JUMO mTRON T Operating Manual

JUMO mTRON T
Measuring, control, and automation system
Multifunction Panel 840
Operating Manual
70506000T90Z001K000
V3.00/EN/00575639
Menu structure of the multifunction panel 840
Chapter 11 "Device manager", page 101
Chapter 9 "Alarm and event lists", page 89
Chapter 6 "Multichannel controller module", page 51
Chapter 7 "Visualization", page 53
Chapter 8 "Memory display (History)", page 85
Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
1.1 Available technical documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1.2 Base units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1.3 Input/output modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.1.4 Special modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.1.5 Operating, visualization, recording . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.1.6 Power supply units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.2 Safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.2.1 Warning symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.2.2 Note signs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.2.3 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.2.4 Qualification of personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.3 Acceptance of goods, storage, and transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.3.1 Checking the delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.3.2 Notes on storage and transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.3.3 Returning goods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.3.4 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.4 Identifying the device version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1.4.1 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
1.4.2 Order details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.4.3 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.4.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.4.5 General accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.5 System version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
2.1 Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.2 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.3 Display and control elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.4 Connection elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.5 Use of the interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.6 Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.6.1 Standard, time, and event operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
2.6.2 Eco operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2.7 Batch reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
2.7.1 General information on batches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
2.7.2 Batch texts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
3.1 General information on installation/dismounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.2 Mounting in a panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.2.1 Multifunction panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.3 Strain relief for interface cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3
Contents
3.4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
4.1 Installation notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.2 Electrical isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.3 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.3.1 Connection elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.3.2 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.3.3 Terminating resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.3.4 Voltage supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4.4 Functional test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
5.1 Operating concept and graphic elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.1.1 Status line and Title line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.1.2 Visualization window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.1.3 Function selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5.2 Operation example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6 Multichannel controller module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
7 Visualization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
7.1 Function overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
7.2 Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.3 Bar graph . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7.4 Text image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
7.4.1 Group display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
7.4.2 Channel display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
7.5 Process screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
7.6 Digital . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
7.7 Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
7.8 Current batch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
7.8.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
7.8.2 Batch control via barcode scanner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
7.9 Last completed batch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
7.9.1 Batch evaluation: Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
7.9.2 Batch evaluation: Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
7.10 Counters/Integrators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
7.10.1 Group display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
7.10.2 Individual display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
7.11 User operating level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
7.12 Enter comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
4
Contents
8 Memory display (History) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
9 Alarm and event lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
9.1 Selection from the multichannel controller module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
9.2 Selection from one of the visualizations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.3 Calling up from the memory display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.4 Acknowledgement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.5 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
10 Memory manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
11 Device manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101
11.1 Device info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
11.1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
11.1.2 CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
11.2 Audit Trail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
11.3 Program schema . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
11.3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
11.3.2 Editing programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
11.3.3 Section data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
12 Parameterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113
12.1 CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
12.2 Controller... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
12.3 HMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
12.3.1 Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
12.3.2 Counters/Integrators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
12.3.3 Batches/Plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
12.3.4 Device settings (as of system version 02) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
13 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
13.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
13.1.1 Selecting configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
13.1.2 Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
13.2 Selectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
13.2.1 Analog selector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
13.2.2 Digital selector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
13.3 Device data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
13.3.1 Device data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
13.3.2 Setup info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
13.4 Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
5
Contents
13.4.1 Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
13.4.2 Image names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
13.4.3 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
13.4.4 User operating level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
13.4.5 Colors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
13.4.6 Controller screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
13.5 Analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
13.5.1 Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
13.6 Analog variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
13.6.1 Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
13.7 Integer variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
13.7.1 Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
13.8 Digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
13.8.1 Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
13.9 Digital variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
13.9.1 Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
13.10 Text variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
13.11 Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
13.11.1Analog channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
13.11.2Digital channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
13.11.3Counters/Integrators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
13.11.4Diagram view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
13.11.5Standard operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
13.11.6Event operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
13.11.7Time operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
13.12 Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
13.13 Batches/Plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
13.13.1Binary linking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
13.13.2Batch info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
13.14 Modbus/TCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
13.15 Serial interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
13.15.1Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
13.16 Web server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
13.17 Counters/Integrators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
13.17.1General settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
13.17.2Specific settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
13.18 NV connecting lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
13.18.1NV connecting list: Analog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
13.18.2NV connecting lists: Digital . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
13.18.3Analog signals (overview) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
13.18.4Digital signals (overview) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
13.19 Undocumented parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
14 Configuration – in setup program only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
14.1 User area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
6
Contents
14.1.1 Configuring parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
14.2 Batch text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
14.3 E-mail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
14.3.1 E-mail server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
14.4 Modbus frames for reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
14.5 Modbus frames for writing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
14.6 Process screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
14.6.1 Process screen editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
14.6.2 Create process screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
14.6.3 Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
14.6.4 Authorization (as of system version 02) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
14.6.5 Object types for process screens (overview) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
14.6.6 General object features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
14.6.7 Display objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
14.6.8 Input objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
14.6.9 Preview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
15 Online parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
15.1 Display print-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
15.2 Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
15.3 Enabling of extra codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
15.4 Resetting the user list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
15.5 Date and time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
15.6 Deleting internal measurement-data memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
15.7 Calibrate / test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
15.7.1 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
15.7.2 Touch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
15.7.3 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
15.7.4 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
15.8 Writing interface texts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
15.8.1 Batch info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
15.8.2 Batch recipe exists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
15.8.3 Ext. event text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264
16 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .265
16.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
16.1.1 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
16.1.2 Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
16.1.3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
16.1.4 Case and ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
16.1.5 Approval/approval marks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
16.2 Memory requirements for measurement data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
16.3 Barcode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
16.3.1 Batch control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
7
Contents
16.3.2 Batch texts (examples) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
16.3.3 Program generator control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273
16.4 China RoHS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
8

1.1 Available technical documentation

The documents specified below are available for the measuring, control, and automation sys­tem (previous document number in parentheses).

1.1.1 General information

Product Type of documentation No. Printed PDF file
Measuring, control, and automation system
1
Accessory subject to charge
2
Includes an overview of the purpose and content of all documents
Data sheet 70500000T10... - X System manual
Setup program manual 70500000T96...
System description
1
2
70500000T90... (B 705000.0)
(B 705000.6) 70500000T98...
(B 705000.8)

1 Introduction

X-
-X
-X

1.1.2 Base units

Product Type of documentation No. Printed PDF file
Central processing unit
Data sheet 70500100T10... - X Operating manual 70500100T90...
(B 705001.0)
Modbus interface description 70500100T92...
(B 705001.2.0)
PROFIBUS-DP interface description 70500103T92...
(B 705001.2.3) digiLine interface description 70500106T92... - X Installation instructions 70500100T94...
(B 705001.4) CODESYS OPC server
operating manual Process engineering application
operating manual Operating manual
Thyristor power controller (type 70906x; integration in the measuring, control, and automation system)
70500151T90...
(B 705001.5.1)
70500152T90... - X
70500153T90... - X
-X
-X
-X
XX
-X
9
1 Introduction

1.1.3 Input/output modules

Product Type of documentation No. Printed PDF file
Multichannel controller module
Relay module 4-channel
Analog input module 4-channel
Analog input module 8-channel
Analog output module 4-channel
Digital input/ output module 12-channel
Data sheet 70501000T10... - X Operating manual 70501000T90...
(B 705010.0) Installation instructions 70501000T94...
(B 705010.4) Data sheet 70501500T10... - X Operating manual 70501500T90...
(B 705015.0) Installation instructions 70501500T94...
(B 705015.4) Data sheet 70502000T10... - X Operating manual 70502000T90...
(B 705020.0) Installation instructions 70502000T94...
(B 705020.4) Data sheet 70502100T10... - X Operating manual 70502100T90...
(B 705021.0) Installation instructions 70502100T94...
(B 705021.4) Data sheet 70502500T10... - X Operating manual 70502500T90... - X Installation instructions 70502500T94... X X Data sheet 70503000T10... - X Operating manual 70503000T90...
(B 705030.0) Installation instructions 70503000T94...
(B 705030.4)
-X
XX
-X
XX
-X
XX
-X
XX
-X
XX

1.1.4 Special modules

Product Type of documentation No. Printed PDF file
Router module Data sheet 70504000T10... - X
Installation instructions 70504000T94...
10
XX
(B 705040.4)

1.1.5 Operating, visualization, recording

Product Type of documentation No. Printed PDF file
Multifunction panel 840
Data sheet 70506000T10... - X Operating manual 70506000T90...
Modbus interface description 70506000T92...
1 Introduction
-X
(B 705060.0)
-X
(B 705060.2.0) Installation instructions 70506000T94...
Operating panels Data sheet 70506500T10... - X
Operating manual 70506500T90... - X

1.1.6 Power supply units

Product Type of documentation No. Printed PDF file
24 V power supply units
Data sheet 70509000T10... - X Operating instructions QS5.241 X ­Operating instructions QS10.241 X -
XX
(B 705060.4)
11
1 Introduction
&

1.2 Safety information

1.2.1 Warning symbols

DANGER!
This symbol indicates that personal injury caused by electrical shock may occur if the re­spective precautionary measures are not carried out.
WARNING!
This symbol in connection with the signal word indicates that personal injury may occur if the respective precautionary measures are not carried out.
CAUTION!
This symbol in connection with the signal word indicates that damage to assets or data loss will occur if the respective precautionary measures are not taken.
CAUTION!
This symbol indicates that components could be destroyed by electrostatic discharge (ESD = Electro Static Discharge) if the respective cautionary measures are not taken. Only use the ESD packages intended for this purpose to return device inserts, assembly groups, or assembly components.
READ DOCUMENTATION! This symbol – placed on the device – indicates that the associated device documentation
has to be observed. This is necessary to recognize the kind of the potential hazards as
well as the measures to avoid them.

