JUMO STM-RW-2, STM-RW-2/OS Operating Instructions Manual

Flue gas Thermostat
Type STM-RW-2
B 60.1540.0
Operating Instructions
10.03/00329536
Please read these Operating Instructions before commissioning the instrument. Keep the manual in a place that is accessible to all users at all times. Please assist us to improve these operating instructions, where necessary. Your suggestions will be appreciated.
661 6003-0
+49
661 6003-607
+49
All necessary settings, and where appropriate, alterations inside the instrument are described in these operating instructions. However, if any difficulties should still arise dur­ing commissioning, you are asked not to carry out any unauthorized manipulations on the unit. You could endanger your rights under the instrument warranty! Please contact the nearest subsidiary or the head office in such a case.
Contents
1 Introduction 4
1.1 Typographical conventions
1.1.1 Warning signs ................................................................................................. 4
1.1.2 Note signs ...................................................................................................... 4
1.2 Application
....................................................................................................
.........................................................................
2 Instrument identification 6
2.1 Nameplate
2.2 Type designation
.....................................................................................................
..........................................................................................
3 Mounting 7
3.1 Dimensions
3.2 Mounting the flue gas thermostat
3.3 Opening / closing the housing
3.4 Setpoint adjustment
...................................................................................................
..............................................................
....................................................................
.....................................................................................
4
5
6 6
7 8 9 9
4 Installation 10
4.1 Regulations and notes
4.2 Electrical connection
...............................................................................
.................................................................................
10 10
5 Instrument description 11
5.1 Technical data
5.2 Maintenance/fault
.............................................................................................
......................................................................................
11 11
1 Introduction
1.1 Typographical conventions
1.1.1 Warning signs
V
Danger
This sign is used when there may be are ignored or not followed correctly!
Caution
A
1.1.2 Note signs
H v
1
abc
This sign is used when there may be are ignored or not followed correctly!
Note
This sign is used when your
Reference
This sign refers to
Footnote
special attention
further information
danger to personnel
damage to equipment
is drawn to a remark.
in other chapters or sections.
if the instructions
if the instructions
Footnotes are remarks that consist of two parts:
Marking in the text and the footnote text. The marking in the text is arranged as continuous superscript numbers. The footnote text (in smaller typeface) is placed at the bottom of the page and
starts with a superscript number.
Action
This sign indicates that The individual steps are marked by this asterisk, e. g.
Open housing
refer to specific points
an action to be performed
in the text. Footnotes
is described.
4
1.2 Application
The flue gas thermostat is used for monitoring flue gas temperatures on solid­fuel boilers in dual operation with oil-heated boilers.
Caution
A
When burning solid fuels, it is necessary to ensure that they are approved in accordance with the corresponding local regulations on emission protection. If this is ignored, corrosive gases may destroy the thermostat!
1 Introduction
Operation
The flue gas thermostat operates on the principle of rod expansion. The immersion tube and the metal rod inside it have different expansion coeffi­cients, producing a temperature-dependent difference in length which acts on the microswitch through a mechanism. The microswitch is operated above a set temperature limit. After the immersion tube has cooled down by approx. 10 to 30 °C, the microswitch is reset. Should the immersion tube break, the circuit is opened permanently.
5
2 Instrument identification
2.1 Nameplate
Fig. 1 Nameplate
Identify the instrument type by the nameplate and the type designation
2.2 Type designation
STM-RW -2 STM rod thermostat with microswitch
-RW flue gas temperature monitor (ATW) with changeover
-2 with internal scale
STM-RW -2 /OS
/OS as STM-RW-2, but microswitch with 2 separate circuits
Basic type
contact
Extra code
1 x break contact (n.c.) 1 x make contact (n.o.)
6
e
The installation must be run down before mounting the flue gas thermostat
A
H
Type STM-RW-2 !
The mounting site should be easily accessible and as far as possible free from shock and vibration. The permissible ambient temperature must be observed (note possible radiant heat).
