JUMO dTRANS T03 J, dTRANS T03 Series, dTRANS T03 TU, dTRANS T03 B, dTRANS T03 BU Operating Instructions Manual

...
Page 1
dTRANS T03 J
956530/...
dTRANS T03 B
956531/...
dTRANS T03 T
956532/...
dTRANS T03 BU
956533/...
dTRANS T03 TU
956534/...
Analoger Messumformer
mit digitaler Einstellung
Analog transmitter
with digital adjustment
B 95.6530
Betriebsanleitung
Operating Instructions
09.03 / 00392647
Page 2
Page 3
Inhalt
1 Typenerklärung .......................................................... 4
1.1 Grundausführung................................................................4
1.2 Serienmäßiges Zubehör......................................................5
1.3 Zubehör...............................................................................5
2 Installation ................................................................. 6
2.1 Anschluss dTRANS T03 J - Typ 956530/... ........................6
2.2 Anschluss dTRANS T03 B - Typ 956531/...........................7
2.3 Anschluss dTRANS T03 T - Typ 956532/...........................8
2.4 Anschluss dTRANS T03 BU - Typ 956533/........................9
2.5 Anschluss dTRANS T03 TU - Typ 956534/... ...................10
2.6 Abmessungen ...................................................................11
2.7 Anschlussbeispiel Stromausgang mit Netzgerät ..............13
2.8 Anschlussbeispiel Stromausgang mit Speisetrenner .......13
2.9 Anschlussbeispiel Spannungsausgang ............................14
3 Setup-Programm ..................................................... 15
3.1 Hardware- und Software-Voraussetzungen .....................15
3.2 Konfigurierbare Parameter................................................15
3.3 Abgleichbare Parameter ...................................................15
3.4 Anschlussschema (Abgleich neuer Messbereich) ............16
3.5 Funktionsübersicht ...........................................................17
3.5.1 Messbereich abgleichen ............................................18
3.5.2 Feinabgleich durchführen ..........................................24
3.5.3 Tag-Nummer eingeben ..............................................25
4 Technische Daten Zweidraht-Messumformer ...... 26
5 Technische Daten Dreidraht-Messumformer ....... 29
3
Page 4
1 Typenerklärung
1.1 Grundausführung JUMO dTRANS T03
(1) Grundausführung
dTRANS T03 J
956530
956531
956532
analoger Zweidraht-Messumformer zum Einbau in Anschlusskopf Form J (nur Zweileiter)
dTRANS T03 B analoger Zweidraht-Messumformer zum Einbau in Anschlusskopf Form B
dTRANS T03 T analoger Zweidraht-Messumformer zur Montage auf Tragschiene
dTRANS T03 BU
956533
956534
xxxxx 88 werkseitig eingestellt
xxxxx 99 Konfiguration nach Kundenangaben
xxxx 001 Pt 100 in Dreileiterschaltung
x 003 Pt 100 in Zweileiterschaltung
xxx 005 4 … 20 mA
x x 040 0 … 10 V
analoger Dreidraht-Messumformer zum Einbau in Anschlusskopf Form B
dTRANS T03 TU analoger Dreidraht-Messumformer zur Montage auf Tragschiene
(2) Grundtypergänzung
(Fühlerbruch: positiv; Leitungswiderstand: 0 Ω)
(im Klartext angeben)
(3) Eingang
(4) Ausgang
(1) (2) (3) (4)
Bestellschlüssel /--
Bestellbeispiel 956531 / 88 - 001 - 005
4
Page 5
1 Typenerklärung
1.2 Serienmäßiges Zubehör
- Betriebsanleitung
- Befestigungsmaterial
1.3 Zubehör
- PC-Setup-Programm, mehrsprachig
- PC-Interfaceleitung (galvanisch getrennt) mit TTL/RS 232-
Umsetzer, Netzteil (AC 230 V) und Adapter
- Netzgeräte 1- und 4-fach (Typenblatt 95.6024)
- Trennverstärker und Speisetrenner (Typenblatt 95.6055)
- Messumformer-Speisegerät (Typenblatt 95.6056)
- Befestigungselement zur Montage von Typ 956531/... und Typ 956533/... auf Tragschiene - Verkaufs-Artikel-Nummer: 00352463
5
Page 6
2 Installation
2.1 Anschluss dTRANS T03 J - Typ 956530/...
Setup
Anschluss für Anschlussbelegung
Spannungs­versorgung DC 7,5 ... 30 V bzw. Stromausgang 4 ... 20 mA
Analoge Eingänge
Widerstands­thermometer in Zweileiter­schaltung
+1
-2
3 4
U
R
R U
B
B b
---------------------=
= Bürdenwiderstand = Spannungs-
7,5V
b
22mA
versorgung
serienmäßig R R
= Leitungswider-
L
= 0
L
stand je Leiter
6
Page 7
2 Installation
2.2 Anschluss dTRANS T03 B - Typ 956531/...
Setup
Anschluss für Anschlussbelegung
Spannungs­versorgung DC 7,5 ... 30 V bzw. Stromausgang 4 ... 20 mA
Analoge Eingänge
Widerstands­thermometer in Zweileiter­schaltung
Widerstands­thermometer in Dreileiter­schaltung
+1
-2
3 5 6
3 5 6
U
R
R U
B
B b
---------------------=
= Bürdenwiderstand = Spannungs-
7,5V
b
22mA
versorgung
serienmäßig R R
= Leitungswider-
L
= 0
L
stand je Leiter
R
11
L
= Leitungswider-
R
L
stand je Leiter
H
Bei der Montage des Messumformers Typ 956531/... mit dem Befestigungselement auf Tragschiene (Verkaufs­Artikel-Nummer 00352463) ist auf EMV-gerechte Leitungs­verlegung zu achten.
7
Page 8
2 Installation
2.3 Anschluss dTRANS T03 T - Typ 956532/...
Anschluss für Anschlussbelegung
Spannungs­versorgung DC 7,5 ... 30 V bzw. Stromausgang
+81
-82
R
R U
B
B b
U
---------------------=
7,5V
b
22mA
= Bürdenwiderstand = Spannungs-
4 ... 20 mA
versorgung
Analoge Eingänge
Widerstands-
serienmäßig R
11
thermometer
12
in Zweileiter-
13
R
= Leitungswider-
L
stand je Leiter
schaltung Widerstands-
11
thermometer
12
in Dreileiter-
13
11
R
L
R
= Leitungswider-
L
stand je Leiter
schaltung
= 0
L
8
Page 9
2 Installation
4
6
2.4 Anschluss dTRANS T03 BU - Typ 956533/...
Setup
Anschluss für Anschlussbelegung
Spannungs­versorgung DC 15 ... 30 V
Spannungs­ausgang 0 … 10 V
Analoge Eingänge
Widerstands­thermometer in Zweileiter­schaltung
Widerstands­thermometer in Dreileiter­schaltung
+1
-2
-2 +3
4 5 6
4 5 6
Last 10 k
serienmäßig R R
= Leitungswider-
L
L
stand je Leiter
11
R
L
R
= Leitungswider-
L
stand je Leiter
= 0
12
+–3+
5
54
6
H
Bei der Montage des Messumformers Typ 956533/... mit dem Befestigungselement auf Tragschiene (Verkaufs­Artikel-Nummer 00352463) ist auf EMV-gerechte Leitungs­verlegung zu achten.
9
Page 10
2 Installation
2.5 Anschluss dTRANS T03 TU - Typ 956534/...
Anschluss für Anschlussbelegung
Spannungs­versorgung DC 15 ... 30 V
Spannungs­ausgang
+81
-82
-82 +83
Last 10 k
0 ... 10 V
Analoge Eingänge
Widerstands-
serienmäßig R
11
thermometer
12
in Zweileiter-
13
= Leitungswider-
R
L
stand je Leiter
schaltung Widerstands-
11
thermometer
12
in Dreileiter-
13
11
R
L
= Leitungswider-
R
L
stand je Leiter
schaltung
= 0
L
81 82
+–83+
10
Page 11
2 Installation
2.6 Abmessungen
dTRANS T03 J - Typ 956530/...
Setup
dTRANS T03 B - Typ 956531/... dTRANS T03 BU - Typ 956533/...
Setup
11
Page 12
2 Installation
dTRANS T03 T - Typ 956532/... dTRANS T03 TU - Typ 956534/...
12
Page 13
2 Installation
2.7 Anschlussbeispiel Stromausgang mit Netzgerät
Zweidraht-Messumformer (Typ 956530/..., 956531/..., 956532/...)
2.8 Anschlussbeispiel Stromausgang mit Speisetrenner
Zweidraht-Messumformer (Typ 956530/..., 956531/..., 956532/...)
13
Page 14
2 Installation
2.9 Anschlussbeispiel Spannungsausgang
Dreidraht-Messumformer (Typ 956533/..., 956534/...)