1.2.2 Note signs

NOTE!
This symbol refers to important information about the product, its handling, or additional use.
REFERENCE! This symbol refers to further information in other sections, chapters, or manuals.
FURTHER INFORMATION!
This symbol is used in the tables and refers to further information in connection with the table.
DISPOSAL!
This device and the batteries (if installed) must not be disposed in the garbage can after use! Please ensure that they are disposed properly and in an environmentally friendly manner.
12

1.2.3 Intended use

The modules described are intended for measuring, control, an d automation t asks in an ind us­trial environment, as described in the technical data. Oth er uses or uses beyond th ose defined are not viewed as intended uses.
The modules are built according to the relevant standards and directives as well as the appli­cable safety regulations. Nevertheless, incorrect use may lead to bodily injury or property dam­age.
To avoid danger, the modules may only be used:
For the intended use
When in good order and condition
When taking into account the technical documentation provided Even if a module is used correctly and according to the intended use, it may still cause appli-
cation-related dangers (e.g. due to missing safety devices or incorrect settings).

1.2.4 Qualification of personnel

This document contains the necessary information for the intended use of the modules to which it relates.
It is intended for technically qualified personnel who have received special training and have the appropriate knowledge in the field of automation technology (measuring, process, and con­trol technology).
The appropriate level of knowledge and the technically fault-free implementation of the safety information and warnings contained in the technical documentation provided are prerequisites for risk-free mounting, installation, and startup as well as for ensuring safety when operating the described modules. Only qualified personnel have the required specialist knowledge to cor­rectly interpret and implement the safety information and warnings contained in this document in specific situations.
1 Introduction
13
1 Introduction

1.3 Acceptance of goods, storage, and transport

1.3.1 Checking the delivery

Ensure that the packaging and contents are not damaged
Check that the delivery is complete using the delivery papers and the order details
Inform the supplier immediately if there is any damage
Store damaged parts until clarification is received from the supplier

1.3.2 Notes on storage and transport

Store the module in a dry and clean environment. Observe the admissible ambient condi­tions (see "Technical data")
The transport of the module is to be shockproof
The original packaging provides optimum protection for storage and transport

1.3.3 Returning goods

In the event of repair, please return the module in a clean and complete state. Use the original packaging to return goods.
Accompanying letter for repair
Please include the completed accompanying letter for repair when returning goods. Do not forget to state the following:
Description of the application and
Description of the error that has occurred
The accompanying letter for repair can be downloaded online from the manufacturer's website (use the search function if necessary).
Protection against electrostatic discharge (ESD)
(ESD = electrostatic discharge) To prevent damage from ESD, electronic modules or component s must be handled, packaged,
and stored in an ESD-protected environment. Measures against electrostatic discharge and electrical fields are described in DIN EN 61340-5-1 and DIN EN 6 1340-5-2 "Protection of elec­tronic devices from electrostatic phenomena".
When returning electronic modules or components, please note the following:
Sensitive components must only be packaged in an ESD-protected environment. Work­spaces such as this divert electrostatic charges to ground in a controlled manner and pre­vent static charges due to friction capacities.
Only use packaging for ESD-sensitive modules/components. These must consist of con­ductive plastics.
No liability can be assumed for damage caused by ESD.
14
CAUTION!
Electrostatic charges occur in non-ESD protected environments. Electrostatic discharges can damage modules or components. For transport purposes, use only the ESD packaging provided.

1.3.4 Disposal

Disposing of the device
DISPOSAL!
Devices and/or replaced parts should not be placed in the refuse bin at the end of their ser­vice life as they consist of materials that can be recycled by specialist recycling plants.
Dispose of the device and the packaging material in a proper and environmentally friendly manner.
For this purpose, observe the country-specific laws and regulations for waste treatment a nd disposal.
Disposing of the packaging material
The entire packaging material (cardboard packaging, inserts, plastic film, and plastic bags) is fully recyclable.
1 Introduction
15
1 Introduction
(A)

1.4 Identifying the device version

1.4.1 Nameplate

Position
The nameplate (A) is affixed to the case.
Content
It contains important information. This includes:
Device type
Compare the specifications on the nameplate with the order. Identify the supplied device version using the order details of the respective module.
Part no. (TN)
The part no. clearly identifies an article in the catalog. It is important for communication between the customer and the sales department.
16
Description Designation on the name-
plate
Device type Typ 705060/8-00-00-36/213 Part no. TN 00580746 Fabrication number F-Nr 0070033801211010006 Voltage supply - DC 24 V +25/-20 %
Example
Fabrication no. (F-Nr)
Among other things, the fabrication number contains the date of production (year/week). Example: F-Nr = 0070033801211010006 The figures concerned are in positions 12, 13, 14, and 15 (from the left). The device was therefore produced in the 1st calendar week of 2011.

1.4.2 Order details

(1) Basic type
705060 Multifunction panel 840 (1x Ethernet (RJ45), 1x system bus In (RJ45), 1x system bus
Out (RJ45), 2x USB host)
(2) Version
8 Standard, with factory settings
(3) Interface Com1
00 Not used 51 RS232 Modbus RTU 54 RS422/485 Modbus RTU
1 Introduction
(4) Interface Com2
00 Not used 51 RS232 Modbus RTU 54 RS422/485 Modbus RTU
(5) Voltage supply
36 DC 24 V +25/-20 %
(6) Extra codes housing
000 No extra code 444 Stainless steel front with design foil (neutral)
(7) GL approval
000 Without approval 062 With GL approval
(8) Extra codes
000 No extra code 213 Recording function
1
The power supply unit used must also have a GL type approval (e.g. type 705090).
(1) (2) (3) (4) (5) (6) (7) (8)
Order code /---/ , , Order example 705060 / 8 - 00 - 00 - 36 / 000 , 000 , 213
1
17
1 Introduction

1.4.3 Scope of delivery

1 multifunction panel 840 in the ordered version 8 mounting elements 1 strain relief for interface cable 1 template for panel cut-out 1 Installation Instructions

1.4.4 Accessories

Description Part no.
Extra codes (activations): Recording function (extra code 213) 00569508 Additional accessories: Bar code scanner Gryphon GD4130 00407798 Memory stick USB 2.0 (2 GB)
1
The specified USB memory stick is tested and designed for industrial use. No liability is assumed for other brands.
1
00505592

1.4.5 General accessories

Description Part no.
JUMO mTRON T system manual, English 00575577 Setup program with program editor JUMO mTRON T (on MiniDVD), incl. USB cable
(A-plug to mini-B-plug, 3 m) Program editor JUMO mTRON T (on MiniDVD), incl. USB cable (A-plug to mini-B-
plug, 3 m) PCA3000/PCC JUMO software package 00431884 PC Evaluation Software PCA3000 00431882 Release automatic print for PC Evaluation Software PCA3000 00505548 PCA Communication Software PCC 00431879 Plant Visualization Software JUMO SVS3000: See data sheet 700755 ­USB cable A-plug mini-B-plug 3 m 00506252
Content of the Mini-DVD:
Setup program with program editor JUMO mTRON T in case of part no. 00569494
Program editor JUMO mTRON T in case of part no. 00622333
CODESYS programming software (free version)
CODESYS Repository Package - Operating panels (free version)
GSD file JUMO mTRON T - CPU (free version)
PC Evaluation Software PCA3000 (30-day trial version)
PCA Communication Software PCC (30-day trial version)
Documentation in PDF format
00569494
00622333
18

1.5 System version

The system version of the measuring, control, and automation system is determined by the compatibility index of the base unit.
Example composition of a version number for the central processing unit: 248.xx.yy 248 = basic version, xx = compatibility index (system version), yy = current version In this document, functions which depend on the system version are marked accordingly (e.g.
"as of system version 02").
1 Introduction
19
1 Introduction
20

2.1 Brief description

Com1 / Com2
RS232 (Modbus RTU) or RS422/485 (Modbus RTU)
Voltage supply
Setup
USB device interface for setup program or communication software
Bus Out (system bus)
For connection to a router
LAN (Ethernet)
Mainly for use of the integrated web server, the setup program, the visualization software, or the communication software
Bus In (system bus)
For connection to a base unit or router
USB1 / USB2
USB host interface to read data via memory stick
705060
The multifunction panel 840 with TFT -touchscreen allows easy and clearly-arran ged measured data visualization, operation, configuration, and parameterization of the system.
The TFT color screen has a screen size of 21.3 cm (8.4“), a resolution of 640 × 480 pixels, 256 colors, and LED backlight.
As the interface between man and machine, the panel allows an optimum and clearly-arranged view of the process status and the system parameters. In addition, it is perfe ctly suitable for the display and operation of controller screens, process screens, the program editor, and the op­tional recording function. Setpoint values, batch text, parameters, and configuration data can be directly entered and changed by the user on the screen.
The process data that is transmitted by the system bus is shown in real time. Data archiving and evaluation is made possible by established PC-programs.
In addition to the standard interfaces (LAN, USB), two optional serial interfaces can be con­nected to a barcode scanner, modem, or other Modbus devices (master, slave).
The user can comfortably configure the multifunctional panel 840 with the setup p rogram. And many functions are also configurable directly on the multifunction panel 840.