3.1 Dimensions
3 Mounting
Fig. 2 Type STM-RW-2
7
3 Mounting
3.2 Mounting the flue gas thermostat
A
The thermostat is installed The temperature probe must be at right angles to the flow direction and must be exposed to the flue gas for its entire active length. The probe end must have a clearance of at least 10 mm in the axial direction.
h
Secure the flue gas thermostat by its G 1/2 pipe thread.
without
a pocket.
Fig. 3 Installation of temperature probe
8
3.3 Opening/closing the housing
3 Mounting
Opening/closing the cover
Unscrew housing screws ( 1 )
Remove cover ( 2 ).
(1)
(1)
Fig. 4 Opening/closing the housing cover (1) Housing screws
(2) Cover
(1)
(1)
(2)
3.4 Setpoint adjustment
Open housing cover, see above
Adjust setpoint on the spindle ( 1 ) using a screwdriver.
Fig. 5 Setpoint adjustment ( 1 ) Spindle
(1)
9
4 Installation
4.1 Regulations and notes
The electrical connection must only be carried out by properly qualified per-
sonnel. The choice of cable, the installation and the electrical connection must con-
form to the requirements of VDE 0100 “Regulations on the Installation of Power Circuits with nominal voltages below 1000 V” or the appropriate local regulations.
If contact with live parts is possible while working on the unit, it must be
completely disconnected from the supply. Earth the instrument at the PE terminal with the protective earth conductor.
This cable must have at least the same cross-section as used for the supply cables. Earth cables must be wired in a star configuration to a common earth point that is connected to the protective earth of the supply. Do not loop earth cables, i.e. do not run them from one instrument to another.
4.2 Electrical connection
Make connection according to the connection diagram
10
Fig. 6 Type STM-RW-2
Fig. 7 Type STM-RW-2/OS
5.1 Technical data
5 Instrument description
Limit range
Permissible ambient temperature
Contact rating
Switching differential
Switching point accuracy referred to switch-off point
Mean ambient temperature error
standard: special version:
at probe: max. +700°C at thermostat head: max. +80°C, min. -50°C
10(2) A, 230 V AC, p.f. = 1(0.6)
0.25 A, 230 V DC
Limit range STM-RW-2 STM-RW-2/OS +40°C to +120°C 10 to 18°C 10 to 30°C +20°C to +400°C 10 to 22°C 10 to 40°C
Limit range Scale start Scale end
+40°C to +120°C
+20°C to +400°C + 0°C
switching point displacement, referred to the deviation from +22°C ~ 0.07 °C/°C
+40°C to +120°C (factory-set to +100°C)
+20°C to +400°C (factory-set to +120°C)
+ 0°C
–10°C
–15°C
+ 0°C –10°C
+ 0°C –20°C
Protection
Fusing required
Operating medium
Time constant
Operating position
Action
IP54 to EN 60 529, operation under normal conditions
16 A
flue gas
45 sec
to DIN 16 257, NL0 — NL90 (other NL on request)
to EN 60730-1 Type 2BL= automatic action with micro switch-off in operation,
no auxiliary energy supply required.
5.2 Maintenance/fault
The flue gas thermostat requires no maintenance. In the event of a fault, please contact your supplier or the head office (see back cover for address).
11
JUMO GmbH & Co. KG
Street address: Moltkestraße 13 - 31 36039 Fulda, Germany Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House Temple Bank, Riverway Harlow, Essex CM20 2TT, UK Phone: +44 1279 635533 Fax: +44 1279 635262 e-mail: sales@jumo.co.uk Internet: www.jumo.co.uk
JUMO PROCESS CONTROL INC.
885 Fox Chase, Suite 103 Coatesville, PA 19320, USA Phone: 610-380-8002
1-800-554-JUMO Fax: 610-380-8009 e-mail: Internet: www.JumoUSA.com
info@JumoUSA.com
Loading...