Dreidraht­Messumformer
-
=
+
+
0...10 V
Netzgerät
-
+
=
~
Regler
+
N
L1
Anzeige­gerät
+ +- - -
0...10 V
Registrier­gerät
14
Page 15
3 Setup-Programm
Das Setup-Programm dient zum Abgleich des Messumformers mit Hilfe eines PC. Der Anschluss erfolgt über ein PC-Interface (inkl. Netzteil und Adapter) und der Setup-Schnittstelle des Messumfor­mers.
H
Zum Abgleichen muss der Messumformer an eine Span­nungsversorgung angeschlossen sein. Steht kein Netzgerät oder Speisetrenner zur Verfügung, können die Typen 956530/..., 956531/... und 956532/... zur Konfiguration mit einer 9 V Blockbatterie versorgt werden.
3.1 Hardware- und Software-Voraussetzungen
Für den Betrieb und die Installation des Setup-Programms müssen folgende Hardware- und Software-Voraussetzungen erfüllt sein:
- IBM-PC oder kompatibler PC ab 486DX-2-100
- 64 MB Hauptspeicher
- 10 MB freier Festplattenspeicher
- CD-ROM-Laufwerk
- 1 freie serielle Schnittstelle
- Windows 95, 98, ME oder Windows NT 4.0, 2000
3.2 Konfigurierbare Parameter
- TAG-Number (8 Zeichen)
- Verhalten bei Fühlerbruch/-kurzschluss
3.3 Abgleichbare Parameter
- Messbereichsanfang, Messbereichsende
- Gesamtleitungswiderstand (Hin- und Rückleiter) bei Zweileiterschaltung
15
Page 16
3 Setup-Programm
3.4 Anschlussschema (Abgleich neuer Messbereich)
Anzeigegerät
0...10V
+
Präzisions­widerstandsdekade
dTRANS T03 BU
-
-
+
Spannungsversorgung
DC 15...30V
dTRANS T03 B
Spannungsversorgung
DC 7,5...30V / 25mA
-
+
Anzeigegerät
4...20mA
TTL/RS 232-Umsetzer
Präzisions­widerstandsdekade
Adapter
AC 230V Netzteil
Spannungswahlschalter muss auf 9 Volt stehen
H
Für die Kommunikation zwischen Messumformer und Set­up-Programm ist es erforderlich, dass der Messumformer und das Interface mit der entsprechenden Spannung ver­sorgt werden.
16
Page 17
3 Setup-Programm
3.5 Funktionsübersicht
Nach dem Programmstart erscheint folgender Dialog:
Folgende Funktionen stehen zur Verfügung:
- Messbereich abgleichen
- Feinabgleich durchführen
- Tag-Nummer eingeben
- Abbrechen
Bedienphilosophie
Nur, wenn die Funktion „Messbereich abgleichen“ aufgerufen wird, stehen alle Unterfunktionen zur Verfügung.
Nach direktem Funktionsaufruf des Feinabgleichs oder der Tag­Nummer kann nur die aufgerufene Funktion genutzt werden. Da­durch wird eine ungewollte Veränderung des Messbereiches ver­mieden.
17
Page 18
3 Setup-Programm
3.5.1 Messbereich abgleichen
Voraussetzungen
Zur Erreichung der im Typenblatt angegebenen Genauigkeiten sind folgende Voraussetzungen zu schaffen:
- Präzisionswiderstandsdekade Genauigkeit: ± 0,05 % - Auflösung: 0,01
- Strom- / Spannungs-Messgegerät Genauigkeit: ± 0,05 % ± 10 µA / ± 5 mV
- Warmlaufzeit: 2 min
- Messumformer je nach verwendetem Typ beschalten (siehe Kapi­tel 3.4 „Anschlussschema (Abgleich neuer Messbereich)“)
18
Page 19
3 Setup-Programm
Abgleichvorgang
h Starten Sie das PC-Setup-Programm und wählen die Funktion
„Messbereich abgleichen“.
Folgende Programmoberfläche erscheint:
Menüleiste
Symbolleiste
Arbeitsbereich
19
Page 20
3 Setup-Programm
h Rufen Sie die Funktion mit Hilfe der Menüleiste (Extras ! Abglei-
chen) oder mit der Symbolleiste oder durch Doppelklicken im Arbeitsbereich (Gerätedaten) auf.
Es erscheint die Dialogbox „Abgleich“:
Stellen Sie den abzugleichenden Messbereich ein.
Beachten Sie, dass die Messbereichsanfangswerte in Abhängig-
1
keit der Messbereichsspanne
stehen. Das Setup-Programm
überwacht bei der Veränderung der Messbereichgrenzen die Ein­gabe und warnt vor Fehleingaben.
1
Messbereichsspanne = Messbereichsende - Messbereichsanfang
20
Page 21
3 Setup-Programm
Im folgenden Bild wird eine fehlerhafte Eingabe gezeigt.
Fehlermeldung
Mit Hilfe der Schaltfläche „Messbereichs-Diagramm“ werden Ih­nen alle möglichen Messbereichsanfangswerte in Abhängigkeit der Messbereichsspanne angezeigt.
21
Page 22
3 Setup-Programm
Messbereichsspanne = Messbereichsende - Messbereichsanfang
22
Page 23
3 Setup-Programm
Beispiel einer Berechnung:
Messbereichsanfang = -50 °C, Messbereichsende = 250 °C
Messbereichsspanne = Messbereichsspanne = 250 °C - (-50 °C) Messbereichsspanne = 300 K
Der Messbereichsanfang ist so zu wählen, dass er innerhalb
A H
h Haben Sie einen gültigen Messbereich gewählt, starten Sie durch
Betätigen der Schaltfläche „Abgleichen“ den Abgleichvorgang.
der grauen Fläche liegt.
Bei Messbereichsspannen kleiner 75 °C sind nur die Messbereichsanfangswerte -40 °C, -20 °C, 0 °C, +20 °C und +40 °C zulässig.
Messbereichsende - Messbereichsanfang
Folgen Sie den weiteren Anweisungen des Setup-Programmes.
H
Denken Sie daran, dass bei der Zweileiter-Schaltung der Gesamtleitungswiderstand angegeben werden muss, damit eine maximale Messgenauigkeit erreicht werden kann.
23
Page 24
3 Setup-Programm
3.5.2 Feinabgleich durchführen
Unter Feinabgleich ist eine Korrektur des Ausgangssignales eines abgeglichenen Messumformers zu verstehen. Das Signal kann im Bereich von ± 0,2 mA bei Stromausgang und ± 0,1 V bei Spannungs­ausgang korrigiert werden.
Ablauf
h Starten Sie das PC-Setup-Programm und wählen die Funktion
„Feinabgleich durchführen“.
h Rufen Sie die Funktion mit Hilfe der Menüleiste (Extras ! Feinab-
gleich) oder mit der Symbolleiste auf.
Es erscheint die Dialogbox „Feinabgleich“:
h Mit Hilfe der Pfeil-Schaltflächen nehmen Sie den Feinabgleich vor
und schließen ihn durch „OK“ ab.
H
Beachten Sie, dass beim Feinabgleich des Offsets und des Messbereichendes jeweils das entsprechende Eingangs­signal anliegt.
24
Page 25
3 Setup-Programm
3.5.3 Tag-Nummer eingeben
Mit der Tag-Nummer (max. 8 Zeichen) können Sie eine Kennzeich­nung (Bezeichnung der Messstelle) im Messumformer abspeichern.
Ablauf
h Starten Sie das PC-Setup-Programm . h Rufen Sie die Funktion mit Hilfe der Menüleiste (Editieren ! Tag-
Nummer) oder durch Doppelklicken im Arbeitsbereich (Tag-Num­mer) auf.
Es erscheint die Dialogbox „Tag-Nummer“:
h Geben Sie die Nummer ein und schließen den Dialog durch „OK“
ab.
h Übertragen Sie die Tag-Nummer mit Hilfe der Menüleiste (Daten-
transfer ! Datentransfer zum Gerät) oder mit der Symbolleiste in den Messumformer.
