. The assignment to the individual motor types is shown in square brackets.
P41-f_mot_min [ASM, -, -]
Absolutely minimum inverter frequency, set internally to 0 in the case of BLDC and BLDCS motors. In ASM motor, serves for establishing the lower limit of the inverter frequency. Minimum value: 30 Hz Maximum value: 100 Hz Factory setting: 50 Hz
P42-f_mot_max [ASM, BLDC, BLDCS]
Absolutely maximum inverter frequency. The output frequency of the inverter is limited to this value to protect the motor. This value is set to the maximum rated frequency in the case of ASM motors; in the case of BLDC and BLDCS motors, this value should be set about 10% higher than the maximum rated frequency. In addition, this parame­ter must be set larger than
P41_f_mot_min
Specific values: [100] f_mot_nom
-f_mot_max is taken from the nominal motor frequency P91-f_mot_nom Minimum value: 101 Hz Maximum value: 3000 Hz Factory setting: [100]
f_mot_nom (see P91)
P43-V_mot_max [ASM, BLDC, BLDCS]
Maximum motor voltage between two phases, serves for protecting the motor from excessively high voltages. The inverter output voltage is limited to this value. Specific values: [0]
V_mot_nom
- V_mot_max is taken from the nominal motor voltage P92-V_mot_nom Minimum value: 1 V Maximum value: 250 V Factory setting: [0]
V_mot_nom (see P92)
36
Page 39
Configuration
P44-I_limit [ASM, BLDC, BLDCS]
Limitation of phase current for normal motor running. The inverter limits the output current to I_limit. The stop current (
P57-I_DC_stop) and, in the case of the BLDC motor, the startup current (P52-I_start)
are unaffected by this. Specific values: [0.4]
1.5*I_nom - I_limit is set to 1.5 times the nominal motor current from P93-I_mot_nom.
Minimum value: 0.5 A Maximum value: 12 A Factory setting: [0.4]
1.5*I_nom (see P93-I_mot_nom)
P46-t_rise [ASM, BLDC, BLDCS]
Rise time of frequency 0 to
P42-f_mot_max
The rise time is effective at motor start and in the case of changes of nominal frequency. If the rise time is set too small, the motor current increases up to the current limit
P44-I_limit, thus automatically increasing the
rise time. Minimum value: 0.5 sec Maximum value: 400 sec Factory setting: 5 sec
P47-t_fall [ASM, BLDC, BLDCS]
Delay from
P42-f_mot_max to frequency 0.
The delay is effective in the case of changes of nominal frequency and in the case of a motor stop only if
P48-t_stop is set to t_fall.
Minimum value: 0.5 sec Maximum value: 400 sec Factory setting: 5 sec
P48-t_stop [ASM, BLDC, BLDCS]
Stop delay time from
P42-f_mot_max to frequency 0. The inverter reduces its frequency after the specified
ramp, and the motor operates as a generator. The rotational energy is converted into heat in the brake resist­ance. The stop time is effective only at a motor stop, after which DC braking is also performed (see
P55-t_DC_brake and P56-I_DC_brake).
If
t_stop is set too short, the inverter limits the generator current to the value of P44-I_limit and the
actual stop time of the motor automatically increases but vibrations may occur during the braking process. Specific values: [0,3]
DC-brake
- At stop, the system switches directly to DC brake, there is no generator braking and the total
rotational energy is converted into heat in the rotor.
[0.4]
t_fall
- t_stop is set internally as the delay (P47-t_fall). Minimum value: 0.5 sec Maximum value: 400 sec Factory settting: [0.4]
t_fall (see P47-t_fall)
P50-motor start [ASM]
Motor start influences the start behaviour of the ASM motors. The catch circuit prevents an overcurrent if the inverter is switched to the running motor. The inverter starts at the maximum motor frequency
P42-f_mot_max and reduces its frequency until the inverter frequency has adapted to the motor frequency.
This process takes not more than 1 second. Values: [0]
Normal
-Normal motor start from the frequency P41-f_mot_min, no catch circuit.
[1]
Catch power on
- The catch circuit is active only when the inverter knows nothing about the actual motor
speed, for example after power on and reset, unless a speed sensor is used. If the motor was braked via the generator brake, the next motor start takes place without a catch circuit. If the motor is braked only via the DC brake (
P48-t_stop = DC-brake), the catch circuit is
active at every motor start. [2]
Catch always
- Catch circuit active at every motor start Factory setting: [0]
Normal
37
Page 40
Configuration
P51-t_start [-, BLDC, -]
Startup time for microstep startup in BLDC motor from 0 Hz to
P53-f_start.
With t_start > 0.5 sec sind,
P52-I_start and P53-f_start must also be input.
In the case of the microstep startup, the BLDC motor is operated as a synchronous motor with constant current (
P52-I_start) . The output frequency is slowly increased from 0 to the start frequency (P53-f_start),
after which the system switches to controlled motor running with e.m.f. measurement. In the case of small cen­trifugal masses, the start ramp can be switched off or shorter times set. In the case of larger centrifugal mass­es, longer times should be set. Specific values: [0.4]
without ramp - microstep startup ramp switched off
Minimum value: 0.5 sec - start up with microstep startup ramp Maximum value: 100 sec
Factory setting: [0.4]
without ramp
P52-I_start [-, BLDC, -]
Startup current for microstep startup, can be selected only if
P51-t_start > 0. Low currents should be set
for a soft and quiet start and higher currents for fast start and larger centrifugal masses. Minimum value: 0.4 A Maximum value: 12 A Factory setting: 0.4 A
P53-f_start [-, BLDC, -]
Startup frequency for microstep startup. If
P51-t_start is set to [0.4] without ramp, the motor start begins
at the frequency f_start; if a ramp time is set in
P51-t_start, the startup begins at frequency 0 and is slowly
increased up to f_start. On reaching the start frequency, the microstep startup is terminated. If the motor does not start up reliably, f_start should be increased. Minimum value: 1 Hz Maximum value: 30 Hz Factory setting: 5 Hz
P48=Stopzeit
P48=DC-Bremsen
P46-t_hoch
f
f_soll f_rated
P48-t_stop
P53-
f_anlauf
P53-
f_start
I_motor =
P52-I_anlauf
I_motor_max =
P44-I_limit
I_motor =
P57-I_DC_halt
I
Synchron, gesteuerter Anlauf (open loop)
Synchronous, controlled start (open loop)
Synchron, geregelter Hochlauf (closed loop)
Synchronous, regulated run up (closed loop)
P51-t_anlauf P51-t_start
P52-I_start
P46-t_rise
P48=Stop time
P48=DC braking
P57-I_DC_stop
38
Page 41
Configuration
P54-t_off [-, BLDC, -]
Switch-off time of the inverter. In the microstep startup, the inverter is repeatedly switched off briefly in a cyclic manner in order to measure the e.m.f. voltage of the BLDC motor; this is used for detecting the position of the rotor at low speeds. In the case of larger inductances of the motor winding, longer times should be set.