2.2 Block diagram

2 Description

21
2 Description
(1) (2)

2.3 Display and control elements

(1) Front with decor foil (2) Screen (touchscreen)
22

2.4 Connection elements

(1) (2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
2 Description
(1) USB device interface (setup) (2) USB host interface 1 (3) USB host interface 2 (4) System bus In (5) System bus Out (6) LAN interface (7) Com1 interface (8) Com1 terminating resistor (9) Com2 interface (10) Com2 terminating resistor
(11) Voltage supply In, DC 24 V (12) Functional grounding
CAUTION!
Functional grounding: Connection terminal for functional ground. To meet the specified EMC characteristics, this terminal must be connected to functional ground.
23
2 Description

2.5 Use of the interfaces

Interface Used for ...
USB device interface Setup program USB host interface 1 Connection of a USB memory stick USB host interface 2 Connection of a USB memory stick System bus In Connection to base unit
System bus Out Connection to router module LAN interface Setup program
Com1 interface Connection to Modbus master device
Com2 interface Connection to Modbus master device
Connection to router module
•Web server
Mail server
Connection to Modbus slave devices
Connection of a barcode reader
Connection of a modem
Connection to Modbus slave devices
Connection of a barcode reader
Connection of a modem
24

2.6 Operating modes

NOTE!
The operating modes play a role in the configuration of the groups of the multifunction panel. This chapter contains the necessary basic knowledge relating to the operating modes.
Chapter 13.11.5 "Standard operation", page 158Chapter 13.11.6 "Event operation", page 161Chapter 13.11.7 "Time operation", page 162
NOTE!
Groups can only be configured if the extra code "Registration function" is active. The user can see whether this extra code is active via the "Device info" function. If the extra code is not active, the user can subsequently activate this using the setup pro­gram.
Chapter 11.1 "Device info", page 104Setup program:
P
ROJECT > HARDWARE ARRANGEMENT > HMI > GENERAL > OPTIONS

2.6.1 Standard, time, and event operation

2 Description
The operating modes decide the rate at which measurement data is saved.
3 operating modes
The multifunction panel has 3 operating modes:
Standard operation
Time operation
Event operation
The following settings are among those that can be made for each of the three operating modes:
Memory values
Memory rate
Memory values
The "Memory values" parameter specifies whether the average, minimum, maximum, and cur­rent values of the period between two memory rates or the peak values (envelope diagram) will be saved. With the "Min./max. values" setting, the minimum and maximum value of the last capture period (memory rate) are saved. An additional option for the "Memory value" parameter is "Eco operation". This is a special memory mode that is described separately in Chapter 2.6.2 "Eco operation", page 27.
Memory rate
The "Memory rate" parameter specifies the time between 2 saved values. The diagram feed speed corresponds to the memory rate, i.e. with a memory rate of 5 s, for example, the memory value will be entered into the diagram every 5 s.
Standard operation
If the multifunction panel is not in event or time operation, standard operation is active.
25
2 Description
Time operation
For time operation, the user can enter a time frame (max. 24 hours) during which a specific memory value and a specific memory rate will be active.
Event operation
Event operation is activated via the control signal, which is assigned e.g. to an event or an alarm. For example, event operation can be used to reduce the memory rate when an alarm is activated.
Priority
The priority of the operating modes with regard to one another is allocated as follows:
Operating mode Priority
Standard operation Low Time operation Medium Event operation High
Active operating mode
The active operating mode is shown in the diagram using the various symbols after the current diagram feed speed (memory rate):
Operating mode Symbol
Standard operation Time operation Event operation
Memory requirements
A memory space of 99 MB is available for measurement data recording. The space required depends on the data records which shall be stored. The following information can be used as a basis for a rough estimate:
Group of 6 analog inputs and 6 digital inputs, per storage: max. 48 byte
Group of 6 analog inputs and 6 digital inputs, memory rate 125 ms, per second: 225 byte
Report, regardsless of the type of report (daily, monthly, ...): 151 byte
Counter/integrator (at closing): 25 byte
Batch (at closing): 2 kB
Alarm/event entry: 6 byte
Audit-Trail message: 100 byte
Examples for a group of 6 analog inputs and 6 digital inputs: Memory rate 1 s: 4.1 MB/day; 124 MB/month Memory rate 30 s: 0.13 MB/day; 4,1 MB/month (plus memory required for all other data records)
26

2.6.2 Eco operation

t1 t1
(1)
(1)
The parameters for eco operation are set in the menu for standard operation. However, eco operation can be used with all three operating modes.
In eco operation, the instantaneous values (current values) are recorded in a specified mini­mum memory rate (independent of the tolerance band).
(1) Tolerance band
t1 Saving via "Min. memory rate" (controlled save)
2 Description
The value for the tolerance band (1) is stated with regard to the unit of the analog channels (e.g. ± 1 °C). If the measured values exit the tolerance band and if the new measured valu e out side of the tolerance band is present at least for the duration of the memory rate configured in the active operating mode, it will be recorded, saved, and provided with a new tolerance band.
27
2 Description
10s
10s
10s
10s
10s
10s 10s 10s
t
t1
t2
t3
t4
10s
t6
t5
t1 Saved via "Min. memory rate" (controlled save) and new tolerance band is set. t2 Not saved, as the measur ed value at the e nd of the memo ry rate (10 s) is once again within the
tolerance.
t3 The new tolerance b and is saved and set, as the measured value at the end of the memory rate
had left the tolerance band.
t4 The new tolerance b and is saved and set, as the measured value at the end of the memory rate
had left the tolerance band. t5 Saved via "Min. memory rate" (controlled save) and new tolerance band is set. t6 Not saved, as the measur ed value at the e nd of the memo ry rate (10 s) is once again within the
tolerance.
NOTE!
It is not mandatory to register when the tolerance band has been exited. If the measured val­ues return to the tolerance band within the memory rate (t2), no registration takes place; the "Min. memory rate" is always active.
28

2.7 Batch reporting

NOTE!
Batch reporting (batches) can also be configured and used without the extra code "Registra­tion function". A typical application of the batches without the extra code "Registration function " is the trans­mission of texts to the PLC (central processing unit).
The configuration of the batches is described in the following chapter: Chapter 13.13 "Batches/Plants", page 167

2.7.1 General information on batches

Batches enable the design of a flexible form for the description of a batch process within the multifunction panel. A maximum of nine batches can be recorded simultaneously.
The batches can be controlled (start/stop) via one of the digital signals (control signals), via the touchpad (interface on the screen), or via a barcode scanner.
Further information on control using a barcode reader can be found in: Chapter 7.8.2 "Batch control via barcode scanner", page 71
2 Description
For batches, a distinction is made between two visualizations. The following are available:
Current batch report
Completed batch report Further information on visualization can be found in:
Chapter 7.8 "Current batch", page 69Chapter 7.9 "Last completed batch", page 74
29
2 Description
(1) (2)
(3)
(4)
(5)

2.7.2 Batch texts

How can something be edited?
(1) Text left column (2) Text right column (3) Batch number (4) Batch start, end, duration (5) Batch selection
Text left column
The text in the left column or the left half of the screen can be edited on the multifunction panel and using the setup program.
Multifunction panel:
C
ONFIGURATION > HMI > BATCHES/PLANTS > BATCH 1 TO 9 > BATCH INFO 1 TO 10 > TEXT
LEFT
Setup program:
HMI > C
INFO
Text right column
The text in the right column or half of the screen can be edited on the multifunction panel and using the setup program.
Multifunction panel:
C
ONFIGURATION > HMI > BATCHES/PLANTS > BATCH 1 TO 9 > BATCH INFO 1 TO 10 > TEXT
RIGHT
and
C
ONFIGURATION > HMI > BATCHES/PLANTS > BATCH 1 TO 9 > BATCH INFO 1 TO 10 > FACTO-
RY SETTING
COLUMN
ONFIGURATION LEVEL > BATCHES/PLANTS > BATCH 1TO 9 > BATCH INFO > BATCH
1 TO 10 > EDIT > TEXT LEFT COLUMN
COLUMN
30
Multifunction panel:
V
ISUALIZATION > CURRENT BATCH
Then change the batch if required and implement the edit by activating the yellow text
1
fields.
Setup program:
HMI > C
INFO
ONFIGURATION LEVEL > BATCHES/PLANTS > BATCH 1TO 9 > BATCH INFO > BATCH
1 TO 10 > EDIT > TEXT RIGHT COLUMN
and
HMI > C
INFO
ONFIGURATION LEVEL > BATCHES/PLANTS > BATCH 1TO 9 > BATCH INFO > BATCH
1 TO 10 > EDIT > FACTORY SETTING
Batch number
Permanent changes to the batch number can only be made on the multifunction panel. Multifunction panel:
P
ARAMETERIZATION > HMI > BATCHES/PLANTS > BATCH NUMBER 1 TO 9
It can be temporarily changed on the multifunction panel; HMI batch number will be incremented and reactivated.
Batch start, end, duration
If the batch start, end, and duration are used, the lines can no longer be edited.
2 Description
2
at the end of a batch, the internal
Batch selection
This function is used to directly select and display one of the active batches. Simply touch one of the batch names displayed after calling up the function.
NOTE!
The function is only available if more than one batch is active.
1
Only available if the respective batch parameter "Editable?" is set to Yes.
2
Only available if the respective batch parameter "Editable?" is set to Yes.
31
2 Description
32