25
Page 26
4 Technische Daten Zweidraht-Messumformer
Typ 956532/...
dTRANS T03 T
Typ 956531/...
dTRANS T03 B
Typ 956530/...
dTRANS T03 J
bei Messspanne = 75 K: ±50 °C
bei Messspannen > 75 K: siehe Seite 22
negativ: 3,6 mA
Feinabgleich per PC möglich
Messbereiche mit PC-Setup-Programm abgleichbar;
Messeingang Pt 100 (DIN EN 60 751)
Messbereichsgrenzen -200 … +850 °C
Anschlussart Zweileiterschaltung Zwei-/Dreileiterschaltung Zwei-/Dreileiterschaltung
kleinste Messspanne 25 K
größte Messspanne 1050 K
Eingang Widerstandsthermometer
Nullpunktverschiebung bei Messspannen < 75 K feste Nullpunkteinstellung: -40 °C, -20 °C, 0 °C, 20 °C, 40 °C
Sensorleitungswiderstand
bei Dreileiteranschluss 11 Ω je Leitung
Sensorleitungswiderstand
bei Zweileiteranschluss 0 Ω Leitungswiderstand
Sensorstrom 0,5 mA
Messrate Dauermessung, da analoger Signalpfad
26
Besonderheiten Abgleich in °C oder °F;
Messbereichsunterschreitung abfallend bis 3,6 mA
Messkreisüberwachung
Messbereichsüberschreitung ansteigend auf 22 mA … < 28 mA (typisch 24 mA)
Fühlerkurzschluss 3,6 mA
Fühler- und Leitungsbruch positiv: 22 mA … < 28 mA (typisch 24 mA)
Page 27
4 Technische Daten Zweidraht-Messumformer
Typ 956532/...
dTRANS T03 T
1
2
oder ± 0,2 K
1,2
Typ 956531/...
dTRANS T03 B
1
± 0,2 %
± 0,01 % / K Abw. von 22 °C
± 0,01 % / V Abweichung von 24 V
Typ 956530/...
dTRANS T03 J
Ausgangssignal eingeprägter Gleichstrom 4 ... 20 mA
Übertragungsverhalten temperaturlinear
Übertragungsgenauigkeit ± 0,1 %
Ausgang
Dämpfung der Restwelligkeit
der Versorgungsspannung > 40 dB
Bürde (Rb) Rb = (Ub - 7,5 V) / 22 mA
Bürdeneinfluss ± 0,02 % / 100 1Einstellzeit bei Temperaturänderung 10 ms
Abgleichbedingungen DC 24 V / ca. 22 °C
Abgleichgenauigkeit
Spannungsversorgung (Ub) DC 7,5 ... 30 V
Spannungsversorgung
27
Verpolungsschutz ja
Alle Angaben beziehen sich auf den Messbereichsendwert 20 mA 2Der größere Wert hat Gültigkeit
Spannungsversorgungseinfluss
1
Betriebstemperaturbereich -40 ... +85 °C -40 ... +85 °C -25 ... +70 °C
Lagertemperaturbereich -40 ... +100 °C
Temperatureinfluss
Klimafestigkeit rel. Feuchte 95 % im Jahresmittel ohne Betauung
Umwelteinflüsse
Vibrationsfestigkeit gemäß GL Kennlinie 2 gemäß GL Kennlinie 2 -
Page 28
4 Technische Daten Zweidraht-Messumformer
­IP 20
2,5 mm²;
Typ 956532/...
dTRANS T03 T
Typ 956532/...
dTRANS T03 T
auf Hutschiene
auf Hutschiene
15 mm (EN 50 045);
Klasse B
EN 61 326
Typ 956531/...
dTRANS T03 B
Industrie-Anforderung
Typ 956530/...
dTRANS T03 J
-
IP 54 / IP 00
-
IP 54 / IP 00
Drehmoment max. 0,6 Nm
Typ 956531/...
dTRANS T03 B
Typ 956530/...
dTRANS T03 J
1,75 mm²;
Drehmoment max. 0,6 Nm
35 mm x 7,5 mm (EN 50 022);
DIN 43 729;
auf G-Schiene (EN 50 035)
(auf Anfrage);
im Aufbaugehäuse
erforderlich)
im Schaltschrank
(Befestigungselement
die Montage darf nur mit original Zubehör erfolgen!
- Störaussendung
- Störfestigkeit
EMV
IP-Schutzart
Alle Angaben beziehen sich auf den Messbereichsendwert 20 mA
- im Anschlusskopf / offene Montage
- auf Hutschiene
1
Material Polycarbonat (vergossen) Polycarbonat (vergossen) Polycarbonat
Gehäuse
Schraubanschluss 1,5 mm²;
Drehmoment max. 0,15 Nm
28
Montage im Anschlusskopf Form J im Anschlusskopf Form B
Einbaulage beliebig
Gewicht ca. 12 g ca. 45 g ca. 70 g
Page 29
5 Technische Daten Dreidraht-Messumformer
Typ 956534/...
dTRANS T03 TU
negativ: 0 V
Typ 956533/...
dTRANS T03 BU
bei Messspanne = 75 K: ±50 °C
bei Messspannen > 75 K: siehe Seite 22
Feinabgleich per PC möglich
Messbereiche mit PC-Setup-Programm abgleichbar;
Messeingang Pt 100 (DIN EN 60 751)
Messbereichsgrenzen -200 … +850 °C
Anschlussart Zwei-/Dreileiterschaltung
kleinste Messspanne 40 K
größte Messspanne 1050 K
Eingang Widerstandsthermometer
Nullpunktverschiebung bei Messspannen < 75 K feste Nullpunkteinstellung: -40 °C, -20 °C, 0 °C, 20 °C, 40 °C
Sensorleitungswiderstand
bei Dreileiteranschluss 11 Ω je Leitung
Sensorleitungswiderstand
bei Zweileiteranschluss 0 Ω Leitungswiderstand
Sensorstrom ≤ 0,5 mA
Messrate Dauermessung, da analoger Signalpfad
29
Besonderheiten Abgleich in °C oder °F;
Messbereichsunterschreitung 0 V
Messbereichsüberschreitung ansteigend auf > 11 V … < 14 V (typisch 12 V)
Fühlerkurzschluss 0 V
Messkreisüberwachung
Fühler- und Leitungsbruch positiv: ansteigend auf > 11 V … < 14 V (typisch 12 V)
Page 30
5 Technische Daten Dreidraht-Messumformer
1
2
oder ± 0,2 K
1,2
Typ 956534/...
dTRANS T03 TU
1
± 0,2 %
± 0,01 % / K Abw. von 22 °C
± 0,01 % / V Abweichung von 24 V
Typ 956533/...
dTRANS T03 BU
Ausgangssignal Gleichspannung 0 ... 10 V
Übertragungsverhalten temperaturlinear
Übertragungsgenauigkeit ± 0,2 %
Ausgang
Dämpfung der Restwelligkeit
der Versorgungsspannung > 40 dB
Last 10 k
Lasteinfluss ± 0,1 %
Einstellzeit bei Temperaturänderung 10 ms
Abgleichbedingungen DC 24 V / ca. 22 °C
Abgleichgenauigkeit
Spannungsversorgung (Ub) DC 15 ... 30 V
Spannungsversorgung
30
Verpolungsschutz ja
Alle Angaben beziehen sich auf den Messbereichsendwert 10 V 2Der größere Wert hat Gültigkeit
Spannungsversorgungseinfluss
1
Betriebstemperaturbereich -40 ... +85 °C -25 ... +70 °C
Lagertemperaturbereich -40 ... +100 °C
Temperatureinfluss
Klimafestigkeit rel. Feuchte 95 % im Jahresmittel ohne Betauung
Umwelteinflüsse
Vibrationsfestigkeit gemäß GL Kennlinie 2 -
Page 31
5 Technische Daten Dreidraht-Messumformer
­IP 20
2,5 mm²;
Typ 956534/...
dTRANS T03 TU
Typ 956534/...
dTRANS T03 TU
auf Hutschiene
auf Hutschiene
15 mm (EN 50 045);
Klasse B
EN 61 326
Industrie-Anforderung
Typ 956533/...
dTRANS T03 BU
-
IP 54 / IP 00
Drehmoment max. 0,6 Nm
Typ 956533/...
dTRANS T03 BU
Drehmoment max. 0,6 Nm
35 mm x 7,5 mm (EN 50 022);
DIN 43 729;
auf G-Schiene (EN 50 035)
(auf Anfrage);
im Aufbaugehäuse
erforderlich)
im Schaltschrank
(Befestigungselement
die Montage darf nur mit original Zubehör erfolgen!
- Störaussendung
- Störfestigkeit
EMV
IP-Schutzart
- im Anschlusskopf / offene Montage
- auf Hutschiene
Alle Angaben beziehen sich auf den Messbereichsendwert 10V
1
Gehäuse
Material Polycarbonat (vergossen) Polycarbonat
Schraubanschluss 1,75 mm²;
31
Montage im Anschlusskopf Form B
Einbaulage beliebig
Gewicht ca. 45 g ca. 70 g
Page 32
Page 33
Page 34
JUMO GmbH & Co. KG
Hausadresse: Moltkestraße 13 - 31 36039 Fulda, Germany Lieferadresse: Mackenrodtstraße 14 36039 Fulda, Germany Postadresse: 36035 Fulda, Germany Telefon: +49 661 6003-725 Telefax: +49 661 6003-681 E-Mail: mail@jumo.net Internet: www.jumo.net
JUMO Mess- und Regelgeräte Ges.m.b.H.
Pfarrgasse 48 1232 Wien, Austria Telefon: +43 1 610610 Telefax: +43 1 6106140 E-Mail: info@jumo.at Internet: www.jumo.at
JUMO Mess- und Regeltechnik AG
Seestrasse 67, Postfach 8712 Stäfa, Switzerland Telefon: +41 1 928 24 44 Telefax: +41 1 928 24 48 E-Mail: info@jumo.ch Internet: www.jumo.ch
Page 35
dTRANS T03 J
Type 956530/...
dTRANS T03 B
Type 956531/...
dTRANS T03 T Type 956532/...
dTRANS T03 BU
Type 956533/...
dTRANS T03 TU
Type 956534/...
