JUMO dTRANS p02 Operating Instructions Manual

dTRANS p02
Pressure Transmitter
B 40.4385
Operating Instructions
07.01/00365643
Contents
1 Typographical conventions __________________________ 4
1.1 Warnings ____________________________________________________ 4
2 General ____________________________________________ 5
2.1 Preface _____________________________________________________ 5
2.2 Application __________________________________________________ 6
3 Delivery package _______________________________ ____ 7 4 Instrument identification _____________________________ 8
4.1 Nameplate __________________________________________________ 8
4.2 Type designation _____________________________________________ 9
4.3 Dimensions/details __________________________________________ 10
4.4 Dimensions: "non-flush pressure connections" __________________ 10
4.5 Dimensions: "flush pressure connections" ______________________ 11
5 Instrument description _____________________________ 12
5.1 Technical data _____________________________________________ 12
6 Mounting __________________________________________ 14
6.1 General ____________________________________________________ 14
6.2 Prior to mounting ____________________________________________ 14
6.3 Mounting by the pressure connection __________________________ 15
6.4 Mounting by the housing _____________________________________ 15
6.5 Pressure connection _________________________________________ 16
6.6 Use inside the Ex area ____ ___________________________ ________ 16
7 Installation ________________________________________ 17
7.1 Electrical connection _________________________________________ 17
7.2 Testing the output signal _____________________________________ 19
®
7.3 Connection of a HART
modem ______________________________ 19
7.4 Connection of a HART® communicator ________________________ 20
®
7.5 Testing the HART
7.6 Electrical connection in the hazardous (Ex) area _________________ 21
communication ____________________________ 20
Contents
8 Commissioning ____________________________________ 23
8.1 Characteristic _______________________________________________ 23
8.2 Self-test ___________ _____________________________ ____________ 24
8.3 Measuring the absolute pressure ______________________________ 26
8.4 Measuring the gauge pressure ________________________________ 29
9 Adjustment options ________________________________ 32
9.1 The level concept __________________ _________________________ 32
9.2 Sequence for keypad operation _______________________________ 33
9.3 Display level ________________________________________________ 34
9.4 Parameter level _____________________________________________ 35
9.5 Detailed explanations ________________________________________ 38
10 Opening the instrument ____________________________ 41
10.1 Unscrewing the bezel ring or housing cover ____________________ 41
11 Rotating the instrument ____________________________ 42
11.1 Rotating ______________ _______________________ _______________ 42
12 Maintenance _______________________________________ 43
12.1 Trouble-shooting ____________________________________________ 43
13 Appendix __________________________________________ 46
13.1 EC Type-Examination Certificate ______________________________ 46
13.2 Supplement to EC Type-Examination Certificate ________________ 52
13.3 EU Declaration of Conformity ATEX ____________________________ 56
13.4 Settings ____________________________________________________ 58

1 Typographical conventions

1.1 Warnings

Danger
This sign is used when there may be are disregarded or not followed accurately!
Caution
This sign is used when there may be instructions are disregarded or not followed accurately!

1.2 Note signs

Note
This sign is used when your
Reference
This sign refers to
abc
1
Footnote
Footnotes Markings in the text and the footnote text.
special attention
further information
refer to certain points
danger to personnel
damage to equipment or data
is drawn to a remark.
in other chapters or sections.
in the text. Footnotes consist of two parts:
if the instructions
if the
The markings in the text are arranged as continuous superscript numbers.
Action
This sign indicates that an The individual steps are marked by this asterisk. Example:
Remove crosspoi nt s crew.
Press the key.
action to be perform e d
is described.
4

2.1 Preface

2 General

Please read these Operating Instructions before commissioning the instru­ment. Keep the manual in a place which is accessible to all users at all times.
Please assist us to improve these operating instructions where necessary.
Your suggestions are welcome. Phone Germany (0661) 6003-714
abroad (+49) 661 6003-0
Fax Germany (06 61) 6003-605
abroad (+49) 661 603-607
All necessary settings are described in this manual. If any difficul­ties should still arise during commissioning, you are asked not to carry out any unauthorized manipulations on the unit. You could endanger your rights under the instrument warranty!
Please contact the nearest subsidiary or the main factory in such a case.
When returning modules, assemblies or components, the regula­tions of EN 100 015 “Protection of electrostatically sensitive com­ponents” must be observed. Use only the appropriate ESD pack­aging for transport.
Please note that we cannot accept any liability for damage caused by ESD.
ESD=electrostatic discharge
5
2 General

2.2 Application

General The type JUMO dTRANS p02 is used to measure the pressure of corrosive

and non-corrosive gases, vapors and liquids. The pressure transmitter uses the piezo-resistive effect to make the measurement. The output signal is a pro­portional DC current which is linearly proportional to the input pressure.

Version with Ex protection

The JUMO dTRANS p02 pressure transmitter in intrinsically safe version marked II 1/2 G EEx ia IIC T6, is suitable for mounting within the hazardous area Zone 1 for connection to Zone 0.
The EC Type-Examination Certificate for the JUMO dTRANS p02 is: PTB 98 ATEX 2194
If this pressure transmitter is used in areas with potentially explosive atmo­spheres, the appropriate regulations for installing and operating equipment in such areas must be observed.
The diaphragms of the JUMO dTRANS p02 pressure transmitter must not be damaged. Do not insert any objects into the bores of the pressure connections!
6