Setting rule: If the BLDC motor starts up poorly or synchronizes poorly with the motor, longer times should be
set; it may also be necessary to increase the startup frequency in
P53-f_start.
Minimum value: 200 µs Maximum value: 1000 µs Factory setting: 600 µs
P55-t_DC_brake [ASM, -, -]
Time for DC brake in ASM motor, 0 = no DC brake. If this parameter is set to values > 0,
P56-I_DC_brake should also be set.
Specific values: [0]
DC-brake off - There is no DC braking
Minimum value: 0.1 sec Maximum value: 120 sec Factory setting: 2 sec
P56-I_DC_brake [ASM, -, -]
Current for DC brake in ASM motor, displayed only if
P55-t_DC_brake is not set to off.
Minimum value: 0.1 A Maximum value: 12 A Factory setting: 1 A
P57-I_DC_stop [ASM, BLDC, BLDCS]
Stop current, this current flows in the stopped motor through 2 phases; the 3rd motor phase is currentless and the motor is thus braked (ASM motor) or is kept in a defined position (BLDC or BLDCS motor). Specific values: [0]
Off - With stopped motor, no stop current is output
Minimum value: 0.1 A Maximum value: 3 A Factory setting: [0]
Off
Drehzahl/speed
Strom/current
Stop­Halten
Gleichstrombremse DC brake
P57-I_DC_halt P57-I_DC_stop
I_motor
Motorstrom Motor current
P56-I_DC_brems P56-I_DC_brake
Stop
Motordrehzahl Motor speed
Generatorbremse Generator brake
P55-t_DC_brems P55-t_DC_brake
P48-t_stop
0
P41-f_mot_min
N_soll N_rated
Motor Normallauf Normal operation
Zeit Time
Bremsvorgang ASM-Motor Braking process for ASM motor!
39
Page 42
Configuration
P58-emerg. stop [ASM, BLDC, BLDCS]
Parameter influences the behaviour on mains failure. Values: [0]
off
- At mains failure, the motor runs out freely and there is no braking. [1]
On
- The motor is braked with maximum power of the brake resistance as long as the inverter can still supply itself from the motor voltage. Factory setting: [0]
off
P59-speedsensor [ASM, - , -]
Number of pulses of the speed sensor for the ASM motor. Specific values: [0]
No sensor
- The speed sensor input at X7.3 is inactive. If P70-control is set to speed control, the speed sensor cannot be switched off since it is required for speed control. If
P102-motorcoding is set to
more than 4 motors, no speed sensor can be used since both functions share the input H1 (X7.3) and setting of P102 is then not possible. Motor coding for up to 4 motors and speed sensors can be used simultaneously. Minimum value: 1 pulse / revolution Maximum value: 10 pulses / revolution Factory setting: [0]
No sensor
Motor U/f-characteristic [ASM, -, -]
The voltage/frequency table describes the key points of the motor voltage at specific frequencies for the ASM motor. With the factory setting, characteristic points KP1... KP3 are set to the nominal frequency and the nominal volt­age of the motor.
With input from the table, the following must be noted:
The frequencies must be equal or must increase in the sequence f1, f2 and f3. (
P61-f1 <= P63-f2 <= P65-f3)
For identical frequencies, the voltage too must be identical (if e.g.
P61-f1 = P63-f2, P62-U1 must also
be equal to
P64-U2)
If one of the above-mentioned conditions is infringed, a brief warning message is obtained and the value input continues and can be terminated with the
! key.
In the case of nominal frequencies which are higher than the highest frequency in the table,
P66-U3 is
assumed as the voltage.
In the event of input difficulties, make the input in the sequence P66...P60.
U_motor V_motor
f
P41-f_mot_min
0
0
P60-U_Anlauf/ P60-V_boost
P66-U3/V3
P64-U2/V2
P62-U1/V1
P61-f1 P63-f2 P65-f3
KP2
KP3
KP1
40
Page 43
Configuration
P60-V_start [ASM, - -]
U/F-characteristic: Startup voltage at frequency zero. The minimum frequency to be output by the inverter is specified in
P41-f_mot_min, and the output voltage at
this frequency is calculated using the U/F characteristics. Specific values [0]
3%_V_nom
- the startup voltage at f=0 is set internally to the value of 3% of the rated motor voltage from
P92-V_mot_nom.
Minimum value: 1 V Maximum value: 50 V Factory setting: [0]
3%_V_nom
P61-f1 [ASM, - -]
U/f-characteristic: Frequency of characteristic point KP1 Specific values: [29]
f_nom
- the value of the nominal motor frequency from P91-f_mot_nom is used Minimum value: 30 Hz Maximum value: 3000 Hz Factory setting: [29]
f_nom
P62-U1 [ASM, - -]
U/f-characteristic: Voltage of characteristic point 1 Specific values: [0]
V_nom
- the value fo the rated motor voltage from P92-V_mot_nom is used Minimum value: 1 V Maximum value: 250 V Factory setting: [0]
V_nom
P63-f2 [ASM, - -]
U/f-characteristic: Frequency of characteristic point KP2 Specific values: [29]
f_nom
- the value of the nominal motor frequency from P91-f_mot_nom is used Minimum value: 30 Hz Maximum value: 3000 Hz Factory setting: [29]
f_nom
P64-V2 [ASM, - -]
Specific values: [0]
V_nom
- the value of the rated motor voltage from P92-V_mot_nom is used Minimum value: 1 V Maximum value: 250 V Factory setting: [0]
V_nom
P65-f3 [ASM, - -]
U/f-characteristic: Frequency of characteristic point KP3 Specific values: [29]
f_nom
- the value of the rated motor frequency from P91-f_mot_nom is used Minimum value: 30 Hz Maximum value: 3000 Hz Factory setting: [29]
f_nom
P66-V3 [ASM, - -]
U/f-characterstic: Voltage of characteristic point KP3 Specific values: [0]
V_nom
- the value of the rated motor voltage from P92-V_mot_nom is used Minimum value: 1 V Maximum value: 250 V Factory setting: [0]
V_nom
41
Page 44
Configuration
B 3.13 Control
P70-control
[ASM, -, -] Selection of the speed control for ASM motors Values: [0]
U/f table
- Voltage control via U/f table, no rise [1]
-I*R-load-comp.
- I*R and load compensation, the motor voltage is adapted as a function of the load. The parameters
P71-I*R-factor, P72-loadcomp and P73-comp-t_filt should be set.
[2] -
Slip + I*R
- Slip compensation with I*R and load compensation, the output frequency of the inverter is increased with increasing load and the motor voltage is also adapted as a function of the load. The parameters
P71-I*R-factor, P72-Loadkomp, P73-Komp-t_filt,
P75-slipkomp and P76-slip-t_filt should be set.