Analog transmitter
with digital adjustment
B 95.6530
Operating Instructions
Page 36
Page 37
Contents
1 Type designation ....................................................... 4
1.1 Basic version.......................................................................4
1.2 Standard accessories .........................................................5
1.3 Accessories.........................................................................5
2 Installation ................................................................. 6
2.1 Connection dTRANS T03 J - Type 956530/... ....................6
2.2 Connection dTRANS T03 B - Type 956531/.......................7
2.3 Connection dTRANS T03 T - Type 956532/.......................8
2.4 Connection dTRANS T03 BU - Type 956533/....................9
2.5 Connection dTRANS T03 TU - Type 956534/... ...............10
2.6 Dimensions .......................................................................11
2.7 Connection example: current output with supply unit......13
2.8 Connection example: current output with supply
isolator ....................................................................................13
2.9 Connection example: voltage output................................14
3 Setup program ......................................................... 15
3.1 Hardware and software requirements ..............................15
3.2 Configurable parameters ..................................................15
3.3 Parameters that can be calibrated....................................15
3.4 Connection layout (calibrate new range) ..........................16
3.5 Overview of functions .......................................................17
3.5.1 Calibrating the range..................................................18
3.5.2 Performing the fine calibration...................................24
3.5.3 Entering the TAG number ..........................................25
4 Technical data for 2-wire transmitter .................... 26
5 Technical data for 3-wire transmitter .................... 29
3
Page 38
1 Type designation
1.1 Basic version JUMO dTRANS T03
(1) Basic version
dTRANS T03 J
956530
956531
956532
analog 2-wire transmitter for mounting inside terminal head Form J (2-wire only)
dTRANS T03 B analog 2-wire transmitter for mounting inside terminal head Form B
dTRANS T03 T analog 2-wire transmitter for rail mounting
dTRANS T03 BU
956533
956534
xxxxx 88 factory-set
xxxxx 99 configuration to customer specification
xxxx 001 Pt 100 in 3-wire circuit
x 003 Pt 100 in 2-wire circuit
xxx 005 4 — 20 mA
x x 040 0 — 10 V
analog 3-wire transmitter for mounting inside terminal head Form B
dTRANS T03 TU analog 3-wire transmitter for rail mounting
(2) Basic type extension
(probe break: positive; lead resistance: 0 Ω)
(please specify in plain text)
(3) Input
(4) Output
(1) (2) (3) (4)
Order code /--
Order example 956531 / 88 - 001 - 005
4
Page 39
1 Type designation
1.2 Standard accessories
- Operating Instructions
- fixing items
1.3 Accessories
- PC setup program, multilingual
- PC interface cable (electrically isolated) with TTL/RS 232 converter, power supply (230 V AC) and adapter
- supply units 1-way and 4-way (Data Sheet 95.6024)
- isolating amplifier and supply isolator (Data Sheet 95.6055)
- supply unit for transmitters (Data Sheet 95.6056)
- fixing bracket for mounting Type 956531/... and Type 956533/... on rail, Sales No. 00352463
5
Page 40
2 Installation
2.1 Connection dTRANS T03 J - Type 956530/...
Setup
Connection for Terminals
Supply voltage
7.5 — 30 V DC or current output 4 — 20 mA
Analog inputs
Resistance thermometer in 2-wire circuit
+1
-2
3 4
U
R
R U
R R
B
B b
L L
---------------------=
= burden resistance = supply voltage
= 0 Ω as standard = lead resistance
7.5V
b
22mA
per conductor
6
Page 41
2 Installation
2.2 Connection dTRANS T03 B - Type 956531/...
Setup
Connection for Terminals
Supply voltage
7.5 — 30 V DC or current output 4 — 20 mA
Analog inputs
Resistance thermometer in 2-wire circuit
Resistance thermometer in 3-wire circuit
+1
-2
3 5 6
3 5 6
U
R
R U
B
B b
---------------------=
= burden resistance = supply
7.5V
b
22mA
voltage
R
= 0as standard
L
R
= lead resistance
L
per conductor
R
11
L
= lead resistance
R
L
per conductor
H
When mounting the transmitter Type 956531/... on the rail, using the mounting bracket (Sales No. 00352463), make sure to route the cables in accordance with the EMC regula­tions.
7
Page 42
2 Installation
2.3 Connection dTRANS T03 T - Type 956532/...
Connection for Terminals
Supply voltage
7.5 — 30 V DC or current output
+81
-82
R
B
R
= burden resistance
B
U
= supply
b
4 — 20 mA
Analog inputs
Resistance
11
thermometer
12
R
= 0as standard
L
R
= lead resistance
L
in 2-wire
13
circuit Resistance
11
thermometer
12
11
R
L
R
= lead resistance
L
in 3-wire
13
circuit
U
---------------------=
7.5V
b
22mA
voltage
per conductor
per conductor
8
Page 43
2 Installation
4
6
2.4 Connection dTRANS T03 BU - Type 956533/...
Setup
Connection for Terminals
Supply voltage 15 — 30 V DC
Voltage output 0 — 10 V
Analog inputs
Resistance thermometer in 2-wire circuit
Resistance thermometer in 3-wire circuit
+1
-2
-2 +3
4 5 6
4 5 6
load 10 k
R
= 0as standard
L
R
= lead resistance
L
per conductor
11
R
L
R
= lead resistance
L
per conductor
12
+–3+
5
54
6
H
When mounting the transmitter Type 956533/... on the rail, using the mounting bracket (Sales No. 00352463), make sure to route the cables in accordance with the EMC regula­tions.
9
Page 44
2 Installation
2.5 Connection dTRANS T03 TU - Type 956534/...
Connection for Terminals
Supply voltage 15 — 30 V DC
Voltage output
+81
-82
-82 +83
load 10 k
0 — 10 V
Analog inputs
Resistance
11
thermometer
12
R
= 0as standard
L
= lead resistance
R
L
in 2-wire
13
circuit Resistance
11
thermometer
12
11
R
L
= lead resistance
R
L
in 3-wire
13
circuit
81 82
+–83+
per conductor
per conductor
10
Page 45
2 Installation
2.6 Dimensions
dTRANS T03 J - Type 956530/...
Setup
dTRANS T03 B - Type 956531/... dTRANS T03 BU - Type 956533/...
Setup
11
Page 46
2 Installation
dTRANS T03 T - Type 956532/... dTRANS T03 TU - Type 956534/...
Mounting rail: C-rail 35mm x 7.5mm EN 50 022
Mounting rail: C-rail 15mm EN 50 045
Mounting rail: G-rail EN 50 035
12
Page 47
2 Installation
2.7 Connection example: current output with supply unit
2-wire transmitter (Type 956530/..., 956531/..., 956532/...)
RecorderIndicatorController
2-wire transmitter
=
-
+
-
- -+ ++
4 — 20 mA
Supply unit
7.5 —30 V DC
+
_
-
~
2.8 Connection example: current output with supply
isolator
2-wire transmitter (Type 956530/..., 956531/..., 956532/...)
RecorderIndicatorController
2-wire transmitter
+
Supply isolator
+
+
+
+ +- - -
=
=
4—20 mA
-
-
~
=
4—20 mA / 0—20 mA
-
L1 N
+
+
-
+ +- - -
0—10 V
13
Page 48
2 Installation
2.9 Connection example: voltage output
3-wire transmitter (Type 956533/..., 956534/...)
RecorderIndicatorController
3-wire transmitter
=
+
0 — 10 V
-
+
Supply unit
-
=
+
~
L1
+
N
+ +- - -
0 — 10 V
14
Page 49
3 Setup program
The setup program is available for calibrating the transmitter from a PC. Connection is through the PC interface (incl. power supply and adapter) and the setup interface of the transmitter.
H
In order to calibrate the transmitter, it has to be connected to the supply voltage. If no supply unit or supply isolator is available, Types 956530/..., 956531/... and 956532/... can be configured using a 9 V block battery as a power source.
3.1 Hardware and software requirements
The following hardware and software requirements have to be met for installing and operating the setup program:
- IBM-compatible PC from 486DX-2-100
- 64 MB main memory
- 10 MB available on hard disk
-CD-ROM drive
- 1 free serial interface
- Windows 95, 98, ME or Windows NT 4.0, 2000
3.2 Configurable parameters
- TAG number (8 characters)
- Response to probe break / short-circuit
3.3 Parameters that can be calibrated
- Range start, range end
- Total lead resistance (out and return conductor) for 2-wire circuit
15
Page 50
3 Setup program
3.4 Connection layout (calibrate new range)
Indicator
0 — 10V
+
Precision decade resistor
dTRANS T03 BU
-
-
+
Supply voltage
15 — 30V DC
dTRANS T03 B
Supply voltage
7.5 — 30V / 25mADC
-
+
Indicator
4 — 20mA
TTL/RS232 converter
Precision decade resistor
Adapter
230 V AC power supply
voltage selector must be set to 9 V
H
For the communication between transmitter and setup pro­gram, the transmitter and the interface have to be supplied with the appropriate voltage.
