All parameter settings are described in detail in the chapter "Configuration".
This operating overview shows all possible parameters of the device series.
Depending on the order specifications or current configuration, any parameters that are not required are hidden.
Please read this operating manual before starting up the device.
B
This operating manual is valid from device software version [256.01.02].
Keep the operating manual in a place accessible to all users at all times.
We welcome any suggestions you may have to help us improve this operating
manual.
Phone+49 661 6003-727
Fax+49 661 6003-508
The power controller produces the power required at the analog input or in
manual mode. Safety devices operating independently of the power controller
must be fitted to safely switch off the downstream heating process in the event
of temperature overranges.
The power controller may only be operated with original JUMO semiconductor fuses.
Please check that the correct spare part has been used during fuse
replacement.
All necessary settings are described in this Operating Manual.
If the power controller is handled in any way that is not described in the
Operating Manual or that is expressly forbidden, this will jeopardize your
warranty rights.
Please contact the nearest subsidiary or the head office should you encounter
any problems.
Service hotlineFor technical questions
Phone support in Germany:
Phone: +49 661 6003-300 or -653 or -899
Fax:+49 661 6003-881729
Email:service@jumo.net
2011-07-01/00561073 [SCR Power Controller TYA202]7
1 Introduction
E
V
E
When accessing the inner parts of the device and returning device modules,
assemblies or components, please observe the regulations as per EN 613405-1 and EN 61340-5-2 "Protection of electronic devices from electrostatic
phenomena". Only use ESD packaging for transport.
Please note that we cannot accept any liability for damage caused by ESD
(electrostatic discharge).
ESD=Electro Static Discharge
1.2Typographical conventions
1.2.1 Warning signs
Caution
This symbol is used if there is a risk of injury to persons if the
instructions are ignored or not followed correctly.
Caution
ESD
Dangerous
voltage
Hot
surface,
fire hazard/
danger of burns
This symbol is used if there is a risk of damage to equipment or
data if the instructions are ignored or not followed correctly.
This symbol is used where special care is required when handling
components susceptible to damage through electrostatic
discharge.
This symbol indicates dangerous voltage that will cause electric
shock if you come into contact with live components.
This symbol indicates the presence of a hot surface that can cause
burns if touched.
Do not install any heat sensitive components and devices close to
the power controller.
82011-07-01/00561073 [SCR Power Controller TYA202]
1.2.2 Note signs
v
B
Note
Reference
Footnote
abc
1 Introduction
This symbol indicates particularly important information.
This symbol refers to further information in other manuals,
chapters or sections.
1
Footnotes are remarks referring to specific points in the text.
Footnotes consist of two parts:
A marker in the text and the footnote text itself.
The markers in the text consist of consecutive superscript
numbers.
1.2.3 Perform an action
Action to be
performed
Vital text
Chain of
command
h Insert
plug
Configuration level ➔ Power
controller
1.2.4 Representation
This symbol indicates the description of an action to be
performed. The individual steps are marked by an asterisk.
This text contains important information, and it is vital that you
read it before proceeding.
Small arrows between words are intended
➔ Operating mode
to facilitate faster location of parameters in
the configuration level.
Keys
Keys are shown as symbols or text.
Key combinations are shown with a plus sign.
2011-07-01/00561073 [SCR Power Controller TYA202]9
1 Introduction
1.3Order specifications
The type plate is affixed to the right-hand side of the case.
1.3.1 Scope of delivery
1 Operating Manual B70.9062.0
1 SCR power controller in the version ordered
1:1 patch cable
102011-07-01/00561073 [SCR Power Controller TYA202]
1.3.2 Accessories
1 Introduction
Semiconductor fuses
A semi-conductor fuse is fitted in the power controller to protect the SCR
module. The "LED Fuse" is lit red in the event of a fault.
v Chapter 8.2 „Replace defective semi-conductor fuse“
PartLoad current
Super fast semi-conductor fuse 50AIN = 20A70/00513108
Super fast semi-conductor fuse 80AIN = 32A70/00068011
Super fast semi-conductor fuse 80AIN = 50A70/00068011
Super fast semi-conductor fuse 160AIN = 100A70/00081801
Super fast semi-conductor fuse 350AIN = 150A70/00083318
Super fast semi-conductor fuse 350AIN = 200A70/00083318
Super fast semi-conductor fuse 350AIN = 250A70/00083318
1.3.3 General accessories
PartSales No.
Setup program 70.9061 TYA 201
(also runs for the TYA 202)
USB cable A-plug B-plug 3m70/00506252
Mounting set for DIN rail installation:
Type 70.9062/8-01-20...70/00555172
Types 70.9062/8-01-32 and 70.9062/8-01-5070/00555527
Sales No.
Inom. = IN
70/00544869
2011-07-01/00561073 [SCR Power Controller TYA202]11
1 Introduction
1.4Brief description
DeviceThe JUMO TYA 202 represents a consistent further development of the JUMO
power controller technology and switches resistive-inductive loads via a threephase current economy circuit in the star/delta three-phase mode. The microprocessor controlled power controller displays all parameters in a back-lighted
LCD display and is operated using the 4 keys on the front.
ApplicationSCR power controllers are employed where larger resistive and resistive-in-
ductive loads have to be switched, e.g. in industrial kiln construction and in
plastics processing. The SCR power controller comprises SCRs connected in
anti-parallel, the insulated cooling body and the control electronics.
InstallationSCR power controllers units up to a load current of 32A can be either clipped
onto a 35 mm mounting rail or fitted to the wall on a mounting plate. Devices
with a load current exceeding 32A have to be fitted to the wall.
Operating
modes
Cascade
control
StandardsThe SCR power controllers comply with VDE 0160 5.5.1.3 (5/88) and VDE
Advantages- Teach-in function for the detection of partial load failure
The TYA 202 operates in burst-firing mode. In burst-firing mode, the first halfcycle can be optimally cut back by means of an adjustable phase angle for
driving transformer loads.
It is possible to preset a base load, and depending on the device type, to set a
current limit or a resistance limitation for the load.
A soft start can be set to avoid high starting or inrush currents.
2
Available cascade controls are U, U
loop is not affected by fluctuations in the supply voltage during the control
process.
0106 Part 100 (3/83). Grounding is required in conformity with the regulations
of the responsible electric utility company.
- Network load optimization through dual energy management
- Transmission of the setup data is also possible without voltage supply to
the device (supply via USB port)
, I, I2 or P control. Therefore the control
122011-07-01/00561073 [SCR Power Controller TYA202]
1.5Standards, approvals and conformity
Test basis for the device characteristics is the Low Voltage Directive DIN EN
50178.
Test basis for the EMC Directive is DIN EN 61326-1.
Standard
Electrical connectionDIN VDE 0100
Protection rating IP 20 panel-
mounting devices
Climatic ambient conditionsClass 3K3
Air temperature and rel. humidityDIN EN 60721-3-3
Storage temperature Class 1K5DIN EN 60721-3-1
Operating conditions
Pollution degree
Overvoltage category
Test voltages
Impulse withstand voltage
AC voltage RMS
DIN EN 60529
DIN EN 50178
DIN EN 50178
1 Introduction
Residual current circuit breakerDIN EN 50178
Electromagnetic compatibility
Emitted interference
Interference resistance
Mechanical tests/inspections:
Vibration test 3M2
Toppling test Class 2M1
Inscriptions/labels, markingDIN EN 50178, DIN EN 61010-1
ApprovalsStandard
cUL applied for
(not for type: 70.9061/8-0X-20...)
CE conformityLow Voltage Directives 2006/95/EC
ConformityStandard
RoHs2002 / 95 EC
DIN EN 61326-1
Class A- For industrial applications only
Industrial requirements
IN EN 60068-2-6, DIN EN 60721-3-3
DIN EN 60068-2-31, DIN EN 60721-3-2
508C Power Conversation Equipment
(Category NRNT2)
C22.2 NO. 14-05 Industrial Control Equipment
(Category NRNT8)
2011-07-01/00561073 [SCR Power Controller TYA202]13
1 Introduction
142011-07-01/00561073 [SCR Power Controller TYA202]
2.1Important installation notes
V
2 Installation
Safety regulations
Fuse protectionk Fuse protection in accordance with VDE regulations must be installed for
k The choice of cable material, the installation and the electrical connection
of the device must conform to the requirements of VDE 0100 "Regulations
on the Installation of Power Circuits with Nominal Voltages below AC
1000 V" or the appropriate local/national regulations.
k Only allow qualified electricians to carry out the electrical connection.
k An isolating switch must be connected between the supply and the device
to allow disconnection of the device (all poles) from the voltage supply before the inside of the device is accessed.
k Clearance/safety distances in the device meet the requirements for double
insulation.
When mounting the connecting cable, ensure that the cables are fitted according to regulations and that the safety gaps are maintained.
the wiring of the voltage supply in the power section. The supply protection
can also be achieved by a circuit-breaker in the supply lead. This must be
dimensioned for the power consumption of the power controller.
k A semi-conductor fuse is installed to protect the controller in the event of a
ground fault/short circuit. In the event of a fault/defect, it may only be replaced by an original JUMO semi-conductor fuse.
v Chapter 8.2 „Replace defective semi-conductor fuse“
WiringLoad and control cables should be laid separately if possible. Fuses (e.g. 2A
type Neozed) must also be fitted in the control circuit for lead protection.
