JUMO JU 701060/812-31 Datasheet

JUMO GmbH & Co. KG
Delivery address:Mackenrodtstraße 14,
Postal address: Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net
36039 Fulda, Germany 36035 Fulda, Germany
JUMO Instrument Co. Ltd.
JUMO House Temple Bank, Riverway Harlow, Essex CM 20 2TT, UK Phone: +44 1279 635533 Fax: +44 1279 635262 e-mail: sales@jumo.co.uk Internet: www.jumo.co.uk
JUMO PROCESS CONTROL INC.
885 Fox Chase, Suite 103 Coatesville PA 19320, USA Phone: 610-380-8002
1-800-554-JUMO Fax: 610-380-8009 e-mail: info@JumoUSA.com Internet: www.JumoUSA.com
JUMO eTRON M Electronic Microstat
76 x 36 mm format
Brief description
The JUMO eTRON M is a compact, digital electronic thermostat for simple temperature control (heating or cooling). The measurement input permits the connection of resistance thermometers or thermocouples, or standard current or voltage signals. The measured value is shown on a 3-digit backlit display. The switching states of relays K1 and K2 are indicated by two LEDs. The instrument incorporates a simple defrosting function as well as an operating hours counter, which can, for instance, be used to record the operating time of a cooling compressor. The instrument can be operated from 4 keys on the front panel. The electrical connection is made via screw terminals on the back of the instrument. A setup program and a PC interface are available as accessories, for simple configuration and parameterization from a PC.
Block structure
Data Sheet 70.1060
Type 701060/XX2...
Page 1/4
Key features
k Integrated defrosting function
k Heating or cooling is configurable
k Limit monitoring
k Available for resistance thermometer,
thermocouple, standard current or voltage signals, according to choice
k Choice of a 10A relay or
two 5 A relays
k Adjustable switching hysteresis
k Time-delayed switch-on after
power-on is selectable, e. g. for staggered starting of several equipment units
k Operating hours counter
k Symbols for operating modes, °C, °F,
hours, minutes and seconds in display
k Parameter level protected by code
k Setup program for configuration and
archiving via PC
k Customized linearization via tabular
function in the setup program
k UL approval
Displays and controls
LC display 3-digit segment display, 13 mm high, and symbols for temperature
unit, h, min, s, defrosting and heating, with red background lighting
Status indication
Keys
Setup interface
02.07/00440437
LED K1/K2 lights up when relay K1/K2 is energized. LED K1/K2 goes out when relay K1/K2 is de-energized.
for start-stop
programming
increase parameter value
decrease parameter value
The instrument is linked to the PC via a PC interface with TTL/RS232 converter and adapter (3-pin).
Technical data
Data Sheet 70.1060JUMO GmbH & Co. KG • 36035 Fulda, Germany Page 2/4
Measurement input
Resistance thermometer
Designation Measuring range Meas. accuracy1/
ambient temperature error
Pt100 EN 60 751 -200 to +600°C 0.1%/ 100ppm/°C is recognized is recognized Pt1000 EN 60 751 -200 to +600°C 0.1%/ 100ppm/°C is recognized is recognized
Recognition of ... Probe short-circuit
Probe break
KTY2X-6 (PTC) -50 to +150 °C 1%/ 100ppm/°C is recognized is recognized Resistance 0 — 3000 customer table
3
0.1%/ 100ppm/°C
3
= 0 is recognized Measuring current for Pt100: 0.2 mA, for Pt1000, KTY2X-6 and resistance: 0.02 mA Lead compensation is adjustable via the parameter Lead compensation resistance
The total resistance (sensor+lead) must not exceed 320for Pt100 and 3200for Pt1000, KTY2X-6 or resistance. Thermocouple Fe-Con J EN 60 584 -200 to +999 °C 0.4%/ ≤100ppm/°C
Fe-Con L DIN 43 710 -200 to +900 °C 0.4%/ ≤100 ppm/°C NiCr-Ni K EN 60 584 -200 to +999 °C 0.4%/ ≤100ppm/°C
-10 to 60 mV customer table
3
0.1%/ 100ppm/°C
2
2
2
3
- is recognized
- is recognized
- is recognized
- is recognized
For the voltage input (-10 to 60 mV), terminal temperature compensation can be used for thermocouples. Internal terminal temperature compensation can be switched off via the setup program (0°C).