[3]
N-control + I*R
- The ASM motor is controlled via a speed control; a speed sensor must be connected at X7 for this purpose and the parameter
P59-speedsensor must be set appropriately
beforehand. An I*R and load compensation is applied to the speed control. The parameters
P71-I*R-factor, P72-Loadkomp, P73-Komp-t_filt, P81-N-contr-KP , P82-N-contr-t_n , P83-N-contr-t_v and P84-N-con-t_fil should be set.
Factory setting: [0]
U/f table
P71-I*R-factor [ASM, -, -]
Factor of the I*R compensation, the inverter output voltage is adapted as a function of the motor load. The aim of the I*R compensation is to keep the magnetic flux in the motor constant. The I*R compensation is effective in particular at low speeds or low voltages, and the speeds decrease less sharply under load. The I*R factor corresponds to the ohmic resistance of the motor, measured between two motor cables. U =
P71-I*R-factor * (P18-I_mot_real - (P93-I_mot_nom * P94-cos phi)
V_mot = U_table + U
U_table corresponds to the U/f table voltage, calculated from the values P60...P66 Specific values: [0]
off - I*R compensation switched off
Minimum value: 0.1 V/A (slight rise) Maximum value: 30 V/A Factory setting: [0]
off
P72-Loadkomp [ASM, -, -]
Factor of the load compensation, the inverter output voltage is adapted as a function of the motor load. With the load compensation, it is possible to ensure that the motor consumes only little current during idling (little heating up) but that the magnetization current is appropriately increased under load. This makes it possible to reduce the heating up of the motor, and the speed decrease in the load is smaller. The load compensation is applied in particular at medium and high speeds or voltages and supplements the I*R compensation. U = U_table *
P72-Loadkomp * (P18-I_mot real - (P93-I_mot_nom * P94-cos phi)
V_mot = U table + U
U_table corresponds to the U/f table voltage, calculated from the values P60...P66 Specific values: [0]
off - Load compensation switched off
Minimum value: 0.1 %/A (slight rise) Maximum value: 40 %/A (very sharp rise) Factory setting: [0]
off
P73-komp-t_filt [ASM, -, -]
Filter time of the I*R and load compensation This makes it possible to influence the rapidity of the I*R and load compensation. If the motor tends to vibrate under load, higher values should be set. Minimum value: 1 ms Maximum value: 1000 ms Factory setting: 20 ms
42
Page 45
Configuration
P75-slipkomp [ASM, -, -]
In the case of asynchronous motors, the fact that the actual speed deviates from the nominal speed under load is disadvantageous and is caused by the motor slip. Depending on the dimensioning of the motor, the slip is up to 10% at nominal load. As a result of the slip compensation, the inverter increases the output frequency as a function of real motor current according to the following formula: f =
P75-slipkomp * (P18-I_mot_real - (P93-I_mot_nom * P94-cos phi)
f_off =
P10-f_nom_int + ∆f
Specific values: [0]
off - slip compensation switched off
Minimum value: 0.1 %/A Maximum value: 10.0 %/A Factory setting: [0]
off
P76-slip-t_filter [ASM, -, -]
Filter time of the slip compensation. This makes it possible to influence the rapidity of the slip compensation. If the motor tends to vibrate, higher values should be set. Minimum value: 1 ms Maximum value: 1000 ms Factory setting: 20 ms
P77-I-limtr-KP [ASM, BLDC, BLDCS]
Only in special cases should this parameter be changed from the factory setting.
P77-I-limtr-KP influences the control (PI) for the motor current limitation, it being possible to set the gain
(proportional part) here. Minimum value: 2 % Maximum value: 200 % Factory setting: 40 %
P78-I-limtr-t_n [ASM, BLDC, BLDCS]
Only in special cases should this parameter be changed from the factory setting.
P78-I-limtr-t_n influences the control (PI) for the motor current limitation, it being possible to set the
reset time (I-part) here. Longer times make the control slower. If the times are too short, the current control tends to oscillate. Specific values: [1000]
without I-part - I-part is switched off
Minimum value: 1 ms Maximum value: 999 ms Factory setting: 10 ms
P79-V-contr-KP [ASM, BLDC, BLDCS]
Only in special cases should this parameter be changed from the factory setting.
P79-V-contr-KP influences the control (PI) for the internal intermediate circuit voltage, it being possible to
set the gain (proportional part) here. The motor voltage is generated from the intermediate circuit voltage by the inverter. Minimum value: 5 % Maximum value: 100 % Factory setting: 20 %
P80-V-contr-t_n [ASM, BLDC, BLDCS]
Only in special cases should this parameter be changed from the factory setting.
P80-V-contr-t_n influences the control (PI) for the internal intermediate circuit voltage, it being possible to
set the reset time (integral part) here. Longer times make the control slower. Specific values: [1000]
without I-part - I-part is switched off
Minimum value: 5 ms Maximum value: 999 ms Factory setting: 10 ms
43
Page 46
Configuration
P81-N-contr-KP [ASM, BLDC, BLDCS]
This parameter influences the control (PID) for the motor speed, it being possible to set the gain (proportional part) here. Minimum value: 5 % Maximum value: 500 % Factory setting: 50 %
P82-N-contr-t_n [ASM, BLDC, BLDCS]
This parameter influences the control (PID) for the motor speed, it being possible to set the reset time (integral part) here. Shorter times make the control faster and longer times make it slower. Specific values: [1000]
without I-part - I-part is switched off
Minimum value: 5 ms Maximum value: 999 ms Factory setting: 250 ms
P83-N-contr-t_v [ASM, BLDC, BLDCS]
This parameter influences the control (PID) for the motor speed, it being possible to set the derivative time (D-part) here. Longer times make the control faster and shorter times make it slower. Specific values: [0]
without D-part - D-part switched off
Minimum value: 1 ms Maximum value: 300 ms Factory setting: 30 ms
P84-N-contr-t_fil [ASM, BLDC, BLDCS]
This parameter influences the control (PID) for the motor speed, it being possible to set the filter before the D-part here. The filter makes the D-part smoother and slightly slower. In the case of longer times, the tendency of the D-part to oscillate is damped. Minimum value: 1 ms Maximum value: 300 ms Factory setting: 200 ms
B 3.14 Monitoring
P85- motor prot.
[ASM, BLDC, BLDCS] The temperature of the motor can be monitored with various sensors, and the sensor type should be set here. Values: [0]
no sensor
- there is no temperature monitoring of the motors [1]
PTC
- Positive temperature coefficient sensor (according to DIN 44081) with fixed switching thresh-
olds, the cut-out temperature is determined by the sensor itself.
[2]
KTY
- Analogue semiconductor sensor, the swiching threshold can be set with P86-R_protect
Factory setting: [0] no sensor
P86-R_protect [ASM, BLDC, BLDCS]
Resistance value of the KTY sensor at the cut-out point, selectable only if
P85-motor prot. is set to KTY.