PE connectionh Provide a direct connection between the PE of the supply network and PE
of the power controller. Connect to the PE terminal.
The cross-section of the PE conductor must be at least as large as the crosssection of the voltage supply conductors to the power section. If the protective earth conductor is not part of the supply cable or its sheathing, the chosen
2
conductor must have a cross-section of at least 2.5 mm
tected) or at least 4mm
v see VDE 0100 Part 540
Checkh that the data given on the type plate (rated load voltage, load current) corre-
sponds to the data for the system.
h that the rotary electrical field has clockwise phasing (if the economy circuit
configuration is used).
h that the configuration e.g. of the analog inputs correspond to the wiring.
h Only connect the analog input for default set point values to the master. The
slave receives its information via the patch cable.
2
(if the PE conductor is not mechanically protected).
(if mechanically pro-
Load
connection
h The electronic switching device (2 antiparallel SCRs) are in circuit between
the terminals U1 and U2.
2011-07-01/00561073 [SCR Power Controller TYA202]15
2 Installation
h Load leads and cables for control inputs should be routed separately as far
as possible.
h Wire up the connections from supply line – SCR power controller – load as
per the wiring diagram, and check them.
Phase positionThe voltage supply for the control electronics and the load voltage
must have an identical phase position.
Control inputsThe terminal strips for the control connections (inputs and outputs) are de-
signed for safety separation from the supply line input (SELV). In order not to
impair this safety separation, all connected circuits must also have safety separation. The auxiliary voltages which are required must be safe extra-low voltages (SELV).
2.1.1 Ambient conditions
Incorrect useThe device is not suitable for use in potentially explosive atmospheres.
Vibration, dust
and soiling
Climatic
conditions
Avoid additional heat
sources
Power dissipation
Ensure that the installation site is free from vibrations, aggressive media and
dust so that the ventilation slits do not become clogged.
- Relative humidity: 5...85 % without condensation (3K3 as per EN 60721)
- Ambient temperature range: 0 ... 45 °C (3K3 as per EN 60721-3-3)
- Storage temperature range: -30...70 °C Class 1K5
h Ensure that the ambient temperature at the installation site is not increased
by other heat sources or heat accumulation.
- Do not install the controller too near to the heating process (kiln).
- Avoid exposure of the controller to direct sunlight.
Occurs in the form of dissipated heat at the cooling body of the master and
slave device and has to be dissipated at the place of installation (e.g. in the
switch cabinet) according to the climatic conditions.
2.1.2 Filtering and interference suppression
In order to prevent radio-frequency interference, such as would occur with soft
start in phase-angle mode, electrical apparatus and systems must have interference suppression implemented.
The control electronics of the SCR power controller meets the EMC requirements of EN 61 326.
However, electrical modules such as SCR power controllers do not have any
purpose by themselves. They provide a function as part of a complete system
or installation.
Where applicable, the entire load circuit of the power controller must have
suitable interference suppression filters fitted in addition by the system provider.
There are a number of specialist companies that provide appropriate ranges of
162011-07-01/00561073 [SCR Power Controller TYA202]
2 Installation
455060
75
20
200
T/°C
150
Load current/A
Reduction at a temperature of 45°C:
2%/Kelvin
70%
250
100
50
filters to deal with any interference problems. Such filters are usually provided
as complete modules, ready to be wired into the system.
2.1.3 Permissible load current depending on the ambient temperature
Destruction due to overheating:
During prolonged operation with maximum load current, the cooling body and
the area around it will heat up.
For this reason, at ambient temperatures above 45°C it is necessary to reduce
the maximum load current as shown in the diagram to prevent destruction of
the SCR module.
Ensure that the device temperature for master or slave shown on the display
does not exceed 100°C.
At a device temperature >100°C the message "Attention: High temperature"
appears.
At a device temperature >105°C, the load current is reduced in increments for
each degree of temperature increase by 10% of the rated current.
The power controller current is switched off completely at a device temperature >115°C.
v Chapter 8 „Fault messages and alarms“
2011-07-01/00561073 [SCR Power Controller TYA202]17
2 Installation
TYA202
20A
TYA202 32A
TYA202 50A
2.1.4 Wall mounting with screws (ex factory)
The power controllers with load current 20...100A are fastened to a fire resistant switch cabinet wall with 2 screws. The left-hand hole is better accessible
in the top area.
The power controllers with load current 150 ... 250A are fastened with 4
screws.
182011-07-01/00561073 [SCR Power Controller TYA202]
TYA202100A
2 Installation
TYA202
150/200A
2011-07-02/00561073 [SCR Power Controller TYA202] 19
2 Installation
TYA202250A
202011-07-02/00561073 [SCR Power Controller TYA202]
Hot
surface
2 Installation
The power controller heats up during operation depending on the
load up to a temperature of 105°C.
Ensure that the lamellae of the cooling body are vertically aligned to
allow the heat to be dissipated through natural convection.
Fire hazard:
Do not install any heat sensitive components and devices close to
the power controller.
Integrated ventilator in 250A power controller:
The temperature of the air drawn in through the ventilation grille
must not exceed 35° C. Ensure that the inlet air of the built-in ventilators can be extracted from the bottom and escape at the top
without any obstructions.
2.1.5 Fixing onto DIN rail (accessories)
The power controllers up to 32A can be fastened to a DIN rail using the respective accessories.
v Chapter 1.3.3 „General accessories“
h Hook the spring clip into the DIN rail from above.
h Swivel the power controller down until the lug engages on the DIN rail with
an audible click.
2011-07-01/00561073 [SCR Power Controller TYA202]21
2 Installation
144
132.2
1.5
25.3
1508.4
12.2
3.5
155
90
36936
17.4
8.4
2.2Dimensions
2.2.1 Type 709062/8-0X-020-XXX-XXX-XX-25X
222011-07-01/00561073 [SCR Power Controller TYA202]
2.2.2 Type 709062/8-0X-032-XXX-XXX-XX-25X
Subject to technical alterations!
2 Installation
2011-07-01/00561073 [SCR Power Controller TYA202]23
2 Installation
Subject to technical alterations!
2.2.3 Type 709062/8-0X-050-XXX-XXX-XX-25X
242011-07-01/00561073 [SCR Power Controller TYA202]
2.2.4 Type 709062/8-0X-100-XXX-XXX-XX-25X
Subject to technical alterations!
2 Installation
2011-07-01/00561073 [SCR Power Controller TYA202]25
2 Installation
250
126120
13.1
1.5
285
18
250
320
112
13
112
30
11.2
Subject to technical alterations!
2.2.5 Type 709062/8-0X-150-XXX-XXX-XX-25X
Type 709062/8-0X-200-XXX-XXX-XX-25X
262011-07-01/00561073 [SCR Power Controller TYA202]
2.2.6 Type 709062/8-0X-250-XXX-XXX-XX-25X
120126
18
1.5
285
13.1
250
250
350
112
13
112
30
11.2
Subject to technical alterations!
2 Installation
2.2.7 Clearances (all types)
h Allow a clearance of 10 cm from the floor.
h Allow a clearance of 15 cm from the ceiling.
h When fitted next to each other, no spacing between the units is required.
2011-07-01/00561073 [SCR Power Controller TYA202]27
2 Installation
282011-07-01/00561073 [SCR Power Controller TYA202]
3 Electrical Connection
Dangerous voltage
h Disconnect the system from the electrical supply (all poles).
3.1Plug-in screw terminals
Tools- Slotted screwdrivers, blade width 2, 3 and 5 mm
- Ring or open jaw spanner, width across flats 7, 10, 13 mm
3.1.1 Type 709062/8-0X-20-XXX-XXX-XX-25X
The device with a load current of 20A is connected via plug-in screw terminals.
Only allow qualified electricians to carry out the electrical connection!
Dangerous voltage will cause electric shock if you come into contact
with live components.
K
TerminalVersionConductor
cross-section
Maximum
tightening
torque
X2_1 and X2_2Slotted screws, blade width 2 mm
X3Slotted screws, blade width 3 mm
U2, N/L2, V, L1, U1Slotted screws, blade width 5 mm
Ground terminal PEThreaded pin M4 with hexagon
nut,
0.2-1.5mm
0.5-2.5mm
0.5-6 mm
Cable lug with
Hole: 4 mm
2
2
2
0.25 Nm
0.5 Nm
0.6 Nm
3 Nm
width across flats 7mm
2011-07-01/00561073 [SCR Power Controller TYA202]29
3 Electrical Connection
3.2Cable lugs and plug-in screw terminals
3.2.1 Type 709062/8-0X-032-XXX-XXX-XX-25X
Devices with load current 32...50A are equipped with plug-in screw terminals
in the control section and cable lugs in the power section.
TerminalVersionConductor cross-
section
X2_1 and X2_2Slotted screws, blade width 2 mm0.2...1.5mm
X3Slotted screws, blade width 3 mm0.5...2.5mm
U2, U1 M6 recessed head screws6...25mm
Only use 60°C or 60°C / 75°C copper lines for applications as per UL!