3 Delivery package

Operating Instructions B 40.4385

JUMO calibration certificate

Setup program

These operating instructions are a comprehensive guide for the installation, electrical connection, commissioning, operation and parameterization of the JUMO dTRANS p02 pressure transmitter.
A JUMO calibration certificate and a setup print-out comes with each pressure transmitter. The se documents contain information on the parameter settings and/or the measured characteristic data for the transmitter concerned.
If this calibration certificate is lost, or should you need an additional one, it can be ordered from JUMO stating the serial No. of the pressure transmitter (see nameplate),
see addresses of suppliers on the back of the operating instructions
All the parameters of the transmitter can be conveniently checked and adjusted by using the setup program. Furthermore, additional functions are available such as:
- recording of measurements
- graphical display of temperature and pressure
- comprehensive diagnostic messages
- indication of the complete order code and instrument configuration (for repeat orders).
The setup program is available on request, at extra cost, Sales No. 40/00365072.
®
HART

Power supply A supply unit with a supply isolator is available on request, at extra cost,

modem The HART
HART Sales No. 40/00345666.
Sales No. 40/00389710.
®
modem serves to connect the JUMO dTRANS p02 to a PC. The
®
modem is available on request, at extra cost,
7

4 Instrument identification

4.1 Nameplate

Nameplate on a pressure transmitter without approval for use within the hazardous (Ex) area.
Nameplate on a pressure transmitter with approval for use wi thin the hazard­ous (Ex) area.
8

4.2 Type designation

(1) Basic type
404385 pressure transmitter dTRANS p02 with sensing element
(2) Basic type extensions
0none 1 Protection EEx ia IIC (PTB 98 ATEX 2194) 4 for increased temperature of medium up to 200°C
9 special version
(3) Nominal input range
414 -100 to +100 mbar gauge pressure 453 -0.6 to +0.6mbar gauge pressure 457 -1 to +4 bar gauge pressure 461 -1to +25 bar gauge pressure 464 -1to +100 bar gauge pressure 468 -1to +600 bar gauge pressure 487 0 to +0.6 bar absolute pressure 491 0 to +4 bar absolute pressure 495 0 to +25 bar absolute pressure
(4) Output
405 4 — 20mA with HART
(5) Process connection
504 512 564 571 604 taper connection with slotted ring nut DN25 to DIN 11 851 606 taper connection with slotted ring nut DN40 613 clamp connection DN25 to DIN 32 676 616 clamp connection DN50 to DIN 32 676
(6) Material of process connection
20 stainless steel 82 Hastelloy C276, Mat. Ref. 2.4819 99 special material
(7) Electrical connection
06 screw terminals 33 Harting connector Han 7D /Han 8D (8U)
(8) Filling medium of measuring system
0none 1 silicone oil 2 halogenized filling oil
1
not for nominal range -1 to 100 bar and -1 to 600 bar gauge pressure
2
not with Protection EEX ia II C
4 Instrument identification
in piezo-resistive or thin-film technology
1
(only with process connections 571, 604, 606, 613 and 616)
®
protocol
1
/2" pipe to EN 837
1
/2" - 14 NPT to DIN 837
1
/2" - 14 NPT female
3
/4" pipe flush to DIN 837
1
1
1,2 1,2 1,2
1
2
1,2
(1) (2) (3) (4) (5) (6) (7) (8)
Order code 404385 / 405 Order example 404385 / 0 - 457 - 405 - 504 - 20 - 06 - 1
9
4 Instrument identification
4.3 Dimensions/details
(2)
131
(1)
(3)
(6) (7)
(4)
Ø76
76
170
69
G 1/2
(5)
(8)
(9)
(10)
G 1/2
NTS 527
(1) Cover for electrical connection (6) Electrical connection,
M 20x1.5 cable gland
(2) PE connection (7) Blanking plug (electrical connection or
instrument mounting possible)
(3) Cover flap (keypad underneath) (8) Electrical connection,
Harting connector Han 7D / Han 8D (8U) (4) Bezel (9) LCD display (5) Process connection (10) Special version “Process connection":
pressure sensor connected to indicating
unit via attached cable
L
15

4.4 Dimensions: "non-flush pressure connections"

10
512
18
1/2-14 NPT
504
Ø17.5
Ø6
3
20
3
1/2-14 NPT fe male
1/2-14 NPT-Innen
22.5
564
18
27 a/f
SW 27
4 Instrument identification

4.5 Dimensions: "flush pressure connections"

604 / 606
taper connection with slotted ring nut
Kegelstutzen mit Nutüberwurfmutter
1
L
DN
25 40
604 / 606
to DIN 11 851
nach DIN 11 851
D
2
D
1
D
3
D
4
D
Ø44 Ø56
1D2
D
3
RD 52x1/6
Ø35
RD 65x1/6
Ø48 Ø78
D
4L1L2
Ø63
613 / 616
613 / 616
to DIN 32 676
nach DIN 32 676
2
51
3
D
1D2
Ø50.5 Ø43.5
Ø64 Ø56.5
NTS
613
616
2
L
NTS 604
21
15
606
15
DN
DIN32676DN(Zoll)
(inch)
1.5"
25
1" 2"
50
D D
Nominal Size
ISO 2852
25 25 51
40
1
2
Storlek
SMS 3017
571
32 a/f
SW 32
32
3/4" pipe
G 3/4
Ø31.9
20
16
11

5 Instrument description

5.1 Technical data

5.1.1 For pressure transmitters without intrinsic safety

Range Start and end of range can be adjusted continuously within the measurin g
range. The measuring span should not go below 10% of the nominal range.
Chapter 4.1 "Nameplate", page 8;
For setting the measurement start or span:
"Measurement start, blind setting", page 38
"Measurement span, blind setting", page 38
Mechanical shock
Mechanical vibration
Protection with connecting cable: IP65 to EN 60 529
Material of wetted components
Material for housing
Permissible temperature of medium
Permissible ambient temperature
50 g / 11msec
5 g max. at 10 — 2000 Hz
standard: stainless steel, Mat. Ref. 1.4435, 1.4571
for range
aluminium die-casting GDAl Si 12
-30 to +120°C (with halogenized filling oil: -40 to +85°C)
-20 to +85°C, to DIN 16086 (at temperatures below -20°C, the LCD display may not be readable).
60 bar: stainless steel, Mat. Ref. 1.4571, 1.4542
Overload limit
Bursting pressure
12
4 x full scale 2 x full scale with range
10 x full scale, 2000 bar max.
100 bar
5 Instrument description

