JUMO dTRANS S08 03, dTRANS S08 04, dTRANS S08 05, dTRANS S08 08, dTRANS S08 09 Operating Manual

Page 1
Zone 2
ZONE 2
JUMO dTRANS S08 XX
Signal/isolating converter series 6 mm
707203, 707204, 707205, 707208, 707209
Operating Manual
V1.00/EN/00698691
Page 2
2 V1.00/EN/00698691 - 70720300T90Z001K000
Signal/isolating converter series 6 mm
JUMO dTRANS S08 03 / JUMO dTRANS S08 04 / JUMO dTRANS S08 05 / JUMO dTRANS S08 08 /
JUMO dTRANS S08 09
Table of contents
Warning ................................................................................................ 3
Symbol identification .................................................................................... 3
Safety instructions ...................................................................................... 3
UL installation ....................................................................................... 4
IECEx, ATEX installation in Zone 2 ..................................................................... 4
Flexible supply.......................................................................................... 6
Mounting and demounting of JUMO dTRANS T/S08 ........................................................ 7
Installation on DIN rail / power rail ........................................................................ 8
Supply of power rail ..................................................................................... 8
Marking................................................................................................. 8
Side label ............................................................................................... 9
Applications ............................................................................................ 10
Product overview ....................................................................................... 11
Order................................................................................................... 12
Accessories ............................................................................................. 12
Accessories for power rail devices ........................................................................ 12
Technical data .......................................................................................... 12
Connections ............................................................................................ 15
LED indication........................................................................................... 16
DIP-switch programming................................................................................. 17
JUMO dTRANS S08 04 ................................................................................ 17
JUMO dTRANS S08 05 ................................................................................ 18
JUMO dTRANS S08 09 ................................................................................ 18
Page 3
V1.00/EN/00698691 - 70720300T90Z001K000 3
Warning
To avoid the risk of electric shock and fire, the safety instructions of this guide must be observed and the guidelines followed. The specifications must not be exceeded, and the device must only be applied as described in the following. Prior to the commissioning of the device, this installation guide must be examined carefully. Only qualified personnel (technicians) should install this device. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Until the device is fixed, do not connect hazardous voltages to the device.
To avoid explosion and serious injury: Modules having mechanical failures must be returned to JUMO GmbH & Co. KG for repair or replacement.
Repair of the device must be done by JUMO GmbH & Co. KG only.
In applications where hazardous voltage is connected to in-/outputs of the device, sufficient spacing or isolation from wires, terminals and enclosure - to surroundings (incl. neighboring devices), must be ensured to maintain protection against electric shock.
Potential electrostatic charging hazard. To avoid the risk of explosion due to electrostatic charging of the enclosure, do not handle the units unless the area is known to be safe, or appropriate safety measures are taken to avoid electrostatic discharge.
Symbol identification
Triangle with an exclamation mark: Read the manual before installation and commissioning of the
device in order to avoid incidents that could lead to personal injury or mechanical damage.
The CE mark proves the compliance of the device with the essential requirements of the directives.
Ex devices have been approved acc. to the ATEX directive for use in connection with installations in
explosive areas.
Safety instructions
Receipt and unpacking
Unpack the device without damaging it and check whether the device type corresponds to the one ordered. The packing should always follow the device until this has been permanently mounted.
Environment
Avoid direct sun light, dust, high temperatures, mechanical vibrations and shock, and rain and heavy moisture. If necessary, heating in excess of the stated limits for ambient temperatures should be avoided by way of ventilation. The device can be used for Measurement Category II and Pollution Degree 2. The device is designed to be safe at least under an altitude up to 2 000 m.
Mounting
Only technicians who are familiar with the technical terms, warnings, and instructions in the manual and who are able to follow these should connect the device.
GENERAL
CAUTION
HAZARDOUS
VOLTAGE
Page 4
4 V1.00/EN/00698691 - 70720300T90Z001K000
Should there be any doubt as to the correct handling of the device, please contact your local distributor or, alternatively,
JUMO GmbH & Co. KG
www.jumo.net
Mounting and connection of the device should comply with national legislation for mounting of electric materials, i.e. wire cross section, protective fuse, and location.
Descriptions of input / output and supply connections are shown in this installation guide and on the side label.
The device is provided with field wiring terminals and shall be supplied from a Power Supply having double / reinforced insulation. A power switch should be easily accessible and close to the device. The power switch shall be marked as the disconnecting unit for the device.
