JUMO iTRON B 70.2040 Operating Instructions Manual

Type 702042 Type 702044 Type 702041
JUMO iTRON
Compact
microprocessor
Operating Instructions
controllers
B 70.2040
2008-11-11/00357918
)
)
E
Please read these Operating Instructions carefully before starting up the instrument. Keep these operating instructions in a place which is at all times accessible to all users. Please assist us to improve these operating instructions where necessary. Your suggestions will be most welcome.
Phone in Germany (0661) 6003-727
from abroad (+49) 661 6003-0
Fax in Germany (0661) 6003-508
abroad (+49) 661 6003-607
All necessary settings are described in these operating instructions. However, if any difficul­ties should still arise during start-up, you are asked not to carry out any unauthorized ma­nipulations on the unit. You could endanger you rights under the instrument warranty! Please contact the nearest subsidiary or the main factory in such a case.
When returning chassis, assemblies or components, the regulations of EN 100 015 “Protec­tion of electrostatically sensitive components” must be observed. Use only the appropriate ESD packaging for transport.
Please note that we cannot accept any liability for damage caused by ESD (electrostatic dis­charge).
Contents
1 Identifying the instrument version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1 Displays and keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2 Principle of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3 Operation of the timer function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.1 Process value input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.2 Logic input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.3 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.4 Limit comparator (alarm contact) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.5 Ramp function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
5.6 Self-optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
5.7 Level inhibit via code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.8 Timer function (extra code) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6 Configuration and parameter tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7 Alarm messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
8 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Contents
1 Identifying the instrument version
(1) (2) (3) (4) (5) (6)
7020 .. / .. – ... – ... – .. / ... ,...

1 Identifying the instrument version

(1) Basic type
(bezel in mm)
(2) Basic type
extension
(3) Inputs 888 =
(4) Outputs 000 = Standard Type 702040/41 Type 702042/43/44
1. single-setpoint controller with limit comparator, see factory settings under configuration and parameter level
2. see customer’s ordering text or settings under configuration and parameter level
40 =48x24, 41 = 48 x 48, 42 = 48 x 96 (portrait), 43 = 96 x 48 (landscape), 44 = 96 x 96
88 =
controller type configurable
99 =
controller type configured to customer specification inputs configurable
999 =
inputs configured to customer specification
Output 1 relay (n.o. make) relay (n.o. make) Output 2 logic 0/5V, optionally
Output 3 (not available) relay (n.o. make)
Options Type 702040/41 Type 702042/43/44
113 =Output 2
(outputs 1+3 as for Standard)
101 =Output 2
(output 1 as for Standard)
1
1
configurable als logic input
logic 0/12V, optionally configurable als logic input
relay (n.o. make) (logic input is always available)
2
2
logic 0/5V
logic 0/12V
not possible
4
(5) Supply 16 =
(6) Extra code 210 =
Delivery package Type 702040/41 Type 702042/43/44
1. The linearizations for KTY11-6 and thermocouple B have been deleted.
10— 18 V DC
22 =
20—53V AC/DC, 48—63Hz
23 =
110—240V -15/+10% AC 48— 63Hz Timer function
220 =
Timer function + limit switch
1
1 mounting frame 2 mounting brackets 1 seal, 1 Operating instructions 70.2040
1 Identifying the instrument version
5

2 Installation

2 Installation
Installation 702042 as 702044.
Type (bezel) Panel cut-out (WxH)
702040 (48mm x 24mm) 45 702041 (48mm x 48mm) 45 702042 (48mm x 96mm) 45 702043 (96mm x 48mm) 92 702044 (96mm x 96mm) 92
+0.6
+0.6
+0.6
+0.8
+0.8
x 22.2 x 45 x 92
x 45
x 92
1. Push on seal
2. Insert instrument
in mm
+0.3
+0.6
+0.8
+0.6
+0.8
3. Push on mounting brackets
4. Tighten screws
Edge-to-edge-mounting
(minimum spacings of panel cut-outs)
horizontal vertical
> 8mm > 8mm > 8mm > 8mm > 10mm > 10mm > 10mm > 10mm > 10mm > 10mm
6
3 Electrical connection
Installation notes
- The choice of cable, the installation, the fusing and the electrical connection must conform to the requirements of VDE 0100 “Regulations on the Installation of Power Circuits with nominal voltages below 1000V”, or the appropriate local regulations.
- The electrical connection must only be carried out by qualified personnel.
- If contact with live parts is possible when working on the instrument, it must be isolated on both poles from the supply.
- A current limiting resistor interrupts the supply circuit in the event of a short-circuit. The load circuit must be fused for the maximum relay current in order to prevent welding of the output relay contacts in the event of an external short-circuit.
- Electromagnetic compatibility conforms to the standards and regulations listed under Technical Data.
- Run input, output and supply lines separately and not parallel to each other.
- Do not connect any additional loads to the supply terminals of the instrument.
- The instrument is not suitable for installation in hazardous areas.
- Apart from faulty installation, there is a possibility of interference or damage to controlled processes due to incorrect settings on the controller (setpoint, data of parameter and

