JUMO ETH-20, ETH-70 Operating Manual

H
Please read these operating instructions before placing the instrument in service. Keep the manual in a place which is accessib le to all users at all times. Please assist us in improving these operating instructions where necessary. Your comments will be appreciated. Telephone +49 661 6003-716 Fax +49 661 6003-504
H
H
The instruments are maintenance-free. In the event of malfunction, please return the instrument to the supplier with precise details of the fault. The staff at our field offices, branches, and agencies are always available to provide service and advice.
JUMO GmbH & Co. KG
Company address: Moritz-Juchheim-Strasse 1
36039 Fulda, Germany
Delivery address: Mackenrodtstrasse 14
36039 Fulda, Germany
Postal address: 36035 Fulda, Germany Phone: +49 661 6003-716 Fax: +49 661 6003-504 E-mail: mail@jumo.net Internet: www.jumo.net
JUMO Mess- und Regelgeräte Ges.m.b.H.
Pfarrgasse 48, 1232 Vienna, Austria Phone: +43 1 610610 Fax: +43 1 6106140 E-mail: info@jumo.at Internet: www.jumo.at
JUMO Mess- und Regeltechnik AG
Laubisrütistrasse 70, 8712 Stäfa, Switzerland Phone: +41 1 928 24 44 Fax: +41 1 928 24 48 E-mail: info@jumo.ch Internet: www.jumo.ch
1.
Introduction / Application
ETH series fitted thermostats are approved as:
safety temperature limiters (STB).
safety temperature monitors STW (STB)
Type examination to:
- DINEN14597
- Pressure Equipment Directive 97/23/EC
Safety instructions
Physical and toxicological properties of substances which may escape, should the system fracture:
H
Fitted thermostats of type series ETH comply with VDE 0631.
End of scale Danger-
ous reac­tions
Fire/
explosion hazard
Water
contami
nation
Tox ic o lo gy
Ignition
tempera-
ture
°C
Explosion
limit
% v/v
irri­tant
danger
to health
toxic
liquid-filled
+200°C < +200 °C no +355 °C 0 .6 - 8 yes yes
1
no
+200 °C ≤+350 °C no +490 °C - - yes yes
1
no
gas-filled
+400 °C ≤+500 °C no
H
1
Should the measuring system fracture, the fill fluid may escape. At
present, there is no restrictive statement from the health authorities concerning danger to health in the event of short-t erm exposure at low concentration, for example, should the measuring system fracture.
2. Instrument identification / type declaration
Type designation
Nameplate
(reference example) (1) Type ( 2 ) Order code ( 3 ) Limit value/max. housing
temperature/contact rating
( 4 ) Manufacturing number/
sales number
( 5 ) Mark of approval/
connection diagram ( 6 ) Year of manufacture ( 7 ) Week of manufacture
ETH . - . . / ETH Fitted thermostat with microswitch
with capillary
-20 safety temperature monitor STW (STB), with changeover contact
-70 Safety temperature limiter (STB) with break contact and restart lockout
/au gold-plated snap-action switch contact
/U only with STB. microswitch with normally-closed
contact, restart lockout, and additional signal contact
B 60.2010.0
Operating Manual
2009-03-06/00073781
3. Mounting / general information
Capillary / temperature probe / pocket
General information
If the capillary of the surface-mounting thermostat is cut through or becomes
kinked, this could result in permanent dev ice failure!
The minimum bending radius allowed for the capillary is 5 mm.
JUMO pockets must be used when installing the temperature probe, if the approval
for the surface-mounting thermostat is to remain valid.
The temperature probe must be fully immersed in the measurement medium.
When air is the measurement medium, you must choose a process connection
without a pocket.
To ensure the general accuracy of the operating value, the instruments must only
be used with the pockets supplied on delivery (diameter D = 8, 10 mm).
Only a probe of diameter d = 8 mm may be used in pockets of D = 10 mm.
Multiple assignments of pockets are only allowed with 2 or 3 cylind rical probes of
Ø 6 mm and pockets of 15 x 0.75 mm.
If two probes are assigned, the spring clip provided on delivery must be installed in
the pocket.
With pockets U, US, E, ES, and EZS made from St 35.8I/16Mo 3 materials, the
permitted operating period at operating temperatures above 420 °C is limited to 200,000 hours. Compliance with TRD 508 is essential for applications in this range.
Mounting the thermostat head
Any installation position
Mount the thermostat head
On the chassis with 2 M3 screws
( 1 ) screw ( 2 ) panel
( 1 )
( 2 )
4. Dimensions
Panel cut-out
Dimensions
ETHf-20
ETHf-70
Fitted thermostat
Type s erie s ETH
ETH-20
ETH-70
Approved probes and pockets
A U UO US ES
Plain cylindrical probe Screw-in pocket with screw-in
spigot Form A to DIN 3852/2. With fixing screw
Pocket as screw-in pocket, with screw-in spigot Form "A" to DIN 3852/2, with fixing screw
Weld-in pocket with fixing screw and clamp
For code "f" pocket as weld-in pocket, with welding shoulder; pocket secured with union nut, connection "C".