JUMO dTRANS T/S08 must be mounted on a DIN rail according to EN 60715.
UL installation
Use 60/75°C copper conducters only.
Wire size. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AWG 26-12
UL file number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E201387
The device is an Open Type Listed Process Control Equipment. To prevent injury resulting from accessability to live parts the equipment must be installed in an enclosure.
The power supply unit must comply with NEC Class 2, as described by the National Electrical Code® (ANSI / NFPA 70).
IECEx, ATEX installation in Zone 2
IECEx DEK 18.0006 X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ex nA IIC T4 Gc
DEKRA 18ATEX0007 X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II 3G Ex nA IIC T4 Gc
For safe installation the following must be observed. The device shall only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
The devices shall be installed in a suitable enclosure providing a degree of protection of at least IP54 according to EN60529, taking into account the environmental conditions under which the equipment will be used.
Page 5
V1.00/EN/00698691 - 70720300T90Z001K000 5
When the temperature under rated conditions exceeds 70°C at the cable or conduit entry point, or 80°C at the branching point of the conductors, the temperature specification of the selected cable shall be in compliance with the actual measured temperature.
Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.
For installation on power rail in Zone 2, only Power rail profile (TN: 00697614) supplied by Power connector unit for dTRANS T/S08 XX (TN: 00697612) is allowed.
To prevent ignition of the explosive atmospheres, disconnect power before servicing and do not separate connectors when energised and an explosive gas mixture is present.
Do not mount or remove devices from the power rail when an explosive gas mixture is present.
Cleaning
When disconnected, the device may be cleaned with a cloth moistened with distilled water.
Liability
To the extent the instructions in this manual are not strictly observed, the custom er cannot advance a demand against JUMO GmbH & Co. KG that would otherwise exist according to the concluded sales agreement.
Page 6
dTRANS T/S08 PCU
6 V1.00/EN/00698691 - 70720300T90Z001K000
Flexible supply
The technical specifications specifies the maximum required power at nominal operating values, e.g. 24 V supply voltage, 70°C ambient temperature, 600 Ω load, and 20 mA output current.
Protective fuse: 2.5 A.
Power rail solution #1:
Alternately, you can connect 24 VDC to any one JUMO dTRANS T/S08 device with power rail connector which will then energize other units on the rail.
Protective fuse: 2.5 A.
DIN rail solution - device daisy chain:
The units can be supplied with 24 VDC ±30% via direct wiring and a loop between the devices.
Power rail solution #2:
The JUMO dTRANS T/S08 PCU power connector unit allows easy connection of a 24 VDC / 2.5 A source to the power rail.
Protective fuse: 0.4 A.
External fuse characteristics:
The 2.5 A fuse must break after not more than 120 seconds at 6.4 A.
Page 7
V1.00/EN/00698691 - 70720300T90Z001K000 7
Mounting and demounting of JUMO dTRANS T/S08
Picture 1:
Mounting on DIN rail / power rail. Click the device onto the rail.
Picture 2:
Demounting from DIN rail / power rail. First, remember to demount the connectors with hazardous voltages. Detach the device from the DIN rail by lifting the bottom lock.
Picture 3:
Wire size AWG 26-12 / 0.13 x 2.5 mm
2
stranded wire.
Screw terminal torque 0.5 Nm.
Page 8
8 V1.00/EN/00698691 - 70720300T90Z001K000
Installation on DIN rail / power rail
The devices in the JUMO dTRANS T/S08 series can be installed on a DIN rail or on a power rail. For marine applications the devices must be supported by a module stop (TN: 00697615). Power supply units can be mounted on the power rail according to customer requirements.
If you want to install a JUMO dTRANS T/S08 device with power rail connectors on a standard DIN rail, the head of the screws holding the 7.5 mm DIN rail shall be no more than 3.5 mm high in order to avoid short circuit between the power rail connectors on the device and the screws.
Supply of power rail
It is possible to supply the power rail via the supply terminals. The terminals can pass a current of max. 400 mA.
Marking
The front cover of the JUMO dTRANS T/S08 devices has been designed with an area for affixation of a click-on marker. The area assigned to the marker measures 5 x 7.5 mm. Markers from Weidmüller’s MultiCard System, type MF 5/7.5, are suitable.