3 Installation

3.1 General information on installation/dismounting

DANGER!
With multichannel controller module 705010 and relay module 705015, the load circuits from relay or solid state relay outputs can be operated with a dangerous electrical voltage (e.g. 230 V). There is a risk of electric shock. Prior to the installation/dismounting of these modules or the removal of the module insert, the load circuits are to be disconnected from the voltage and the terminal strips are to be re­moved from the module. This work must only be performed by qualified personnel.
WARNING!
The modules must never be installed in areas with an explosion hazard. There is the risk of an explosion. The entire system must only be used outside of areas with an explosion hazard.
Mounting site
All modules have protection type IP20 and are only intended for use in fireproof con trol cabinets or switch boxes. The mounting site should be virtually vibration-free. Electromagnetic fields caused by equipment such as motors or transformers should be avoided.
Multifunction panel 840 has protection type IP67 at the front and is intended for installation in a panel cut-out. The rear has protection type IP20.
Climatic conditions
The ambient temperature and the relative humidity at the mounting site must correspond to the technical data. Aggressive gases and vapors have a negative ef fect on the operating life of the modules. The mounting site must be free from dust, powder, and other suspended matter so that the cooling slots do not become blocked.
DIN rail
All modules are mounted on a DIN rail according to DIN EN 60715 (35 mm × 7.5 mm × 1 mm). For reasons of stability, the spacing of the fastening screws for the DIN rail should not exceed 200 mm. The minimum distances for the modules that are specified in the module-specific in­stallation or operating instructions must be observed.
Installation position
The DIN rail should be mounted horizontally so that all modules are arranged vertically. Other­wise the admissible ambient temperature range will be restricted.
Space requirement
The modules require the minimum distances shown in the following figure for the purpose of installation/dismounting and for future maintenance or replacement. In the event of shorter dis­tances the minimum bending radius of the cables, the performance of the electrical inst allation, and the clear arrangement of the plant are no longer guaranteed.
33
3 Installation
(A)
(B)
(B2)
(A1)
(C)
(C)
(C3)
(C3)
(D)
(D4)
(C)
(C)
(C)
(C)
(C)
(C)
(C3)
(C3)
(C3)
(C3)
(C3)
(C3)
(B2)
(B)

3.2 Mounting in a panel

3.2.1 Multifunction panel

Mounting a multifunction panel 840 (705060)
Procedure:
Step Activity
1 Insert the device (A) into the panel cut-out (A1) from the front until the two side springs (B)
click into place (B2). The springs facilitate the mounting, but do not replace the fastening elements (step 2).
2 Insert the fastening elements (C) into the recesses of the case (C3) and use a screwdriver
(D) to evenly clamp them against the rear side of the panel with a torque of 0.5 Nm (D4).
NOTE!
The provided template is to be used to create the panel cut-out. This is the only way to guar­antee optimum positioning of the multifunction panel.
34

3.3 Strain relief for interface cable

(A)(B)
(B)
3 Installation
(A) Panel for strain relief (B) Fastening screws
Procedure:
Step Activity
1 Loosen the fastening screws (B) (do no t re mo ve ). 2 Place the panel for strain relief (A) on the case and retighten the fastening screws (B).
NOTE!
The interface cables can be attached to the panel using cable ties for strain relief.
NOTE!
If the cable shield is connected to the case of the multifunction panel, the exterior sheathing of the interface cable must be removed at the location of the strain relief.
35
3 Installation
58
5
235
195
219
31
51
179

3.4 Dimensions

36

4.1 Installation notes

NOTE!
These installation notes apply for the entire measuring, control, and automation system and, on some occasions, are only applicable for a specific module. The respective connection diagram shows the context.
Requirements for the personnel
Work on the modules must only be carried out to the extent described and, like the electrical connection, only by qualified personnel.
Before plugging and unplugging connection cables ensure that the person performing the work is electrostatically discharged (e.g. by touching grounded metallic parts).
Cables, shielding, and grounding
When selecting the cable material, when installing, and when performing the electrical con­nection of the module, the regulations of DIN VDE 0100 "Erection of power installations with rated voltages up to 1000 V" and the respective national regulations (e.g. on the basis of IEC 60364) are to be observed.
Certain cables must be heat resistant up to at least 80 °C at maximum load. The relevant instructions in the connection diagram of the affected modules must be observed.
Route input, output, and supply cables separately and not parallel to one another.
Only use shielded and twisted probe and interface cables. Do not route the lines close to current-carrying components or cables.
For temperature probes, ground the shielding on one side in the control cabinet.
Do not perform loopthroughs on the grounding cables, but route the cables individually to a shared grounding point in the control cabinet; in doing so, ensure that the cables are as short as possible. Ensure that the equipotential bonding is correct.

4 Electrical connection

Electrical safety
Isolate power supply units from the voltage supply on the primary side if there is a risk of touching parts with dangerous electrical voltage (e.g. 230 V) in the course of work.
The fuse rating of the power supply units on the primary side should not exceed a value of 10 A (inert).
With modules with relay or solid state relay outputs, the load circuits can be operated with a dangerous electrical voltage (e.g. 230 V). Disconnect load circuits from the voltage supply during installation/dismounting and electrical connection.
In order to prevent the destruction of the relay or solid state relay outputs in the event of an external short circuit in the load circuit, the load circuit should be fused to the maximum ad­missible output current.
The modules are not suitable for installation in areas with an explosion hazard.
In addition to a faulty installation, incorrectly set values on the module could also impair the correct function of the following process. Therefore, ensure that safety devices independent of the module (e.g. overpressure valves or temperature limiters/monitors) are available and that it is only possible for qualified personnel to define settings. Please observe the corre­sponding safety regulations in this context.
37
4 Electrical connection
USB device interface
System bus In
Interface Com2
»
Voltage supply DC 24 V
Interface Com1
»
AC 1500 V
»
AC 1000 V
System bus Out
AC 1500 V
LAN
AC 1500 V
AC 30 V DC 50 V
AC 30 V DC 50 V
USB host interface 1
USB host interface 2
References to other information
The electromagnetic compatibility meets the standards and regulations cited in the techni­cal data.
The USB device interface and voltage supply in the central processing unit 705001 are not electrically isolated. In general, please observe the specifications regarding electrical isola­tion.

4.2 Electrical isolation

38

4.3 Connection diagram

(1) (2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
CAUTION!
At maximum load, the temperature at the "+24 V" and "GND" terminals (Voltage supply In) may exceed 60 °C. As a result the insulation of the cable may be damaged. The cable must be heat resistant up to at least 80 °C.

4.3.1 Connection elements

4 Electrical connection
(1) USB device interface (setup) (2) USB host interface 1 (3) USB host interface 2 (4) System bus In (5) System bus Out (6) LAN interface (7) Com1 interface (8) Com1 terminating resistor (9) Com2 interface (10) Com2 terminating resistor
(11) Voltage supply In, DC 24 V (12) Functional grounding
CAUTION!
Functional grounding: Connection terminal for functional ground. To meet the specified EMC characteristics, this terminal must be connected to functional ground.
39
4 Electrical connection
8
1
8
1
6
7
8
9
2
3
4
5
1
6
7
8
9
2
3
4
5
1
6
7
8
9
2
3
4
5
1

4.3.2 Interfaces

Connection Designation Connection element
USB device Setup
USB host USB1,
USB2
System bus In, System bus Out
Bus In, Bus Out
1 TX+ 2 TX­3 RX+ 6 RX-
Ethernet LAN 1 TX+
2 TX­3 RX+ 6 RX-
Serial interface (RS232), optional
Serial interface (RS422), optional
Com1, Com2
Com1, Com2
2 RxD 3 TxD 5 GND
3 TxD+ 4 RxD+ 5 GND 8 TxD­9 RxD-
Serial interface (RS485), optional
Com1, Com2
3 TxD+/RxD+ 5 GND 8 TxD-/RxD-
Transmit data + Transmit data ­Receive data + Receive data -
Transmit data + Transmit data ­Receive data + Receive data -
Receive data Transmit data Ground
Transmit data + Receive data + Ground Transmit data ­Receive data -
Transmit/receive data + Ground Transmit/receive data -
40

4.3.3 Terminating resistors

2
1
3
4
ON
332 ?
120 ?
332 ?
GND
+5 V
4
9
332 ?
120 ?
332 ?
GND
+5 V
3
4
3
8
1
2
U
+
-
x
The internal terminating resistors for the Com1 and Com2 interfaces are only relevant for RS422/485.
The terminating resistors are deactivated by default. To activate them, DIP switches 1 to 4 for the relevant interface must be pushed upward using a suitable tool such as a ballpoint pen (ON position).
The following figure shows the position of the DIP switches when the terminating resistors are activated.
NOTE!
To ensure fault-free operation, terminating resistors are required at the start and end of an RS422/485 transmission path.
Internal terminating resistors
4 Electrical connection

4.3.4 Voltage supply

Connection Terminals Symbol and terminal designation
24 V DC +24 V and GND +24 V
GND
41
4 Electrical connection

4.4 Functional test

Once the electrical connection is complete, the following points must be checked:
1) Voltage supply
2) Connection to system bus
3) Errors during initialization
Voltage supply
If Then
the voltage supply is present the multifunction panel star ts.
Connection to system bus
The "Bus In" input must be connected to a "Bus Out" output of a base unit or a router module.
Errors during initialization
If errors occur during the initialization, the user must monitor the configuration of the system using the setup program and rectify errors.
the screen shows a start picture.
Startup
The checks described above complete the process of installation and electrical connection. For startup, use the additional documentation (operating manual or system manual).
The "Introduction" chapter of this document contains an overview of all documentation for the measuring, control, and automation system.
42

5.1 Operating concept and graphic elements

(1)
(2)
(3)
Operating concept
The operating concept of the multifunctional panel is as clear and simple as you could imagine. The user controls the panel by touching the screen (touchscreen) with a fingertip.

5 Operation

(1) Status and title line (2) Visualization window (3) Function selection
NOTE!
Do not use any objects that are sharp or have sharp edges, otherwise the screen may be scratched.
43
5 Operation
(1) (2) (3)
(2)

5.1.1 Status line and Title line

This line displays alarm and error messages as well as general information on the active dis­play (e.g. sampling rate). It is automatically hidden by the system if required.
(1) Area for text and e rror messages; if the text
is displayed with a red background, it relates to an alarm (error message)
(3) Area fo r symbols relating to communication
with other modules
Symbol (2) Meaning
Sampling rate (5 s) and operating mode (standard operation) Sampling rate (125 ms) and operating mode (event operation) Sampling rate (1 s) and operating mode (time operation) Data read-out is currently being performed by the PCA communication software
PCC.
Symbol (3) Meaning
Base unit is in RUN status Base unit is in STOP status Communication with base unit not interrupted Communication with base unit interrupted Communication with base unit interrupted
(2) Area for symbols relating to the panel
44
NOTE!
If the text is displayed with a read background, it relates to an error message.