16
Page 51
3 Setup program
3.5 Overview of functions
The following dialog appears after the program start:
The following functions are available:
- Calibrate range
- Perform fine calibration
- Enter TAG number
- Cancel
Operational philosophy
All sub-functions will only be available when the function “Calibrate range” has been called up.
When fine calibration or the TAG number is called up directly, only the function that was called up can be used. This prevents an unin­tentional alteration of the range.
17
Page 52
3 Setup program
3.5.1 Calibrating the range
Preconditions
The following preconditions are necessary for achieving the accura­cies specified in the data sheet:
- precision decade resistor accuracy: ± 0.05 %, resolution: 0.01
- ammeter / voltmeter accuracy: ± 0.05 % ± 10 µA / ± 5 mV
- warming-up time: 2 min
- connect transmitter according to the type used, see Chapter 3.4 “Connection layout (calibrate new range)”
18
Page 53
3 Setup program
Calibration procedure
h Start up the PC setup program and select the function “Calibrate
range”.
You will see the following program interface:
Menu bar
Icon bar
Working area
19
Page 54
3 Setup program
h Call up the function by using the menu bar (Extras ! Calibrate) or
the icon bar , or double-click on the working area (instrument data).
The dialog box “Calibration” appears:
Set the range to be calibrated.
Please note that the range-start values are related to the range
1
span
. If the range limits are modified, the setup program will
monitor the input and come up with an error message.
1
range span = range end – range start
20
Page 55
3 Setup program
The screenshot below shows such an erroneous entry.
Error message
When you activate the “Range diagram” button, all the possible range-start values in relation to the range span will be shown to you.
21
Page 56
3 Setup program
range span = range end – range start
22
Page 57
3 Setup program
Calculation example:
range start = –50 °C, range end = 250 °C
range span = range end range span = 250 °C – (–50 °C) range span = 300 °C
When selecting the range start, make sure it lies within the
A H
h When you have selected a valid range, start the calibration proce-
dure by activating the “Calibrate” button.
gray area.
For spans that are smaller than 75 °C, the only permissible range-start values are: -40 °C, -20 °C, 0 °C, +20 °C and +40 °C.
– range start
The setup program will instruct you further.
H
Please remember that, for a 2-wire circuit, the total lead re­sistance has to be specified in order to achieve maximum measurement accuracy.
23
Page 58
3 Setup program
3.5.2 Performing the fine calibration
Fine calibration means adjustment of the output signal of a calibrat­ed transmitter. The signal can be adjusted within the range of ± 0.2 mA for current output, and ± 0.1 V for voltage output.
Procedure
h Start up the PC setup program and select the function “Perform
fine calibration”.
h Call up the function by using the menu bar (Extras ! Fine calibra-
tion) or use the icon bar .
You will see the dialog box “Fine calibration”:
h Perform the fine calibration by using the arrow buttons and click
on “OK”.
H
When performing fine calibration of the offset and range end, make sure that the corresponding input signal is present.
24
Page 59
3 Setup program
3.5.3 Entering the TAG number
The TAG number (max 8 characters) is available for storing an iden­tifier (designation of measurement point) in the transmitter.
Procedure
h Start up the PC setup program. h Call up the function by using the menu bar (Edit ! TAG number)
or by a double-click on the working area (TAG number).
The dialog box “TAG number” will appear:
h Enter the number and confirm the dialog by clicking on “OK”. h Transfer the TAG number to the transmitter by using the menu bar
(Data transfer ! Data transfer to instrument), or with the help of the icon bar .
25
Page 60
4 Technical data for 2-wire transmitter
dTRANS T03 T
Type 956532/...
dTRANS T03 B
Type 956531/...
dTRANS T03 J
Type 956530/...
negative: 3.6 mA
for span = 75 °C: ±50 °C
for spans > 75 °C: see page 22
fine calibration from PC is possible
ranges can be calibrated by using the PC setup programm;
Measurement input Pt100 (EN 60 751)
Range limits -200 to +850 °C
Connection circuit 2-wire circuit 2-/3-wire circuit 2-/3-wire circuit
Smallest span 25°C
Largest span 1050 °C
Input for resistance thermometer
Zero shift for spans < 75 °C fixed zero: -40 °C, -20 °C, 0 °C, 20 °C, 40 °C
Sensor lead resistance
for 3-wire connection 11 Ω per conductor
Sensor lead resistance
26
for 2-wire connection 0 Ω lead resistance
Sensor current 0.5 mA
Sampling rate continous measurement because of analog signal path
Features calibration in °C or °F;
Underrange falling to 3.6 mA
Measuring circuit monitoring
Overrange rising to 22 mA to < 28 mA (typically 24 mA)
Probe short-circuit 3.6 mA
Probe and lead break positive: 22 mA to < 28 mA (typically 24 mA)
Page 61
4 Technical data for 2-wire transmitter
dTRANS T03 T
Type 956532/...
1
2
or ≤ ± 0.2 °C
1,2
dTRANS T03 B
Type 956531/...
dTRANS T03 J
Type 956530/...
Output
Output signal proportional DC current 4 — 20 mA
Transfer characteristic linear with temperature
Transfer accuracy ± 0.1 %
Damping of ripple
on supply voltage > 40 dB
Burden (Rb) Rb = (Ub - 7.5 V) / 22 mA
Burden error ± 0.02 % / 100 1Settling time on a temperature change 10 msec
Calibration conditions 24 V DC / approx. 22 °C
Calibration accuracy ± 0.2 %
Supply voltage (Ub) 7.5 — 30 V DC
Supply
Reverse polarity protection yes
All details refer to the range-end value 20 mA 2The larger value applies.
Supply voltage error ± 0.01 % per V deviation from 24 V
1
Operating temperature range -40 to +85 °C -40 to +85 °C -25 to +70 °C
Storage temperature range -40 to +100 °C
Ambient conditions
Temperature error ± 0.01 % per °C deviation from 22 °C1Climatic conditions rel. humidity 95 % annual mean, no condensation
Vibration strength to GL Characteristic 2 to GL Characteristic 2 -
27
Page 62
4 Technical data for 2-wire transmitter
dTRANS T03 T
Type 956532/...
­IP20
on C-rail
dTRANS T03 T
-
polycarbonate
Type 956532/...
2.5 mm²;
max. torque 0.6 Nm
on C-rail
15 mm (EN 50 045);
on G-rail (EN 50 035)
35 mm x 7.5 mm (EN 50 022);
Class B
EN 61 326
dTRANS T03 B
Type 956531/...
industrial requirements
dTRANS T03 J
Type 956530/...
IP54 / IP00
-
IP54 / IP00
dTRANS T03 B
dTRANS T03 J
polycarbonate
Type 956531/...
Type 956530/...
1.75 mm²;
(encapsulated)
max. torque 0.6 Nm
(encapsulated)
max. torque 0.15 Nm
DIN 43 729;
(on request);
in switchgear cabinet
in surface-mounting case
required)
(fixing bracket is
use only original accessories for mounting!
- interference emission
- noise immunity
EMC
IP protection
All details refer to the range-end value 20 mA
- in terminal head / open mounting
- on C-rail
1
Housing
Material polycarbonate
Screw terminal 1.5 mm²;
Mounting inside terminal head Form J inside terminal head Form B
Operating position any
Weight approx. 12 g approx. 45 g approx. 70 g
28
Page 63
5 Technical data for 3-wire transmitter
Type 956534/...
dTRANS T03 TU
negative: 0 V
Type 956533/...
dTRANS T03 BU
for span = 75 °C: ±50 °C
for spans > 75 °C: see page 22
fine calibration from PC is possible
ranges can be calibrated through PC setup program;
Measurement input Pt100 (EN 60 751)
Range limits -200 to +850 °C
Connection circuit 2-/3-wire circuit
Smallest span 40 °C
Largest span 1050 °C
Input for resistance thermometer
Zero shift for spans < 75 °C fixed zero: -40 °C, -20 °C, 0 °C, 20 °C, 40 °C
Sensor lead resistance
for 3-wire connection ≤ 11 Ω per conductor
Sensor lead resistance
29
for 2-wire connection 0 Ω lead resistance
Sensor current 0.5 mA
Sampling rate continuous measurement because of analog signal path
Features calibration in °C or °F;
Underrange 0 V
Overrange rising to > 11 V to < 14 V (typically 12 V)
Probe short-circuit 0 V
Measuring circuit monitoring
Probe and lead break positive: rising to > 11 V to < 14 V (typically 12 V)
Page 64
5 Technical data for 3-wire transmitter
2
or ± 0.2 °C
1,2
± 0.2 %
1
Type 956534/...
dTRANS T03 TU
± 0.01 % per V deviation from 24 V
Type 956533/...