Minimum value: 500 Maximum value: 4000 Factory setting: 1200
44
Page 47
Configuration
B 3.15 Nominal motor values
In this section, the nominal data of the connected motor should be input. The nominal data are shown on the rating plate or the data sheet.
P90-motortype [ASM, BLDC, BLDCS]
Input of motor design. Values: [0]
no motor - no motor defined
[1]
ASM - three-phase asynchronous motor
[2]
BLDC - brushless DC motor without sensors
[3]
BLDCS - brushless DC motor with sensors (not in series version)
Factory setting: [0]
no motor
P91-f_mot_nom [ASM, BLDC, BLDCS]
Nominal motor frequency according to rating plate in Hertz. Minimum value: 30 Hz Maximum value: 3000 Hz Factory setting: 50 Hz
P92-V_mot_nom [ASM, BLDC, BLDCS]
Rated motor voltage according to rating plate. Minimum value: 0 V Maximum value: 250 V Factory setting: 30 V
P93-I_mot_nom [ASM, BLDC, BLDCS]
Rated motor current (apparent current in one phase) according to rating plate. Minimum value: 0.5 A Maximum value: 8.0 A Factory setting: 1.0 A
P94-cos phi [ASM, BLDC, BLDCS]
Motor power factor cosine phi according to rating plate. Minimum value: 20 % Maximum value: 100 % Factory setting: 85 %
P96-no. of poles [ASM, BLDC, BLDCS]
Number of poles in the motor. This parameter is used for speed display in min
-1
.
Note that the number of poles and not the number of pole pairs should be input here.
Minimum value: [2] 2 poles Maximum value: [8] 8 poles Factory setting: [2] 2 poles
45
Page 48
Configuration
B 3.16 Device parameters, remote control
P100-R_ext_brake
Resistance value of the external brake resistance at X6. The value of the external brake resistance must be in the range from 27 to 100 W, and
P101-P_ext_brake
should also be set for this purpose. The resistor should be connected to terminal X6.1-3 and the bridge at X6.2-3 should be removed. If P100 is set to internal, the internal brake resistance (80W) is active, and a bridge should be connected at X6.2-3. Parallel operation of internal and external brake resistances is not possible. Specific values: [26]
internal - the internal brake resistance is used
Minimum value: 27 Maximum value: 100 Factory setting: [26]
internal
P101-P_ext_brake
Power of the external brake resistance at X6, can be selected only if
P100-R_ext_brake is not set to internal.
Minimum value: 150 W Maximum value: 1000 W Factory setting: 150 W
P102-motorcoding
By means of this parameter, the motor coding is switched on and the number of motors used is input (see Section A4.5 Motor coding). A setting to 5...8 motors is possible only if no speed sensor is used, since both functions share the input H1 (X7.3) (see
P59-speedsensor).
Only the coding inputs H1...H3 actually required are evaluated.
Value Display Function Coding inputs used
H1(X7.3) H2(X7.4) H3(X7.5)
[1]
Motorcode OFF - Motor code switched off - - -
[2]
2 motors M1-M2 - Coding with 2 motors - x -
[3]
3 motors M1-M3 - Coding with 3 motors - x x
[4]
4 Motors M1-M4 - Coding with 4 motors - x x
[5]
5 Motors M1-M5 - Coding with 5 motors x x x
[6]
6 Motors M1-M6 - Coding with 6 motors x x x
[7]
7 Motors M1-M7 - Coding with 7 motors x x x
[8]
8 Motors M1-M8 - Coding with 8 motors x x x
P104-fixfreq.FF1
Value of the fixed frequency FF1 which can be selected via the remote control. By means of parameter
P8-speed disp, this parameter can be changed from frequency display to speed
display, the number of motor poles
P96-no. of poles being taken into account.
Minimum value: 30 Hz Maximum value: 3000 Hz Factory setting: 100 Hz
P105-fixfreq.FF2
Value of fixed frequency FF 2 Minimum value: 30 Hz Maximum value: 3000 Hz Factory setting: 100 Hz
P106-fixfreq.FF3
Value of fixed frequency FF3 Minimum value: 30 Hz Maximum value: 3000 Hz Factory setting: 100 Hz
P107-fixfreq.FF4
Value of fixed frequency FF4 Minimum value: 30 Hz Maximum value: 3000 Hz Factory setting: 100 Hz
46
Page 49
Configuration
P110-input IN1
Function of the digital input IN1 Values: [0]
off
- Input has no function [1]
run/stop
- U_high = run, U_low = stop [2]
run
- Pulse at U_high = run, after which the input can return to U_low, the inverter remaining in the started state. The pulse must be at least 60 ms long. For stopping, an input (
P111-input IN2 ... P113-input IN4) should be configured for stop.
Factory setting: [0]
off
P111- input IN2
Function of the digital input IN2 Values: [0]
off
- Input has no function [1]
stop
- Motor stop (V_high = stop, V_low = run enable) [2]
Reset
- Reset (pulse at V_high = trigger reset) [3]
fixfreq. on
- Current nominal speed value is a fixed frequency, and the input must be high for this purpose. This selection of the fixed frequency FF1...FF4 is performed by inputs IN5 and IN6. The fixed frequencies themselves should be set with P104...P107. [4]
CCW rotation
- CCW motor operation (U_high = CCW)
Factory setting: [0]
off
P112- input IN3
Function of the digital input IN3 Values: - see under parameters
P111-input IN2
Factory setting: [0] off
P113- input IN4
Function of the digital input IN4 Values: - see under parameter
P111-input IN2
Factory setting: [0] off
47
Page 50
Configuration
P120-relay REL1
Output value of relay REL1 Values: [0]
off :
- no function, relay is in opened state. [1]
operation:
- The inverter is ready for operation, the motor can be started. [2]
failure:
- The inverter is in the error state, the motor cannot be started and a reset is required. [3]
overload:
- The motor current has reached the current limit. (
P17-I_mot_app >= P44-I_limit, -10% hysteresis)
[4]
N_rated reached:
- The actual speed of the motor has reached the rated speed (
P14-f_motor = P10-f_rated_act, ±10% hysteresis).
[5]
current limit
- The real motor current is higher than the current warning threshold (
P18-I_mot_real >= P125-I_warning, 10% hysteresis).
[6]
motortemp:
- The temperature sensor in the motor indicates that the temperature is too high (see
P85-motor prot. and P86-R_protect).
[7]
motor stands:
- The motor is stationary, depending on motor type. The ASM motor: if a speed sensor is present, this signal becomes active after the end of the braking process, consisting of generator brake and DC brake (see
P48-t_stop and P55-t_DC_brake). After the inverter has
been switched on or after a reset, the motor stands signal is inactive. If a speed sensor is configured with
P59-speedsensor, this signal becomes active at an actual motor
stoppage (f<1Hz). BLDC motor: The signal becomes active if the actual motor stoppage is detected from the e.m.f. voltage. [8]
motor runs:
- This is the inverted motor stands signal.