5.1.2 Visualization window

(1)
(2)
The visualization of the measuring data and control data takes place in this area of the screen (underneath the status and title line and above the function selection). The area for the config­uration of the system will continue to be used.
Example: Visualization of a controller (controller screen)
5 Operation
Example: Visualization of an analog channel
(1) Diagra m header (2) Diagram
45
5 Operation
(1)
(1)
Diagram header
The diagram header (the numerical measured value display on the screen) is displayed directly underneath the status and title line and is available in the following display types:
•Diagram
History (of diagram display)
•Digital
The diagram header can be switched on and off.
(1) Alarm
NOTE!
A channel alarm is marked orange (Alarm1) or red (Alarm2). The colors can be configured in the setup program.
Diagram
Under History (for the diagram display), the user can switch between the min. and max. display if the diagram header is switched on. Whether the min. and max. values are available simulta­neously depends on the current operating mode setting of the group.
Diagram header in the Diagram visualization:
Diagram header in the digital visualization:
46
(1) Symbols
In the area of the diagram (graphic measured value display), various symb ols are displa yed in addition to the measurement data. Alarm diagrams are marked red or orange (this can be con­figured using the setup program).
Symbol Meaning
(1)
(2)
(3)
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11)
Comment was entered Event has occurred Alarm no longer present (on multifunction panel) Alarm was reported (on multifunction panel) Event has occurred (on base unit)
In addition, the communication with the operator (device configuration, inspection of alarm and event lists, etc.) is performed in the visualization window.

5.1.3 Function selection

5 Operation
(1) Set functions (2) Variable functions with changing symbols (3) Function is performed if the user touches
the screen
The functions of the multifunction panel are selected in the function selection area. The sym­bols in area (2) change depending on the function performed.
The function selection of the normal display is subsequently shown if the vertical diagram (di­agram display) has been selected.
(1) Device manager (2) Memory manager (3) Alarm and event lists (4) Controller (5) Visualization
(visualization of current data) (7) Memory display (History) (8) Diagram view (9) Channel rotation (10) Group rotation
(1 1) Normal display (Home)
(6) Group selec tion
NOTE!
If not all functions can be selected, the functions must first be released by changing the con­figuration. The setup program may be required for this purpose.
47
5 Operation

5.2 Operation example

Start
An analog channel is displayed.
Operation
Step Activity
1 Select the Visualization menu by touching the touchscreen.
The "Visualization" menu is shown.
48
Step Activity
2 Select bar graph display by touching the touchscreen.
5 Operation
The "Bar graph" display mode is started.
49
5 Operation
50

6 Multichannel controller module

(1)
(2)
(3)
This chapter describes the visualization and operation of the control channels and the program generator.
Select the multichannel controller module or the program generator
The multichannel controller module or the program generator is selected via the button that is highlighted.
(1) Exit function (2) Program generator (3) Multichannel controller module (controller
Exit function
Touch the screen here to exit the function and return to the visualization from which it was called up.
Prog. generator
After this function is called up, an overview of the nine program generators will be shown. Touching an entry will open the corresponding generator screen.
The operation of the program generators is described in operating manual B 705001.0
(central processing unit).
The program generators can also be controlled by a barcode scanner (select program number , start and stop program).
Chapter 16.3.3 "Program generator control", page 273
screen)
51
6 Multichannel controller module
Multichannel controller module (controller screen)
If only one controller channel is configured, then the corresponding controller screen will be dis­played immediately.
If multiple controller channels are configured, an overview of the active controller channels will be shown. Selecting a controller channel also opens the corresponding controller screen.
The operation of the controller channels is described in operating manual B 705010.0 (mul-
tichannel controller module).
52
Selecting visualization
The type of visualization (diagrams, bar graph, etc.) is initiated using the button shown above. The following maximum selection of visualizations is available.

7 Visualization

Step Activity
1 Select the desired visualization by touching the screen.
The visualization is displayed.
Example: Diagram
The available functions at the bottom of the screen vary depending on the visualization select­ed.
53
7 Visualization

7.1 Function overview

Diagram
Chapter 7.2 "Diagram", page 56
Bar graph
Chapter 7.3 "Bar graph", page 58
Text image
Chapter 7.4 "Text image", page 60
Process screen
Chapter 7.5 "Process screen", page 64
Digital
Chapter 7.6 "Digital", page 65
Reports
Chapter 7.7 "Reports", page 67
Current batch
Chapter 7.8 "Current batch", page 69
Completed batches
54
Chapter 7.9 "Last completed batch", page 74
Counters/Integrators
Chapter 7.10 "Counters/Integrators", page 78
User operating level
Chapter 7.11 "User operating level", page 81
Enter comments
There is no separate function selection for entering comment s. The current one is retain ed until the function is called up. The comment entered is recorded in the event list.
Chapter 7.12 "Enter comments", page 82
NOTE!
The first five functions in the function selection (from the left) are the same in all five visual­izations. These relate to superordinate functions. Changes can only be made to the final six functions.
7 Visualization
55
7 Visualization
(1)
(2)
(3)
(5) (6) (7) (8) (9) (10)
(4)

7.2 Diagram

In this visualization, the individual signals run across the screen from top to bottom (vertical dis­play).
(1) Alarm (2) Operating mode (3) Alarm (4) Communication status (5) Group selection (6) Memory display (7) Numerical measured value display (8) Channel rotation (9) Group rotation (10) Home button
Horizontal present ati on
As of system version 03, the analog and digital channels can also be displayed horizontally. The header rows of the vertical presentation (channel name, ana log value, switch symbol) are then shown on the right of the analog and digital traces.
Alarm
An alarm (Alarm1 or Alarm2) is marked with an orange or red background and an orange or red diagram. The colors can be configured in the setup program and using the multifunction panel.
Sampling rate and operating mode
Chapter 5.1.1 "Status line and Title line", page 44
Communication status
Chapter 5.1.1 "Status line and Title line", page 44
56
Group selection
(1) (5)(2)
(3) (4)
(1)
This function is used to directly select and display one of the active groups. Simply touch one of the group designations displayed after calling up the function.
NOTE!
The function is only available if more than one group is active.
Memory display
This function is used to start the display of the data available in the history memory. Chapter 8 "Memory display (History)", page 85
Numerical measured value display
This function can be used to show and hide the numerical measured value display (diagram header) and the digital tracks, and to activate the envelope diagram display.
Chapter 5.1.2 "Visualization window", page 45
Channel rotation
This function activates the display of various limits. Touching the button repeatedly shifts the channel limits within the group and then subsequently hides them.
7 Visualization
NOTE!
The function is only available if more than one analog channel is active in a group.
Group rotation
In contrast to the "Group selection" function, in which any group can be selected, this function displays the groups one after the other.
NOTE!
The function is only available if more than one group is active.
(1) Range start (2) Limit value 1 (3) Current measured value (4) Limit value 2 (5) Range end (6) Memory display
(1) Group number
57
7 Visualization
(1)
(3)
(6) (7) (8)
(2)
(5)
(4)
Home button
This function calls up a defined visualization. The function must be activated and configured via the setup program.
Setup program:
HMI > C

7.3 Bar graph

In this visualization, the analog channels are displayed numerically and as a bar graph (col­umns). In addition to the analog channels, the digital channels are displayed at the bottom of the screen.
ONFIGURATION LEVEL > SCREEN > USER OPERATING LEVEL
(1) Alarm (2) Communication status (3) Limit value 1 (4) Alarm (5) Limit value 2 (6) Group selection (7) Group rotation (8) Home button
NOTE!
If only the digital channels are to be shown, the "Digital" visualization is recommended. Chapter 7.6 "Digital", page 65
Alarm
An alarm (Alarm1 or Alarm2) is marked with an orange or red background and an orange or red bar. The colors can be configured in the setup program and using the multifunction panel.
Communication status
Chapter 5.1.1 "Status line and Title line", page 44
58
Group selection
(1)
This function is used to directly select and display one of the active groups. Simply touch one of the group designations displayed after calling up the function.
NOTE!
The function is only available if more than one group is active.
Group rotation
In contrast to the "Group selection" function, in which any group can be selected, this function displays the groups one after the other.
(1) Group number
NOTE!
The function is only available if more than one group is active.
7 Visualization
Home button
This function calls up a defined visualization. The function must be activated and configured via the setup program.
Setup program:
HMI > C
ONFIGURATION LEVEL > SCREEN > USER OPERATING LEVEL
59
7 Visualization
(5) (7) (8)
(3)
(4)
(1)
(2)
(6)

7.4 Text image

In this visualization, the analog channels are displayed numerically together with the channel designation and the channel description. In addition to the analog channels, the digital chan­nels can be visualized on the right side of the screen.