EBCDQV
( A ) = washer / ( B ) = seal
For code "f" pocket as screw-in pocket, with screw-in spigot Form A to DIN 3852/2; pocket secured with union nut, probe mounting "C"
Probe mounting "C" with loose coupling, threaded at both ends
Plain cylindrical probe with shoulder and union nut. Shoulder brazed or welded to capillary
Plain cylindrical probe, threaded connector brazed or welded to capillary
For code "f" double threaded coupling for subsequent capillary mounting. Probe temperature max. +200 °C
For code "f" clamping gland for subsequent capillary mounting. Probe temperature max. +200 °C
SW
ØD
G
L1
S
Permissible loading on the pocket U, US, UZ, UZS, E, ES, and EZS pockets
Steel pocket
Materials:
Tub e: St 3 5. 8 I Screw-in nipple up to 300
°
C: 9 SMnPb.28 K
Screw-in nipple up to 450
°
C: 16 Mo 3 (turned groove)
Weld-in nipple: 16 Mo 3 (without turned groove)
Loading
Permissible incident flow velocity
A
The values below refer to the maximum loading on the probe mounting concerned. The actual maximum sealable pressure depends on the mounting conditions and may possibly be lower.
Temperature Tube diameter "D"
8 x 0.75 mm
or conical
10 x 0.75 mm 15 x 0.75 mm
maximum permissible pressure 100 °C 89 bar 72 bar 48 bar 150 °C 83 bar 67 bar 45 bar 200 °C 78 bar 63 bar 42 bar 300 °C 59 bar 47 bar 32 bar 350 °C 50 bar 40 bar 27 bar 400 °C 46 bar 37 bar 25 bar 450 °C 24 bar 19 bar 13 bar
Temperature: +200
°
C Heat carrier: air ( 1 ), water, oil ( 2 ) Tube diameter "D". 08mm
10 mm
. . . . . . . . . . . . . .
15 mm
Permissible incident flow velocity (m/sec) at maximum permitted pressure loading and different immersion tube lengths ( S ).
( 1 ) air ( 2 ) water, oil ( S ) immersion tube length
Pocket
A
The values below refer to the maximum loading on the probe mounting concerned. The actual maximum sealable pressure depends on the mounting conditions and may possibly be lower.
Immersion tube length 200 mm:
Material: steel
Temperature: +200 °C Heat carrier: air ( 1 ), water, oil ( 2 ) Tube diameter "D". 08mm
10 mm
. . . . . . . . . . . . . .
15 mm
Permissible incident flow velocity (m/sec) at maximum permitted pressure loading and different immersion tube temperatures ( t ).
( 1 ) air ( 2 ) water, oil ( t ) temperature
Stainless steel
Tube and nipple: X 6 CrNiMoTl 17 122
Temperature Tube diameter "D"
8x0.75mm
or conical
10 x 0.75 mm 15 x 0.75 mm
maximum permissible pressure
100
°
C92bar74bar50bar
150
°
C88bar71bar48bar
200
°
C83bar67bar45bar
300
°
C72bar58bar39bar
400
°
C67bar54bar36bar
Brass
Tube and nipple: CuZn
Temperature Tube diameter "D"
8 x 0.75 mm 10 x 0.75 mm 15 x 0.75 mm
maximum permissible pressure
100
°
C50bar40bar27bar
150
°
C48bar39bar26bar
Probe mountings B, C, D
(probe in di rect contact with med ium)
Process connections
A, H, UO, Q and V
must only be used in unpressurized media.
Mounting the probe
Nipple material
CuZn 39 9 SMnPb.28K X 6 CrNiMoTi 17 122
Max. temperature
200 °C 300 °C 400 °C
Probe material Ø mm Device function
TW STB, STW (STB)
Cu-DHP 04 06bar 2bar
05 05bar 06 04bar 07 03bar 08 03bar 09 03bar
10 03bar
1.4571 (V4A); St 35 04 - 10 10 bar 2 bar
H
The temperature probe ( 2 ) must be fully immersed in the medium, otherwise there will be appreciable variations in the switching point.
(1) Clamp ( 2 ) Temperature probe (3) Capillary (4) Pocket (5) Spring clip
In the "U" and "US" probe mountings of thermostats with capillary, the temperature probe is held in position by sliding a clamping clip over the capillary and clamping it with a screw in the enlarged open end of the pocket. With "B, C, D, E, ES, Q and V" probe mountings, the probe is held in position by the fitting attached to the capillary at the factory.
(1)
( 2 )
(1)
(3)
( 2 )
(4)
(5)
5. Installation
Regulations and notes
V
The electrical connection must only be carried out by qualified personnel.
The choice of cable, the installation and the electrical connection must
conform to the requirements of VDE 0100 “Regulations on the Installation of Power Circuits with Nominal Voltages below 1000 V” and the appropriate local regulations.
If contact with live parts is possible when working on the device, it must be
completely disconnected from the electrical supply.