N/L2, V, L1Slotted screws,
blade width 3 mm
Ground terminal PEThreaded pin M6 with hexagon
nut,
width across flats 10mm
0.5...4mm
(0.5...2.5mm
ferrule)
Cable lug
Hole: 6 mm
2
2
2
2
or
2
with
Maximum
tightening torque
0.25 Nm
0.5 Nm
5 Nm
0.5 Nm
5 Nm
302011-07-01/00561073 [SCR Power Controller TYA202]
3.2.2 Type 709062/8-0X-050-XXX-XXX-XX-25X
3 Electrical Connection
2011-07-01/00561073 [SCR Power Controller TYA202]31
3 Electrical Connection
3.2.3 Type 709062/8-0X-100-XXX-XXX-XX-25X
Devices with load current 75...100A are equipped with plug-in screw terminals
in the control section and cable lugs in the power section.
362011-07-01/00561073 [SCR Power Controller TYA202]
3 Electrical Connection
3.3.1 Three-phase economy circuit, Master/Slave for resistive loads in star,
delta circuit or transformer loads (resistive-inductive)
PrerequisitesThe devices have to have the same type code and the same device software
version to allow the Master/Slave operation.
The two devices are connected by a max. 30 cm patch cable.
The figure shows the wiring of a TYA 202 that is available completely installed
and configured at the factory but behaves identically to two individual TYA 201
devices in Master/Slave mode.
Operating
method
In the standard version, the master-slave economy circuit operates with a U
control. The control electronics of the master power controller perform the actual power control function, and drive the slave unit in synchronization. This
makes it possible to drive transformer loads. The combination of the fixed cy-
2
cle time and the U
tion for the individual load resistances, even in the event of a partial load failure.
control makes it possible to achieve good voltage regula-
2
2011-07-01/00561073 [SCR Power Controller TYA202]37
3 Electrical Connection
382011-07-01/00561073 [SCR Power Controller TYA202]
4 Operation
(1)
(2)
(3)
(4)
(5)
(7)
(6)
(7)
Adhere to the
switch-on
The voltage supplies to the control electronics and to the power section must
be switched on simultaneously.
sequence
Under no circumstances may the voltage supply for the control
electronics be switched on before the load voltage! This is especially
important for operating transformer loads and resistive loads with a
large temperature coefficient (TC >> 1)!
4.1Display after switch-on of the device
SequenceWhen the voltage supply is switched on, the LED Power is continuously lit
green first and an hour glass appears on the display. Then, the master is synchronised with the slave device and a rotary field detection is carried out. If all
devices are wired correctly, the controller displays the mains voltage.
Malfunction
messages
4.1.1 Display and control elements
LegendRemarkFig.
1
2
3
4
LED Power (green) is continuously lit when the voltage
supply is connected.
It flashes regularly when the display light is switched
off.
v Chapter 9 „What to do if ...“
Display (96 x 64 pixels) with white background lighting.
The info line at the bottom of the display indicates current settings and error messages.
The LED Fuse (red) is lit when the semi-conductor fuse
is blown on the corresponding power controller.
LED K1 (yellow) Malfunction message display
v Chapter 8 „Fault messages and alarms“
5Keys:
Increasing the value / previous parameter
Reducing the value / next parameter
Cancel / one level back
Programming / one level deeper
6
7
USB setup interface
Configuration is carried out on the LH device and automatically transmitted to the RH device via the patch
cable.
Spring clip to release plastic case
v Chapter 8.2 „Replace defective semi-conduc-
tor fuse“
Use and to view current measured values such as currents, voltage
2011-07-01/00561073 [SCR Power Controller TYA202]39
4 Operation
Designation
Measured value
Info line or error
actual value, set point value load resistance, device temperature and power.
This information is also shown in the diagnosis window of the setup program.
vChapter 7 „Setup program“
4.1.2 Display of measured values
Measured value
overview
Meaning of the
symbols in the
info line
In this level, the designation of the measured value is shown in the top line and
the numerical value with the unit in the center.
The info line at the bottom shows the signal flow diagram: Input ->Processing -> Output in the device at a glance. It is also used to display
temporary statuses (e.g. error messages).
v Chapter 8 „Fault messages and alarms“
Input signalCascade
control
VoltageNone
CurrentU
InterfaceI
2
2
Operating mode
load output
Soft start with phase
angle control
Burst-firing mode
Binary input1UBurst-firing mode with
a start
Binary input2IHalf-wave control
Input signal
incorrectly
configured
402011-07-01/00561073 [SCR Power Controller TYA202]
PLogic, general
Logic
(switch)
Invalid
control
configured
Logic with a start
Logic with a default
values
Logic with a start and
a default values
Firing-pulse
inhibit
4 Operation
4.1.3 Display in the configuration level
Scroll barThe menu point marked with a black background is selected and contains
further parameters.
If there are more than 3 menu points in a level, a scroll bar appears showing
the current position in the menu.
Navigation
Numerical entry
or
selection
Once you have found the desired parameter, you can use or to
enter a numerical value or select a parameter.
h Save the setting using .
If you do not want to save the value, the entry can be aborted with .
2011-07-01/00561073 [SCR Power Controller TYA202]41
4 Operation
4.1.4 Display of error messages and particular statuses
Cyclic
display
Examples
The symbols for input, cascade control and operating mode are displayed
alternately in the info line together with error messages or information about
particular statuses.
vChapter 8 „Fault messages and alarms“
All parameters for the maximum device extension level are listed in the
following tables. Depending on the order specifications (see type plate or
device information) or current configuration, any parameters that are not
required are masked out.
422011-07-01/00561073 [SCR Power Controller TYA202]
4.2Operator level
This contains the parameters that can be changed during operation without a
restart (reset).
They are factory supplied without a password but can be protected if required
with a 4-digit code.
vChapter 5.1.11 „Changing codes“
The power controller can be adapted to the system and optimized during
operation.
h From the measured value overview press the key
h Select the operator level and press the key again
4 Operation
Editing a
parameter
4.2.1 Device data
The changes will become effective immediately.
If the correct setting e.g. for the display contrast has been found, it can be
saved by pressing .
If you do not want to save the value, the entry can be aborted with .
Value rangeYour setting:
0...50...100 %
0000...1440 min
k / Bold = factory setting
4.2.2 Power controller
Value rangeYour setting:
0...70...90°el
2011-07-01/00561073 [SCR Power Controller TYA202]43
4 Operation
10% ... max. load
current of the
device type +10%
Current load current
0...999.99
Current resistance
k / Bold = factory setting
4.2.3 Set point value configuration
Value rangeYour setting:
0 ... 180°el
Current load voltage
and load current
Current load voltage
Current load voltage
0 ...100...115%
- of the maximum
load voltage,
- of the max. load
current
or
- of the power
0 ...100%
- of the maximum
load voltage,
- of the max. load
current
or
- of the power
k / Bold = factory setting
442011-07-01/00561073 [SCR Power Controller TYA202]
4.2.4 Monitoring
Current measured
value
4 Operation
The value to be monitored is adjustable.
vChapter 5.1.5 „Monitoring“
Load voltage is used in this example.
Value rangeYour setting:
0 ... 9999.9
0 ... 9999.9
Current measured
value
Current deviation
from teach-in
0 ...1 ... 9999.9
10...50%
k / Bold = factory setting
2011-07-01/00561073 [SCR Power Controller TYA202]45
4 Operation
This function is not factory configured.
This window only appears after the following setting in
the configuration level:
h Use the key to change to the configuration level
h Monitoring
h Press the key
h Change to the operator level
hPress the key
Now a mask appears asking if the status is to be
applied now. If the answer to this is yes,
h Press the key and the current load status will be
Any change in the load (load error) will be evaluated by
the device on the basis of this status.
Overcurrent
k / Bold = factory setting
➔ Teach-in type load monit. ➔ Manual
setting
Now the function "Manual teach-in" has been
configured.
➔ Monitoring
➔ Load monit. teach-in
applied as the OK status.
462011-07-01/00561073 [SCR Power Controller TYA202]
5.1Configuration level
or Profibus DP
v Chapter 5.1.1 „Device data“
v Chapter 5.1.2 „Power controller“
v Chapter 5.1.3 „Analog inputs“
etc.
The configuration level contains the parameters for the configuration of the
power controller.
If parameters of this level are changed during operation, this causes the power
controller to be locked (inhibited). In this state it does not provide any power.
When the configuration level is exited, a restart (reset) is performed and the
power controller will then provide the required power again.
Access to this level can be inhibited with a password.
However, it is factory supplied without a password.
All parameters for the maximum device extension level are listed in the
following tables. Depending on the device version (see rating plate) or
configuration, parameters that are not required are hidden.
The configuration level is accessed from the measured value overview using
the following keys:
h From the measured value overview press the key
5 Configuration
Parameter
groups
h Select Configuration level and press .
The parameters are assigned to the following groups that are explained in
detail in the form of tables in sub-chapters on the following pages.
2011-07-01/00561073 [SCR Power Controller TYA202]47
5 Configuration
5.1.1Device data
Basic settings for display and temperature unit
Value/settingsDescription
Temperature unit
°C Defines the unit for displayed temperatures, such as the
°F
device temperature.
Display contrast
Switch off
display light
Apply factory
settings
0...50...100 %Light/dark contrast setting
0000...1440 minThe background lighting of the display is switched off after the
Apply now?The factory settings are restored when the PGM key is
k / Bold = factory setting
5.1.2Power controller
Settings for the area of application of the power controller
Value/settingsDescription
SCR controlContinuous (power
controller)
Logic (switch)The power controller behaves like a switch and regulates the
k/ bold = factory setting
set number of minutes. LED Power (green) flashes.
0000 means: Background lighting is always switched on
pressed.
