The JUMO eTRON M is a compact, digital electronic thermostat for simple temperature
control (heating or cooling). The measurement input permits the connection of resistance
thermometers or thermocouples, or standard current or voltage signals. The measured
value is shown on a 3-digit backlit display. The switching states of relays K1 and K2 are
indicated by two LEDs.
The instrument incorporates a simple defrosting function as well as an operating hours
counter, which can, for instance, be used to record the operating time of a cooling
compressor.
The instrument can be operated from 4 keys on the front panel. The electrical connection
is made via screw terminals on the back of the instrument.
A setup program and a PC interface are available as accessories, for simple configuration
and parameterization from a PC.
Block structure
Data Sheet 70.1060
Type 701060/XX2...
Page 1/4
Key features
k Integrated defrosting function
k Heating or cooling is configurable
k Limit monitoring
k Available for resistance thermometer,
thermocouple, standard current or
voltage signals, according to choice
k Choice of a 10A relay or
two 5 A relays
k Adjustable switching hysteresis
k Time-delayed switch-on after
power-on is selectable, e. g. for
staggered starting of several
equipment units
k Operating hours counter
k Symbols for operating modes, °C, °F,
hours, minutes and seconds in display
k Parameter level protected by code
k Setup program for configuration and
archiving via PC
k Customized linearization via tabular
function in the setup program
k UL approval
Displays and controls
LC display3-digit segment display, 13 mm high, and symbols for temperature
unit, h, min, s, defrosting and heating, with red background lighting
Status
indication
Keys
Setup
interface
02.07/00440437
LED K1/K2 lights up when relay K1/K2 is energized.
LED K1/K2 goes out when relay K1/K2 is de-energized.
for start-stop
programming
increase parameter value
decrease parameter value
The instrument is linked to the PC via a PC interface with TTL/RS232
converter and adapter (3-pin).
Technical data
Data Sheet 70.1060JUMO GmbH & Co. KG • 36035 Fulda, GermanyPage 2/4
Measurement
input
Resistance
thermometer
DesignationMeasuring rangeMeas. accuracy1/
ambient
temperature error
Pt100 EN 60 751-200 to +600°C0.1%/ ≤100ppm/°Cis recognizedis recognized
Pt1000 EN 60 751-200 to +600°C0.1%/ ≤100ppm/°Cis recognizedis recognized
= 0Ωis recognized
Measuring current for Pt100: 0.2 mA, for Pt1000, KTY2X-6 and resistance: 0.02 mA
Lead compensation is adjustable via the parameter Lead compensation resistance
The total resistance (sensor+lead) must not exceed 320Ω for Pt100 and 3200Ω for Pt1000, KTY2X-6 or resistance.
ThermocoupleFe-Con J EN 60 584-200 to +999 °C0.4%/ ≤100ppm/°C
Fe-Con L DIN 43 710-200 to +900 °C0.4%/ ≤100 ppm/°C
NiCr-Ni K EN 60 584-200 to +999 °C0.4%/ ≤100ppm/°C
-10 to 60 mV customer table
3
0.1%/ ≤100ppm/°C
2
2
2
3
-is recognized
-is recognized
-is recognized
-is recognized
For the voltage input (-10 to 60 mV), terminal temperature compensation can be used for thermocouples.
Internal terminal temperature compensation can be switched off via the setup program (0°C).
Current0 — 20 mA-2 to 22 mA
0.1%/ ≤100ppm/°C
3
--
scalable with and
or customer table
4 — 20 mA2.4 to 21.6 mA
0.1%/ ≤100ppm/°C 3is recognizedis recognized
scalable with and
Input resistance R
Voltag e0 — 10 V-1 to 11 V
IN
≤ 3Ω
0.1%/ ≤100ppm/°C--
scalable with and
or customer table
Input resistance RIN ≥ 100kΩ
1.) The accuracies refer to the measuring range span.
2.) valid from -50°C
3.) A valid customer table must be entered via the setup program and changed over to in the instrument. This may reduce the measuring accuracy.