Current 0 — 20 mA -2 to 22 mA
0.1%/ 100ppm/°C
3
--
scalable with and
or customer table
4 — 20 mA 2.4 to 21.6 mA
0.1%/ 100ppm/°C 3is recognized is recognized
scalable with and
Input resistance R Voltag e 0 — 10 V -1 to 11 V
IN
3
0.1%/ 100ppm/°C - -
scalable with and
or customer table
Input resistance RIN ≥ 100kΩ
1.) The accuracies refer to the measuring range span.
2.) valid from -50°C
3.) A valid customer table must be entered via the setup program and changed over to in the instrument. This may reduce the measuring accuracy.
Additional data
Sampling time 250 msec Input filter 1st order digital filter; filter constant adjustable from 0.1 — 99.9sec Measurement offset adjustable from -99.9 to +99.9 via the parameter Special features display of temperature unit: °C, °F (Fahrenheit) or switched-off Customer table The setup program acquires a maximum of 20 value pairs and uses them for the linear interpolation
of 20 new calibration points.
Ambient conditions
Ambient temperature range 0 to +50°C, with side-by-side mounting: 0 to +40°C Storage temperature range -40 to +70°C Climatic conditions 75% rel. humidity, no condensation Cleaning and care of front panel The front panel can be cleaned with all the usual cleaning and rinsing agents.
Do not use solvents such as methylated spirit, white spirit, P1 or xylene!
Output
1 relay (changeover contact) for Type 701060/XX1-XX
2 relays (make contacts) for Type 701060/XX2-XX
150,000 operations at 10A 250V AC 50Hz resistive load
100,000 operations at 5A 250 V AC, 50Hz resistive load
Supply
Supply voltage 230V AC +10/-15%, 48 — 63Hz or 115 V AC +10/-15%, 48 — 63Hz (isolated from measurement input)
12 — 24V DC +15/-15 %, 24V AC +15/-15%, 48 — 63Hz (not isolated from measurement input)
Power consumption <3VA
Housing
Material polycarbonate Mounting in panel cut-out with bezel seal Operating position unrestricted Weight approx. 160g Protection front IP65, rear IP20 Flammability class UL 94 V0
02.07/00440437
Data Sheet 70.1060JUMO GmbH & Co. KG • 36035 Fulda, Germany Page 3/4
Electrical data
Data backup EEPROM
Connection via screw terminals for wire cross-section up to 4 mm
and 2.5 mm
Electromagnetic compatibility
interference emission immunity to interference
Operating conditions The instrument is designed as a panel-mounting unit.
Electrical safety to EN 61 010, Part 1
product family standard: EN 61 326
to industrial requirements
overvoltage category III, pollution degree 2
2
stranded wire
Class B
2
solid wire
Connection diagram
Type 701060/XX1-31: Measurement input and supply voltage Type 701060/XX2-31: Measurement input and supply voltage are not isolated from eacht other! are not isolated from eacht other!
Dimensions
Type 701060/XX2-XX
02.07/00440437
Timing functions
Data Sheet 70.1060JUMO GmbH & Co. KG • 36035 Fulda, Germany Page 4/4
Order details
701060/ JUMO eTRON M
8 factory-set, configurable within the
9 configured to customer specification
1 Pt100 in 2-wire circuit
2 Fe-Con J
3 0—20 mA
4 0—10 V
1 1 changeover contact 10A 250V 2 2 make contacts 5A 250V
Order code / - -
Order example 701060 / 811 - 02 - 061
factory-set
1.) It is not possible to switch from one meas. input group to another
(1) Basic version
(2) Basic type extension Versi on
measurement input group
Measurement input group
Pt1000 in 2-wire circuit KTY2X-6
Fe-Con L NiCr-Ni K
4—20 mA
Number of relays
(3) Supply 02 230 V AC +10/-15% 48 — 63Hz 05 115 V AC +10/-15% 48 — 63Hz 31 12 — 24 V DC +15/-15 % /
24V AC +15/-15%, 48 — 63 Hz
(4) Approvals 000 none 061 Underwriters Laboratories Inc. (UL)
(1) (2) (3) (4)
1
Suitable transducers can be found in these data sheets:
- 90.2005 Push-in resistance thermometers
- 90.2105 Screw-in resistance thermometers
- 90.1002 and subsequent ones for screw-in thermocouples
- 90.1101 and subsequent ones for push-in thermocouples
- 90.1221 Mineral-insulated thermocouples
Accessories
Setup program, multilingual PC interface with TTL / RS232C converter and adapter (pins)
02.07/00440437
Loading...