7.4.1 Group display

(1) Channel name (2) Channel description (3) Communication status (4) Alarm (5) Group selection (6) Channel display (7) Group rotation (8) Home button
Communication status
Chapter 5.1.1 "Status line and Title line", page 44
Alarm
Group selection
An alarm (Alarm1 or Alarm2) is marked with an orange or red background. The colors can be configured in the setup program and using the multifunction panel.
This function is used to directly select and display one of the active groups. Simply touch one of the group designations displayed after calling up the function.
NOTE!
The function is only available if more than one group is active.
60
Channel display
(1)
The function switches to the channel display. Chapter 7.4.2 "Channel display", page 62
Group rotation
In contrast to the "Group selection" function, in which any group can be selected, this function displays the groups one after the other.
(1) Group number
NOTE!
The function is only available if more than one group is active.
Home button
This function calls up a defined visualization. The function must be activated and configured via the setup program.
Setup program:
HMI > C
7 Visualization
ONFIGURATION LEVEL > SCREEN > USER OPERATING LEVEL
61
7 Visualization
(7) (9) (10)
(3)
(6)
(1)
(2)
(8)
(5)
(4)

7.4.2 Channel display

(1) Channel name (2) Channel description (3) Communication status (4) Limit value 2 (5) Limit value 1 (6) Alarm (7) Channel selection (8) Group display (9) Channel rotation (10) Home button
Communication status
Chapter 5.1.1 "Status line and Title line", page 44
Alarm
An alarm (Alarm1 or Alarm2) is marked with an orange or red background. The colors can be configured in the setup program and using the multifunction panel.
Channel selection
This function is used to select and display one of the active analog channels. Simply touch one of the channel names displayed after calling up the function.
NOTE!
The function is only available if more than one analog channel is active in the selected group.
Group display
The function switches to the group display. Chapter 7.4.1 "Group display", page 60
62
Channel rotation
In contrast to the "Channel selection" function, in which any channel can be selected, this func­tion displays the channels one after the other.
NOTE!
The function is only available if more than one analog channel is active in the selected group.
Home button
This function calls up a defined visualization. The function must be activated and configured via the setup program.
Setup program:
HMI > C
7 Visualization
ONFIGURATION LEVEL > SCREEN > USER OPERATING LEVEL
63
7 Visualization
(2)
(4)
(1)
(3)

7.5 Process screen

In this visualization, selected measurement signals and backgrounds are displayed in a maxi­mum of 18 process screens. The screens are prepared and configured using the setup pro­gram.
Scope per process screen:
1 background image, 640 × 480 pixels, max. 256 colors
150 objects, such as analog and digital signals, icons, texts, bar graphs, and switch ele­ments
Setup program:
HMI > S
ETUP ONLY > PROCESS SCREENS
(1) Communication status (2) Example: Text and analo g channe l (nu meri-
(3) Example: Text and analog channel (bar
graph)
NOTE!
In the visualization of analog channels in the process screen, there is no color change in the event that a limit value is not reached or is exceeded. A color change can be realized, how­ever, with the PLC function (extra code 224 required for central processing unit 705001).
Communication status
Chapter 5.1.1 "Status line and Title line", page 44
Home button
This function calls up a defined visualization. The function must be activated and configured via the setup program.
64
cal)
(4) Home button
Setup program:
(1)
(3) (4) (5) (6) (7)
(2)
HMI > C

7.6 Digital

In this visualization, only the digital channels are displayed; the analog channels are not shown.
7 Visualization
ONFIGURATION LEVEL > SCREEN > USER OPERATING LEVEL
(1) Operating mode (2) Communication status (3) Group selection (4) Memory display (5) Numerical measured value display (6) Group rotation (7) Home button
Horizontal present ati on
As of system version 03, the digital channels can also be displayed horizontally. The header rows of the vertical presentation (channel name, switch symbol) are the n shown on the right of the digital traces.
Sampling rate and operating mode
Chapter 5.1.1 "Status line and Title line", page 44
Communication status
Chapter 5.1.1 "Status line and Title line", page 44
65
7 Visualization
(1)
Group selection
This function is used to directly select and display one of the active groups. Simply touch one of the group designations displayed after calling up the function.
NOTE!
The function is only available if more than one group is active.
Memory display
This function is used to start the display of the data available in the history memory. Chapter 8 "Memory display (History)", page 85
Numerical measured value display
This function can be used to show and hide the numerical measured value display (diagram header) and the digital tracks, and to activate the envelope diagram display.
Chapter 5.1.2 "Visualization window", page 45
Group rotation
In contrast to the "Group selection" function, in which any group can be selected, this function displays the groups one after the other.
NOTE!
The function is only available if more than one group is active.
Home button
This function calls up a defined visualization. The function must be activated and configured via the setup program.
Setup program:
(1) Group number
HMI > C
ONFIGURATION LEVEL > SCREEN > USER OPERATING LEVEL
66

7.7 Reports

(2)
(3)
(5)
(9) (10) (11) (12)
(4)
(1)
(6)
(7)
(8)
This lists every report on all of the analog channels in a group. Each group has its own config­urable report.
7 Visualization
(1) Current report (2) Type of report (3) Completed report (4) Communication status (5) Maximum (6) Minimum (7) Average (8) Period (9) Group selection (10) Channel rotation
(11) Group rotation (12) Home button
Current report
The report data of the current capture period is displayed in this area. The title of the report is composed of the channel name and the report type.
Type of report
This function is used to switch between the individual report types for the current channel. To display a different report type, the user simply needs to touch the corresponding button (in this example, from "Total" to "Extern").
Completed report
The report data of the previous capture period is displayed in this area.
Maximum
The current maximum value of the current capture period is displayed in this area. In addition to the value and the unit, the date is also displayed.
67
7 Visualization
(1)
Minimum
The current minimum value of the current capture period is displayed in this area. In addition to the value and the unit, the date is also displayed.
Average
The current average of the current capture period is displayed in this area.
Period
The start (date and time) and the current time of th e current capture period are displayed in this area. The current time is saved at the end of a capture per iod. The st art a nd end a re therefore recorded.
Group selection
This function is used to directly select and display one of the active groups. Simply touch one of the group designations displayed after calling up the function.
NOTE!
The function is only available if more than one group is active.
Channel rotation
This function is used to switch between the individual channels of the active group.
Group rotation
In contrast to the "Group selection" function, in which any group can be selected, this function displays the groups one after the other.
(1) Group number
NOTE!
The function is only available if more than one group is active.
Home button
This function calls up a defined visualization. The function must be activated and configured via the setup program.
Setup program:
HMI > C
ONFIGURATION LEVEL > SCREEN > USER OPERATING LEVEL
68

7.8 Current batch

(1)
(3)
(4)
(6) (7) (8)
(5)
(2)

7.8.1 General information

Using the multifunction panel, nine different batches (batch reports) can be recorded and reg­istered in parallel. In the visualization, a distinction is made between a "current batch" and the last "completed batch". The number of batch reports used and the text in the batch visualization can be configured on the multifunction panel or using the setup program.
7 Visualization
(1) Batch start/batch end (2) Batch texts, "left column" (3) Batch status (4) Batch texts, "right column" (5) Communication status (6) Batch selection (7) Batch rotation (8) Home button
Batch start/batch end
Batch texts, "left column"
If the batch start was selected using the touchpad, then the batch reporting is started and ended by touching the button. If a different type of batch start has been selected, the button is inactive.
NOTE!
There must be at least 5 seconds between the end of a batch (batch end) and the next start (batch start). A new batch can only be started once this period has elapsed.
The texts in the "left column" are predetermined by the configuration and cannot be changed during batch reporting.
69
7 Visualization
(1)
Batch status
The batch status indicates whether batch reporting is in progress or is waiting for a start sign al.
Batch reporting is waiting for start signal Batch reporting is active, data is recorded
Batch texts, "right column"
The texts in the "right column" are predetermined by the configuration and can be changed in various ways prior to the start of and during batch reporting.
Texts that are displayed on the multifunction panel with a yellow background can be changed directly by the user.
Procedure:
Step Activity
1 Touch text with yellow background. 2 Select or enter new text (depending on configuration).
The changed batch texts are saved at the end of a batch report togeth er with the batch data.
These are subsequently reset to the original texts (depending on the configuration).
Chapter 7.8.2 "Batch control via barcode scanner", page 71
Communication status
Chapter 5.1.1 "Status line and Title line", page 44
Batch selection
This function is used to directly select and display one of the active batches. Simply touch one of the batch names displayed after calling up the function.
NOTE!
The function is only available if more than one batch is active.
Batch rotation
In contrast to the "Batch selection" function, in which any batch can be selected, this function displays the batches one after the other.
(1) Batch name
NOTE!
The function is only available if more than one batch is active.
70
Home button
BATCH1
BATCH2
This function calls up a defined visualization. The function must be activated and configured via the setup program.
Setup program:
HMI > C
ONFIGURATION LEVEL > SCREEN > USER OPERATING LEVEL