Screwable module stop for rail profile
< 3.5 mm
> 24 mm
35 mm
Page 9
V1.00/EN/00698691 - 70720300T90Z001K000 9
Side label
Page 10
10 V1.00/EN/00698691 - 70720300T90Z001K000
Signal/isolating converter series 6 mm
JUMO dTRANS S08 03 / JUMO dTRANS S08 04 / JUMO dTRANS S08 05 /
JUMO dTRANS S08 08 / JUMO dTRANS S08 09
The product family JUMO dTRANS S08 03, S08 04, S08 05, S08 08 & S08 09 are slimline isolaters for 24 VDC fixed supply and can be used for different purposes.
• Can be supplied separately or installed on power rail
• Can be delivered with customer parameterisation on request
• Approvals by CE, UL, DNV, GL, ATEX zone 2 and IECEx zone 2
• Possibility of loop supply output
Applications
The JUMO dTRANS S08 isolator family are designed for the automation and process industries. These devices are the result of extensive development and test procedures making them very well suited for conversion and galvanic isolation in the following applications:
• Isolation and 1:1 conversion of current signals in the range 0…20 mA.
• Isolation and conversion of standard DC signals.
• Power supply and signal isolator for 2-wire transmitters.
• Isolation and splitting of standard DC signals.
• Installation in ATEX Ex zone 2 / IECEx zone 2.
• Suitable for environments with high vibration stress, e.g. ships
Page 11
V1.00/EN/00698691 - 70720300T90Z001K000 11
Product overview
Typ e no. JUMO dTRANS S08 03 JUMO dTRANS S08 04 JUMO dTRANS S08 05
Product name Isolated repeater Isolated converter Isolated converter
Description Fixed loop isolator / repeater. Loop isolator / converter for
standard DC signals.
DIP-switch setup.
Loop isolator / converter for
standard DC signals.
DIP-switch setup.
Low cost.
Parameterisation None DIP-switch DIP-switch
Input signal 0…23 mA 0/2…10 V
0/1…5 V
0/4…23 mA
0/2…10 V
0/1…5 V
0/4…23 mA
Loop supply output >17 V @ 20 mA
Output signal (active) 0…23 mA (1:1) 0/2…10 V
0/1…5 V
0/4…23 mA
0/2…10 V
0/1…5 V
0/4…23 mA
Approvals UL, safety,
ATEX zone 2, IECEx zone 2,
DNV-GL, marine
UL, safety, ATEX zone 2, IECEx zone 2,
DNV-GL, marine
UL, safety,
DNV, marine,
GL, marine
Typ e no. JUMO dTRANS S08 08 JUMO dTRANS S08 09
Product name Isolated repeater / splitter Isolated converter / splitter
Description Fixed loop isolator /
repeater with dual output.
Loop isolator / converter for
standard DC signals.
DIP-switch setup.
Dual output.
Parameterisation None DIP-switch
Input signal 0…23 mA 0/2…10 V
0/1…5 V
0/4…23 mA
Loop supply output >17 V @ 20 mA
Output signal (active) 0…23 mA (1:1) 0/2…10 V
0/1…5 V
0/4…23 mA
Approvals UL, safety,
ATEX zone 2, IECEx zone 2,
DNV-GL, marine
UL, safety, ATEX zone 2, IECEx zone 2,
DNV-GL, marine
Page 12
12 V1.00/EN/00698691 - 70720300T90Z001K000
Accessories
TN: 00697615 = Screwable module stop for rail profile
Accessories for power rail devices
TN: 00697612 = Power connector unit for dTRANS T/S08 XX TN: 00697614 = Power rail profile (7.5 mm / 750 mm)
Technical data
Environmental conditions:
Operating temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25°C to +70°C
Operating temperature, JUMO dTRANS S08 05 . . . . . . . . . . . . . . . . . . 0 to +70°C
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -40°C to +85°C
Calibration temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20...28°C
Relative humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 95% RH (non-cond.)
Protection degree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP20
Installation in pollution degree 2 & overvoltage category II.
Mechanical specifications:
Dimensions (HxWxD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 x 6.1 x 115 mm
Weight approx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 g
DIN rail type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DIN EN 60715 - 35 mm
Wire size. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.13...2.5 mm
2
/ AWG 26...12 stranded wire
Screw terminal torque. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5 Nm
Vibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 60068-2-6
2...25 Hz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±1.6 mm
25...100 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±4 g
Order
Type Product name Description Order code
707203 JUMO dTRANS S08 03 Signal isolator (mA) 00697481
707204 JUMO dTRANS S08 04 Signal converter (V, mA)/
supply isolator
00697482
707205 JUMO dTRANS S08 05 Eco signal converter (V, mA) 00697484
707208 JUMO dTRANS S08 08 Signal isolator/splitter (mA) 00697485
707209 JUMO dTRANS S08 09 Signal converter (V, mA)/
supply isolator/splitter
00697486
Page 13
V1.00/EN/00698691 - 70720300T90Z001K000 13
Common electrical specifications:
Supply voltage, DC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16.8...31.2 VDC
Power requirements:
Max. required power is the maximum power needed at power supply terminals or rail connector. Max. power dissipation is the maximum power dissipated at nominal operating values.