The power controller regulates the power for the load continuously depending on the default set point value.
power by switching ON or OFF.
482011-07-01/00561073 [SCR Power Controller TYA202]
5 Configuration
Value/settingsDescription
Cascade controlU2, U, I2, I , PNote: Cascade control only appears when:
SCR control
Cascade control loops are used to eliminate or compensate
for external interference, such as fluctuations in the supply
voltage and changes in resistance which would have a negative effect on the control loop.
The setting U is used when the load voltage is to be directly
proportional to the default set point value.
The setting I is used when the load current is to be directly linear in relation to the default set point value.
If the temperature behavior of the heating elements is not linear or the heating elements are subject to aging, the following
cascade controls are advantageous:
2
is used for:
U
- positive temperature coefficient, molybdenum disilicide
R » is constant
- if
- brightness control.
➔ Continuous (controller).
2
is used for:
I
- negative temperature coefficient (TC)
P is used for:
- temperature-dependent TC
- free-running economy circuit
- general applications,
- SIC load with automatic aging compensation
switched offThe diagram shows how the phase angle is specified via a
standard signal without cascade control.
k/ bold = factory setting
2011-07-01/00561073 [SCR Power Controller TYA202]49
5 Configuration
u
t
500ms
520
u
t
100ms
14
u
t
u
t
aa
Value/settingsDescription
Cycle timeFixed (500ms)
(for slow heating elements)
This setting is only available in burst-firing mode.
For a fixed period of 500ms, for example, at an output level of
20% 5 sine waves are switched on and 20 are switched off.
Min. duty cycle
a start
Fastest possible
(for heating elements
that respond quickly)
The cycle time is variable for this setting. The device tries to
find the shortest possible cycle time for whole sine wave cycles. For an output level of 20%, this means one sine wave ON
and four sine waves OFF.
None
3 full sine waves
(for controlling transformer loads)
Dependent upon the setting for cycle time.
At least 3 full sine waves are always let through.
At an output level of 50%, for example, 3 sine waves are
switched on and off at the fastest cycle time possible.
no This setting is only available in burst-firing mode.
yes
If "Yes" is set, the first half-wave of each pulse group is cut
back with the set phase angle a.
Angle a start0 ...70...90°elPhase angle for astart
Soft start
502011-07-01/00561073 [SCR Power Controller TYA202]
noThis setting determines the starting behavior of the power
controller after power ON. The factory setting is "off".
yes
"yes" means that a soft start with phase angle control or pulse
groups is executed after mains ON.
k/ bold = factory setting
Value/settingsDescription
u
t
Softstartzeit
u
t
Taktzeit
Type of soft startWith phase angle
control
With pulse groupsThis setting is present in the operating mode "burst-firing
5 Configuration
The phase angle is steadily reduced starting from 180° until
a full wave has passed through.
The soft start has been completed and the power controller
switches to burst-firing mode.
Note: If the output level drops to 0% for longer than 8 seconds, the power controller restarts with a soft start once the
output level increases again.
If the current limitation is activated during the soft start phase,
reaching the full wave depends on the current limitation.
mode with fixed cycle time" as well as "with fastest cycle time
possible".
During the soft start time the ON/OFF ratio is
increased from 0 to max. 100%.
Soft start duration1 ... 65535sThis is the duration of the soft start.
Current limiting
noNo current limiting
yesCurrent limiting is realized by means of phase angle control.
During this, the load current is monitored for the set current
limit value.
Only those phase angles are permitted that do not exceed the
current limit value.
It is also possible to activate an external current limit
via a binary input.
Chapter 5.1.6 „Binary inputs“
current limit10% ... max. load
current +10% of the
device type
Varies according to the type of device.
For 20A power controllers it is possible to set 2 ... 22A.
v Chapter 1.3 „Order specifications“
Note:
Ensure that the value exceeds 10% of the max. controller current, i.e. >2 A for type 70.9062/8-01-020...
k/ bold = factory setting
2011-07-01/00561073 [SCR Power Controller TYA202]51
5 Configuration
Value/settingsDescription
Resistance limitation
Resistance limit
value
Dual energy management
Note: Resistance limitation is only possible for controllers
with current and voltage measurement in which the cas-
cade control P (code 001 in the
noNo resistance limitation
yesThe load resistance is monitored to ensure that the set resis-
tance limit is not exceeded.
In phase angle control mode, limitation is made via the phase
angle a.
In burst-firing mode, limitation is made via the ON/OFF ratio of
the sine waves.
order code) is integrated.
v Chapter 6.6 „Resistance limitation (R control)“
0...999.99If the load resistance exceeds this value, it is limited by phase
angle control or limitation of the switched sine waves.
switched offThis parameter only appears for the following settings:
Device1
Device2
Cycle time: Fixed (500ms),
v Chapter 5.1.2 „Power controller“ ➔ Cycle time
Operating mode: Burst-firing operation
This allows 2 devices
consume energy from the power supply at the same time for
small output levels.
This avoids current peaks.
1
to be set in such a way that they do not
v Chapter 6.4 „Dual energy management“
1. The Master/Slave connection, type 70.9062, is treated as "one“ device.
k/ bold = factory setting
522011-07-01/00561073 [SCR Power Controller TYA202]
5.1.3Analog inputs
The power controller has a voltage and a current input.
These inputs (default set point value) specify the required output at the load
output.
In most cases this signal is transmitted as a standard signal by an electronic
controller or a PLC and is adjusted with these settings.
Value/settingsDescription
Current measuring
range
0 ... 20mA This setting specifies which standard current signal is to be
4 ... 20mA
Customer specific
5 Configuration
connected.
vChapter 3.3 „Connection diagram“
Current measuring
range, start
Current measuring
range, end
Voltage measuring
range
Voltage measuring
range, start
Voltage measuring
range, end
0 ...20mANote: This parameter only appears when "Customer specific"
is set for the current measuring range (see above).
0 ...20mANote: This parameter only appears when "Customer specific"
is set for the current measuring range (see above).
0 ... 10V This setting specifies which standard voltage signal is to be
2 ...10V
0 ...5V
1 ... 5V
Customer specific
0 ...10VNote: This parameter only appears when "Customer specific"
0 ...10VNote: This parameter only appears when "Customer specific"
k / Bold = factory setting
1. Analog input inverting:
If, for example, 20mA is set for the start of the current measuring range and 0mA for
the end, the power controller is switched off at 20mA and switched on at 0 mA.
connected.
vChapter 3.3 „Connection diagram“
1
is set for the voltage measuring range (see above).
is set for the voltage measuring range (see above).
2011-07-01/00561073 [SCR Power Controller TYA202]53
5 Configuration
5.1.4Set point value configuration
Here you can determine the analog input that specifies the set point value, how high
the base load should be and which alternative value is to be used in the event of a
fault.
Value/settingsDescription
Default set point
value
Current inputThis setting specifies which analog input is to supply the set
point value for the power output.
Voltage input
Binary input 1Note: This setting is only available when the controller ➔ SCR
control
In this case, the power controller is controlled like a solid state
Binary input 2
Via interfaceThis means that the set point value for the power output is
relay (SSR) via binary input 1 or 2.
Contact: closed
(with factory-set control direction).
provided via an interface.
➔ Logic (switch) is set.
➔ 100% and open ➔ 0%
Default value in the
event of a fault
Value in the event
of a fault
Maximum control
variable
Last valueThe current, voltage and interface inputs are monitored for
faults/errors (line/wire breaks or bus errors). This setting is
used for specifying which alternative value is to be used by the
power controller if the default set point value is faulty.
The factory setting specifies use of the last valid value.
Voltage input or cur-
rent input
Value, adjustableThis means that the "Value in the event of a fault" is used.
000.0 This value is used in the event of a fault.
0 ...100...115%
- of the maximum
load voltage,
- of the power
0 ...100%
- of the max. load
current
Depending upon which input is set for the default set point
value, the second (still free) input appears at this point.
If a fault (e.g. line/wire break) occurs at the current input that is
factory set for the default set point value, the power controller
then uses the value at the voltage input.
This setting is only available when the controller➔ SCR con-
➔ continuous (controller) is set.
trol
The unit depends on the setting for cascade control and de-
vice type:
- for I, I
- for U, U
- for P: 0 ...115% of the power 20A x 264.5V=5290W
2
: 0 ...100 % of the max. load current, e.g.20A)
2
: 0 ... 115% of the max. load voltage e.g. 264.5V
542011-07-01/00561073 [SCR Power Controller TYA202]
5 Configuration
Control signal
P
Base load: 680 W
Maximum
Output level: 3680 W
0 mA
20 mA
3000W0...20mA
Ⳏ
Base load
Base load
0 ...100%
- of the maximum
load voltage,
- of the max. load
current
- of the power
k/ bold = factory setting
Unit depending on the setting for cascade control and device
type:
- for voltage: 0 ... 115% of the max. load voltage, e.g. 264.5V
- for current: 0 ...100% of the max. load current, e.g. 20A)
- for power: 0 ...115% of the power 20A x 264.5V=5290W
v Chapter 1.3 „Order specifications“
2011-07-01/00561073 [SCR Power Controller TYA202]55
5 Configuration
5.1.5Monitoring
An internal measured value can be monitored to ensure the adherence to limit
values.
Depending on the switching behavior, an overrange or underrange is output at
the binary output (option: relay or optocoupler).