3 Electrical connection

7
configuration levels, internal adjustments). Safety devices independent of the controller, such as overpressure valves or temperature limiters/monitors, should always be provided and should be capable of adjustment only by specialist personnel. Please refer to the appropriate safety regulations in this connection. Since auto-tuning (self­optimization) cannot be expected to handle all possible control loops, there is a theoretical possibility of unstable parameter settings. The resulting process value should therefore be monitored for its stability.
- All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables (do not run them in the vicinity of power cables or components). The shielding must be grounded to the earth potential on the instrument side.
3 Electrical connection
8
Type 702040/41
Thermocouple
Pt100/1000 (3-wire)
Pt100/1000 KTY11-6 (2-wire)
Current 0/4—20mA
Voltage 0/2—10V
Output 2
Logic output Relay 5V(12V)/20mA
+
J
J
+
+
Process value input
1
Output 1
2
+
Logic input
floating contact
V
1. Output or logic input (configurable)
2. resistive load
250V/3A
1
The electrical con­nection must only be carried out by qualified personnel.
Supply see label
NL198654321
AC
110—240V
AC/DC
20—53V
DC
=
10—18V
3 Electrical connection
+
+
9
Type 702040/41 with 2 relay outputs (option)
Thermocouple
Pt100/1000 (3-wire)
Pt100/1000 KTY11-6 (2-wire)
Current 0/4—20 mA
Voltage 0/0.2—1 V
Logic input
+
J
J
V
+
+
Process value input
-
Outputs
Relay 250 V/3 A
12
7
The electrical connection must only be carried out by qualified personnel.
Supply see label
NL19854321
AC
110—240V
AC/DC
+
20—53V
DC
=
+
10—18V
3 Electrical connection
10
Type 702042/43/44
Thermocouple
Pt100/1000 (3-wire)
Pt100/1000 KTY11-6 (2-wire)
Current 0/4—20mA
Voltage 0/2—10V
Output 2
Logic output
5V(12V)/20mA
+
J
J
+
+
Process value input
Relay Relay
+
Logic input
floating contact
The electrical connection must only be carried out by qualified
V
personnel.
250V/3A 250V/3A
Output 3Output 1
22
Supply see label
13 N L1121097654321
AC
110—240V
AC/DC
20—53V
DC
=
10—18V
2. resistive load
3 Electrical connection
+
+
11

4 Operation

4.1 Displays and keys

Example: Type 702041
(1) Display
7-segment display 4 places, green
Character height Type 702040/41/42: 10mm
Display range -1999 to +9999 digit Decimal places none, one, two Unit
(2) Status indicators
LED two LEDs for the outputs 1 and 2, yellow
(3) Keys
q, i, d
Display alternates when setpoints, parameters and codes are entered and indicated.
Type 702043/44: 20mm
°C/ °
F (process value display)
for operating and programming the instrument. Dynamic modification of settings and parameters.
h Increase value with h Decrease value with d
Automatic value acceptance after 2 seconds.
i
4 Operation
12