Factory setting: [4]
n_rated reached
P121- relay REL2
Output value of relay REL2. Values: - see under parameter
P120-relay REL1
Factory setting: [3] overload
P122- relay REL3
Output value of relay REL3. Values: - see under parameter
P120-relay REL1
Factory setting: [7] motor stands
P123- relay REL4
Output value of relay . Values: - see under parameter
P120-relay REL1
Factory setting: [2] failure
P125-I_warning
Value of the variable current limit for the relay output, this can be used for detecting a specific motor load, a relay output (
P120- relay REL1 ... P123- relay REL4) must be configured with the current limit
function for this purpose. The value has no effect on the current limitation. Minimum value: 0.4 A Maximum value: 12 A Factory setting: 0.4 A
48
Page 51
Configuration
P130-analogue AIN1
Function of the analogue input 1 (AIN1) Werte: [0]
off
- Input has no function [1]
f_rated
- The voltage present at AIN1 is used as the rated speed value. The frequency limit should be set for the input voltage V_e = 0V in
P135-f_rem_min and for V_e = 10V in P136-f_rem_max.
Factory setting: [0]
off
P131- analogue AIN2
Function of the analogue input 2 (AIN2) Values: [0]
off
- Input has no function [1]
torque
- The voltage present at AIN2 is used as a value for the current limitation (torque limitation). An input voltage of V_e = 0V corresponds to a current value of 0 A, V_e = 10V corresponds to the full current limit as specified in
P44-I_limit.
Factory setting: [0]
off
P132-analogue AOU1
Function of the programmable analogue output 1 (AOUT1). Werte: [0]
off
- The output has no function, output voltage 0V [1]
I_mot_real
- Real motor current (P18-i_mot_real), 10V = P44-I_limit [2] f_motor 3000Hz
- Motor frequency (P14-f_motor), 0V=0Hz, 10V = 3000Hz [3]
f_motor 1000Hz
- Motor frequency (P14-f_motor), 10V = 1000Hz [4]
f_out 3000Hz
- Inverter output frequency (P13-f_out_act), 10V=3000Hz [5]
f_out 1000Hz
- Inverter output frequency (P13-f_out_act), 10V=1000Hz [6]
P_out 3000W
- Inverter output power (P19-P_real), 10V = 3000W [7]
P_out 1000W
- Inverter output power (P19-P_real), 10V = 1000W [8]
V_link circ
- Intermediate circuit voltage (P16V_link_circ) 10V = 400V [9]
f_rated_act
- Current rated frequency (P10-f_rated_act) 10V = 1000Hz
Factory setting: [1]
I_mot_real
P133-analogue AOU2
Function of the programmable analogue output 2 (AOUT2). Values: - see
P132-analogue AOU1
Factory setting: [3] f_motor 1000Hz
49
Page 52
Configuration
P135-f_rem_min
Minimum rated frequency for analogue rated frequency default AIN1 at V_e = 0V. This parameter is evaluated only if
P130-analogue AIN1 is configured for rated frequency.
By means of parameter
P8-speed displ, this parameter can be changed from frequency display to speed
display, the number of poles of the motor
P96-no. of poles being taken into account.
Minimum value: 0 Hz Maximum value: 3000 Hz Factory setting: 0 Hz
P136-f_rem_max
Maximum rated frequency for analogue rated frequency default AIN1 at V_e = 10V. This parameter is evaluated only if
P130-analogue AIN1 is configured for rated frequency.
By means of parameter
P8-speed displ, this parameter can be changed from frequency display to speed
display, the number of poles of the motor
P96-no. of poles being taken into account.
Minimum value: 0 Hz Maximum value: 3000 Hz Factory setting: 3000 Hz
P137-f_stop_ana
Stop frequency from analogue rated frequency signal; this makes it possible to achieve an automatic motor stop with counterclockwise rotation of the nominal value potentiometer or analogue voltage 0 V. The motor is automatically stopped if the rated frequency default at analogue input AIN1 falls below the value of this parameter. By means of parameter
P8-speed displ, this parameter can be changed from frequency
display to speed display, the number of poles of the motor
P8-no. of poles being taken into account.
In this context, also see the parameter
P135-f_rem_min and P136-f_rem_max.
Values: [0]
off - no automatic stop
[1]
f_mot_min - the value from P41-f_mot_min is used
Minimum value: 2 Hz Maximum value: 3000 Hz Factory setting:
off
P150-end (display value)
Last parameter number; serves as end mark.
50
Page 53
Error messages
B 4 Error messages
If a warning occurs, the warning LED H2 (yellow) lights up and the motor can continue running. If an error is detected, the fault LED H5 (red) lights up and the motor is stopped. The following is applicable for both types of error: If the configuration mode or the special functions mode is active, the error number is shown in the LCD display only on entry into the normal state. In the normal state, it is possible to change between the standard display and the error display using the Enter key
".
If the reason for a warning disappears, the message too is deleted from the display. In order to be able to exit an error state, a reset must be triggered (either through the key combination
!/$ or
through a remote control reset). With a reset, a total initialization of the device is triggered. If the error persists, the error display immediately appears again.
The last 5 error messages are stored in the parameter
P30-1st error to P34-5th error, warning
messages not being taken into account here. This makes it possible to trace the error history.
B 4.1 Hold function
At the time the error occurs, all display values are stored. As long as the error state is present, the values are displayed from the hold memory. The LCD display H1 shows an error symbol . The standard display (see
P4-display) and the parameters
P10 to P19 are effected. With the Hold function, it is possible to determine retrospectively the operating point which triggered the error
state. If a reset is triggered, the hold display and the values in the hold memory are deleted.