Value/settingsDescription
Limit value monitoring
Switched offNo monitoring
Load voltage
Load current
Power
Resistance
Supply voltage
Device temperature
These measured values can be monitored and are dependent
upon the ordered device type.
Min. limit value
alarm
Max. limit value
alarm
Limit value
hysteresis
0 ... 9999.9If the measured value goes under the value specified here, a
fault message is displayed at the bottom of the display and
the yellow LED K1 lights up. The binary output switches
according to the set control direction, as described in the
diagram.
The unit of the limit value corresponds to the value to be
monitored.
0 ... 9999.9If the measured value exceeds the value specified here, a fault
message is displayed at the bottom of the display and the
yellow LED K1 lights up.
The binary output switches according to the set control
direction, as described in the diagram.
The unit of the limit value corresponds to the value to be
monitored.
0 ...1 ... 9999.9Hysteresis at the top and bottom limit of the monitoring range
562011-07-01/00561073 [SCR Power Controller TYA202]
Load monitoringNoneThe load is not monitored.
Undercurrent
Overcurrent
Note: This parameter is only available if the device type is
equipped with a cascade control I, I
ment of the current.
v Chapter 6.1 „Detection of load faults“
Note: This setting is only available if load monitoring for un-
dercurrent or overcurrent has been set.
Limit value, load
monitoring
0...10 ... 100%This setting is used to specify the percentage by which the
load current has to have decreased or increased to trigger a
load fault.
5 Configuration
2
or P, permitting measure-
Load type, load
monitoring
Teach-in type, load
monitoring
Monitoring of the
supply voltage drop
StandardStandard setting (suitable for most load types)
Infrared radiators
automatic (once)The teach-in value is automatically determined once after
Specifically suitable for short-wave infrared radiators
each power ON.
v Chapter 6.1.1 „Teach-In“
ManualTeach-in can be performed in manual mode or at the operator
level.
v Chapter 6.2.2 „Configuring the teach-in (prerequisite
for teach-in in manual mode)“
v Chapter 4.2.4 „Monitoring“
Automatic (cyclically) Teach-in is cyclically performed at a time interval of 1 minute.
nono monitoring
yes
k/ bold = factory setting
If the effective values of the analyzed half-waves diverge from
each other by more than 10%, an alarm message is displayed
and the binary output for multi-input fault warning is switched
loads from destroying the semi-conductor fuse due to a DC
component.
If there are no more supply voltage drops, the firing-pulse in-
hibit is canceled and the power controller continues operation
e.g. with a soft start.
2011-07-01/00561073 [SCR Power Controller TYA202]57
5 Configuration
7
8
3,3V
5k
W
5.1.6Binary inputs
2 binary inputs are provided, and an additional binary input for firing-pulse inhibit to which a potential-free contact can be connected.
The following functions can be triggered with binary input 1 and 2:
Ext. current limiting
External current,
limit value
h Use the key to change to the Config level
Value/settingsDescription
This function can only be set with the following
presettings:
Possibility 1:
Controller
controller
Possibility 2:
Controller
Controller
Controller
If, for example, "Binary input 1“ is set here, the current limit
value set under "Controller
ten when the binary input is closed and the "External current
limit value“ (further down in the table) becomes effective.
switched offNo ext. current limiting
Binary input 1
Binary input 2
Ext. binary input1
Ext. binary input2
10% ... max. load
current +10% of the
device type
External current limiting is controlled by binary input1
External current limiting is controlled by binary input2
External current limiting is controlled via an interface
External current limiting is controlled via an interface
This parameter only appears if a binary input is set for external
current limitation.
The max. load current varies according to the device type.
For 20A power controllers it is possible to set 2 ... 22A.
➔ Operating mode ➔ Phase angle control and
➔ Current limitation ➔ Ye s
➔ Operating mode ➔ Pulse groups
➔ Soft start ➔ yes
➔ Current limiting ➔ yes
No external switch-off, i.e. the background lighting
behaves as configured in Chapter 5.1.1
Switch-off is controlled by binary input1
Switch-off is controlled by binary input2
Switch-off is controlled via an interface
Switch-off is controlled via an interface
The firing-pulse inhibit can be triggered when the change-over
contact is closed or open.
v Chapter 3.3 „Connection diagram“
Open, load ON
Open, load OFF
k/ bold = factory setting
582011-07-01/00561073 [SCR Power Controller TYA202]
Value/settingsDescription
5 Configuration
Control direction,
binary input1
Control direction,
binary input2
Open, inactiveThe function for binary input 1 can be triggered when the
Open, active
Open, inactiveThe function for binary input 1 can be triggered when the
Open, active
k/ bold = factory setting
change-over contact is open or closed.
change-over contact is open or closed.
2011-07-01/00561073 [SCR Power Controller TYA202]59
5 Configuration
13
14
15
E
S
C
Ö
P
Optocoupler
Relay
13
14
15
E
S
Optocoupler
Relay
C
Ö
P
13
14
15
E
S
Optocoupler
Relay
C
Ö
P
13
14
15
E
S
C
Ö
P
Optocoupler
Relay
5.1.7Binary output
This parameter is used to specify the control direction of the binary output. It is controlled by the multi-input interference signal.
v Chapter 8.1 „Binary signal for collective fault“
Control direction,
binary output
h Use the key to change to the Config level
Value/settingsDescription
N/C contactNo fault message pending:
14 and 15 pole and N/C contact closed or
13 and 15 optocoupler, collector-emitter loop high-impedance
Fault message pending:
13 and 15 pole and N/O contact closed or
13 and 15 optocoupler, collector-emitter loop low-impedance
N/O contactNo fault message pending:
13 and 15 pole and N/O contact closed or
13 and 15 optocoupler, collector-emitter loop low-impedance
➔ Binary output
Fault message pending:
14 and 15 pole and N/C contact closed or
13 and 15 optocoupler, collector-emitter loop high-impedance
k/ bold = factory setting
602011-07-01/00561073 [SCR Power Controller TYA202]
5.1.8Actual value output
The actual value output is an analog output at which different internal values
can be output as a standard signal.
Value/settingsDescription
Signal type of
actual value output
Switched offNo signal output at the actual value output.
0 ... 20mA
4 ...20mA
0 ... 10V
2 ...10V
0 ...5V
1 ... 5V
5 Configuration
The standard signal to be output at the actual value output is
set here.
The "value to be output" is output in the form of a current
signal at the actual value output.
The "value to be output" is output in the form of a voltage
signal at the actual value output.
Value to be output
Signal range
start value
Signal range
end value
5.1.9RS422/485
Interface parameters for RS422/485 (see interface description B70.9061.2)
Baud rate
The value to be output at the actual value output is selected
here.
Load voltageEach of these values has to undergo a plausibility check.
Load voltage
Load current
Load current
Power (in W)
Power (in W)
Resistance
Supply voltage
Device temperature
Set point value
0 ... 9999.9Bottom limit for the "value to be output"
0 ... 9999.9Top limit for the "value to be output"
k / Bold = factory setting
Value/settingsDescription
9600
19200
38400
2
2
Example:
Depending on the device type, the load voltage can be
between 0 and 500V.
As the signal range of 0 ... 9999.9 is factory set, the end value
must be adjusted to 500.0 to allow utilization of the full signal
range.
Data format8-1-noneData bits-stop bits-parity check
8-1-odd
8-1-even
8-2-none
Device address
Min. response time 0 ... 500ms
1 ...255
k / Bold = factory setting
2011-07-01/00561073 [SCR Power Controller TYA202]61
5 Configuration
5.1.10 PROFIBUS-DP
Interface parameter for PROFIBUS-DB (see separate manual)
Value/settingsDescription
Device address
1 ...125If a "0" is set for the device address, the bus fault error
message is not displayed.
Data format
Motorola, Intelk / Bold = factory setting
5.1.11 Changing codes
It is possible to enter passwords (4-digit numeric codes) for manual mode,
operator level and configuration level to protect them from unauthorized
access.
Value/settingsDescription
Code Manual mode 0000 ... 9999
Code User level
Code Config.level
0000 ... 99990000 means: No inhibit
0000 ... 99990000 means: No inhibit
k / Bold = factory setting
0000 means: No inhibit
9999 means: Level is hidden
9999 means: Level is hidden
622011-07-01/00561073 [SCR Power Controller TYA202]
5.2Configuration example
Attention:
- make sure that the rotating
electric field is right handed!
- only possible in burst firing mode
- SCR load voltage =U
L
Fuse for control
electronics 2A
Fusing to protect the
power section cabling
0(4)...20mA
Setpoint lnput:
U= phase-phase voltage
U= phase-neutral voltage
U= voltage on thyristor power unit
L
N
Thy
P= total controlled power
I= current in phase conductor
I= current in thyristor power unit
tot
L
Thy
ohmic load star
connection
U1U2
N/L2L1V
13
14
15
1211
1089
7
6
5
42
3
1
8
1
U1U2
Semiconductor-
fuse
Semiconductor-
fuse
N/L2L1V
13
14
15
1211
1089
7
6
5
42
3
1
8
1
S
Relay
Ö
P
-
+
Patchcable
TYA 202
E
Optocoupler
C
U= U
ThyL
I=
Thy
P
tot
3 · U
N
=
P
tot
3 UL·
I=
ThyIL
I
Thy
L1NL2
L3PE
U
L
U
N
I
L
RequirementsController load voltage 400V
Load voltage 230V (star connection)
3 heating elements (3 elements with 1kW each connected in parallel)
Load current: 9000W/(3x230V)= 13A
Temperature coefficient TC = 1
Operating mode: Phase-angle control
5 Configuration
Cascade control: U
2
Base load: 0%; maximum output level 100%
Default set point value via input signal of 0 ... 20mA.