4.2 Principle of operation

Normal display
The display shows the process value.
Operating level
The setpoint pears in the display. When the ramp function is active, the ramp setpoint activated timer function, the timer value The setpoint is altered dynamically using the matically after approx. 2 sec.
Parameter level
The setpoints, the limit value of the limit comparator, the controller parameters and the ramp slo­pe are programmed here.
Configuration level
The basic functions of the controller are set here.
SP is input here. On active setpoint switching via the logic input, SP 1 or SP 2 ap-
SPr is displayed. With
tior the timer start value ti0 is shown.
i and d keys. The setting will be accepted auto-
In order to make the settings, it is necessary to change to the configuration level
A via the parameter y:0 (parameter level).
Timer level
The current timer value (only when the timer has been started) and the timer start value are al­tered here. The parameters at this level are marked with an underscore in the display.
Time-out
If no operation occurs, the controller returns automatically to normal display after approx. 30 sec (exception: with timer functions starting via power ON, the timer value is displayed). If the timer value is displayed at the operating level, time-out is not active.
4 Operation
13
Normal display
Process value
259
Time-out
(30s)
or
qd+
Operating level
Ramp setpoint* (display only)
Setpoint (with setpoint
switching
or )SP 1 SP 2
Timer value* (operating only; different display depending on timer condition (see table))
* only displayed if function is configured
SPr
SP
ti
ii d/+
> 2s
after last parameter
> 2s
Time-out
Parameter level
- setpoint 1+2
- limit value for limit comparator
- controller parameters
- ramp slope
Pb:1
Y.0
after last parameter
Configuration level
- configuration codes
- standard signal scaling
- process value correction
- switching differential of limit comparator
Timer level (timer stopped!)
alter current timer value (only when timer has been started)
set/alter timer start value
Underscore to differentiate operating and timer level
A
C111
ti
ti0
via
> 2s
y.0 !
4 Operation
14

4.3 Operation of the timer function

The timer can be operated with the keys (start, stop, cancel, acknowledge) if the timer at opera­ting level is indicated. Time-out is not active here. If the logic input is configured accordingly, then a key, such as the the timer value does not appear in the display.
Possible displayed parameters for timer function at operating level
Display State/Action Display State/Action
When the timer has been started, the decimal point in the display for the timer value will blink!
i key, can be used. In this case, the timer can also be operated even if
Timer not running h Start with i
Timer has been started but the tolerance limit has not yet been reached
h Cancel with i + d Timer running;
tiis displayed
h Stop with i h Cancel with i + d
Timer has stopped
h Continue with i h Cancel with i + d
Timer has run down h Acknowledge with any key
(timer start value ti0 is indicated) With time-delayed control (C120=3), acknowledge with i + d
4 Operation
15

5 Functions

We recommend the following procedure:
h Familiarize yourself with the controller functions h Enter the configuration codes and the parameter values in the tables provided for this pur-
pose in Chapter 6. Write down the appropriate values ( ), or mark selection with a cross ( ). The parameters and the configuration codes are listed in the order of their
X
appearance. Parameters which are not relevant are masked out (see table below).
h Enter the configuration code and parameters on the instrument
Configuration Masking out the parameters for Parameter
Single-setpoint controller Double-setpoint controller Pb:2, Cy 2, db, HyS.2 Double-setpoint controller Limit comp. for Type 702040/41
Limit comparator no function Limit comparator HySt, AL Limit comparator activated Logic input for Type 702040/41 Resistance thermometer, thermocouple Standard signal scaling SCL, SCH Ramp function off Ramp function Setpoint switching not activated Setpoints at the parameter level SP 1, SP 2 Timer function: no function Timer function ti, C121, C122, C123 Type 702040/41 Output 3 C118
1. not for Type 702040/41 with 2 relay outputs (option)
Logic input for Type 702040/41
1
1
C114, HySt, AL C117
C117
rASd, SPr
5 Functions
16

5.1 Process value input

Symbol Notes
C111 C112 SCL
Transducer/probe (process value input) vpage 31
Unit of process value (°C/°F)/decimal places of display vpage 31
Start/end value of value range for standard signals vpage 35
Example: 0—20 mA→20—200°C: SCL = 20 / SCH = 200
SCH OFFS
dF
Process value correction vpage 35
Using the process value correction, a measured value can be corrected by a programmable amount upwards or downwards (offset). Lead compensation can be implemented in software for 2-wire circuit through process value correction.
Examples:
Measured value Offset Displayed value
294.7 + 0.3 295.0
295.3 - 0.3 295.0 Filter time constant (damping) to adapt the digital input filter (0sec = filter off) vpage 36
if dF high: - high damping of interference signals
- slow reaction of the process value display to changes in the process value
- low cut-off frequency (2nd order low-pass filter)
5 Functions
17