7.8.2 Batch control via barcode scanner

If a barcode scanner is connected to the multifunction p anel and correctly configured, the batch start, the batch end, and the entry of batch texts in a current batch report can be controlled us­ing a barcode scanner. The barcodes used all correspond to the type "Code39".
Prerequisites
The interface to which the barcode scanner is connected must have the "Report" type con­figured to Barcode.
If the batch start and batch end can be activated, the "Batch start" parameter must be con­figured to Barcode.
For each line in the right-hand column of the batch visualization that is to be entered using the barcode scanner, the "Text right column" parameter must be configured to Barcode.
7 Visualization
Activating the batch
NOTE!
Prior to entering commands using a barcode scanner, the corresponding batch visualizat ion 1 to 9 must be prepared for the barcode commands by scanning "BATCH1 to 9", indepen­dent of whether or not this is automatically shown. Instead of the key words "BATCH1 to 9“ it is possible to scan the batch name. Thereby it is important to pay attention to the exact spelling (allowed are capital letters A-Z, numbers 0-9, special characters $%/+.- and space character).
Showing the batch report
If one of the visualizations is active and nothing is currently being edited or entered, th e current batch report can be shown using the barcode scanner. The requirements for this are that the batch is active and the parameter
C
ONFIGURATION > HMI > SCREEN > BARC. -> CURR. BATCH = Yes
. Activate batch report for batch 1 and show if required:
Activate batch report for batch 2 and show if required:
71
7 Visualization
BATCH3
START
STOP
Activate batch report for batch 3 and show if required:
Chapter 16.3 "Barcode", page 269
Starting and ending batch report
If the batch report for start/end is configured using the barcode reader, it is started and ended as follows.
Starting batch report:
Step Activity
1 Scan barcode for batch reporting (batch 1 to 9). 2 Scan Start.
Ending batch report:
Step Activity
1 Scan barcode for batch reporting (batch 1 to 9). 2 Scan Stop.
NOTE!
If batch reporting is stopped, texts that were activated using a barcode are reset to the default text or retained in the current batch report, depending on the "Delete line" parameter. The texts are saved in the completed batch report.
72
Activating batch texts
TOOTHED DI SK 34
RES ET
If a line of a batch report is configured for the barcode activation, the activation is performed as follows.
Activating text:
Step Activity
1 Scan barcode for batch reporting (batch 1 to 9). 2 Scan text.
The first line of the activated batch report, which is configured for text entry via barcode, is
automatically filled with the text corresponding to the barcode. If multiple lines are config­ured for the barcode activation, these are processed consecutively from top to bottom.
7 Visualization
NOTE!
A bar code can contain up to 10 batch texts which are separated by dollar signs (total lenght max. 63 characters). When scanning, the texts are written consecutively from top to bottom in the appropriately configured lines of the activated batch report.
Resetting entry
Scanning Reset:
Step Activity
1 Scan Reset.
The default texts (parameter factory settings) are displayed and the first line is prepared for
the entry again.
Barcodes summary
All necessary barcodes are summarized again in Chapter 16.3 "Barcode", page 269.
NOTE!
The batch control codes (BATCH1 to BATCH9, START, STOP, RESET) cannot be used to set batch texts.
73
7 Visualization
(1)
(4) (6) (7)
(3)
(2)
(5)

7.9 Last completed batch

(1) Batch texts, "left column" (2) Batch texts, "right column" (3) Communication status (4) Batch selection (5) Batch evaluation (6) Batch rotation (7) Home button
Communication status
Chapter 5.1.1 "Status line and Title line", page 44
Batch selection
This function is used to directly select and display one of the active batches. Simply touch one of the batch names displayed after calling up the function.
NOTE!
The function is only available if more than one batch is active.
Batch evaluation
Completed batches can be evaluated in two ways:
Diagrams (graphic visualization)
Report (numerical visualization)
Chapter 7.9.1 "Batch evaluation: Diagrams", page 75Chapter 7.9.2 "Batch evaluation: Report", page 76
74
Batch rotation
(1)
(1)
In contrast to the "Batch selection" function, in which any batch can be selected, this function displays the batches one after the other.
NOTE!
The function is only available if more than one batch is active.
Home button
This function calls up a defined visualization. The function must be activated and configured via the setup program.
Setup program:
(1) Batch name
HMI > C
ONFIGURATION LEVEL > SCREEN > USER OPERATING LEVEL
7 Visualization

7.9.1 Batch evaluation: Diagrams

(1) End batch evaluation
The operation of the batch evaluation corresponds to the operation of the function "Memory dis­play".
Chapter 8 "Memory display (History)", page 85
End batch evaluation
This function is used to end the evaluation; the "Last completed batch" visualization is called up again.
75
7 Visualization
(1)
(6) (8)
(2)
(3)
(4)
(5) (7)
(1)

7.9.2 Batch evaluation: Report

(1) Specifications for maximum (2) Specifications for minimum (3) Specifications for average (4) Specifications for batch start and batch end (5) Group selection (6) Channel rotation (7) Group rotation (8) End batch evaluation
Group selection
This function is used to directly select and display one of the active groups. Simply touch one of the group designations displayed after calling up the function.
NOTE!
The function is only available if more than one group is active.
Channel rotation
This function is used to switch between the individual channels of the active group.
Group rotation
In contrast to the "Group selection" function, in which any group can be selected, this function displays the groups one after the other.
76
(1) Group number
NOTE!
The function is only available if more than one group is active.
End batch evaluation
This function is used to end the evaluation; the "Last completed batch" visualization is called up again.
7 Visualization
77
7 Visualization
(2)
(4)
(7) (8)
(3)
(1)
(5)
(6)

7.10 Counters/Integrators

This visualization displays the current counter and integrator statuses as well as the operating hours counter. 12 counters/integrators (channels) can respectively b e displayed in a joint over­view or individually. The counter , integrator, and operating hours counter feature is determined by the configuration of the device.

7.10.1 Group display

(1) Group display (2) Individual display (3) Communication status (4) Channel description (5) Co un te r/ i nt eg ra to r status (6) Alarm (7) Group rotation (8) Home button
Group display
By touching the respective tab, the user can display 12 counters/integrators in a joint overview . Chapter 7.10.1 "Group display", page 78
Individual display
Communication status
By touching one of the counter/integrator numbers, the user can switch to the corresponding individual display.
Chapter 7.10.2 "Individual display", page 79
Chapter 5.1.1 "Status line and Title line", page 44
78
Alarm
(2)
(4)
(11) (12)
(3)
(1)
(6)
(10)
(5)
(8) (9)
(7)
An alarm (Alarm1 or Alarm2) is marked with an orange or red background. The colors can be configured in the setup program and using the multifunction panel.
Group rotation
The function switches to the next counters/integrators.
NOTE!
This function is only available if sufficient counters/integrators have been configured.
Home button
This function calls up a defined visualization. The function must be activated and configured via the setup program.
Setup program:
HMI > C
ONFIGURATION LEVEL > SCREEN > USER OPERATING LEVEL

7.10.2 Individual display

7 Visualization
(1) Group display (2) Individual display (3) Communication status (4) Type of capture period (5) Channel name and channel description (6) Counter/integrator status (7) Limit value 1 (8) Limit value 2 (9) Alarm (10) Data of the last recorded period
(11) Group rotation (12) Home button
79
7 Visualization
Group display
By touching the respective tab, the user can display 12 counters/integrators in a joint overview . Chapter 7.10.1 "Group display", page 78
Individual display
By touching one of the counter/integrator numbers, the user can switch to the corresponding individual display.
Chapter 7.10.2 "Individual display", page 79
Communication status
Chapter 5.1.1 "Status line and Title line", page 44
Alarm
An alarm (Alarm1 or Alarm2) is marked with an orange or red background and an orange or red bar. The colors can be configured in the setup program and using the multifunction panel.
Group rotation
The function switches to the next counters/integrators.
NOTE!
This function is only available if sufficient counters/integrators have been configured.
Home button
This function calls up a defined visualization. The function must be activated and configured via the setup program.
Setup program:
HMI > C
ONFIGURATION LEVEL > SCREEN > USER OPERATING LEVEL
80

7.11 User operating level

(1)
(3) (4) (5)
(2)
In this visualization, the displays configured by the user are used by the multifunction panel. Setup program:
HMI > C
ONFIGURATION LEVEL > SCREEN > USER OPERATING LEVEL
7 Visualization
(1) Type of visualization (2) Communication status (3) Visualization selection (4) Visualization rotation (5) Home button
Type of visualization
The visualization to be displayed is shown here. The available function buttons – between (3) and (4) in the image – will be used differently depending on the type. The functions are de­scribed in the respective sections in this chapter.
Communication status
Visualization selection
Visualization rotation
Chapter 5.1.1 "Status line and Title line", page 44
This function is used to directly select one of the configured visualizations. Simply touch one of the visualizations displayed after calling up the function.
In contrast to the "Visualization selection" function, in which any visualization ca n be selected, this function displays the available visualizations one after the other.
81
7 Visualization
(1)
(2)
(3)
Home button
This function calls up a defined visualization. The function must be activated and configured via the setup program.
Setup program:
HMI > C

7.12 Enter comments

This function can be used to enter a text (max. 31 characters) that is entered following the com­pletion of the entry in the event list of the multifunction panel and in the batch reports.
In the diagram display, for example, the text entry is marked with a pencil.
ONFIGURATION LEVEL > SCREEN > USER OPERATING LEVEL
(1) Input mask (2) Communication status (3) Function selection
Input mask
Here, the text entered by the user is displayed during the entry phase.
Communication status
Chapter 5.1.1 "Status line and Title line", page 44
Function selection
The available functions depend on the active visualization. The functions are described in the respective sections in this chapter.
82
Further information
Chapter 9 "Alarm and event lists", page 89Kapitel 7.2 „Diagram“
You can find the text again in the event list under the entry "All events", as well as in the corre­sponding batch.
7 Visualization
83
7 Visualization
84