Additional data
Sampling time250 msec
Input filter1st order digital filter; filter constant adjustable from 0.1 — 99.9sec
Measurement offsetadjustable from -99.9 to +99.9 via the parameter
Special featuresdisplay of temperature unit: °C, °F (Fahrenheit) or switched-off
Customer tableThe setup program acquires a maximum of 20 value pairs and uses them for the linear interpolation
of 20 new calibration points.
Ambient conditions
Ambient temperature range0 to +50°C, with side-by-side mounting: 0 to +40°C
Storage temperature range-40 to +70°C
Climatic conditions≤ 75% rel. humidity, no condensation
Cleaning and care of front panelThe front panel can be cleaned with all the usual cleaning and rinsing agents.
Do not use solvents such as methylated spirit, white spirit, P1 or xylene!
Output
1 relay (changeover contact)
for Type 701060/XX1-XX
2 relays (make contacts)
for Type 701060/XX2-XX
150,000 operations at 10A 250V AC 50Hz resistive load
100,000 operations at 5A 250 V AC, 50Hz resistive load
Supply
Supply voltage230V AC +10/-15%, 48 — 63Hz or 115 V AC +10/-15%, 48 — 63Hz (isolated from measurement input)
12 — 24V DC +15/-15 %, 24V AC +15/-15%, 48 — 63Hz (not isolated from measurement input)
Power consumption<3VA
Housing
Materialpolycarbonate
Mountingin panel cut-out with bezel seal
Operating positionunrestricted
Weightapprox. 160g
Protectionfront IP65, rear IP20
Flammability class UL 94 V0
02.07/00440437
Data Sheet 70.1060JUMO GmbH & Co. KG • 36035 Fulda, GermanyPage 3/4
Electrical data
Data backupEEPROM
Connectionvia screw terminals for wire cross-section up to 4 mm
and 2.5 mm
Electromagnetic compatibility
interference emission
immunity to interference
Operating conditionsThe instrument is designed as a panel-mounting unit.
Electrical safetyto EN 61 010, Part 1
product family standard: EN 61 326
to industrial requirements
overvoltage category III, pollution degree 2
2
stranded wire
Class B
2
solid wire
Connection diagram
Type 701060/XX1-31: Measurement input and supply voltageType 701060/XX2-31: Measurement input and supply voltage
are not isolated from eacht other!are not isolated from eacht other!
Dimensions
Type 701060/XX2-XX
02.07/00440437
Timing functions
Data Sheet 70.1060JUMO GmbH & Co. KG • 36035 Fulda, GermanyPage 4/4
Order details
701060/JUMO eTRON M
8factory-set, configurable within the
9configured to customer specification
1Pt100 in 2-wire circuit
2Fe-Con J
30—20 mA
40—10 V
11 changeover contact 10A 250V
22 make contacts 5A 250V
Order code / - -
Order example701060 /811 -02 -061
factory-set
1.) It is not possible to switch from one meas. input group to another
(1) Basic version
(2) Basic type extension
Versi on
measurement input group
Measurement input group
Pt1000 in 2-wire circuit
KTY2X-6
Fe-Con L
NiCr-Ni K
4—20 mA
Number of relays
(3) Supply
02230 V AC +10/-15% 48 — 63Hz
05115 V AC +10/-15% 48 — 63Hz
3112 — 24 V DC +15/-15 % /
24V AC +15/-15%, 48 — 63 Hz
(4) Approvals
000none
061Underwriters Laboratories Inc. (UL)
(1)(2)(3)(4)
1
Suitable transducers can be found in these data sheets:
- 90.2005 Push-in resistance thermometers
- 90.2105 Screw-in resistance thermometers
- 90.1002 and subsequent ones for screw-in thermocouples
- 90.1101 and subsequent ones for push-in thermocouples
- 90.1221 Mineral-insulated thermocouples
Accessories
Setup program, multilingual
PC interface with TTL / RS232C converter and adapter (pins)
02.07/00440437