5.2 Logic input

Key inhibit Operation is possible from keys. No operation from keys. Level inhibit Access to the parameter and
Ramp stop Ramp running Ramp stopped Setpoint switching Setpoint SP 1 is active Setpoint SP 2 is active
Timer control Acknowledge start/stop/continue/timer run-down (edge-triggered)
Symbol Notes
C117
Function of the logic input vpage 33
On Type 702040/41, the parameter C117 is masked out if output 2 has been programmed as controller output (C113) or the limit comparator has been configured (C114) (double assign­ment; not on Type 702040/41 with 2 relay outputs (option)).
configuration levels is possible. Starting self-optimization is possible.
The appropriate symbols SP 1 and SP 2 are displayed at the operating level.
No access to the parameter and configuration levels. Starting self-optimization is not possible.
5 Functions
18

5.3 Controller

Controller structure
The controller structure is defined via the parameters Example: Setting for PI controller
Symbol Notes
C113
C116
C118
Pb:1 Pb:2 dt
rt
Cy 1 Cy 2
Controller type and assignment of the controller outputs to the physical outputs 1+2 vpage 32
Outputs in fault condition vpage 33
The switching states of the outputs are defined here in the event of over/underrange, probe break/short circuit or display overflow. v Chapter 7
Assignment of the outputs vpage 33
Only for Type 702042/43/44; overwrites the assignment of C113 (controller type as C113)
Proportional band 1 (controller output 1) vpage 36 Proportional band 2 (controller output 2)
Influences the P action of the controller. If Pb=0, the controller structure is not effective.
Derivative time vpage 36
Influences the D action of the controller. If dt=0, the controller has no D action.
Reset time vpage 36
Influences the I action of the controller. If rt=0, the controller has no I action.
Cycle time 1 (controller output 1) vpage 36 Cycle time 2 (controller output 2)
The cycle time has to be selected so that the energy supply to the process is virtually continuous, while not subjecting the switching elements to excessive wear.
Pb .1=120, dt=0sec, rt=350sec
Pb, dt and rt.
5 Functions
19
Symbol Notes
db
Contact spacing vpage 36 for double-setpoint controller
HYS.1 HYS.2
Y:0
Y:1 Y:2
Differential 1 (controller output 1) vpage 36 Differential 2 (controller output 2)
for controllers with Pb.1=0 or Pb.2=0
Working point (basic load) vpage 36 Output if process value=setpoint
Output limiting vpage 36
y:1 - maximum output y:2 - minimum output
For controllers without controller structure (Pb.1=0 or Pb.2=0), it is necessary
H
that y:1=100% and y:2=-100%.
5 Functions
20

5.4 Limit comparator (alarm contact)

lk1
On
On
lk2 lk3
On
On
lk4
On
lk7 lk8
Symbol Notes
C114 Hyst AL
Limit comparator function (lk1— lk8) vpage 32
Differential of limit comparator vpage 35
Limit value of limit comparator vpage 36
lk5
On
On
On
lk6
lk1—lk6: Monitoring referred
to the setpoint.
lk7 / lk8: Monitoring referred
to a fixed value
w = setpoint, x = process value
AL.
5 Functions
21

5.5 Ramp function

Symbol Note
C115 C117 rAsd
Ramp function (on/off, time unit) vpage 32
Ramp stop via logic input (floating contact) vpage 33
Ramp slope in °C/h or °C/min vpage 36
J
SP1
SP2
t1 power ON (SP 1 active) t2— t3 power failure or overrange/underrange t4—t5 ramp stop t6 setpoint switching to
ramp setpoint SPr
process value
t2 t3 t4 t5 t6 t
t1
SP 2
5 Functions
22

5.6 Self-optimization

Self-optimization determines the optimum controller parameters for PID or PI controllers. The following controller parameters are defined: The controller selects procedure a or b, depending on the size of the control deviation:
a) Self-
optimization in the approach phase
x = process value w = setpoint
Starting self-optimization
Start
rt, dt, Pb:1, Pb:2, Cy 1, Cy 2, dF
Switching level
b) Self-
optimi­zation at set­point
Start
5 Functions
H
Self-optimization is automatically terminated, or can be can­celled.
Starting self-optimization is not possible with active level inhibit and ramp function.
i + d >2s
i+ d
260
tunE
23