5.1.2 For pressure transmitters with intrinsic safety

Explosion protection
EC Type­Examination Certificate
Permissible ambient temperature
EEx ia IIC T4—T6, to EN 50 014 and EN 50 020 (CENELEC)
PTB 98 ATEX 2194
Temperature class
T4 T5 T6
+85°C +75°C +60°C
13

6 Mounting

6.1 General

Open cover flap The cover flap can be opened with a coin.

The keys for operating the JUMO dTRANS p02 are underneath the cover flap. For details on the setting options see:
"The level concept", page 32ff.

List of functions

Affix one of the enclosed lists of functions to the cover flap.

6.2 Prior to mounting

De-pressurize the system befor e mounting the JUMO dTRANS p02 pressure transmitter!
The installation site should be readily accessible, as close as pos­sible to the measurement point, and largely free from vibration. The permissible ambient temperature limits must be observed (note possible radiant heat).
The JUMO dTRANS p02 pressure transmitter may be mounted above or below the pressure tapping.
The measurement arrangements below serve as an example and can be altered according to the requirements of the measurement task.
14
6 Mounting

Operating position

The normal operating position of the JUMO dTRANS p02 pressure transmitter is vertically upright.
Depending on the conditions of the measurement site, the pressure transmit­ter can also be mounted in a different orientation. In accordance with the required operating position, the LC D can be rotated in 90° steps, see
"Rotating the instrument", page 42.

6.3 Mounting by the pressure connection

6.4 Mounting by the housing

There are M 20x1. 5 threads on either side of the housing. One of the threads is used to screw in the cable gland (optionally right or left). The other thread can be used to mount the pressure transmitter.
p
15
6 Mounting

6.5 Pressure connection

Seals Seals to EN 837 or DIN 16 258 may be used.

Tightening torque

Check for tightness

200 Nm max. The correct tightening torque depends on the size, materi al and shape of the
seal that is used, as well as on the pressure connection of the pressure trans­mitter.
After establishing the pressure connection, it must be checked for tightness.
Note the sequence when opening or closing the valves!
"Measuring the absolute pressure", page 26ff
or
"Measuring the gauge pressure", page 29ff.

6.6 Use inside the Ex area

.

Seals

With intrinsically safe protection EEx ia IIC, when used in Zone 0 with process connection 504, a flat metal gasket ring, e.g. to EN 837 or DIN 16 258, must be used
16

7.1 Electrical connection

Earth the instrument!
HARTTEST
+
-
1
2
+
-
Unscrew the cover from the housing
"Unscrewing the bezel ring or housing cover", page 41.

7 Installation

General notes - cable diameter 6 to 12 mm

- conductor cr oss- se c tion up t o 1.5mm
- route signal lines separately from cables with voltages above 60 V
- use shielded cables with twisted cores
- avoid the neighborhood of large electrical systems
- the full specification according to HART with shielded cables
2
‚ version 5.1, will only be achieved
7.1.1 Connection with screw terminals/Harting connector Han 7D/Han 8D (8U)
Connection diagram
HARHARTTEST
-
+
8
2+
1
2
+
-
1-
Screw terminals Harting connector
17
7 Installation
Connection Terminals
Screw terminals Assignment
Supply
11.5 — 36 V DC
11.5 — 30 V DC for intrinsically safe version
Output 4 — 20 mA 2-wire
proportional current 4 to 20 mA in supply Test connection for current output
internal resistance of ammeter
10
Test connection for HART
®
burden must be present! Potential equalization
(with intrinsically safe circuit)
1 L+
2 L-
1 L+
2 L-
1 L+
2 L-
1 L+
2 L-
TEST +
TEST -
TEST +
®
HART
Shield 8
Connection
HARTTEST
+
-
1
2
+
-
1
Burden
1
Burden (UB - 11.5 V) / 0.022 A Burden with HART
-
Supply voltage
11.5—36 VDC
+
®
min. 250 Ω, max. 1100
18
Unscrew the housing cover
"Unscrewing the bezel ring or housing cover", page 41.
Insert the cable through the cable gland.
Make the connection according to the connection diagram.
Close the housing cover.

7.2 Testing the output signal

HARTTEST
+
-
1
2
+
-
7 Installation
Output signal
-
+
Burden
1
1
Burden (UB - 11,5 V) / 0.022 A Burden with HART
®
min. 250 , max. 1100
test
4—20 mA
-
Supply voltage
11.5—36 VDC
+
Test connection via faston connectors 2.8 x 0.8 mm or test termi­nals.