8 Memory display (History)

The "Memory display" function can be used to display and check data recorded using t he mul­tifunction panel. The size of the memory for the memory display can be configured.
Setup program:
HMI > C
The memory display can be activated in the "Diagram" and "Digital" visualizations and is also used to display completed batch reports.
NOTE! The memory display can only be called up if the parameter HMI > C
ROUPS > GROUP X > STATUS is set to "Display / Save" in the configuration of the group.
G
Selecting the memory display
The memory display is selected via the button shown above.
Example: Calling up the memory display in the "Diagram" visualization
ONFIGURATION LEVEL > DEVICE DATA > HISTORY MEMORY
ONFIGURATION LEVEL >
85
8 Memory display (History)
(1)
(2)
(3)
(8) (9) (10) (11) (12) (13)
(4)(2)
(5) (6) (7)
Overview
(1) Diagram header (2) Recording data (3) Cursor (4) Communication status (5) Event list (6) Scroll by line (downward) (7) Scroll by line (upward) (8) Scroll by page (downward) (9) Scroll by page (upward) (10) Zoom and search
(11) Diagram view (12) Channel rotation
(13) Exit memory display
Diagram header
The diagram header is only displayed if it is also displayed in the visualization from which the "Memory display" function is called up.
Recording data
In the status and title line, the following data on the current cursor position is displayed:
•Date
Magnification (Zoom factor)
Memory rate
Cursor
After the "Memory display" function is called up, a cursor is shown in the centre of the visual­ization window. The corresponding measured values are shown in the diagram header. In the status and title line, the corresponding time of the current position, the memory rate that was applicable at this time, and the magnification are displayed.
The cursor can be controlled by the user by touching the visualizat ion window with a finger and using the functions (6) to (9).
86
Communication status
Chapter 5.1.1 "Status line and Title line", page 44
Event list
This function is used to display the event list of the visible groups. In the list, the message near­est to the current cursor position is displayed.
Chapter 8 "Memory display (History)", page 85
Scroll by line
This function is used to move the cursor in the visualization window downward and/or upward. The data in the diagram header and in the status an d title line is updated with each movement. If the cursor reaches the edges of the window , the measured value diagram is moved automat­ically and the desired data is shown.
Scroll by page
This function is used to move the display along by an entire screen (page). The data in the di­agram header and in the status and title line is updated with each movement. If required, the sensor automatically positions the cursor at the end of the window.
Zoom and search
This function influences the number of measured values used to calculate a pixel. Th e user can search for measured values according to date and according to time.
8 Memory display (History)
If the user touches "Exit", the dialog window is closed and the display is not changed.
Zoom
The factory setting is "1:1", which means that each measured value in the history memory is displayed. "1:2" means that every second measured value is displayed, etc.
Step Activity
1 To uc h a zo om fact or.
The dialog window is closed automatically and the new zoom factor is activated.
Adjust
87
8 Memory display (History)
(1) (5)(2)
(3) (4)
This function is only available when the data of a completed batch is being displayed. If this function is selected, the zoom factor will automatically be adjusted such that the measured val­ue diagram of the completed batch can be displayed in a window. However, the 1:1 display is to be used for evaluating a batch.
Search
Touching "Search" displays the dialog window for entering the date.
Step Activity
1 Select time and date. 2 Exit the dialog by touching the "OK" button.
If the date entered is in the history memory , the cursor is moved to the desired position and
the data is displayed.
Diagram view
This function determines whether the min. or max. values are displayed in the diagram header (numerical measured value display). Min. or max. values result from there being more mea­sured values recorded than the amount shown. This is the case if "Min./max. value recording" has been activated for an operating mode of a group.
In addition, the user can use this function to decide whether a curve progression is to be shown or hidden.
Channel rotation
This function activates the display of various limits. Touching the button repeatedly shifts the channel limits within the group and then subsequently hides them.
(1) Range start (2) Limit value 1 (3) Current measured value (4) Limit value 2 (5) Range end (6) Memory display
NOTE!
The function is only available if more than one analog channel is active in a group.
Exit memory display
This function is used to exit the display of the data available in the internal working memory of the device.
88

9 Alarm and event lists

All alarms, events, and faults of the entire system are entered in the alarm and event lists. Alarm lists only relate to the multifunction panel. Events and faults can come from the multi­function panel and from the base unit (e.g. central processing unit).
NOTE!
The alarms of the multifunction panel are only entered in the alarm list for as long as the alarm is present. If the alarm disappears again, the corresponding message will also be removed from the alarm list.
NOTE!
In most cases, the user can configure whether a process (e.g. the exceeding of a specific value at an analog input) constitutes an alarm or event.
NOTE!
Event lists contain all events that have occurred, including all alarms and faults.
NOTE!
Each of the lists can contain a maximum of 150 entries. The lists are deleted in the event of reconfiguration.
NOTE!
The lists are not updated whilst the corresponding window is open. Remedy: Touch the "Update" button.
89
9 Alarm and event lists
Detecting alarms and faults
The user can detect the presence of an alarm or a fault on the basis of the color of the bell sym­bol.
If... Then...
(green bell) there is no alarm and no fault.
(red bell) there is an alarm.
(yellow bell) there is a fault.
Selecting alarm and event lists
The alarm and event lists are selected via the button that is highlighted.
The user can make the selection in various places:
Selection from the multichannel controller module (Chapter 6 "Multichannel controller module", page 51)
Selection from one of the visualizations, such as Diagram (Chapter 7.1 "Function overview", page 54)
Selection from the memory display (Chapter 8 "Memory display (History)", page 85).
90
9 Alarm and event lists
(1)
(1)
(2)
(4)
(3)
(2)
(3)

9.1 Selection from the multichannel controller module

Overview
(1) Exit function (2) Module selection (3) View list (4) View list
Exit function
Touch the screen here to exit the function and return to the visualization from which it was called up.
Module selection
Touch the screen here to expand or collapse the corresponding branch of a module in the tree.
List type
Touch the screen here to expand or collapse the corresponding branch in the tree.
View list
Touch the screen here to display the corresponding list. In the lists, in addition to the distinction between alarm and event, there is a further distinction
between two types:
Display of all alarms and/or events (independent of the batch to which these relate)
Display of alarms and/or events that relate to a specific batch
NOTE!
The number of batch-related lists depends on the quantity of the active batch.
Setup program:
HMI > C
ONFIGURATION LEVEL > BATCHES/PLANTS
91
9 Alarm and event lists
(1) (2)
(3)
(4)
(5)
(6)
Event list (HMI)
The following figure shows "All events" from a multifunction panel.
Exit function
Touch the screen here to exit the function and return to the visualization from which it was called up.
Details
If the space for an entry within the list is insufficient, more information on the selected entry can be shown by touching the button.
Update
The display is not cyclically updated. This function is used to update the display, i.e. the system searches for new entries that are not yet present in the list.
Symbols
Chapter 9.5 "Symbols", page 95
Selected entry
The user can select or mark an entry by touching it. The "Details" function can be used to show additional information. This re quires there to be ad-
ditional information available for the selected entry.
(1) Exit function (2) Details (3) Update (4) Symbols (5) Selected entry (6) Scroll display
92
9 Alarm and event lists
(1)

9.2 Selection from one of the visualizations

This function corresponds to the previous chapter. Chapter 9.1 "Selection from the multichannel controller module", page 91

9.3 Calling up from the memory display

If the "Alarm and event lists" function is selected from a memory display, the system displays the events immediately. There are no alarm lists.
The list is limited to the results that are relevant for the group being displayed. The message located nearest to the position of the cursor is highlighted in the list.
(1) Cursor
Event list (HMI)
The following figure shows "All events" from a multifunction panel.
93
9 Alarm and event lists
(1)

9.4 Acknowledgement

Alarms that are sent from the base unit to a multifunction panel must be acknowledged by the user.
(1) Acknowledgement
Acknowledgement
With this function, the user must acknowledge an alarm within the alarm list. Until the alarm has been acknowledged, it will remain in various locations on the multifunction panel.
NOTE!
The "Acknowledgement" function is only available if a user is logged on and acknowledge­ment rights have been allocated to him/her.
NOTE!
The user can configure additional acknowledgements in terms of functions that trigger an alarm. If this is the case, both acknowledgements must be carried out.
94

9.5 Symbols

(yellow bell) Fault (green bell) Outgoing alarm (alarm no longer present) (red bell) Incoming alarm (alarm present)
(no symbol) Additional messages
9 Alarm and event lists
Power on (device was switched on) Power off (device was switched off)
Comment Incoming event (e.g. digital input is closed) Outgoing event (e.g. digital input is opened)
95
9 Alarm and event lists
96
The memory manager contains functions for data exchange between the multifunction panel
(1)
(1)
and a USB memory stick.
Memory manager symbol
(1) Memory manager symbol
The memory manager can be identified by the system using various symbols.

10 Memory manager

This displays the free internal memory with regard to data read-out using a USB memory stick.
This displays the free internal memory with regard to data read-out via an interface.
This displays the free memory of the connected USB memory stick.
Selecting memory manager
The memory manager is not selected by touching the button that is highlighted; it is selected automatically and always when a USB memory stick is inserted into the multifunction panel.
(1) Memory manager functions
97
10 Memory manager
NOTE!
The memory manager functions are only available if a user is logged on and he/she has been allocated the rights for the functions.
NOTE!
In some functions – e.g. in the alarm and event lists – the memory manager only becomes active when the user leaves or exits the function.
NOTE!
The USB memory stick must not be removed whilst data is being transferred to or from the memory stick.
NOTE!
The "Update USB-stick" function reads out data that has not yet been read out. Once it has been read out, the data is marked as read in the device but is not deleted. The "Backup -> USB-stick" function reads out all the data of the internal memory, including the data that has already been read out. This function is therefore ideal for test and service work.
NOTE!
The USB memory stick is not intended to be permanently inserted into the USB socket, as the fact that it is not locked in place means there is no protection against accidental removal.
Safely remove hardware
The user should always call up this function before removing a USB memory stick. This is the only way to ensure that the files on the data carrier will be saved correctly.
If the message "Safe To Remove Hardware" appears, the data carrier can be removed.
Update USB-stick
Measurement data that has not been saved to a USB memory stick is writt en onto the data car­rier.
Backup -> USB-stick
All measurement data in the memory (even data that has already been retrieved) is written to the data carrier.
Save all + update USB
All reports that are running are completed and written to the data carrier along with the mea­surement data that has not yet been saved. The current counter and integrator statuses are also saved.
98
Service data -> USB stick
Special data is saved onto the USB memory stick.
NOTE!
The update must only be performed by a service technician from the manufacturer.
Software update
This function serves to read in new device software (firmware). For this purpose, a special USB memory stick is required that contains the firmware data. These data are available from the manufacturer if required.
NOTE!
This function must only be performed if the user is requested to do so by a service technician from the manufacturer.
10 Memory manager
99
10 Memory manager
100
Loading...