5.7 Level inhibit via code

As an alternative to the logic input, the level inhibit can be set via a code (logic input has priority).
h Set the code using
normal display
q + d (at least 5sec) in
Level inhibit via the logic input will lock the parameter and configuration levels (corresponds to code 011).
Code Operating level Parameter level Configuration level Timer level
000 enabled enabled enabled enabled 001 enabled enabled inhibited enabled 011 enabled inhibited inhibited enabled 111 inhibited
1. The values at the operating level can only be indicated but not modified.
2. Timer operation (start/stop/continue/cancel) will continue to be possible.
1
inhibited inhibited inhibited
2
5 Functions
24

5.8 Timer function (extra code)

Using the timer function, the control action can be influenced by means of the adjustable time
ti0. After the timer has been started by power ON, by pressing the key, or via the logic input,
the timer start value gone above or below a programmable tolerance limit. When the timer has run down, several events are triggered, such as control switch-off (output 0%) and setpoint switching. Furthermo­re, it is possible to implement timer signalling via an output.
Example:
ti0 is counted down to 0, either instantly or after the process value has
w- setpoint x - process value
SP - programmed setpoint ti0- timer start value
----- - timer signalling
(here: C122=1)
i - increment key
5 Functions
25
Notes on the timer function in conjunction with the ramp function
- Generally, the setpoints can also be approached using the ramp function.
- Stopping the timer does not influence the ramp function.
- If control is active after the timer has run down, the current setpoint is approached with the ramp. Cancellation of the timer is followed by a setpoint step without ramp.
- For timer functions with a tolerance limit, only the setpoint (=ramp end value) is monitored.
Note on setpoint switching via the logic input
- Setpoint switching via the logic input is generally possible. An exception here is the timer function “Time-dependent setpoint switching”. In this case, configured setpoint switching via the logic input will not be active.
Note on the display status in the event of a power failure
- The state of the display before the power failure will be restored, except for events that are related to the timer (start, cancel, continue, stop). Then the timer value will be shown in the display.
5 Functions
26
Symbol Notes
C120
C120=1
Timer function vpage 34
Time-limited control: The control is switched off after the timer has run down (output 0%)
C121=1, 2, 5 or 6
C121=3, 4, 7 or 8
Diagrams with and without start above tolerance limit.
---- Tolerance limit
5 Functions
C120=2 Time-dependent setpoint switching: After the start of the timer function, the process is con-
trolled to setpoint SP2. After the timer has run down, the controller automatically switches over to SP1.
C121=2 or 6
C121=1 or 5
C121=3, 4, 7 or 8
27
Symbol Notes
C120
C120=3
Time-delayed control: The control action starts after the timer has run down.
C121=1, 2, 5 or 6
H
After the timer has run down (End), the
i + d keys are used for acknowledge-