Isolation voltage, test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 kVAC
Isolation voltage working. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 VAC (reinforced) /
250 VAC (Zone 2, Div. 2)
Double isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input / output 1 / output 2 / supply
Signal dynamics, input / output . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog signal chain
Signal / noise ratio. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Min. 60 dB
Cut-o frequency (3 dB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . > 100 Hz
Response time (0...90%, 100...10%):
mA / V input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 7 ms
Accuracy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ±0.05% of span
Accuracy, JUMO dTRANS S08 05 . . . . . . . . . . . . . . . . . . . . . . . . . . < ±0.2% of span
Temperature coecient. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ±0.01% of span / ˚C
Temperature coecient, JUMO dTRANS S08 05 . . . . . . . . . . . . . . . . . < ±0.015% of span / ˚C
Auxiliary supplies:
2-wire supply (terminal 3 and 4) . . . . . . . . . . . . . . . . . . . . . . . . . . > 17 VDC / 20 mA
Current input:
Measurement range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...23 mA
Programmable measurement ranges . . . . . . . . . . . . . . . . . . . . . . . . 0...20 and 4...20 mA
Input voltage drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 1.5 VDC
Input resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nom. 20 Ω + PTC 50 Ω
Voltage input:
Measurement range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...10.25 VDC
Programmable measurement ranges . . . . . . . . . . . . . . . . . . . . . . . . 0...10 / 2...10 / 0...5 / 1...5 VDC
Input resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≥ 500 kΩ
Current output:
Signal range (span) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...23 mA
Programmable signal ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...20 / 4...20 mA
Load, JUMO dTRANS S08 03, S08 04 & S08 05. . . . . . . . . . . . . . . . . . 600 Ω
Load, JUMO dTRANS S08 08 & S08 09 . . . . . . . . . . . . . . . . . . . . . . . 300 Ω per channel
Load stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 0.002% of span / 100 Ω
Current limit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 mA
Voltage output:
Signal range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...10 VDC
Programmable signal ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...10 / 2...10 / 0...5 / 1...5 VDC
Load (min.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . >10 kΩ
of span = of the selected range
EMC immunity influence . . . . . . . . . . . . . . . . . . . . . . . . . < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst . . . . . . . . . . . . . . . . . . . . < ±1% of span
Typ e
Max. power
dissipation
Max. required
power
JUMO dTRANS S08 03 0.60 0.65
JUMO dTRANS S08 04 0.55 1.20
JUMO dTRANS S08 05 0.52 0.80
JUMO dTRANS S08 08 0.48 0.75
JUMO dTRANS S08 09 0.60 1.20
Page 14
14 V1.00/EN/00698691 - 70720300T90Z001K000
Observed authority requirements:
EMC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/30/EU
LVD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/35/EU
RoHS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2011/65/EU
Approvals:
DNV-GL, Ships & Oshore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DNVGL-CG-0339
UL, Standard for Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL 61010-1
Safe Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EN 61140
I.S. / Ex approvals:
*ATEX 2014/34/EU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEKRA 18ATEX0007 X
*IECEx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEK 18.0006 X
* Does not apply to JUMO dTRANS S08 05
Page 15
H
I
5
6
7
81
2
3
4
81 82 83 84 85
J
+
-
+
-
mA V
+
-
A
+
-
Tx
C
F
ED
+
-
+
-
V
G
+
-
mA
B
V1.00/EN/00698691 - 70720300T90Z001K000 15
Input
Output
ch. 1
SupplyOutput
ch. 2
Connections
Input signals
JUMO
dTRANS
S08 03
JUMO
dTRANS
S08 04
JUMO
dTRANS
S08 05
JUMO
dTRANS
S08 08
JUMO
dTRANS
S08 09
A
Current x x x x x
B
Tx x x
C
Voltage x x x
Input signals
JUMO
dTRANS
S08 03
JUMO
dTRANS
S08 04
JUMO
dTRANS
S08 05
JUMO
dTRANS
S08 08
JUMO
dTRANS
S08 09
D
Current 1 x x x x x
E
Voltage 1 x x x
F
Current 2 x x
G
Voltage 2 x
Supply
JUMO
dTRANS
S08 03
JUMO
dTRANS
S08 04
JUMO
dTRANS
S08 05
JUMO
dTRANS
S08 08
JUMO
dTRANS
S08 09
H
Supply + x x x x x
I
Supply - x x x x x
J
Power rail connections x x x x x
Page 16
16 V1.00/EN/00698691 - 70720300T90Z001K000
LED indication
The device is equipped with a green power LED in the front to indicate the operation status, see the table below.