51
Page 54
Error messages
B 4.2 Errors on motor control, can be influenced by operator
1 Current limitation active - warning 2 Motor temperature too high 3 Inverter cooler temperature too high 4 Motor current too high, inverter limit exceeded 5 Motor current in generator mode too high, inverter limit exceeded 6 Inverter intermediate circuit voltage V_WR too high 7 Mains input voltage too low 8 Mains input voltage too high 9 Overcurrent error in inverter 10 Overcurrent error in direct current chopper 11 Bridge at X6.2-3 for internal brake resistance missing 12 Bridge at X2 for internal brake resistance connected but external brake resistance configured 13 Nominal speed limitation active 14 Motor emergency stop active because mains voltage too low 15 No motor in parameter
P90-motortype
16 Earth fault in motor or supply cable 17 Motor connection broken
B 4.3 Errors on control panel, can be influenced by operator
20 Remote control analogue input AIN1, voltage greater than 11V 21 Remote control analogue input AIN2, voltage greater than 11V 22 Remote control voltage output FB-+24V short-circuit (voltage less than 18V) 23 Remote control voltage output FB-+7V short-circuit (voltage less than 5.5V) 24 Inadmissible code for motor coding 25 Motor coding changed with running motor 26 Unused motor parameter memory for motor coding 27 Motor coding, more than 4 motors and speed sensor used (conflict at input H1)
B 4.4 Electronics errors on motor control
40 Communication of motor control to control panel broken 41 EEPROM on power circuit board faulty during self-test (data memory) 42 Flash program memory on motor control circuit board faulty 43 EEPROM on motor control circuit board faulty in self-test (data memory) 44 ID in memory incorrect 45 Watchdog reset on motor control 47 Motor type from
P90-motortype (still) not supported - (prototype)
49 Error in real-time converter V_motor in self-test 50 Error in real-time converter I_motor in self-test 51 Error in converter (WR) in self-test 52 Error in DC chopper (GS) in self-test 53 Short-circuit or earth fault in DC chopper (GS) 54 Brake chopper faulty or brake resistance broken in self-test 55 Offset in current measuring circuit (I_wr) too large in self-test 56 Offset in current measuring circuit (I_wr_neg) too large in self-test 57 Actual motor speed too high 58 BLDC motor does not start
B 4.5 Electronics errors on control panel
60 Communication of control panel to motor control broken 61 Flash program memory on control circuit board faulty 62 EEPROM on control circuit board faulty in self-test (data memory) 63 Error while loading a parameter from the EEPROM data memory 64 Error while loading a calibration value from EEPROM data memory 65 Flash program memory on motor control empty 66 Software of control panel and motor control do not correspond. 67 Watchdog reset on control panel
52
Page 55
Error messages
B 4.6 Description of all errors and warnings
W = Warning message, inverter still ready for operation E= Error message, serious fault, inverter not ready for operation, a reset must be triggered
53
No. Description
1 W Warning. Motor current has
reached the current limit (P44-I_limit)
2 E Temperature monitoring
Motor
3 E Temperature monitoring
Inverter cooler
4 E Inverter output current
too large (15A)
5 E Inverter overcurrent protection
Generator operation (15A)
6 E Voltage monitoring Interme-
diate circuit voltage (380V)
7 E Monitoring Mains undervoltage
8 E Monitoring Mains overvoltage
9 E Overcurrent protection in
inverter (peak current)
10 E Overcurrent protection
DC chopper
11 W Monitoring Brake resistance
12 E Monitoring brake resistance
13 W Nominal speed limit active.
The internal nominal speed of the motor control (
P12-f_rated_int) is
limited to the maximum inverter frequency
P42-f_mot_max.
14 W Motor emergency stop is ac-
tivated.
Cause
Motor too highly loaded, rise time
P46-t_rise too short, startup
current P52-I_start too large Motor too hot, possibly sensor cable
break
Inverter overloaded, cooler too hot
Motor current too high, overload
Generator current too high
ASM motor fall time too short
Mains voltage too low
Mains voltage too high
Inverter overloaded, motor short-cir­cuit or earth fault
Device error in inverter
Bridge at X6.2-3 for internal brake resi­stance missing
Bridge at X6.2-3 for internal brake resi­stance connected but external brake resistance configured
P1-f_rated or rated value of
analogue input too high
Mains voltage interruption or mains input voltage too low.
Rectification
Reduce load, adapt parameter
Cool motor reduce load, test sensor and check
P85-motor prot.
and P86-R_protect.
Reduce load, check output currents
Reduce load, check parameter
P44-I_limit
Increase ramp times P47-t_fall or P48-t_stop, if necessary activate catch circuit (P50-motor start)
Adapt parameter
P47-t_fall
Test mains voltage, test mains connection
Test mains voltage, test mains connection
Reduce load, check motor and sup­ply cable for short-circuit and earth fault
Inverter reset, if fault occurs repea­tedly send inverter for repair.
Connect bridge or set
P100-R_ext_brake for
external resistance. Remove bridge or set
P100-R_ext_brake for internal
brake resistance. Check rated parameter value
P1-f_rated, frequency limits for
rated value for remote control
P135-f_rem_min and P136-f_rem_max and fixed
frequencies P104 ... P107, for checking the current rated value
P10-f_rated_act.
Stop motor and start again on control panel, check parameter
P58-emerg. stop,
check mains voltage.
Page 56
Error messages
54
No. Description
15 W No motor defined.
16 E Motor earth fault detected
17 W Motor connection broken
20 W Input voltage at AIN1 (X4.20) is
higher than 11 volt.
21 W Input voltage at AIN2 (X4.21) is
higher than 11 volt.
22 W Remote control voltage out-
put FB-+24V (voltage less than 18V)
23 W Remote control voltage output
FB-+7V (voltage less than
5.5V)
24 W Inadmissible code for motor
coding
25 W Motor coding changed while
motor running.
26 W Unused motor parameter me-
mory for motor coding.
27 W Motor coding for more than
4 motors and speed sensor used (conflict at input H1)
40 E Communication of motor
control to control panel broken
41 W Automatic test on switching on,
data memory of power circuit board
42 E Automatic test on switching on,
program memory
Cause
Parameter
P90-motortype set to
no motor.
Earth fault in motor or in supply cable
No KL motor connected or a motor phase is interrupted
Input voltage too high
Input voltage too high
Voltage too highly loaded or short­circuit
Voltage too highly loaded or short­circuit
Motor coding input set to a higher code number than motors configured in
P102-motorcoding, e.g. coding
input is C4 and only 3 motors con­figured in P102
Motor coding input at X7 changed while motor running.
The value at motor coding input X7 indicates an empty parameter me­mory M1...M8.
P102-motorcoding contains more
than 4 motors and a speed sensor is configured in
P59-speedsensor.
Both functions share the input H1 (X7.3). Loading of the motor para­meter memory M1...M8 is not possible.
Hardware or software interruption of communication
EEPROM on power circuit board faulty
Flash memory on motor control circuit board faulty
Rectification
Set parameter
P90-motortype,
presumably the inverter is still not configured, see Section B 2 Fast commissioning.
Check motor and supply cable.
Check motor connection, adapt parameter P90-motortype
Reduce voltage, check wiring
Reduce voltage, check wiring
Check wiring to X4
Check wiring to X4
Check signal values at X7 (also see
P20-motor code) or parameter P102-Motorcoding.
Check signal values at X7, they may not change while the motor is running (also see P20-motor code).
Check signal values at X7 (also see
P20-motor code) or store parameter
for corresponding motor (see Sec­tion B3.4 SP1 Storing and recalling motor parameters).
Check signal values at X7, adapt parameter
P59-speedsensor or P102-motorcoding, also see P20-motor code.
If the error persists in spite of re­peatedly switching on and off or resetting, a hardware error is present and the inverter should be sent for repair.