Ground the instrument to the protective earth at the PE terminal. The cross-
section of this cable must be at least the same as that of the supply cables. Wire the grounding conductors in a star configuration to a common earth point that is connected to the PE conductor of the electrical supply. Do not loop the grounding cables, that is, do not run them from one instrument to another.
Apart from faulty installation, incorrect settings on the thermostat may also
adversely affect the proper functioning of the subsequent process or cause other damage. It should only be poss ible for qualified personnel to make these settings. Please observe the relevant safety regulations for such matters.
7. Self-monitoring
Response to a fracture of the measuring system
Response to low temperature
Using the STW (STB) as an STB
H
With the STB and STW (STB), a fracture of the measuring system (leaking) causes the circuit to stay open permanently. With the STB, the microswitch is also reset.
H
With the STW (STB) and STB, if the probe temperature falls below the minimum value of
-20 °C, the circuit opens. Once the probe temperature has reached the minimum value, the STB must be reset manually. With the STW, reset is automatic.
V
The required lockout function must be ensured by the downstream circuit. This circuit must comply with VDE 0116.
8. Technical data
Mode of operation
per DINEN60730-1, DINEN60730-2-9, and DINEN14597 STW(STB) 2 BKLNP STB 2 BFHKLNPV
Permissible ambient temperature in operation
Permissible probe temperature: max. end of scale +15%
Permissible storage temperature: max. 50 °C, min. -50 °C
Switching point accuracy
as % of scale range, relative to limit value at TU+22 °C
STB, STW (STB) in top third of scale
at start of scale
Mean ambient temperature effect
as % of scale range, relative to limit value. If the ambient temperature at the thermostat head housing and/or capillary deviates from the calibration ambient temperature value of +22 °C in, the switching point is shifted. Higher ambient temperature = lower switching point Lower ambient temperature = higher switching point
Capillary
Thermostat head
At end of scale
max. +80
°
C+80
°
C
min. -40
°
C +80 °C< 200
°
C
-20
°
C +80 °C 200 °C 350 °C
-40
°
C +80 °C > 350 °C 500 °C
Fitted thermostats with end of scale
< +200
°
C +200 °C ≤ +350 °C
STB/STW (STB) STB/STW (STB)
effect on thermostat head
0.17% per °C 0.13%/K effect on capillary per meter
0.054 %/K 0.11 %/K
+0
-5
%
+0
-10
%
Maximum permissible contact rating
(additional info to details on nameplate) AC 230 V +10%, 10(2) A, cos ϕ = 1(0.6) DC 230 V +10%, 0.25 A or AC 230 V +10%, 6(1.2) A, cos ϕ = 1(0.6) for gold-plated microswitch, extra code /au AC/DC 24 V, 0.1 A
Contact reliability
To ensure maximum switching reliability, we recommend a minimum loading of: 24 V AC/DC, 20 mA for silver contacts (standard) 10 V AC/DC, 10 mA for gold-plated contacts (code /au)
Rated surge voltage
2500 V (over the switching contacts: 400 V)
Overvoltage category II
For required fusing, see maximum switching current
Operating medium
water, oil, air, superheated steam
Time constant t
0.632
Protection
EN 60 529 - IP 00
Fitted thermostats with end of scale
+350
°
C ≤ +500 °C
STB/STW (STB)
effect on thermostat head
0.12%/K
effect on capillary per meter
0.03 %/K
in water in oil in air / superheated
steam
45 s ≤ 60 s ≤ 120 s
Electrical connection
The instrument complies with Protection Class I.
Cu capillary tube with PE function
Connection diagrams
H
1.
Make the connection to the terminals ( 2 ) as shown in the relevant connection diagram.
2.
Connect the protective ground conductor to terminal "PE" ( 1 ).
3.
The reset button ( 3 ) must be free to move.
( 1 ) Protective ground
conductor "PE" ( 2 ) Connection screw ( 3 ) Reset button
H
The connection is suitable for fixed wiring.
Cable entry is without fixed strain relief. Attachment type "X" (no special tools).
Screw terminal for conductor cross-section up to 2.5 mm2.
V
With CrNi capillary tubes "longer than 1000 mm", it is the user's responsibility to provide the requisite protective measures against electric shock.
ETH-20
with changeover contact
ETH-70
with break contact and restart lockout
ETH-70/U
with normally-closed contact, restart lockout, and additional signal contact
( 1 )
( 2 )
ETH-20
( 1 )
( 2 )
( 3 )
ETH-70
6. Setpoint/limit setting
Use a screwdriver to set the switching point on the setpoint adjuster before installation.
Resetting the STB
Once the temperature has fallen below the set limit (safe temperature limit) by about 10% of the scale range, the microswitch can be reset.
Press the reset button ( 1 ).
1.
Press and hold the reset button ( 1 ) until the microswitch is reset
(1) setpoint pointer (2) upper stop ( 3 ) scale graduation ( 4 ) setpoint adjuster
( 1 ) Reset button
(1)
(2) (3) (4)
(1)