These requirements are sufficient for the following power controllers:
Device type70.9062/8-01-020-100
-400-252
2011-07-01/00561073 [SCR Power Controller TYA202]63
5 Configuration
642011-07-01/00561073 [SCR Power Controller TYA202]
6 Special device functions
L3L2L1
L3L2L1
L3L2L1
6.1Detection of load faults
The load monitoring function can detect and signal a load failure, a partial load
failure or a partial load short circuit.
UndercurrentThis function is used for one or more heating elements connected in parallel
that are to be monitored for breakage.
OvercurrentThis function is used for several heating elements connected in series that are
to be monitored for short circuits.
FunctionThis function does not only take the decreasing or increasing load current into
consideration but also includes the load voltage in the monitoring process.
The correct load ratios of the system are saved during teach-in.
Based on this status, the load changes are continuously monitored irrespective of the required output level. In the event of a breakage or short circuit of a
heating element, the load current increases or decreases. This is detected by
the load monitor and a load fault is signaled.
Limit valueA limit value must be entered in the configuration or operator level in % for the
load monitor. This limit value depends upon the number of heating elements
connected in parallel or in series. For heating elements with a temperature coefficient TC 1 the limit value can be taken directly from the following tables:
Undercurrent
Number
of heating
elements
Star connection
with separate
star points without
neutral conductor
Star connection with
common star points
without neutral conductor
Delta connection
510%413%10%317%13%10%
225%20%12%
150%
50%21%
Example:
2 heating
elements
-
The specifications in % refer to load current changes
2011-07-01/00561073 [SCR Power Controller TYA202]65
6 Special device functions
L3L2L1
L3L2L1
Overcurrent
Number of
heating elements
6-
Star connection without
neutral conductor
Delta connection
-
Te mpe rat ure
coefficient (TC)
510%
-
410%10%
314%13%
225%26%
Example for 2
heating elements
The specifications in % refer to load current changes
For heating elements with large positive or negative temperature coefficients it
is necessary to determine a suitable limit value yourself. It helps to monitor the
value of the current percentage deviation from the teach-in values. This value
is displayed in the operator level in the configuration window for the limit value
(Operator level
➔ Monitoring ➔ Limit value load monit.) in the bottom line:
No load monitoring takes place during the soft start phase (that can take longer
when current limiting is active) as the standard operating range of the load is not
yet reached. Teach-in cannot be performed in this phase either.
662011-07-01/00561073 [SCR Power Controller TYA202]
6.1.1 Teach-In
6 Special device functions
Depending on the configuration of the parameter "Load monit. teach-in",
teach-in, i.e. determination of the last measured values in the OK status, is either executed automatically once after mains ON or repeatedly automatically
(cyclically) after 1 minute has elapsed or manually.
"Manual"
teach-in
For "Manual teach-in", the power controller has to be told once after the operating point has been reached that it is to perform the teach-in.
This is possible in the operator level or in manual mode.
v Chapter 4.2.4 „Monitoring“
v Chapter 6.2.2 „Configuring the teach-in (prerequisite for teach-in in manual
mode)“
For this teach-in variant, the teach-in values are then permanently saved. It is
not necessary to perform the teach-in again when the power controller is
switched off and on again.
The teach-in can be repeated whenever necessary. The old teach-in values are
then overwritten by the new ones.
The teach-in values are only deleted if the parameter "Load monitoring teachin" is explicitly configured to "Manual teach-in" or when the factory setting is
applied. The teach-in is not affected by reconfiguration of other parameters.
If "Manual teach-in" has been configured but no teach-in has been conducted
yet, the message "Teach-in load monitoring!" appears on the display as a reminder. Manual teach-in can only be performed at the device itself, not via the
setup program.
To ensure that the load ratios for later operation are recorded precisely, only
perform the teach-in at a load current of at least 20% of the rated value.
Teach-in "Automatically
(once)"
Teach-in "Automatic (cyclically)"
"Automatically (once)" means that the teach-in values are temporarily saved
after each power ON. They are deleted again when the power controller is disconnected from the supply voltage. When the power is switched on again, the
load monitoring function is inactive until the new teach-in has been performed.
To ensure that the load ratios for later operation are recorded precisely, the
teach-in in phase angle control is not performed until the output level has
reached at least 30%. (This constraint is not necessary for burst-firing mode
as the current of a fired SCR power controller is always high enough. In this
case, the teach-in is always performed shortly after power ON or - if configured - after completion of the soft start.)
Automatically cyclically means that the teach-in values are temporarily saved
again at intervals of 1 minute. This setting is particularly suitable for SIC heating elements as in this case the resistance in the load point changes with time
due to aging.
When the power controller is disconnected from the supply voltage, the teachin values detected last are deleted again. When the power is switched on
again, the power controller starts the automatic teach-in detection again.
2011-07-01/00561073 [SCR Power Controller TYA202]67
6 Special device functions
Load voltage
Load current
6.2Manual mode
In this case, the set point value can be manually preset in % without the need
for external wiring via the analog input.
6.2.1 Default set point value in manual mode
StartManual mode, as set in the factory, can be accessed without entering a code.
h Press the key 1 x (manual mode)
h Press the key again
h Increase or reduce the set point value with or
The changes will immediately become effective at the load output and are indicated on the display.
The set point value for manual mode is not saved in the event of a power failure!
After a power failure, the measured value overview is displayed.
6.2.2 Configuring the teach-in (prerequisite for teach-in in manual mode)
The teach-in function records the current/voltage ratio of a load in the OK status.
This function is not factory configured.
v Configuration level See “Teach-in type, load monitoring” on page 57.
Configure
"manual"
teach-in
The power controller is in the level "Measured value overview".
hPress the key
h Set to Config.level
Overcurrent
➔ Teach-in type load monit. ➔ "manually“
➔ Monitoring ➔ Load monitoring ➔ Undercurrent or
hPress the key
II
h Press the key 2 x
The device performs a reset.
682011-07-01/00561073 [SCR Power Controller TYA202]
If the teach-in is being performed for the first time, the message "Teach-in load
monitoring" appears in the bottom line of the display.
6.2.3 Performing teach-in in manual mode
The power controller is in the level "Measured value overview".
h Press the key 2 x to return to manual mode.
If the teach-in is being performed for the first time, the message "Teach-in load
monitoring" appears in the bottom line of the display.
6 Special device functions
Repeat the
teach-in
h Press the key and the following message will appear:
h Press the key and the current load status will be applied as the OK
status.
Any change in the load (load error) will be evaluated by the device on the basis
of this status.
The teach-in can be repeated any number of times in manual mode.
h Press the key and the following message will appear:
h Press the key and the current load status will be applied as the OK
status.
2011-07-01/00561073 [SCR Power Controller TYA202]69
6 Special device functions
A
S
E
6.3Default set point value via potentiometer
For this connect a potentiometer to the voltage input.
It is supplied with DC 10V at terminal 5 of the power controller.
h Set Configuration level
0...10V
h Set Configuration level
➔ Voltage input
Now the power controller power is preset via the external potentiometer.
6.4Dual energy management
Thus, set point values of up to 50% can be preset for 2 Master/Slave controllers without current peaks occurring in the network due to them being
switched on simultaneously.
No current peaks are caused in the network even if the set point values are
asymmetrically distributed, e.g. 30% and 70%.
More than
2 controllers
Prerequisites
If more than 2 power controllers are required in a system, they have to be divided into groups of 2. The setting of the "Dual energy management" parameter (device 1 and 2) is carried out in each group.
- Ensure that the two master/slave devices are wired identically as shown in
the following figure.
- The control electronics and the load circuit must have the same phase.
➔ Analog inputs ➔ Voltage measuring range to
➔ Set point value config. ➔ Default set point value
- Synchronize both master/slave devices of one group by switching them on
simultaneously.
- Burst-firing mode must be configured.
- The cycle time must be set to 500ms (fixed).
- Within one group, one Master/slave device must be configured as Device1
and the other Master/slave device as Device2.
702011-07-01/00561073 [SCR Power Controller TYA202]
6 Special device functions
Fuse for control
electronics 2A
Fusing to protect the
power section cabling
U1U2
N/L2L1V
13
14
15
1211
1089
7
6
5
42
3
1
8
1
U1U2
Semiconductor-
fuse
N/L2L1V
13
14
15
1211
1089
7
6
5
42
3
1
8
1
S
Relay
Ö
P
0(4)...20mA
+
ohmic load star
connection
Patchcable
TYA 202
E
Optocoupler
C
I
1 (Device1)
L1NL2
L3PE
U
L
U
N
U1U2
N/L2L1V
13
14
15
1211
1089
7
6
5
42
3
1
8
1
U1U2
N/L2L1V
13
14
15
1211
1089
7
6
5
42
3
1
8
1
S
Relay
Ö
P
0(4)...20mA
+
Setpoint lnput:
Patchcable
TYA 202
E
Optocoupler
C
Device 1
Device 2
I
2 (Device1)
I
3 (Device1)
I
3 (Device2)
I
2 (Device2)
I
1 (Device2)
I
1
I
2
I
3
Attention:
- make sure that the rotating electric field
is right handed!