If the error persists in spite of repeatedly switching on and off or resetting, a hardware error is present and the inverter should be sent for repair.
If the error persists in spite of repeatedly switching on and off or resetting, a hardware error is present and the inverter should be sent for repair.
Page 57
Error messages
55
No. Description
43 W Automatic test on switching on,
data memory of motor circuit board
44 E Automatic test on switching on,
circuit ID
45 W Watchdog reset on motor
control
47 E Motor type not supported
(prototype)
49 W Error in real-time converter
V_motor in self-test
50 W Error in real-time converter
I_motor in self-test
51 E Error in inverter (WR) in self-
test
52 E Error in DC chopper (GS) in
self-test
53 E Short-circuit in DC chopper
(GS)
54 W Brake chopper faulty or brake
resistance interrupted in self­test
Cause
EEPROM on motor control circuit bo­ard faulty
Motor control circuit board faulty
Strong EMC interference on motor control circuit board
Motor control does not support the configured motor.
Electronics for measuring the effective motor voltage are faulty
Electronics for measuring the effective motor current are faulty
Inverter electronics faulty
DC chopper electronics faulty
DC chopper electronics faulty, possibly earth fault in motor
Brake chopper electronics faulty or brake resistance interrupted
Rectification
If the error persists in spite of re­peatedly switching on and off, a hardware error is present and the inverter should be sent for repair.
If the error persists in spite of re­peatedly switching on and off or resetting, a hardware error is present and the inverter should be sent for repair.
Warning indication is automatically reset after 10 seconds and motor continues to run.
Check parameter
P90-motortype,
bring firmware in motor control to new status (TKD).
If the error persists in spite of re­peated resetting, a hardware error is present and the inverter should be sent for repair.
If the error persists in spite of re­peated resetting, a hardware error is present and the inverter should be sent for repair.
If the error persists in spite of re­peated resetting, a hardware error is present and the inverter should be sent for repair.
If the error persists in spite of re­peated resetting, a hardware error is present and the inverter should be sent for repair.
Check motor for short-circuit or fault. If the error persists in spite of repeated resetting, a hardware error is present and the inverter should be sent for repair.
If the error persists in spite of re­peated resetting, a hardware error is present and the inverter should be sent for repair.
Page 58
Error messages
56
No. Description
55 WOffset in current measuring
circuit (I_wr) too large in self­test
56 WOffset in current measuring
circuit (I_wr_neg) too large in self-test
57 WActual speed of motor too
high
58 E BLDC motor does not start.
The inverter attempts to start the motor depending on
P51-
t_start; after 3 unsuccessful
start attempts or after 15 se­conds, the start procedure is terminated.
60 E Communication of the control
panel to the motor control bro­ken
61 E Automatic test on switching
on, program memory
62 E Automatic test on switching
on, data memory of control circuit board
63 WError while loading a parame-
ter from the EEPROM data memory
64 W Error while loading a calibration
value from the EEPROM data memory
65 E No program in flash memory
of motor control circuit board
66 E Software versions of control
circuit board and of motor control circuit board do not correspond
67 WWatchdog reset on control cir-
cuit board
Cause
Electronics for measuring the inter­mediate circuit voltage are faulty
Electronics for measuring the inter­mediate circuit voltage are faulty
Actual motor speed is 10% above the nominal speed. Motor cannot follow the nominal speed, motor driven externally.
Motor blocked or incorrect start parameters.
Hardware or software interruption of communication
Flash memory on control circuit board faulty
EEPROM on control circuit board faulty
Loss of data, EEPROM on control circuit board faulty
Loss of data, EEPROM on control circuit board faulty
Loss of data, flash on motor control circuit board faulty
Internal communication of control circuit board to motor control circuit board broken since protocols do not match one another.
Strong EMC interference on control circuit board
Rectification
If the error persists in spite of re­peated resetting, a hardware error is present and the inverter should be sent for repair.
If the error persists in spite of re­peated resetting, a hardware error is present and the inverter should be sent for repair.
Decrease nominal speed more slowly or increase power of brake resistance.
Check motor, check parameters P51 ... P54.
If the error persists in spite of re­peatedly switching on and off or resetting, a hardware error is present and the inverter should be sent for repair.
If the error persists in spite of re­peatedly switching on and off or resetting, a hardware error is present and the inverter should be sent for repair
If the error persists in spite of re­peatedly switching on and off or re­setting, a hardware error is present and the inverter should be sent for repair
Input the corresponding parameters again; if the error occurs repeatedly, the inverter should be sent for re­pair.
The inverter is still ready for operation in the uncalibrated state; if the error persists in spite of repeated resetting, the inverter should be sent for repair.
Send inverter for repair or request the flash programming software from KaVo.
Send inverter for repair or request the flash programming software from KaVo
Warning display is automatically reset after 10 seconds, motor continues to run.
Page 59
Conformity Statement
57
We,
KaVo ELEKTROTECHNISCHES WERK Vertriebsgesellschaft m.b.H. Wangener Str. 78 D-88299 Leutkirch im Allgäu
declare that the product
frequency inverter type 4452
-to which this declaration relates complies with the essential safety requirements in accordance with the provisions of the Directive(s)
89/336/EEC (EMC Directive) 73/23/EEC (low-voltage directive).