Condition LED
Output and loop supply
Action required
No supply / device error OFF De-energized
Connect supply /
replace device
Power-up or restart
1 Flash
(0.5 s OFF + 0.5 s ON)
De-energized -
Device OK
Flashing 13 Hz
(15 ms ON)
Energized -
Incorrect DIP-switch setting
Flashing 1 Hz
(15 ms ON)
De-energized
Correct setting and
re-power device
Restarting due to: Supply error/hardware. RAM or program flow error
Flashing 1 Hz
(0.5 s ON)
De-energized
Adjust supply /
replace device
Page 17
1 2 3 4 5 6 7 8 9 10
0…20 mA OFF OFF OFF OFF 0…20 mA OFF OFF OFF NA NA NA
4…20 mA OFF OFF ON OFF 4…20 mA OFF ON OFF NA NA NA
0…10 V OFF ON OFF OFF 0…10 V ON OFF OFF NA NA NA
2…10 V OFF ON ON OFF 2…10 V ON ON OFF NA NA NA
0…5 V OFF ON OFF ON 0…5 V ON OFF ON NA NA NA
1…5 V OFF ON ON ON 1…5 V ON ON ON NA NA NA
0...20 mA Tx ON OFF OFF OFF
4...20 mA Tx ON OFF ON OFF
V1.00/EN/00698691 - 70720300T90Z001K000 17
DIP-switch programming
The devices JUMO dTRANS S08 04, S08 05 and S08 09 can be configured via DIP-switches. The DIP-switches are located on the side of the device and can be adjusted with a small screwdriver or other implement.
Adjustment of DIP-switches. Default factory settings are: Input = 0…20 mA Output = 0…20 mA All DIP-switches in the OFF position
The tables below show the configuration based on DIP-switch settings. NA = no function of DIP-switch.
JUMO dTRANS S08 04
Input setup Output setup
Page 18
1 2 3 4 5 6 7 8 9 10
0…20 mA NA OFF OFF OFF 0…20 mA OFF OFF OFF NA NA NA
4…20 mA NA OFF ON OFF 4…20 mA OFF ON OFF NA NA NA
0…10 V NA ON OFF OFF 0…10 V ON OFF OFF NA NA NA
2…10 V NA ON ON OFF 2…10 V ON ON OFF NA NA NA
0…5 V NA ON OFF ON 0…5 V ON OFF ON NA NA NA
1…5 V NA ON ON ON 1…5 V ON ON ON NA NA NA
1 2 3 4 5 6 7 8 9 10
0…20 mA OFF OFF OFF OFF 0…20 mA OFF OFF OFF OFF OFF OFF
4…20 mA OFF OFF ON OFF 4…20 mA OFF ON OFF OFF ON OFF
0…10 V OFF ON OFF OFF 0…10 V ON OFF OFF ON OFF OFF
2…10 V OFF ON ON OFF 2…10 V ON ON OFF ON ON OFF
0…5 V OFF ON OFF ON 0…5 V ON OFF ON ON OFF ON
1…5 V OFF ON ON ON 1…5 V ON ON ON ON ON ON
0...20 mA Tx ON OFF OFF OFF
4...20 mA Tx ON OFF ON OFF
18 V1.00/EN/00698691 - 70720300T90Z001K000
JUMO dTRANS S08 05
Input setup Output setup
JUMO dTRANS S08 09
Input setup Output setup
Channel 1 Channel 2
Page 19
JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.
Street address: Moritz-Juchheim-Straße 1 36039 Fulda, Germany Delivery address: Mackenrodtstraße 14 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net
JUMO House Temple Bank, Riverway Harlow, Essex, CM20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk
6733 Myers Road East Syracuse, NY 13057, USA
Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com