7.3 Connection of a HART® modem

1L+ 2L-
I
®
HART modem
RS-232-C
up to 15 transmitters
(multidrop mode)
1
Burden ≤ (UB - 11.5 V) / 0.022 A Burden with HART
®
min. 250 Ω, max. 1100
P
Pressure transmitter JUMO dTRANS p0 2
Burden
PC or note-
book
+
-
1
Setup
program
Supply voltage
11.5 —36 V DC
19
7 Installation

7.4 Connection of a HART® communicator

P
up to 15 transmitters
(multidrop mode)
1
Burden ≤ (UB - 11.5 V) / 0.022 A Burden with HART
®
min. 250 Ω, max. 1100
Pressure transmitter JUMO dTRANS p0 2
7.5 Testing the HART
1L+ 2L-
I
®
HART
communicator
®
communication
HART
Burden
®
communicator
or
HART® modem
+
-
1
Supply voltage
11.5 —36 V DC
-
Supply
voltage
HARTTEST
+
-
1
2
+
-
1
Burden
1
Burden (UB - 11.5 V) / 0.022 A Burden with HART
®
min. 250 Ω, max. 1100
11.5 — 36 VDC
+
Test connection via faston connectors 2.8 x 0.8 mm or test termi­nals.
20
7 Installation

7.6 Electrical connection in the hazardous (Ex) area

General The appropriate regulations must be observed when making the electrical

connection; inside the area with an explosion hazard this is, in particular:
- the regulations concerning electrical equipment in areas with an explosion hazard (Elex V)
- the regulation for the installation of electrical equipment in areas with an explosion hazard EN 60 079-14:1997 (VDE 0165)
- EC Type Examination Certificate
The HART® modem must not be used in the hazardous area! The supply must be intrinsically safe and must not exceed the
following maximum values:
: 30 V DC Ii: 100 mA Pi: 750 mW
U
i
The connection of the HART® communicator or the HART modem is optional.
For fault-free communication, the signal circuit must be loaded with a minimum burden of 250 the burden is in most cases already integrated.

7.6.1 Connection diagram “EX”

Site
+
-
1
2
+
-
®
. When supply isolators are used,
Control room
intrinsically safe circuit
(2) +(3)
R
HARTTEST
(1)
not intrinsically safe connections
+
-
+
Supply voltage
-
+
-
Output
Other
units
(2)
R
PC or notebook
®
HART
communicator
intrinsically safe
HART® communicator
intrinsically safe
RS-232-C
HART
modem
®
(1) Supply unit with isolating transformer for connecting a transmitter with
explosion protection
®
(2) Total resistance for HART
1100
max. The current limiting resistor which is integrated in the supply
communicator or HART® modem: 250Ω min.
unit must be included in this calculation.
21
7 Installation
PE connection For operating the pressure transmitter in the Ex area, it must be earthed via the
external ground terminal. In addition, the ground termi nal inside the housing can be used to connect the cable shielding.
22

8.1 Characteristic

8 Commissioning

Output signal and display

Example:
Nominal range 0 — 600 mbar. Range setting 50 — 450 mbar.
Output current [mA]
Fault current
(21.5 or 3.85)
x (x < -600)
Range end (meas. error)
Underrange
(meas. error)
Err
Saturation
(low)
21.50
20.00
4.00
3.85
0
Range start
(nominal)
Below
meas. start
(saturation)
17.5
50
Meas. start (zero)
Meas. end
(zero+span)
Normal range
124.5 mbar
450
Saturation
(high)
600
Range end
(nominal)
Meas. end
exceeded
(saturation)
517.5
Fault current
(21.5 or 3.85)
x (x > 600)
Range end (meas. error)
Overrange
(meas. error)
Err
Pressure [mbar]

Range limits Depending on the range setting and the applied pressure, the output signal

can lie within different ranges:
- normal range (the example shows the linear correlation between pressure and output signal)
- saturation range
- measurement error range
The different ranges are shown in the display as different symbols,
see above
23
8 Commissioning

8.2 Self-test

Active After the supply has been switched on, the pressure transmitter carries out a

self-test.
OK If the result of the self-test is positive, the display that was most recently
selected at the display level will be shown after approx. 20 seconds (on new pressure transmitters, the display “pressure with unit”).
"The level concept", page 32ff.
The 4 — 20 mA signal that is available on the output side is proportional to pressure.
24

Error On over/underrange, an error signal appears,

see below
and
"Trouble-shooting", page 43.
8 Commissioning
25
8 Commissioning

8.3 Measuring the absolute pressure

Gases

Pressure application

Transmitter above the pressure tapping (standard arrangement)
(1) Transmitter (2) Shut-off fitting
2A shut-off valve to process
2B shut-off valve for test connection (3) Pressure line (4) Shut-off valve (5) Shut-off valve (6) Condensation vessel (7) Purge valve
Initial state: all valves closed Operate the shut-off fittings in the following order:
Open shut-off valve (4) at the pressure tapping.
Open shut-off valve (2A).
Check measurement start.
Close shut-off valve (2A).
Open shut-off valve (2B).
Apply a pressure that corresponds to the measurement start to the transmitter, via the test connection of the shut-off fitting (2).
Check output current at the measurement start and correct it if required,
"Output current, measurement start and end", page 38.
Close shut-off valve (2B).
Open shut-off valve (2A).
Transmitter below the pressure tapping (exception)
26

Va pors

8 Commissioning
(1) Transmitter (2) Shut-off fitting
2A shut-off valve to process
2B shut-off valve for test connection (3) Pressure line (4) Shut-off valve (5) Blow-down valve (8) Pressure equaliza tion reservoir

Pressure application

Initial state: all valves closed. Operate the shut-off fittings in the following order:
Open shut-off valve (4) at the pressure tapping.
Wait until steam has condensed in the pressure line.
Open shut-off valve (2A).
Check measurement start.
Close shut-off valve (2A).
Open shut-off valve (2B).
Open drain / purge valve on the transmitter (1) and drain liquid.
Close drain / purge valve on the transmitter (1).
Apply a pressure that corresponds ot the measurement start to the transmitter (1), via the test connection of the shut-off fitting (2).
Check output current at the measurement start and correct it, if required
"Output current, measurement start and end", page 38.
Close shut-off valve (2B).
Open shut-off valve (2A).
27
8 Commissioning

Liquids

(1) Transmitter (2) Shut-off fitting
2A shut-off valve to process 2B shut-off valve for test connection

Pressure application

(3) Pressure line (4) Shut-off valve (5) Blow-down valve
Initial state: all valves closed Operate the shut-off fittings in the following order:
Open shut-off valve (4) at the pressure tapping.
Open shut-off valve (2A).
Check measurement start.
Close shut-off valve (2A).
Open shut-off valve (2B).
Open drain/ purge valve on the transmitter (1) and drain liquid.
Close drain/ purge valve on the transmitter (1).
Apply a pressure that corresponds to the measurement start to the transmitter (1), via the test connection of the shut-off fitting (2).
Check the output current at the measurement start and correct it, if required
"Output current, measurement start and end", page 38.
28
Close shut-off valve (2B).
Open shut-off valve (2A).