dTRANS T03 BU
1
± 0.01 % per °C deviation from 22 °C
Output
Output signal DC current 0 — 10 V
Transfer characteristic linear with temperature
Transfer accuracy ± 0.2 %
Damping of ripple
on supply voltage > 40 dB
Load 10 k
Load error ± 0.1 %
Settling time on temperature change 10 msec
Calibration conditions 24 V DC / approx. 22 °C
Calibration accuracy
Supply voltage (Ub) 15 — 30 V DC
Supply
Reverse polarity protection yes
All details refer to the range-end value 10 V 2The larger value applies
Supply voltage error
1
Operating temperature range -40 to +85 °C -25 to +70 °C
Storage temperature range -40 to +100 °C
Temperature error
Climatic conditions rel. humidity 95 % annual mean, no condensation
Ambient conditions
Vibration strength to GL characteristic 2 -
30
Page 65
5 Technical data for 3-wire transmitter
Type 956534/...
dTRANS T03 TU
Class B
EN 61 326
­IP20
on C-rail
2.5 mm²;
Type 956534/...
dTRANS T03 TU
max. torque 0.6 Nm
on C-rail
15 mm (EN 50 045);
on G-rail (EN 50 035)
35 mm x 7.5 mm (EN 50 022);
industrial requirements
Type 956533/...
dTRANS T03 BU
-
IP54 / IP00
Type 956533/...
dTRANS T03 BU
max. torque 0.6 Nm
DIN 43 729;
(on request);
in surface-mounting case
required)
(fixing bracket is
in switchgear cabinet
use only original accessories for mounting!
- interference emission
- noise immunity
EMC
IP protection
- in terminal head / open mounting
- on C-rail
All details refer to the range-end value 10V
1
Housing
Material polycarbonate (encapsulated) polycarbonate
Screw terminal 1.75 mm²;
Mounting inside terminal head Form B
Operating position any
Weight approx. 45 g approx. 70 g
31
Page 66
Page 67
Page 68
JUMO GmbH & Co. KG
Street address: Moltkestraße 13 - 31 36039 Fulda, Germany Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House Temple Bank, Riverway Harlow, Essex CM20 2TT, UK Phone: +44 1279 635533 Fax: +44 1279 635262 e-mail: sales@jumo.co.uk Internet: www.jumo.co.uk
JUMO PROCESS CONTROL INC.
885 Fox Chase, Suite 103 Coatesville, PA 19320, USA Phone: 610-380-8002
1-800-554-JUMO Fax: 610-380-8009 e-mail: Internet: www.JumoUSA.com
info@JumoUSA.com
Page 69
dTRANS T03 J
Type 956530/...
dTRANS T03 B Type 956531/...
dTRANS T03 T
Type 956532/...
dTRANS T03 BU
Type 956533/...
dTRANS T03 TU
Type 956533/...
Convertisseur de mesure analogique
en technique 2 fils
à réglage numérique
B 95.6530
Notice de mise en service
02.03 / 00392648
Page 70
Page 71
Sommaire
1 Identification du type ................................................ 2
1.1 Exécution de base..............................................................2
1.2 Accessoires de série ..........................................................3
1.3 Accessoires ........................................................................3
2 Installation ................................................................. 4
2.1 Raccordement dTRANS T03 J - Type 956530/..................4
2.2 Raccordement dTRANS T03 B - Type 956531/... ..............5
2.3 Raccordement dTRANS T03 T - Type 956532/... ..............6
2.4 Raccordement dTRANS T03 BU - Type 956533/... ...........7
2.5 Raccordement dTRANS T03 TU - Type 956534/...............8
2.6 Dimensions.........................................................................9
2.7 Exemple de raccordement sortie courant
avec un bloc d’alimentation .............................................11
2.8 Exemple de raccordement sortie courant
avec une alimentation à séparation galvanique ...............11
2.9 Exemple de raccordement sortie tension.........................12
3 Logiciel Setup .......................................................... 13
3.1 Conditions matérielles et logicielles .................................13
3.2 Paramètres configurables.................................................13
3.3 Paramètres réglables........................................................13
3.4 Schéma de raccordement (réglage de la nouvelle
étendue de mesure)..........................................................14
3.5 Vue d’ensemble du fonctionnement.................................15
3.5.1 Réglage de l’étendue de mesure ...............................16
3.5.2 Exécution du réglage fin ............................................22
3.5.3 Saisie du numéro Tag ................................................23
4 Données techniques - Convert. de mesure, 2 fils 24
5 Données techniques - Converti. de mesure, 3 fils 27
1
Page 72
1 Identification du type
1.1 Exécution de base JUMO dTRANS T03
(1) Exécution de base
dTRANS T03 J
956530
956531
956532
Convertisseur de mesure analogique, en technique 2 fils, à monter dans une tête de raccordement forme J (uniquement 2 fils)
dTRANS T03 B Convertisseur de mesure analogique, en technique 2 fils, à monter dans une tête de raccordement forme B
dTRANS T03 T Convertisseur de mesure analogique, en technique 2 fils, à monter sur rail
dTRANS T03 BU
956533
956534
xxxxx 88 Réglage d’usine
xxxxx 99 Configuration spécifique (à indiquer en clair)
xxxx 001 Pt 100 en montage 3 fils
x 003 Pt 100 en montage 2 fils
x x x 005 4 à 20 mA
x x 040 0 à 10 V
Convertisseur de mesure analogique, en technique 3 fils, à monter dans une tête de raccordement forme B
dTRANS T03 TU Convertisseur de mesure analogique, en technique 3 fils, à monter sur rail
(2) Extensions de base
rupture de sonde : positif ; résistance de ligne: 0 Ω)
(3) Entrée
(4) Sortie
(1) (2) (3) (4) Code d’identification
Ex. de commande 956531 / 88 - 001 - 005
/--
2
Page 73
1 Identification du type
1.2 Accessoires de série
- 1 notice de mise en service
- matériel de fixation
1.3 Accessoires
- Logiciel Setup pour PC, multilangue
- Câble d’interface PC (séparé galvaniquement) avec convertisseur
TTL/RS 232, alimentation (230 V AC) et adaptateur
- Alimentation simple ou quadruple (fiche technique 95.6024)
- Alimentation avec amplificateur et séparation galvanique
(fiche technique 95.6055)
- Alimentation pour convertisseur de mesure (fiche technique
95.6056)
- Élément de fixation pour montage du type 956531/... et type
956533/... sur rail - numéro d’article : 00352463
3
Page 74
2 Installation
2.1 Raccordement dTRANS T03 J - Type 956530/...
Setup
Raccordement
Brochage
pour
Alimentation 7,5 à 30 V DC ou sortie courant
+1
-2
4 à 20 mA
Entrées analogiques
Sonde à résistan­ce en montage 2 fils
3 4
U
R
R U
B
B b
---------------------=
=charge = alimentation
de série R R
= résistance de
L
7,5V
b
22mA
= 0
L
chaque conducteur
4
Page 75
2 Installation
2.2 Raccordement dTRANS T03 B - Type 956531/...
Setup
Raccordement
Brochage
pour
Alimentation 7,5 à 30 V DC ou sortie courant
+1
-2
4 à 20 mA
Entrées analogiques
Sonde
3
à résistance
5
en montage 2 fils
6
Sonde
3
à résistance
5
en montage 3 fils
6
U
R
R U
B
B b
---------------------=
=charge = alimentation
de série R R
= résistance de
L
7,5V
b
22mA
= 0
L
chaque conducteur
11
R
L
= résistance de
R
L
chaque conducteur
H
Lors du montage du convertisseur de mesure de type 956531/... avec l’élément de fixation, sur du rail (numéro d’article 00352463), il faut que la pose des câbles soit conforme à la réglementation en matière de CEM.
5
Page 76
2 Installation
2.3 Raccordement dTRANS T03 T - Type 956532/...
à
Raccordement
Brochage
pour
Alimentation 7,5 à 30 V DC ou sortie courant
+81
-82
4 à 20 mA
Entrées analogiques
Sonde
11
à résistance
12
en montage 2 fils
13
Sonde
11
à résistance
12
en montage 3 fils
13
U
R
R U
B
B b
---------------------=
=Charge = Alimentation
de série R R
= résistance de
L
7,5V
b
22mA
= 0
L
chaque conducteur
11
R
L
R
= résistance de
L
chaque conducteur
6
Page 77
2 Installation
4
6
2.4 Raccordement dTRANS T03 BU - Type 956533/...
Setup
Raccordement
Brochage
pour
Alimentation 15 à 30 V DC
Sortie tension 0 à 10 V
+1
-2
-2 +3
Entrées analogiques
Sonde
4
à résistance
5
en montage 2 fils
6
Sonde
4
à résistance
5
en montage 3 fils
6
Charge 10 k
de série R R
= résistance de
L
= 0
L
chaque conducteur
11
R
L
R
= résistance de
L
chaque conducteur
12
+–3+
5
54
6
H
Lors du montage du convertisseur de mesure de type 956531/... avec l’élément de fixation, sur du rail (numéro d’article 00352463), il faut que la pose des câbles soit conforme à la réglementation en matière de CEM.