ment. Set ti0 > 0s
5 Functions
C120=4 Timer: After the start of the timer function, ti0is counted down to 0. The control action is
independent of the timer. Here, too, the timer run-down can be signalled via an output.
C121=1, 2, 5 or 6
Timer signalling C122=3
C122=1
28
Symbol Notes
C121
C122
C123
Start condition of the timer vpage 34
The timer start value ti0 is counted down as selected in the following events:
1. Power ON or logic input/keys
2. Start via keys/logic input
3. Process value has reached tolerance limit (1°C or 5°C) (start via keys/logic input) The position of the tolerance limit depends on the controller type:
- 1-setpoint controller (direct): tolerance limit above setpoint
- 1-setpoint controller (reversed): tolerance limit below setpoint
- 2-setpoint controller: tolerance limit below setpoint If, during the control process, the process value goes above/below the tolerance limit, the
timer will be stopped for the duration of the infringement.
Response to a power failure vpage 34
After a power failure, the condition before the power failure can be restored, or the timer function can be cancelled. If the timer had run down before the power failure, the timer start value will be loaded. The timer will start automatically when C121=1 or 5.
The timer value is saved at one minute intervals, to cover the case of a power failure.
Timer signalling vpage 35
From the start of the timer function until timer run-down, or after the run-down, a signal can be produced via an output.
Time unit for the timer vpage 35
5 Functions
29
Programming example
After the start via the logic input or from the keys, the process has to be controlled for 30 min­utes to a setpoint of 80°C. The control action is to be cancelled in the event of a power failure.
Configuration:
- C111— C116: Controller programming
- C117=5: Logic input = timer control
- C120=1: Timer function = time-limited control
- C121=6: Start condition for timer = via logic input/keys - cancellation on power failure
- C122=0: Timer signalling = no function
- C123=1: Time unit (timer) = mm.ss
Operation:
h Enter the setpoint SP (80°C) h Press the h Change over to the timer level using h Enter the timer start value t h Return to the operating level (timer value) with h Start the control action via the logic input or with i
q key until t i0 is indicated
q (at least 2sec)
i0 _ (30.00)
q
5 Functions
30
6 Configuration and parameter tables
Transducer X
C111
001 Pt 100 (3-wire)
q
006 Pt 1000 (3-wire) 601 KTY11-6 (2-wire)
>2s
003 Pt 100 (2-wire)
y:0
. . .
Pb:1
Normal display/ Operating level
1. SP 1, AL or Pb:1 is shown here, depending on the configuration
2. 0 – 1V for Type 702040/41 with 2 relay outputs (option)
3. 0.2 – 1V for Type 702040/41 with 2 relay outputs (option)
005 Pt 1000 (2-wire) 039 Cu-Con T 040 Fe-Con J 041 Cu-Con U 042 Fe-Con L 043 NiCr-Ni K
q
044 Pt10Rh-Pt S 045 Pt13Rh-Pt R 046 Pt30Rh-Pt B 048 NiCrSi-NiSi N
1
052 Standard signal 0 – 20mA 053 Standard signal 4 – 20mA 063 Standard signal 0 – 10V
q
071 Standard signal 2 – 10V
>2s
2 3
q
Decimal places/unit X
C112
0 9999/°C
1999.9/°C 2 99.99/°C 3 9999/°F
4999.9/°F 5 99.99/°F
q
. . .
X Mark your selection with a
cross.