- only possible in burst firing mode
- SCR load voltage =U
L
Setpoint lnput:
Semiconductor-
fuse
ohmic load star
connection
Fuse for control
electronics 2A
Semiconductor-
fuse
Semiconductor-
fuse
2011-07-01/00561073 [SCR Power Controller TYA202]71
6 Special device functions
t
t
Device 1
Output level 20%
Device
Output level260%
250 ms500 ms750 ms1 s0ms
I
1 Device1
t
I
1
Sum of all
currentsMains
I
21Device
I
31
Device
I
1 Device2I2 Device2
I
3 Device2
I2I
3
The two controllers switch on at an offset time. The energy output is symmetrical on each side of the broken line (see arrows). Overlapping of the two device
currents in one phase is avoided as long as the sum of the output level of the
two devices is lower than 100%. The next current level is only started in the
network if the sum of the output level exceeds 100%.
If a power controller performs a restart when the configuration level
has been exited, it no longer operates in synchronization with the
others.
All master/slave controllers have to be switched on again simultaneously via a common main switch!
722011-07-01/00561073 [SCR Power Controller TYA202]
6 Special device functions
Controller
Furnace
Sensor
SCR
power unit
Supply
voltage
y
R
x
y
-
w
P
230V
P–
U0–·1U
2
R
-------------------------------
09U
2
R
-------------------- -0,81P
230 V
===
6.5Cascade control
Cascade control loops are used to eliminate or compensate for external
interference, such as fluctuations in the supply voltage and changes in
resistance which would have a negative effect on the control loop.
6.5.1 Closed control loop without cascade control
Example
Furnace/kiln
control system
The supply voltage is connected to the power controller. The controller derives
the output level y
from the difference between the set value (w) for the
R
furnace temperature and the actual (or process) value (x) which is acquired by
a sensor inside the furnace. The output level can vary over the range 0 ... 100
% and is produced as a standard signal output, e.g.0 ... 10 V. The output level
signal is fed to the power controller.
The task of the power controller is to feed energy to the heating elements in
the furnace, proportional to the controller output level:
- For an SCR power controller using phase-angle control, this means that
it alters the firing angle over the range from 180° to 0°, corresponding to a
controller output level of 0 ... 100 %.
-If the SCR power controller is using the burst-firing mode, it alters the
duty cycle T from 0 ... 100 % to correspond to the controller output level of
0 ... 100 %.
If the supply voltage drops from AC 230V to AC 207V (-10%) at a controller
output level YR, the power fed to the furnace is reduced by 19%.
(2)
P230V :Power in the load resistance at a supply voltage U of 230V
DP:Power reduction resulting from reduced supply voltage
R:Resistance of the load
This 19% reduction in the energy being fed means that
the furnace temperature falls.
Disadvantage:A continuing constant temperature is no longer assured.
2011-07-01/00561073 [SCR Power Controller TYA202]73
6 Special device functions
Controller
Sensor
Controlled
system
SCR
power controller
Voltage supply
subordinate
control loop
y
R
x
y
w
-
P
Load
U
Load
2
R
---------------- -=
(3)
P
Load
U
Load
2
(4)
U
Load
2
Eingangssignal des Leistungsstellers
(5)
The controller recognizes the deviation through the relatively slow response of
the temperature control loop and increases its output level (yR) until the
furnace reaches the original temperature (250°C) again.
6.5.2 Closed control loop with a subordinate control
To avoid power variations caused by supply voltage fluctuations, a
subordinate control loop is built into the controller system. This makes an
instant correction for variations in the amount of energy provided. The result is
that the power controller always provides a power level (y) at the output that is
proportional to its input signal (yR). The principle of subordinate control loop is
shown in Figure .
A distinction is made between U
2
, I2 and P control loop. U2 control is used in
most applications. There are however some applications where an I
control has advantageous control-loop characteristics (requires recording of
the current in the power controller).
The three different types of subordinate control are described in the following
sections.
2
controlConsidering the power PLoad in a resistive load, we know that it is determined
U
by the voltage on the load, ULoad and the resistance of load, R, as follows:
Equation 3 shows that, for a constant load resistance, the power in this
resistance is proportional to U
A power controller with a U
Load2
.
2
control will regulate in such a manner that the
square of the load voltage is proportional to the signal input (e.g. 0 ... 20mA) to
the controller.
2
or P
Combining equations 5 and 4, we can see that the power in the load
resistance is proportional to the input signal to the power controller.
742011-07-01/00561073 [SCR Power Controller TYA202]
6 Special device functions
P
Load
input signal of power controller (0 ... 20 mA)
U
Last
2
R
--------------- -
(6)
Heating elements that have a positive temperature coefficient (TC), i.e. where
the electrical resistance increases with increasing temperature, are
usually driven from a power controller that incorporates a subordinate Ucontrol () (Figure 1).
These are resistive materials such as
- Kanthal-Super
- tungsten
-molybdenum
- platinum
- quartz radiators
Their cold resistance is substantially lower than their resistance when hot (by a
factor of 6 ... 16). These heating elements are usually run at temperatures
above 1000 °C.
2
Figure 1:Heating element with a positive TC
Power controllers need current limiting for the starting phase. The constant
current and the increasing resistance mean that, initially, the power in the
heating element increases in proportion to R, since the power P = I
2
· R.
When the current falls below the preset limit value, the current limiting is no
longer effective, and the power controller operates with the subordinate U
control, i. e. if the resistance continues to increase, the power fed to the
heating elements falls, since the voltage is held constant:
load
P
= automatically becomes smaller.
This effect supports the entire control loop. As the furnace temperature rises
towards the set value, the power fed to the furnace is reduced (for a given load
voltage), so the power controller itself slows the approach to the set point
2011-07-01/00561073 [SCR Power Controller TYA202]75
2
6 Special device functions
value. This damps out any tendency to overshoot the final temperature.
Other applications for U
2
control are:
- In lighting systems: In this case, the intensity of the illumination is
proportional to U
- Some resistance materials have a TC that is close to 1. These include
heating elements made from nickel /chrome, constantan etc. This does not
place any special demands on the SCR power controller (e. g. current
limiting). The resistance characteristic for a heating element with a TC » 1 is
shown in Figure 2.
2
.
Figure 2:Heating element with TC » 1
2
controlCurrent control (I2 control) is advantageous for heating elements with a
I
negative TC, where the electrical resistance becomes smaller as the
temperature increases (Figure 3).
This behavior is shown by non-metallic materials such as graphite or glass
melts. Molten glass is not usually heated by heating elements but by letting a
current flow through the melt, so that the electrical energy is converted directly
into heat in the molten material. The current is applied through electrodes.
Figure 3:Heating element with a negative TC
762011-07-01/00561073 [SCR Power Controller TYA202]
6 Special device functions
R
Alt
4
----------
P
New
U
NewINew
U
Old
2
-----------
2I
Old
U
OldIOld
P
Old
====
(12)
Looking at the power equation P = I2 · R, we can see that an I2 control has the
2
same regulatory effect on the power as already described for the U
control.
In other words, by regulating a constant current while the temperature rises,
the power in the process is automatically reduced as the resistance falls.
P controlPower control (P control) is a continuous regulation of the product U · I, the
power. In this case, there is a precise linear relationship between the output
power and the level of the signal input ( e.g. 0 ... 20mA) to the SCR power
controller.
A typical application of this type of subordinate control is for regulating heating
elements which are subject to long-term aging combined with a temperaturedependent change in resistance, as is the case with silicon carbide elements
(Figure 4).
Figure 4:Resistance changes for silicon carbide
Silicon carbide heating elements have a nominal resistance that can alter by a
factor of 4 over the long term. So when dimensioning a system, it is necessary
to provide power controllers that can produce twice the (nominal) power for
the heating elements.
This results in double the current for the SCR power controller.
Old Ⳏ old condition of the heating element RNew =
New Ⳏ new condition of the heating element
The relationship is illustrated by the following formula:
P control is also used for free-running economy circuits running off a 3-phase
supply network.
2011-07-01/00561073 [SCR Power Controller TYA202]77
6 Special device functions
Which
operating mode
is suitable for
which load?
Operating moderesistive loadInductive
burst-firing modeX
TC constant TC positive TC nega-
tive
load
Longterm aging
Burst-firing mode with
XX
a start
Burst-firing mode with
XXX
current limiting
Cascade control
2
U
2
I
XXX
XX
PXX
782011-07-01/00561073 [SCR Power Controller TYA202]
6 Special device functions
6.6Resistance limitation (R control)
.
This is only possible in power controllers with current and voltage
measurement that are fitted with cascade control P (Code 001 in
the order code) and only functions for load resistors with positive
temperature coefficient.
In three-phase economy circuits, no direct resistance limitation is
possible because the individual resistance value is not recorded.
However, the limiting function itself can be applied.
FunctionIt operates both in burst-firing mode and phase angle control.
If the current measured value for resistance exceeds the resistance limit,
limited by phase angle control or limitation of the switched sine waves.
it is
Limitation of the
power
The resistance limitation parameter can be used to activate a limitation of the
power output depending on the resistance value R when operating molybdenum disilicide heating elements in order to prevent overheating of the heating
element in the upper temperature range. By measuring the resistance of the
heating elements it is possible to assign a precise heating element temperature.
If the load resistance exceeds this value, it is limited by phase angle control or
limitation of the switched sine waves. This protects the heating element from
overheating.