7
Page 78
2 Installation
2.5 Raccordement dTRANS T03 TU - Type 956534/...
Raccordement
Brochage
pour
Alimentation 15 à 30 V DC
Sortie tension 0 à 10 V
+81
-82
-82 +83
Entrées analogiques
Sonde
11
à résistance
12
en montage 2 fils
13
Sonde
11
à résistance
12
en montage 3 fils
13
Charge 10 k
de série R
= résistance de
R
L
= 0
L
chaque conducteur
11
R
L
= résistance de
R
L
chaque conducteur
81 82
+–83+
8
Page 79
2 Installation
2.6 Dimensions
dTRANS T03 J - Type 956530/...
Setup
dTRANS T03 B - Type 956531/... dTRANS T03 BU - Type 956533/...
Setup
9
Page 80
2 Installation
dTRANS T03 T - Type 956532/... dTRANS T03 TU - Type 956534/...
10
Page 81
2 Installation
2.7 Exemple de raccordement sortie courant
avec un bloc d’alimentation
Convertisseur de mesure en technique 2 fils (types 956530/..., 956531/..., 956532/...)
enregistreurindicateurrégulateur
convertisseur mes. technique 2 fils
+
=
-
-
- -+ ++
4 à 20 mA
alimentation 7,5 à 30 V DC
+
_
-
~
2.8 Exemple de raccordement sortie courant
avec une alimentation à séparation galvanique
Convertisseur de mesure en technique 2 fils (types 956530/..., 956531/..., 956532/...)
enregistreurindicateurrégulateur
alimentation
convertisseur mes. technique 2 fils
avec convertisseur d’isolement
+
+ +- - -
=
+
4 à 20 mA
-
+
-
=
~
L1 N
=
+
-
+
-
11
4 à 20 mA / 0 à 20 mA
+
+ +- - -
0 à 10 V
Page 82
2 Installation
2.9 Exemple de raccordement sortie tension
Convertisseur de mesure en technique 3 fils (types 956533/..., 956534/...)
EnregistreurIndicateurRégulateur
Convertisseur de mesure, en technique 3 fils
+
+
+ +- - -
=
0 à 10 V
-
+
Alimentation
-
=
+
~
0 à 10 V
N
L1
12
Page 83
3 Logiciel Setup
Le logiciel Setup sert à configurer et régler le convertisseur de me­sure à l’aide d’un PC. Le raccordement s’effectue par l’intermédiai­re d’une interface PC (alimentation et adaptateur inclus) et de l’in­terface Setup du convertisseur de mesure.
H
Pour utiliser le logiciel Setup pour PC, il faut raccorder le convertisseur de mesure à une alimentation. Si vous ne dis­posez pas d’un bloc d’alimentation ou d’une alimentation à séparation galvanique, pour configurer le convertisseur de mesure en technique 2 fils vous pouvez l’alimenter avec une pile de 9 V.
3.1 Conditions matérielles et logicielles
Pour installer et exploiter le logiciel Setup, il faut satisfaire les condi­tions matérielles et logicielles suivantes :
- IBM-PC ou compatible PC 486DX-2-100 ou sup.
- 64 Mo de mémoire vive
- 10 Mo libres sur le disque dur
- lecteur de CD-ROM
- 1 port sériel libre
- Windows 95, 98, ME ou Windows NT 4.0, 2000
3.2 Paramètres configurables
- Numéro TAG (8 caractères)
- Comportement en cas de rupture/court-circuit de sonde
3.3 Paramètres réglables
- Début de l’étendue de mesure, fin de l’étendue de mesure
- Résistance de ligne totale (aller et retour) pour le montage 2 fils
13
Page 84
3 Logiciel Setup
3.4 Schéma de raccordement (réglage de la nouvelle
étendue de mesure)
Indicateur
0 à 10V
+
Décade de résistance de précision
dTRANS T03 BU
-
-
+
Alimentation 15 à 30V DC
dTRANS T03 B
Alimentation
7,5 à .30V DC / 25mA
-
+
Indicateur 4 à 20mA
Convertisseur TTL/RS 232
Décade de résistance de précision
Adaptateur
Alimentation 230V AC
Commutateur de choix de la tension positionné sur 9 V
H
Pour la communication entre le convertisseur de mesure et le logiciel Setup, il faut que le convertisseur de mesure et l’interface soient alimentés à la tension indiquée.
14
Page 85
3 Logiciel Setup
3.5 Vue d’ensemble du fonctionnement
La boîte de dialogue suivante apparaît après le lancement du programme :
Les fonctions suivantes sont disponibles :
- Réglage de l’étendue de mesure
- Exécution du réglage fin
- Saisie du numéro TAG
- Annuler
Philosophie de la manipulation
Seul le choix de la fonction “Etalonner l’étendue de mesure” permet d’accéder à toutes les sous-fonctions.
Le choix direct de la fonction “Réglage fin” ou “Numéro TAG” ne permet d’utiliser que la fonction correspondante. Cela permet d’éviter une modification involontaire de l’étendue de mesure.
15
Page 86
3 Logiciel Setup
3.5.1 Réglage de l’étendue de mesure Conditions
Pour obtenir les précisions indiquées dans la fiche technique, il faut satisfaire les conditions suivantes :
- Décade de résistances de précision
Précision : ± 0,05 % - Résolution : 0,01
- Ampèremètre
Précision : ± 0,05 % ± 10 µA / ± 5 mV
- Durée d’échauffement : 2 min
- Câblage du convertisseur de mesure suivant le type utilisé (voir
Chapitre 3.4 „Schéma de raccordement (réglage de la nouvelle étendue de mesure)“)
16
Page 87
3 Logiciel Setup
Processus de réglage
h Démarrez le logiciel Setup pour PC et choisissez la fonction „Ré-
glage de l’étendue de mesure“.
La fenêtre de programme suivante apparaît :
Barre de menu
Barre d’icônes
Surface de travail
17
Page 88
3 Logiciel Setup
h Appelez la fonction à l’aide de la barre de menu (Outils ! Régla-
ge fin), de l’icône ou bien d’un double clic sur la surface de tra­vail (données de l’appareil).
La boîte de dialogue „Réglage“ s’ouvre:
Ajustez l’étendue de mesure à régler.
Attention : la valeur de début de l’étendue de mesure dépend de
1
l’amplitude de mesure
. Lors de la modification des limites de
l’étendue de mesure, le logiciel Setup surveille la saisie et signale les erreurs de saisie.
1
Amplitude de mesure = Fin étendue Début étendue
18
Page 89
3 Logiciel Setup
La figure suivante présente une saisie erronée.
Message d’erreur
Le bouton “Diagramme de l’étendue de mesure” affiche une figure avec toutes les valeurs de début d’étendue de mesure possibles en fonction de l’amplitude de mesure.
19
Page 90
3 Logiciel Setup
Amplitude de mesure = Fin étendue Début étendue
20
Page 91
3 Logiciel Setup
Exemple de calcul :
Début d’étendue de mesure = −50 °C, fin d’étendue de mesure = 250 °C
Amplitude de mesure = Amplitude de mesure = 250 °C − (−50 °C) Amplitude de mesure = 300 °C
Il faut choisir le début de l’étendue de mesure de sorte qu’il
A H
h Lorsque vous avez choisi une étendue de mesure valable, lancez
le processus de réglage en cliquant sur le bouton “Régler”.
se trouve dans la surface grise.
Pour les amplitudes de mesure inférieurs à 75 °C, les seules valeurs de début d’étendue de mesure admissibles sont :
40 °C, 20 °C, 0 °C, +20 °C et +40 °C.
fin étendue début étendue
Suivez les instructions du logiciel Setup qui suivent.
H
Souvenez-vous que pour le montage 2 fils, il faut indiquer la résistance de ligne totale pour obtenir une précision de me­sure maximale.
21
Page 92
3 Logiciel Setup
3.5.2 Exécution du réglage fin
Le réglage fin correspond à une correction du signal de sortie d’un convertisseur de mesure étalonné. Il est possible de corriger le si­gnal sur une plage de ± 0,2 mA avec une sortie courant et ± 0,1 V avec une sortie tension.
Déroulement
h Démarrez le logiciel Setup pour PC et sélectionnez la fonction
“Exécution du réglage fin”.
h Appelez la fonction à l’aide de la barre de menu (Outils ! Régla-
ge fin) ou de l’icône .
La boîte de dialogue „Réglage fin“ apparaît :
h Utilisez les boutons avec des flèches pour effectuer le réglage fin
et validez-le avec “OK”.
H
Attention : lors du réglage fin du début et de la fin de l’offset, il faut appliquer le signal d’entrée correspondant.
22
Page 93
3 Logiciel Setup
3.5.3 Saisie du numéro Tag
Le numéro Tag (max. 8 caractères) permet d’enregistrer un identi­fiant (désignation du point de mesure) dans le convertisseur de mesure.