8.4 Measuring the gauge pressure

Gases

8 Commissioning

Pressure application

Transmitter above the pressure tapping (standard arrangement)
(1) Transmitter (2) Shut-off fitting
2A shut-off valve to process 2B shut-off valve for test connection or vent screw
Initial state: all valves closed Operate the shut-off fittings in the following order:
Open shut-off valve (2B).
Apply a pressure that corresponds to the measurement start to the transmitter, via the test connection of the shut-off fitting (2).
Check measurement start and correct it, if required
"Output current, measurement start and end", page 38.
Close shut-off valve (2B).
Open shut-off valve (4) on the pressure tapping.
Transmitter below the pressure tapping (exception)
(3) Pressure line (4) Shut-off valve (5) Shut-off valve (7) Condensation vessel (8) Purge valve
Open shut-off valve (2A).
29
8 Commissioning

Va pors

(1) Transmitter (2) Shut-off fitting
2A shut-off fitting to process 2B shut-off fitting for test connection or vent screw
(3) Pressure line

Pressure application

(4) Shut-off valve (6) Blow-down valve (9) Pressure equalization reservoir
Initial state: all valves closed Operate the shut-off fittings in the following order:
Open shut-off valve (2B).
Apply a pressure that corresponds to the measurement start to the transmitter, via the test connection of the shut-off fitting (2).
Check measurement start and correct it, if required
"Output current, measurement start and end", page 38.
Close shut-off valve (2B).
Open shut-off valve (4) on the pressur e tapping.
Open shut-off valve (2A).
30

Liquids

8 Commissioning
(1)Transmitter (2)Shut-off fitting
2A shut-off valve to process 2B shut-off valve for test connection or vent screw

Pressure application

(3)Pressure line (4)Shut-off valve (6) Blow-down valve
Initial state: all valves closed Operate shut-off fitting in the following order:
Open shut-off valve (2B).
Apply a pressure that corresponds to the measurement start to the transmitter, via the test connection of the shut-off fitting (2).
Check measurement start and correct it, if required
"Output current, measurement start and end", page 38.
Close shut-off valve (2B).
Open shut-off valve (4) on the pressure tapping.
Open shut-off valve (2A).
31

9 Adjustment options

9.1 The level concept

Two levels In order to make the operation of the pressure transmitter simple and transpar-

ant, the functions of the JUMO dTRANS p02 have been divided into two lev­els.
Both levels can be accessed from the keypad of the transmitter.
The keypad can be found underneath the cover fl ap of the pres­sure transmitter.
"Open cover flap", page 14.
As an alternative to operation from the keys, all the measured val­ues and parameters can be easi ly displayed and / or set up us ing the setup program. Th e setup program is available on request, at extra cost
"Setup program", page 7.

Display level In normal operation, the instrument is in the display level.

Parameter level

The display options are: pressure, measurement, output current, sensor tem­perature or peak-reading pointer. Step thr ough with the or keys.
After applying the supply voltage, and after the end of the self-test, the instrument is in the display level. The display that was most recently selected will be shown (for new instruments ex-works, this is “Pressure with unit”).
At this level, the para meters that can be checked or altered include the follow­ing: measurement start, measurement end, zero, dimensional unit, damping and output current in a fault situation.
32

9.2 Sequence for keypad operation

Layout

after complete run or press "P" key for or pause for > 120 sec> 3 sec
Pressure
with
dim. unit
or
Pressure values
and
sensor temp.
or
Max. pressure
or
Min. pressure
or
Temperature
[°C / °F]
or
Current
[mA]
or
Measurement
[%]
(freely scalable)
or
9 Adjustment options
Parameter levelDisplay level
(Pmin)
Reset
min. pressure
P
(Pmax)
Reset
max. pressure
P
(P0)
Density
correction
P
(P1)
Dimensional
unit
P
(P2)
Meas. start with
given pressure
P
(P3)
Meas. end with
given pressure
P
(P4)
Damping
P
(P5)
Meas. start
(blind setting)
P
(P6)
Meas. span
(blind setting)
> 1 s
> 1 s
> 1 s
> 1 s
> 1 s
> 1 s
> 1 s
> 1 s
(P7)
Zero
adjustment
P
(P8)
Current generator
P
(P9)
Current on fault
P
(P10)
Key inhibit
P
(P11)
Characteristic
(P12)
Start of square root
(P13)
Version
(P14)
Display unit
temperature
> 1 s
P
> 1 s
P
> 1 s
P
> 1 s
> 1 s
> 1 s
> 1 s
P
> 1 s
P
> 3 s
P
> 1 s
Every altered value is accepted after modification ( signalled by a brief display switch-off).
The function “Adjust zero point” is inactive on transmitters for absolute pressure.
33
9 Adjustment options

9.3 Display level

After switching on the pressure transmitter, the last display that was selected will be shown at the display level.