6 Configuration and parameter tables

31
Controller type Output 1 (relay) Output 2+3
C113
10 single setpoint (reversed) controller 11 single setpoint (direct) controller 30 double setpoint controller output 1 controller output 2
20 single setpoint (reversed) 21 single setpoint (direct) 33 double setpoint controller output 2 controller output 1
q
Limit comparator (LK) X
C114
0 no function 1lk 1 2lk 2 3lk 3 4lk 4 5lk 5 6lk 6 7lk 7 8lk 8
reversed = heating (output is active when process value is below setpoint) = controller output 1 direct = cooling (output is active when process value is above setpoint) = controller output 2
LK/timer signalling LK/timer signalling
Further settings for the outputs with Type 702042/43/44, see C118.
1
1
1. A programmed limit comparator (LK) has priority
C115
0 ramp function off
q
1 ramp function (°C/min) 2 ramp function (°C/h)
(logic+relay)
LK/timer signalling LK/timer signalling
controller controller
over the timer signalling.
Ramp function X
q
. . .
X
1 1
6 Configuration and parameter tables
32
. . .
Outputs on fault X
C116
0 0% 1100% 2-100%1 30%1 LK/timer 4100%
1. Minimum output limiting y.2 is effective
2. Maximum output limiting y.1 is effective
C118
0 Functions of outputs as defined under C113
q
1 2 controller output timer signalling limit comparator 3 limit comparator controller output timer signalling 4 limit comparator timer signalling controller output 5 timer signalling controller output limit comparator 6 timer signalling limit comparator controller output
7 8 controller output 1 limit comparator/timer controller output 2 9 controller output 2 controller output 1 limit comparator/timer 10 controller output 2 limit comparator/timer controller output 1 11 limit comparator/timer controller output 1 controller output 2 12 limit comparator/timer controller output 2 controller output 1
LK/timer
1
2
signalling OFF
2
signalling ON
Output 1: Relay (K1)
controller output limit comparator timer signalling
for 1-setpt. contrl.
controller output 1 controller output 2 limit comparator/timer
for 2-setpt. contrl.
q
Output 2: Logic (K2) Output 3: Relay
Logic input X
C117
0 no function 1 key inhibit 2 level inhibit 3 ramp stop 4 setpoint switching 5 timer control
6 Configuration and parameter tables
q
X
33
Timer function X
C120
0 no function 1 time-limited control 2 time-dependent setpoint switching 3 time-delayed control 4 timer (control independent of timer)
q
6 Configuration and parameter tables
. . .
Start condition for timer Action on power failure X
C121
1 after power ON, logic input/keys Condition as before the
q
2 via logic input/keys 3 via logic input/keys; timer counts 1°C
from tolerance limit
4 via logic input/keys; timer counts 5°C
from tolerance limit 5 after power ON, logic input/keys Cancellation of 6 via logic input/keys 7 via logic input/keys; timer counts 1°C
from tolerance limit 8 via logic input/keys; timer counts 5°C
from tolerance limit
The start conditions with tolerance limit (C121=3, 4, 7, 8) are not valid for C120=3 or 4. If C120 is altered, the validity of C121 must be checked.
power failure
timer function (StOP appears in the display)
34
. . .
Timer signalling X
C122
0 no function 1 timer start until run-down 2 after run-down for 10sec 3 after run-down for 1min. 4 after run-down until
acknowledgement
One output has to be configured correspondingly(C113/C118).
Parameter Explanation Value range factory-set Your
SCL
sCH
SPL
SPH
q
OFFS HySt
1. For displays with one or two decimal places, the value range and the factory setting
start value of the standard signal
end value of the standard signal
lower setpoint limiting
upper setpoint limiting
process value correction -1999 to 9999 digit1 0 switching differential of
the limit comparator
change accordingly. Example: 1 decimal place
value range: -199.9 to +999.9
q
-1999 to +9999digit10
-1999 to +9999digit1100
-1999 to +9999digit1-200
-1999 to +9999digit1850
0 — 9999digit
Unit of time (timer) X
C123
1 mm.ss (max. 99.59) 2 hh.mm (max. 99.59) 3 hhh.h (max. 999.9) s = seconds; m = minutes;
h = hours
1
1
6 Configuration and parameter tables
q
setting
35
Parameter Explanation Value range factory-
sP 1 sP 2 AL
Pb:1 Pb:2 dt rt Cy 1 Cy 2 db HYS.1 HYS.2 Y:0 Y:1 Y:2 dF rAsd
1. For displays with one or two decimal places, the value range and the factory setting change accordingly.
setpoint 1 SPL — SPH 0 setpoint 2 SPL — SPH 0 limit value of
limit comparator proportional band 1 0 — 9999digit
proportional band 2 0 — 9999digit derivative time 0 — 9999sec 80sec reset time 0 — 9999 sec 350sec cycle time 1 1.0 — 999.9sec 20.0sec cycle time 2 1.0 — 999.9sec 20.0sec contact spacing 0 — 1000digit1 0 differential 1 0 — 9999digit1 1 differential 2 0 — 9999digit1 1 working point -100 to 100% 0% maximum output 0 — 100% 100% minimum output -100 to +100% -100% filter time constant 0.0 — 100.0sec 0.6sec ramp slope 0 — 999 °C/h (°C/min)10
-1999 to +9999digit10
1
1
set
0 0
You r setting
6 Configuration and parameter tables
36
7 Alarm messages
Display Description Cause/response
The displays for the process value or timer value flashes “1999”. Display current timer value by repeatedly pressing the q key.
The display for the timer value alternates between showing “StOP” and the time.
h Acknowledge by using any
key, (the timer start value
ti0 is loaded)
Over/underrange of process value. Controller and limit comparators referred to the process value input behave in accord­ance with the configuration of the outputs. The timer is stopped.
The timer function has been cancelled due to a supply failure. The timer value that was present at the time of the supply failure will be indicated.

