V1.00/EN/00698691 - 70720300T90Z001K000 13
Common electrical specifications:
Supply voltage, DC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16.8...31.2 VDC
Power requirements:
Max. required power is the maximum power needed at power supply terminals or rail connector.
Max. power dissipation is the maximum power dissipated at nominal operating values.
Isolation voltage, test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 kVAC
Isolation voltage working. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 VAC (reinforced) /
250 VAC (Zone 2, Div. 2)
Double isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input / output 1 / output 2 / supply
Signal dynamics, input / output . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog signal chain
Signal / noise ratio. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Min. 60 dB
Cut-o frequency (3 dB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . > 100 Hz
Response time (0...90%, 100...10%):
mA / V input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 7 ms
Accuracy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ±0.05% of span
Accuracy, JUMO dTRANS S08 05 . . . . . . . . . . . . . . . . . . . . . . . . . . < ±0.2% of span
Temperature coecient. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ±0.01% of span / ˚C
Temperature coecient, JUMO dTRANS S08 05 . . . . . . . . . . . . . . . . . < ±0.015% of span / ˚C
Auxiliary supplies:
2-wire supply (terminal 3 and 4) . . . . . . . . . . . . . . . . . . . . . . . . . . > 17 VDC / 20 mA
Current input:
Measurement range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...23 mA
Programmable measurement ranges . . . . . . . . . . . . . . . . . . . . . . . . 0...20 and 4...20 mA
Input voltage drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 1.5 VDC
Input resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nom. 20 Ω + PTC 50 Ω
Voltage input:
Measurement range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...10.25 VDC
Programmable measurement ranges . . . . . . . . . . . . . . . . . . . . . . . . 0...10 / 2...10 / 0...5 / 1...5 VDC
Input resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≥ 500 kΩ
Current output:
Signal range (span) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...23 mA
Programmable signal ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...20 / 4...20 mA
Load, JUMO dTRANS S08 03, S08 04 & S08 05. . . . . . . . . . . . . . . . . . ≤ 600 Ω
Load, JUMO dTRANS S08 08 & S08 09 . . . . . . . . . . . . . . . . . . . . . . . ≤ 300 Ω per channel
Load stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 0.002% of span / 100 Ω
Current limit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 28 mA
Voltage output:
Signal range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...10 VDC
Programmable signal ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...10 / 2...10 / 0...5 / 1...5 VDC
Load (min.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . >10 kΩ
of span = of the selected range
EMC immunity influence . . . . . . . . . . . . . . . . . . . . . . . . . < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst . . . . . . . . . . . . . . . . . . . . < ±1% of span
Typ e
Max. power
dissipation
Max. required
power
JUMO dTRANS S08 03 0.60 0.65
JUMO dTRANS S08 04 0.55 1.20
JUMO dTRANS S08 05 0.52 0.80
JUMO dTRANS S08 08 0.48 0.75
JUMO dTRANS S08 09 0.60 1.20