Sequence

Action
1
Function Display
(Example)
Display of pressure with dimensional unit
Display of pressure value and sensor temperature in the units selected
Display of the stored maximum pressure
Display of the stored minimum pressure
Display of the sensor temperature in °C or °F
Display of the output current in mA
Display of measurement in %
2
or scaled with freely
selectable dim. unit
1
The sequence can also be stepped through in the opposite direction by using the key.
2 Factory setting: measurement in %. On request, freely scalable through setup program
(0—100% as -9999 to +9999). Unit ca n be s et (maximum 5 digits, restricted A SCI I character set).
34

9.4 Parameter level

9 Adjustment options
Action Function Display
(Example)
Reset the stored minimum
> 1
pressure
second
Reset the stored maximum
> 1
pressure
second
Display and set density
> 1
correction
second
Display and set dimensional unit
> 1
of pressure
second
Possible setting
reset
reset
0.100—5.000
mbar bar psi mmHg mmH ftH
0
2
0
2
inHg
0
inH
2
mH
0
2
MPa Torr kPa
2
kgcm
with keys
+
> 2 seconds
+
> 2 seconds
or
oder
or
oder
"Detailed expla­nations", page 38ff.
"Peak-reading pointer", page 38.
"Peak-reading pointer", page 38.
"Densitiy cor­rection", page 40.
"Dimensional unit", page 38.
> 1 second
> 1 second
> 1 second
Display or set output current at measurement start (with pressure input)
Display or set output current at measurement end (with pressure input)
Display or set damping (time constant)
3.85—
21.50mA 4mA
3.85—
21.50mA 20mA
0.0—100.0sec
or
oder
+
> 2 seconds
or
oder
+
> 2 seconds
oder
or
"Output current, measurement start and end", page 38.
"Output current, measurement start and end", page 38.
"Damping", page 38.
35
9 Adjustment options
Action Function Display
(Example)
Display or set measurement
> 1 second
start (blind setting)
Display or set measurement
> 1 second
span (blind setting)
Zero adjustment
> 1 second
(not for absolute­pressure transmitters)
Set and activate current generator
> 1 second
Possible setting
-110% to +110%1 or
-10 to +110% of nominal range
-210% to +210% of nominal range
0.000
Select:
3.85 mA
4.00 mA
12.00 mA
20.00 mA
with keys
2
> 2 seconds
or
oder
oder
or
or
oder
"Detailed expla­nations", page 38ff.
"Measurement start, blind set­ting", page 38.
"Measurement span, blind set­ting", page 38.
+
"Zero adjust­ment", page 39.
"Current gene­rator", page 39.
21.50 mA
and:
activate
+
> 2 seconds
in fault situation", page 39.
> 1
Display and set output current in fault situation
21.5 mA
3.85 mA
or
oder
second
1
only with transmitters for relative pressure ➩ "Instrument identification", page 8ff.
2
only with transmitters for absolute pressure ➩ "Instrument identification", page 8ff.
"Output current
36
9 Adjustment options
Action Function Display
(Example)
Display and set key inhibit
> 1 second
Possible setting
0:
no inhibit
LA:
all inhibited
LALL:
all inhibited (adjustable via setup program only)
LS:
all inhibited except measurement start and end
LO:
all inhibited except measurement start
with keys
oder
or
"Detailed expla­nations", page 38ff.
"Keys inhibi­ted", page 39.
> 1 second
> 1 second
> 1 second
> 1 second
Display and set characteristic
Display and set starting point of square-root characteristic in percent of range
Display instrument version
Display and set unit of temperature
Lin:
linear
SLin:
square root, linear up to starting point
SoFF:
square root, switched off up to starting point
5.0%—15.0%
°C °F
oder
or
oder
or
or
oder
"Characteri­stic", page 39.
"Characteri­stic", page 39
"Instrument ver­sion", page 40.
"Unit of tempe­rature displa y " , page 40.
37
9 Adjustment options

9.5 Detailed explanations

Peak-reading pointer

Dimensional unit

Output current, measurement start and end

Damping To dampen an unsteady display caused by rapidly changing pressures, the

Minimum and maximum pressures are saved. Both values can be individually display e d and deleted.
If the damping is set to 0 .0sec, minimum and maximum pressures will not be saved.
"Detailed explanations", page 38.
If the damping is 0.0sec, or after a reset of the display, “- - - - -” will be shown.
The pressure can be indicated directly in bar or in another pressure unit.
The output current (in mA) that is available at the start (or end) of the measure­ment can be set within the range +3.85 to +21.5mA. At the same time, the pressure applied is saved as measurement start or end.
time constant for the display, T
At a damping of 0.0sec, the pressure transmitter will not save the minimum and maximum pressures, i.e. the peak-reading pointer function is switched off.
, can be adjusted from 0.0 to 100.0sec.
63

Measurement start, blind setting

Measurement span, blind setting

The measurement start can be set in % of the nominal pressure range. The nominal measurement range is given on the nameplate.
"Nameplate", page 8 .
Example:
The pressure transmitter has a nominal range of 0 to 25bar, but the output sig­nal needs to be proportional in the range 5 to 20bar.
The necessary setting for the measurement start is derived as follows: Nominal range: 0—25bar Meas. start required: 5bar, corresponding to 20% of the nominal range Setting: 20%
The measurement span can be set in % of the nominal measurement range.
Example 1:
The pressure transmitter has a nominal measurement range from 0 to 25bar, but the output signal needs to be proportional in the range 5 to 20bar.
The necessary setting for the measurement span is derived as follows: Nominal range: 0— 25bar Range required: 5—20bar => required span: 15bar Span required: 15bar, corresponding to 60% of the nominal range Setting: 60%
38
9 Adjustment options
Example 2:
Nominal range: 0— 600mbar Range required: -300 to +300mbar Measurement start: -50% Span: 100%