7 Alarm messages

H
The following events come under the heading over/underrange:
- Probe break/short-circuit
- Measurement is outside the control range of the probe that is connected
- Display overflow
37
Measurement circuit monitoring (• = recognized)
Transducer Overrange/
Thermocouple •/• - • Resistance thermometer •/• • Voltage 2 – 10 V and0.2 – 1V
Current 4 – 20mA
0 – 10V and 0 – 1V
0 – 20mA
underrange
•/•
•/-
•/•
•/-
Probe/ lead short-circuit
-
-
Probe/lead break
-
-
7 Alarm messages
38
8 Technical data
Input for thermocouple
Designation
Fe-Con L Fe-Con J EN 60 584 Cu-Con U Cu-Con T EN 60584 NiCr-Ni K EN 60 584 NiCrSi-NiSi N EN 60584 Pt10Rh-Pt S EN 60584 Pt13Rh-Pt R EN 60584 Pt30Rh-Pt6Rh B EN 60584
Measurement accuracy: 0.4% / 100ppm/°C Cold junction: Pt100 internal
1. These ranges refer to the ambiente temperature of 20°C
Input for standard signals
Designation Range
Voltage 0 — 10V, RE > 100kΩ
Current 4 — 20mA, voltage drop 3V
Measurement accuracy: 0.1% / 100ppm/°C
2. 0—1V, RE>10MΩ for Type 702040/41 with 2 relays
3. 0.2—1V, R
2—10V, RE > 100kΩ
RE - input resistance
0 — 20mA, voltage drop 3V
>10MΩ for Type 702040/41 with 2 relays
E
1
Range
-200 to + 900°C
-200 to +1200°C
-200 to + 600°C
-200 to + 400°C
-200 to +1372°C
-200 to +1300°C 0 — 1768°C 0 — 1768°C 0 — 1820°C
2 3
Input for resistance thermometer
Designation Range
Pt100 EN 60751 -200 to +850 °C Pt1000 EN 60751 -200 to +850°C KTY11-6 -50 to +150°C Measurement accuracy:
Pt100/1000: ≤ 0.1% / 50ppm/°C KTY11-6: ≤ 1.0% / 50ppm/°C Sensor lead resistance: 20Ω max. per lead Meas. current: 250µA
Outputs
Relay: n.o.(make) contact; 3A at 250 V AC resistive load; 150,000 operations at rated load Logic 0/5V: Current limiting: 20mA; R Logic 0/12V: Current limiting: 20mA; R
Supply
110 — 240V AC -15/+10% 48 — 63Hz, or
20 — 53V AC/DC 48 — 63Hz, or 10 — 18V DC (Connect to SELV or PELV)
load
load
250 Ω
600 Ω

8 Technical data

39
Controll
er
A
A
Data back
EEPROM
Controller type 1-setpt. controller with
Controller structure P/PD/PI/PID A/D converter resolution >15 bit Sampling time 210msec (250msec with timer
ccuracy of timer: 0.7% / 10 ppm/°C
Test voltages (type test)
to EN 61 010, Part 1, March 1994, overvoltage category II, pollution degree 2, for Type 702040/41 overvoltage category III, pollution degree 2, for Type 702042/43/44
Power consumption: 7VA max. Electrical connection
at the rear via plug-in screw terminals, conductor cross-section ≤ 2.5mm2 (1.3mm2 with Type 702040/41) solid wire or
1.5mm2 (1.0mm2 for Type 702040/41) stranded wire with ferrules
Electromagnetic compatibility: EN 61 326 Immunity to interfer.: Class B, Interfer. emission: industrial requirements
pproval: UL and CSA (only devices with JUMO indication)
limit comparator, 2-setpt. controller
function)
Housing type
plastic housing for panel mounting to DIN 43700
Cleaning the front panel
use warm or hot water (add mildly acidic, neutral or mildly alkaline detergents, if necessary). Do not use any abrasive cleaning agents or high­pressure cleaners. Limited resistance to organic solvents (e. g. spirits, benzol, etc.).
Housing mounting
in panel to DIN 43 834
Ambient and storage temperature
0 to 55°C / -40 to +70°C
Climatic conditions
75% rel. humidity, no condensation
Operating position: any Weight (approx.)
75g (702040) 160g (702043) 95g (702041) 200g (702044)
145g (702042) Protection IP66 (front) to EN 60529 IP20 (rear)
Safety regulation: to EN 61010
up:
8 Technical data
40
JUMO GmbH & Co. KG
Street adress: Moltkestraße 13 - 31 36039 Fulda, Germany Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House Temple Bank, Riverway Harlow, Essex CM20 2TT, UK Phone: +44 1279 635533 Fax: +44 1279 635262 e-mail: sales@jumo.co.uk Internet: www.jumo.co.uk
JUMO Process Control, Inc.
8 Technology Boulevard Canastota, NY 13032, USA Phone: 315-697-JUMO
1-800-554-JUMO Fax: 315-697-5867 e-mail: info@jumo.us Internet: www.jumo.us
Loading...