2011-07-01/00561073 [SCR Power Controller TYA202]79
6 Special device functions
u
t
aa
6.7Current limiting
Factory setting No current limiting is activated.
vChapter 5.1.2 „Power controller“
6.8a start
Factory setting The phase angle of the first half-wave (a start) is not activated.
For transformer loads, the SCR power controllers are operated in burst-firing
mode with phase angle cut-back for the first half-wave.
The factory setting is an angle of 70°el. (electrical). This value can be adjusted
in the configuration level or operator level within the range of 0 ... 90°el.
6.9Monitoring of the supply voltage drop
If the effective values of the analyzed half-waves diverge from each other by
more than 10%, an alarm message is displayed and the binary output for
multi-input fault warning is switched depending on the set control direction.
Immediate firing-pulse inhibit prevents connected transformer loads from destroying the semi-conductor fuse due to a DC component.
If there are no more supply voltage drops, the firing-pulse inhibit is canceled
and the power controller continues operation e.g. with a soft start.
factory settingNo monitoring is activated.
v Chapter 5.1.5 „Monitoring“
802011-07-01/00561073 [SCR Power Controller TYA202]
6 Special device functions
6.10 Firing-pulse inhibit
The inhibit function serves for protecting the SCR power controller and the
connected devices.
InternalThe SCR output is inhibited for the following:
- Device switch-on (during the starting process)
- Reset or restart due to changes in the configuration level
- Insufficient or excessive supply voltage
- Master/slave data line interrupted
- Master/slave synchronization failed
- Setup data transmission to the device
- Device temperature higher than 115°C
- Rotary field errors
- Short-term drops in supply > 10% within a half-wave
v Chapter 5.1.5 „Monitoring“
ExternalThe SCR output can be switched off via the binary input "inhibit"
v Chapter 3.3 „Connection diagram“
or via the PROFIBUS, RS422/485 interfaces.
2011-07-01/00561073 [SCR Power Controller TYA202]81
6 Special device functions
822011-07-01/00561073 [SCR Power Controller TYA202]
7 Setup program
The setup program allows all data for the device to be conveniently set using
the PC and transmitted to the device.
To configure the power controller, simply connect the power controller
to the PC with the USB cable.
As soon as the device is switched on, this configuration data is automatically
applied.
7.1Hardware and software, minimum requirements
- PC Pentium III or higher
- 128 MB RAM, 16 MB free fixed disk memory
-CD-ROM drive
- Free USB interface, mouse connection
- Microsoft Windows® 2000/XP/Vista
7.1.1 Notes for Windows 2000/XP:
UsersIf the computer is accessed by more than one user, then the user who is
logged in must be the one who will subsequently be working with the program.
The user must have administrator rights for the installation of the software.
After installation, the rights can be restricted again.
In the event of non-observance of this information, correct and complete
installation cannot be guaranteed.
Software
versions
The software versions of the device and setup program must be compatible,
otherwise an error message will appear.
h After switching on, press on the device.
The device software version is displayed in the device information menu.
h Click "Info" in the menu bar of the setup program.
In the deviceIn the setup program
2011-07-01/00561073 [SCR Power Controller TYA202]83
7 Setup program
7.2Installation
h Install the setup program.
h Start the setup program.
h Use the supplied USB cable to connect the socket of the power controller
to a USB socket of the PC.
The connected hardware will be detected.
Installation steps
123
45
67
842011-07-01/00561073 [SCR Power Controller TYA202]
Installation steps
7 Setup program
Automatic
detection
Complete
language setting
89
1011
2011-07-01/00561073 [SCR Power Controller TYA202]85
7 Setup program
7.3Program start
h Start the setup program via the windows start menu
h Click Connect in the menu bar
DiagnosisThe diagnosis window appears at the bottom of the screen with the current
measured data. The connection has thus been established.
There is no power from the power controller during the transmission of setup
data "to the device". The device performs a restart after the transmission.
862011-07-01/00561073 [SCR Power Controller TYA202]
7.4Forgotten the code?
If you have forgotten your password, you can read out the device data via the
setup program or enter a new code.
7 Setup program
Reading out
setup data
Entering new
codes
h Perform a Data transfer
The read out codes are visible in the device data menu.
h Enter a new code
h Perform a Data transfer
After the setup data transfer, the device performs a restart and the codes
are activated.
➔ From the device
➔ To the device
2011-07-01/00561073 [SCR Power Controller TYA202]87
7 Setup program
7.5Changing the language of the device texts
The factory set language is specified in the order details. Only one language
can be transmitted to the device with the setup program.
h Connect the device to the PC using the USB cable
h Start the setup program
h Perform a Data transfer
h Edit
h Click Automatic detection and the dialog for the device language will
h Select the desired language
h Continue in the hardware assistant by clicking Continue until it is
➔Execute hardware and the hardware assistant will start
appear.
completed.
Now the device texts in the selected language have been transferred to the
setup file.
➔ From the device
h Perform a Data transfer
h Save the setup file and wait until the data transmission has been
successfully completed.
Now the device will perform a restart and texts will appear on the display in the
desired language.
➔ To the device
882011-07-01/00561073 [SCR Power Controller TYA202]
8 Fault messages and alarms
Cyclical
representation
Examples
Error messageCauseRemedy
Limit value monit.
min. value reached
Limit value monit.
max. value reached
Fault at
connected load
The symbols for input, cascade control and operating mode are displayed alternately in the info line together with error messages or information about
particular statuses.
v Chapter 8 „Fault messages and alarms“
The value has gone below the set limit
value for the min. alarm
The set limit value for the max. alarm has
been exceeded
Break or short-circuit of a load resistor.
v Chapter 6.1 „Detection of load faults“
Check why the value has gone
below the limit value.
Check why the limit value has
been exceeded.
Replace defective heating elements.
tive semi-conductor fuse“
- Check the line fuse for the
load circuit
JUMO for repair.
h Return the device
JUMO for repair.
h Return the device
2011-07-01/00561073 [SCR Power Controller TYA202]91
8 Fault messages and alarms
Error messageCauseRemedy
Slave: Attention!
high temp.
Slave: Limit.
active, high temp.
Slave: Supply volt.
too low
Slave: Supply volt.
too high
Slave: temporary
drop in supply
Device temperature is higher than 100°C- Ensure adequate ventilation
- Reduce load current
- Use SCR power controller
with higher maximum load
current
Device temperature is higher than 105°C
Device too hot!
Power is reduced.
Supply voltage is not within specified tolerance range
v Chapter 10.1 „Voltage supply, load
current“
Supply voltage is not within specified tolerance range
v Chapter 10.1 „Voltage supply, load
current“
Temporary equal proportion for transformer loads has been detected.
- Ensure adequate ventilation
- Reduce load current
- Use SCR power controller
with higher maximum load
current
Check nominal voltage of the
device type
v Chapter 1.3 „Order specifi-
cations“
Check nominal voltage of the
device type
v Chapter 1.3 „Order specifi-
cations“
Ensure stable mains supply.
v Chapter 5.1.5 „Monitoring“
Inhibit by
Inhibit input
Inhibit by
ext. inhibit
Soft start phaseThis display appears until the soft start
Current limitation
active
Resistance
limitation active
A firing-pulse inhibit has been triggered
via a potential-free contact.
No power from the power controller.
The firing-pulse inhibit has been triggered
via an interface.
has been completed.
The required output level causes an excessive load current and is therefore limited to the set value.
The desired output level leads to current/
voltage values that exceed the set load
resistance. The output level is limited to
the permissible resistance to prevent
overheating.
v Chapter 3.3 „Connection di-
agram“
Open the contact between terminal 7 and 8 on screw terminal
X_2.
v Interface manual "Ext. inhib-
it"
v Chapter 5.1.2 „Power con-
troller“
-> Soft start duration
v Chapter 5.1.2 „Power con-
troller“
-> Current limiting
v Chapter 5.1.2 „Power con-
troller“
->
922011-07-01/00561073 [SCR Power Controller TYA202]
8 Fault messages and alarms
8.1Binary signal for collective fault
This signal is used for controlling the binary output and LED K1, and can also
be read out from the power controller via the interfaces.
Using the setup program it is possible to configure which events (alarm and error messages) are to be grouped together as a binary signal for a collective
fault.
All error message are OR-linked and output as a binary signal for collective
fault on the relay output or optocoupler.
In addition, LED K1 lights up yellow.
This alarm can switch a relay at the binary output.
v Chapter 5.1.8 „Actual value output“
2011-07-01/00561073 [SCR Power Controller TYA202]93
8 Fault messages and alarms
A
B
8.2Replace defective semi-conductor fuse
Opening the
case
Caution! Risk of burns!
The device can heat up during operation at the cooling body.
The current device temperature is shown on the display.
v Operating overview (on the first cover page)
h Disconnect the built-in device from the voltage supply (all poles)
v Chapter 3.3 „Connection diagram“
h Check that the device is isolated (check that green LED Power is NOT lit)
h Press spring clip (A) to the right and lever up the plastic case (at the point
marked with an arrow) using a screwdriver (B).
A plug connection separates the display, keys and interface from the power
section and you will be able to see the semi-conductor fuse.
942011-07-01/00561073 [SCR Power Controller TYA202]
8 Fault messages and alarms
8.2.1 Accessories: Semi-conductor fuses
The design of the semi-conductor fuse differs according to the device type.