Zero adjustment

Current generator

Output current in fault situation

When a zero adjustment is made, the transmitter display is set to 0.000. The preset measurement start remains unaffected.
Setting the measurement start:
"Output current, measurement start and end", page 38.
This function is inhibited for absolute-pressure transmitters.
"Nameplate", page 8.
If the “current generator” function is selected, an adjustable constant current is present at the transmitter output.
There is no time-out for this function; the current can remain indef­initely.
This function can only be ended by pressing the key. It is not possible in multidrop mode.
"Connection of a HART® communicator", page 20. In this case,
a constant current of 4mA is present at the output.
In order to indicate measurement errors in the event of over /underrange, or other errors, (e.g. for a connected PLC), the pressure transmitter gives out either 3.85mA or 21.5mA.
P
"Output signal and display", page 23.

Keys inhibited To prevent an unauthorized modification of parameters, some or all of the

parameters can be inhibited.
To remove an inhibit (LA, L0, LS), the key must be pressed for longer than 5 seconds in the display “Output current in fault sit- uation” (P9).
The inhibit “LALL” can only be set or deleted in the setup program.

Characteristic The characteristic of the output current can be selected as:

Lin: linear (proportional to pressure).
SLin: linear up to the starting point, then square root
(proportional to flow-through),
SoFF: square-root (proportional to flow), but switched off up to
the starting point.
The starting point of the square-root characteristic can be adjusted between 5.0 and 15.0% of the output current.
P
39
9 Adjustment options
Characteristics
Output current
[%]
100
80
60
40
20
0
020406080
20
(b)
(a)
100
Pressure [%]
15
10
5
0
012 34
20
(b)
Starting point
linear
(a)

Instrument version

Densitiy correction

(a) = Lin = linear (b) = SLin = square root, linear up to
15
10
(c)
Starting point
starting point
(c) = SoFF = square root, switched off
up to starting point
5
0
012 34
Display format: xx.yy xx = hardware ve rsion yy = software version
Density correction is important for the hydrostatic level measurement for media with densities other than 1 (e.g. pure water). Possible range setting: 0.100—5.000 (kg/dm
3
).
Example
Range: 0—1 bar Scaling: 0—100% => 0—5000 l
Medium Density Measured pressure Output current Display LCD
Water 1.0 0.5 bar 12 mA 2500 liters
Gasoline 0.8 0.5 bar 14 mA 3125 liters

Unit of temperature display

40
The display unit of the measured sensor temperature can be selected as:
°C
°F

10 Opening the instrument

10.1 Unscrewing the bezel ring or housing cover

The bezel ring and the rear housing cover can be unscrewed.
(1)
(1) Housing cover (2) Bezel ring
(2)
Open with a screwdriver
Close by hand without any tools
41

11 Rotating the instrument

11.1 Rotating

Rotating the LCD display

Depending on the operating position required, the LCD display can be rotated in steps of 90°.
Unscrew the bezel ring.
"Unscrewing the bezel ring or housing cover", page 41.
Use a small-bladed screwdriver to carefully push out the catch of the LCD fixing and lever out the display board.
Set the LCD display to the required position (90° steps) in the notches provided.

Rotating the housing

Screw on the bezel ring finger-tight, rotate housing
The housing can be rotated through ± 170° .
Loosen the grub screw (1) with a 2 mm hexagon socket wrench (about half a turn is enough).
Rotate the housing into the required po sition.
(1)
42
Screw up grub screw tightly.

12 Maintenance

12.1 Trouble-shooting

Error/fault Possible cause Remedy
Display: none no supply voltage switch on supply
instrument faulty send instrument to supplier for
repair
Display: overrange,
excessive pressure
Display: underrange,
pressure to o low
Display: pressure can no longer be
measured; overrange, excessive pressure
instrument faulty send instrument back to the
Display: pressure can no longer be
measured; overrange, pressure too low.
instrument faulty send instrument to supplier for
bring pressure back to within range, or adjust range
bring pressure back to within range, or adjust range
bring pressure back to within range, or use instrument with a wider nominal range
supplier for repair bring pressure back to within
range, or use instrument with a wider nominal range
repair
Display: an error in the electronics was
detected during the last self-test
Display: temperature probe faulty send instrument to supplier for
Display: span too small increase span
instrument faulty send instrument to supplier for
send instrument to supp l ier for repair
repair
(at least 5%)
"Measurement start, blind set-
ting", page 38.
repair
43
12 Maintenance
Display: span too small increase span
(at least 5%)
"Measurement start, blind set-
ting", page 38.
instrument faulty send instrument to supplier for
repair
key not responding instrument faulty send instrument to supplier for
P
repair
key
or
key not responding
keys inhibited reset key inhibit
"Keys inhibited", page 39.
instrument faulty send instrument to supplier
for repair
1
You can find the supplier addresses on the back page of the operating
instructions.
1
44
12 Maintenance
45