The following standards or normative documents were used for assessing the product:
EN 50178 Equipping of power current installations with electronic operating materials EN 61800-3 Variable-speed electric drives
Leutkirch, 11.09.2000 M.Mohr
Managing Director
Page 60
Index
58
Accessories...................................7
AIN1...AIN2...............................49
Analogue input ...........................49
Analogue output .........................49
AOU1...AOU2............................49
Apparent motor current ..............35
ASM motor.........................3,26,27
Assembly ....................................16
Basic parameters.....22,24,26,31,33
Basic state....................21,26,27,30
BLDC motor.......................3,26,27
BLDCS motor ....................3,26,27
Brake resistance ...............5; 19; 46
Catch circuit ...............................37
Characteristic point.....................41
Cold conductor ...........................44
Commissioning.................16,21,26
Configuration examples .............27
Configuration......................4,22,24
Connection adapter.......................7
Connection..................................17
Control cables.............................17
Control elements...........................8
Cooling .......................................16
Cosine phi...................................45
Counterclockwise operation.......14
Current limit.........................48; 49
Current limitation .............37,43,48
DC brake.....................................39
DC brake.....................................39
DC braking ...........................37, 39
DC motors ..................................10
Definitions ....................................3
Delay time ..................................37
Description of device ...................4
Device parameters .......24,26,32,46
Digital input...........................14,47
Direction of rotation ...................14
Display values ............................34
e.m.f. voltage........................10; 39
EEPROM......................................3
EMC ...........................................17
Emergency stop .....................14,40
Error display...............................52
Error list......................................52
Error message.......................51; 53
Error number ...................35,36; 52
Error state ..............................24,51
Error............................................52
Factory default ......................22,29
Factory setting ........21,22,26,29,30
Fault........................23,24,35,51,53
FF1...FF4 ....................................46
Fixed frequency..........................46
Generator current .......................37
Hall sensor....................................5
Hold function..............................51
Rated current ..............................45
Rated frequency value................33
Rated frequency..........................45
Rated voltage..............................45
Rating plate...................................9
Real motor current......................35
REL1...REL4..............................48
Relay...........................................48
Remote control parameters.........22
Remote control .........6,10,18,28,46
Reset ............................23,35,51,52
Rise time.....................................37
Safety information.....................2,3
Scope of delivery..........................7
Sensor type .................................44
Slip compensation .................42,43
Slip..............................................43
Software version.........................36
Special functions .........21,22,27,28
Speed control.........................42,44
Speed display..............................34
Speed sensor..........................14,40
Speed sensor ..............5; 14; 20; 40
Standard display .........................23
Standard display ...........................4
Standard factor ...........................33
Standard value display ...............33
Standard value ............................35
Start pulse...................................47
Start/Stop ....................................47
Startup current ............................38
Startup frequency .......................38
Startup time ................................38
Startup voltage............................41
Status ..........................................48
Current limit ...........................48
Failure.....................................48
f_rated reached .......................48
Motor runs ..............................48
Motor stands...........................48
Motor temperature..................48
Operation ................................48
Stop current ................................39
Stop current ................................39
Stop delay time...........................37
Switch cabinet ............................16
Switch-off time...........................39
Technical data ..............................5
Temperature monitoring.............44
Temperature................................44
Test programs........................27,30
Three-phase asynchronous
Torque limitation..................34; 49
U/f characterstics........................40
Voltage control...........................46
Voltage regulation.......................42
Voltage/frequency table ..............40
Warning message .......................53
Warnings.......................................3
I*R compensation ......................42
IN1...IN6.....................................47
Installation .............................16,17
Intermediate circuit voltage...35,43
Inverter frequency .................34,36
maximum................................36
minimum ................................36
KaVo spindle ..............................22
KTY............................................44
Language ....................................33
LCD contrast ..............................27
Load compensation.....................42
M1...M8.......................13,29,35,46
Mains failure ........................14; 40
Mains voltage drop.....................14
Memory ..............................3,25,29
Microstep startup....................3; 38
Mode.....................................11; 34
Motor cables...............................17
Motor coding .........................13,46
Motor coding..................20; 35; 46
Motor connection .......................16
Motor design ..............................36
Motor frequency.........................35
Motor load .............................42,48
Motor parameters ........13,22,29,30
Motor sensors .............................20
Motor stand detection.................14
Motor stands...............................48
Motor start ..................................37
Motor temperature sensor...........20
Motor temperature......................48
Motor type ..................................36
Motor voltage .......................35; 40
maximum................................36
Nominal data ..............................45
Nominal frequency default.........50
Nominal motor data....................45
Nominal speed............10,14,34; 49
Nominal value selection .............14
Normal state .....................4; 22; 27
Number of poles .........................45
Operating hours..........................35
Operating language................24,26
Operating state............................33
Operation ....................................48
Operation .................................5,22
Output current.............................37
Output frequency........................34
Output power..............................35
Overload .....................................48
Parallel........................................34
Parameter list..............................31
PC ...............................................18
Phase current ..............................37
Position detection ..................10,39
Position sensors ................10,20,26
PTC........................................27,44
Pulse amplitude modulation .........4
Page 61
59
Page 62
Customer setting
60
Inverter 4452 motor parameters
Customer: Date: Motor/spindle: Official responsible: Remark :
Sett.- Description Display Use Unit Factory Customer Prio. P ASM BLDC BLDCS setting setting
Special settings
O 41 Min. motor frequency f_mot_min xx x Hz 50 B 42 Max. motor frequency f_mot_max x x x Hz f_mot_nom O 43 Max. motor voltage V_mot_max x x x V U_mot_nom B 44 Current limit I_limit x x x A~ 1.5 * I_nom O2 46 Rise time t_rise x x x s 5.0 O2 47 Delay time t_fall x x x s 5.0 O2 48 Delay time at stop t_stop x x x s t_fall O2 50 Start option (catch) Motorstart x - - - Normal O2 51 Start time t_start - x - s without ramp O2 52 Start current I_start - x - A~ 0.4 O2 53 Start frequency f_start - x - Hz 5 O2 54 Switch-off time WR t_off - x - µs 600 O2 55 DC brake time t_DC_brake x- - s 2 O2 56 DC brake current I_DC_brake x - - A- 1.0 O2 57 Stop current I_DC_stop x x x A- OFF O2 58 Flag emergency stop at
mains failure emerg.stop xx x - off
B 59 Speed sensor pulse count emerg.stop x x x - no sensor
U/f Table
O 60 Startup voltage V_start x - - V~ 3% U_nom O 61 Frequency 1 f1 x - - Hz f_mot_nom O 62 Voltage 1 V1 x - - V~ U_mot_nom O 63 Frequency 2 f2 x - - Hz f_mot_nom O 64 Voltage 2 V2 x - - V~ U_mot_nom O 65 Frequency 3 f3 x - - Hz f_mot_nom O 66 Voltage 3 V3 x - - V~ U_mot_nom
Control
O 70 Control (U/f. I*R, slip, N) Control x - - - U/f table O2 71 I*R comp. rise factor I*R-factor x - - V/A off O2 72 Load comp. rise factor Loadkomp.x - - % off O2 73 I*R and load comp. filter time comp-T-filt x- - ms 20 O2 75 Slip comp. P-factor Slipkomp x - - Hz/A off O2 76 Slip comp filter time slip-T_filt x - - Hz/A 20 W 77 Current limitation I-limtr-KP xx x % 40 W 78 Current limitation I-limtr-Tn x x x ms 10 W 79 Voltage control V-contr-KP xx x % 20 W 80 Voltage control V_contr-Tn xx x ms 10 O3 81 Speed control N-contr-KP xx x % 50 O3 82 Speed control N-contr-Tn x x x ms 250 O3 83 Speed control N-contr-Tv xx x ms 30 O3 84 Speed control N-con-T_fil x x x ms 200
Monitoring: B 85 Sensor type Motor prot xx x - off O 86 Resistance R_protect x x x ohm 1200
Nominal motor data: (according to rating plate)
E 90 Motor design motortype x x x - no motor E 91 Nominal frequency f_mot_nom xx x Hz 50 E 92 Nominal voltage V_mot_nom xx x V 30 E 93 Nominal current I_mot_nom x x x A 1.0 E 94 cos. phi cos phi xx x % 85 E 96 Number of poles no.of poles xx x - 2
Setting priority:
E = Necessary, minimum input, B = required according to mode, O =set for optimization (opt level) W = best left at factory setting
Loading...