Déroulement
h Démarrez le logiciel Setup pour PC. h Appelez la fonction à l’aide de la barre de menu (Editer ! Numé-
ro Tag) ou d’un double clic sur la surface de travail (numéro Tag).
La boîte de dialogue “Numéro TAG” apparaît :
h Saisissez le numéro et validez avec “OK”. h La barre du menu (Transfert de données ! Transfert de données
vers l’appareil) ou l’icône permet de transférer le numéro Tag dans le convertisseur de mesure.
23
Page 94
Entrée - Sonde à résistance
4 Données techniques - Convert. de mesure, 2 fils
24
dTRANS T03 J
Type 956530/...
Entrée de mesure Pt 100 (EN 60 751) Limites de l’étendue de mesure -200 à +850 °C Type de raccordement Montage 2 fils Montage 2/3 fils Montage 2/3 fils Plus petit intervalle de mesure 25 K Plus grand intervalle de mesure 1050 K Décalage du zéro pour amplitudes de mesure <75 K réglage fixe du zéro : -40 °C, -20 °C, 0 °C, 20 °C, 40 °C
pour amplitudes de mesure = 75 K : ±50 °C
pour amplitudes de mesure >75 K : voir page 20
Résistance de ligne du capteur montage 3 fils 11 Ω par conducteur
Résistance de ligne du capteur montage 2 fils 0 Ω résistance de ligne
Courant du capteur 0,5 mA Cadence de scrutation mesure continue puisque cheminement du signal analogique Particularités réglage en °C ou °F ;
étendues de mesure réglables avec le logiciel Setup pour PC ;
réglage fin par PC possible
dTRANS T03 B Type 956531/...
dTRANS T03 T
Type 956532/...
Surveillance du circuit de mesure
Dépassement inférieur de l’étendue de mesure
Dépassement supérieur de l’étendue de mesure
Court-circuit de sonde 3,6 mA Rupture de sonde/ligne positif : 22 mA à < 28 mA (typique 24 mA)
croissant jusqu’à 22 mA à < 28 mA (typique 24 mA)
décroissant jusqu’à 3,6 mA
négatif : 3,6 mA
Page 95
Sortie
Signal de sortie courant continu contraint Transfert linéaire en température Précision du transfert ± 0,1 % Atténuation des ondes résiduelles
de la tension d’alimentation > 40 dB Charge (Rb) Rb = (Ub - 7,5 V) / 22 mA Influence de la charge ± 0,02 % / 100
1
Temps de réponse si variation temp. 10 ms Conditions de réglage 24 V DC / 22 °C env. Précision du réglage
± 0,2 %
1,2
ou ± 0,2 K
Alimentation
4 Données techniques - Convert. de mesure, 2 fils
2
25
Tension d’alimentation (Ub) 7,5 à 30 V DC Protection contre inversions polarité oui Influence de la tension d’alimentation
1
Toutes ces indications se rapportent à la pleine échelle 20 mA
2
C’est la plus grande valeur qui est valable
± 0,01 % / V d’écart par rapport à 24 V
1
Influence de l’environnement
dTRANS T03 J
Type 956530/...
Plage de température fonctionnement -40 à +85 °C -40 à +85 °C -25 à +70 °C Plage de température stockage -40 à +100 °C Influence de la température
± 0,01 % / K d’écart par rapport à 22 °C
Tenue climatique humidité relative 95 % en moyenne annuelle, sans condensation Résistance aux vibrations suivant GL caractéristique 2 suivant GL caractéristique 2 -
dTRANS T03 B Type 956531/...
dTRANS T03 T
Type 956532/...
1
Page 96
dTRANS T03 J
Type 956530/...
CEM
- émission de parasites
- résistance aux parasites
Indice de protection IP
- avec tête de raccordement / montage ouvert
- sur rail oméga
1
Toutes ces indications se rapportent à la pleine échelle 20 mA
IP 54 / IP 00
Boîtier
dTRANS T03 B Type 956531/...
EN 61 326
Classe B
Conditions industrielles
IP 54 / IP 00
-
-
dTRANS T03 T
Type 956532/...
-
IP 20
4 Données techniques - Convert. de mesure, 2 fils
26
dTRANS T03 J
Type 956530/...
Matériel Polycarbonate (moulé) Polycarbonate (moulé) Polycarbonate Raccordement à visser 1,5 mm²;
couple max. 0,15 Nm
Montage dans tête de raccordement
forme J
Le montage ne doit être effectué qu’avec l’accessoire original !
Position d’utilisation au choix Poids env. 12 g env. 45 g env. 70 g
dans tête de raccordement
dTRANS T03 B Type 956531/...
1,75 mm²;
couple max. 0,6 Nm
forme B
DIN 43 729 ;
dans boîtier en saillie
(sur demande);
dans armoire électrique
(élément de fixation
nécessaire)
dTRANS T03 T
Type 956532/...
2,5 mm²;
couple max. 0,6 Nm
sur rail oméga
35 mm x 7,5 mm (EN 50 022);
sur rail oméga
15 mm (EN 50 045 );
sur rail C (EN 50 035)
Page 97
Entrée Sonde à résistance
5 Données techniques - Converti. de mesure, 3 fils
27
dTRANS T03 BU
Type 956533/...
Entrée de mesure Pt 100 (EN 60 751) Limites de l’étendue de mesure -200 à +850 °C Type de raccordement en montage 2/3 fils Plus petit intervalle de mesure 40 K Plus grand intervalle de mesure 1050 K Décalage du zéro pour amplitudes de mesure <75 K réglage fixe du zéro : -40 °C, -20 °C, 0 °C, 20 °C, 40 °C
pour amplitudes de mesure = 75 K : ±50 °C
pour amplitudes de mesure >75 K : voir page 20
Résistance de ligne du capteur montage 3 fils 11 Ω par conducteur
Résistance de ligne du capteur montage 2 fils 0 Ω résistance de ligne
Courant du capteur ≤ 0,5 mA Cadence de scrutation mesure continue puisque cheminement du signal analogique Particularités réglage en °C ou °F ;
étendues de mesure réglables avec le logiciel Setup pour PC ;
réglage fin par PC possible
dTRANS T03 TU
Type 956534/...
Surveillance du circuit de mesure
Dépassement inférieur de l’étendue de mesure
Dépassement supérieur de l’étendue de mesure
Court-circuit de sonde 0 V Rupture de sonde/ligne positif : croissant jusqu’à > 11 V à < 14 V (typique 12 V)
croissant jusqu’à > 11 V à < 14 V (typique 12 V)
0 V
négatif : 0 V
Page 98
Sortie
Signal de sortie tension continue 0 à 10 V Transfert linéaire en température Précision du transfert ± 0,2 % Atténuation des ondes résiduelles
de la tension d’alimentation > 40 dB Charge (Rb) 10 k Influence de la charge ± 0,1 % Temps de réponse si variation temp. 10 ms Conditions de réglage 24 V DC / 22 °C env. Précision du réglage
± 0,2 %
1,2
ou ± 0,2 K
Alimentation
5 Données techniques - Converti. de mesure, 3 fils
2
28
Tension d’alimentation (Ub) 15 à 30 V DC Protection contre inversions polarité oui Influence de la tension d’alimentation
1
Toutes ces indications se rapportent à la pleine échelle10 V
2
LC’est la plus grande valeur qui est valable
± 0,01 % / V d’écart par rapport à 24 V
1
Influences de l’environnement
dTRANS T03 BU
Type 956533/...
Plage de température fonctionnement -40 à +85 °C -25 à +70 °C Plage de température stockage -40 à +100 °C Influence de la température
Tenue climatique humidité relative 95 % en moyenne annuelle, sans condensation Résistance aux vibrations suivant GL catactéristique 2 -
± 0,01 % / K d’écart par rapport à 22 °C
dTRANS T03 TU
Type 956534/...
1
Page 99
CEM
- émission de parasites
- résistance aux parasites
Indice de protection IP
- avec tête de raccordement / montage ouvert
- sur rail oméga
1
Toutes ces indications se rapportent à la pleine échelle 10V
Boîtier
dTRANS T03 BU
Type 956533/...
IP 54 / IP 00
-
dTRANS T03 TU
5 Données techniques - Converti. de mesure, 3 fils
Type 956534/...
EN 61 326
Classe B
Conditions industrielles
-
IP 20
29
dTRANS T03 BU
Type 956533/...
Matériel Polycarbonate (moulé) Polycarbonate Raccordement à visser 1,75 mm²;
couple max. 0,6 Nm
Montage dans tête de raccordement forme B
DIN 43 729 ;
dans boîtier en saillie
(sur demande) ;
dans armoire électrique
(élément de fixation
nécessaire)
Le montage ne doit être effectué qu’avec l’accessoire original ! Position d’utilisation au choix Poids env. 45 g env. 70 g
35 mm x 7,5 mm (EN 50 022) ;
dTRANS T03 TU
Type 956534/...
2,5 mm²;
couple max. 0,6 Nm
sur rail oméga
sur rail oméga
15 mm (EN 50 045) ;
sur rail C (EN 50 035)
Page 100