13 Appendix

13.1 EC Type-Examination Certificate

46
Translation (for information only):
Physikalisch-Technische Bundesanstalt PTB
(Federal Physical-Technical Laboratory)
Braunschweig and Be rlin
13 Appendix
(1) (2) Equipment and Protective Systems Intended for Use in
Potentially Explosive Atmospheres – Directive 94/9/EC
(3) EC Type-Examination Certificate Number:
(4) Equipment: Pressure transmitter Type dTRANS p02 (5) Manufacturer: M. K. JUCHHEIM GmbH & Co. (6) Address: Moltkestraße 13/31, D-36039 Fulda, Germany (7) This equipment and any acceptable variation thereto are specified in the
schedule to this Type-Examination Certificate.
(8) The Physikalisch-Technische Bundesanstalt, notified body No. 0102 in accordance
with Article 9 of the Council Directive 94/9/EC of 23 March 1994, certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of equipment and protective systems intended for use in potentially explosive atmospheres, given in Annex II to the Directive.
The examination and test results are reco rded in the confidential report PTB Ex 98-28372.
(9) Compliance with the Essential Health and Safety Requirements has been assured
by compliance with
EN 50 014:1997 EN 50 020:1994 EN 50 284:1998
EC Type-Examination Certificate
PTB 98 ATEX 2194
(10) If the sign “X” is placed after the certificate number, it indicates that the equipment
is subject to special conditions for safe use specified in the schedule to this certificate.
(11) Thi s EC Type-Examination Certificate relates only to the design and construction of
the specified equipment in accordance with Directive 94/9/EC. Further requirements of this Directive apply to the manufacture and supply of this equipment.
(12) The marking of the equipment shall include the following:
Ex II 1/2G EEx ia IIC T6
Zertifizierungsstelle Explosionsschutz Brunswick, 11 December 1998 (Certifying Body for Explosion Protection) signed
Dr.-Ing. U. Johannsmeyer (stamp) Regierungsdirektor Page 1/3
EC Type-Examination Certificates are not valid without signature and stamp. The certificates may only be circulated without alteration. Extracts or alterations are subject to the approval by the Physikalisch-Technische Bundesanstalt.
Physikalisch-Technische Bundesanstalt, Bundesallee 100, D-38116 Braunschweig, Germany
47
13 Appendix
48
Translation:
Physikalisch-Technische Bundesanstalt PTB
Braunschweig and Be rlin
13 Appendix
(13) (14) EC Type-Examination Certificate PTB 98 ATEX 2194
(15) Description of equipment
The pressure transmitter Type dTRANS p02 is used to convert a physical measurement variable into a standard electrical signal. The transmitter is intended for use in potentially explosive atmospheres.
The electronics housing is installed in hazardous zones which require category 2 equipment. The elements for the process connection are installed in the separating wall which separates the zones requiring category 2 equipment from those with category 1.
The maximum permissible ambient temperature is related to the temperature class as follows:
Electrical data Supply circuit intrinsically safe EEx ia IIC
(terminals X401+, X402-) only for connection to a certified intrinsically safe circuit
Schedule
Temperature class Ambient temperature
T4 85°C T5 75°C T6 60°C
maximum values: U
Sensor circuit and display circuit integral to device, intrinsically safe protection EEX ia IIC
Examination and test report:
EC Type-Examination Certificates are not valid without signature and stamp. The certificates may only be circulated without alteration. Extracts or alterations are subject to the approval by the Physikalisch-Technische Bundesanstalt.
Physikalisch-Technische Bundesanstalt, Bundesallee 100, D-38116 Braunschweig, Germany
PTB Ex 98-28372
= 30 V
i
I
100 mA
i =
P
750 mW
i =
=6 nF
C
i
L
= negligible
i
Page 2/3
49
13 Appendix
50
13 Appendix
Translation:
Physikalisch-Technische Bundesanstalt PTB
Braunschweig and Berlin Schedule to EC Type-Examination Certificate PTB 98 ATEX 2194
(17) Special conditions
not applicable
(18) Essential health and safety requirements
are assured by compliance with the standards cited above
Zertifizierungsstelle Explosionsschutz (Certifying Body for Explosion Protection)
signed Brunswick, 11 December 1998
Dr.-Ing. U. Johannsmeyer (stamp) Regierungsdirektor
Page 3/3
EC Type-Examination Certificates are not valid without signature and stamp. The certificates may only be circulated without alteration. Extracts or alterations ar e subject to the approval by the Physikalisch-Technische Bundesanstalt.
Physikalisch-Technische Bundesanstalt, Bundesallee 100, D-38116 Braunschweig, Germany
51
13 Appendix

13.2 Supplement to EC Type-Examination Certificate

52
Translation:
Physikalisch-Technische Bundesanstalt PTB
Braunschweig and Berlin
Supplement 1
according to Directive 94/9/EC Annex III para. 6
to EC Type-Examination Certificate PTB 98 ATEX 2194
Equipment: Pressure transmitter Type dTRANS p02 Marking: Ex II 1/2G EEx ia IIC T6 Manufacturer: M. K. Juchheim GmbH & Co. Address: Moltkestraße 13 - 31
D-36039 Fulda, Germany
13 Appendix
Description of additions and alterations The pressure transmitter Type dTRANS p02 will in future be manufactured and operated in
accordance with the test documentation listed in the test report. The alterations concern the internal and external construction, for the introduction of other equipment variations, as well as to the “Electrical data” and the type designation. For the equipment version with differential pressure sensor this is:
Pressure transmitter Type dTRANS p02 DELTA
Electrical data
Supply circuit intrinsically safe protection EEx ia IIC (terminals P601+, P602-, or plug connection) only for connection to a certified intrinsically safe circuit
maximum values: U
Display circuit integral to device, in intrinsically safe protection EEx ia IIC Sensor circuit intrinsically safe protection EEx ia IIC
integral to device, or only for connection to the correspond­ing sensor through the appropriate attached cable
= 30 V
i
I
100 mA
i =
750 mW
P
i =
C
=11 nF
i
L
= 170 µH
i
All other data and specifications remain unaffected. Page 1/2 EC Type-Examination Certificates are not valid without signature and stamp. The certificates may
only be circulated without alteration. Extracts or alterations are subject to the approval by the Physikalisch-Technische Bundesanstalt.
Physikalisch-Technische Bundesanstalt, Bundesallee 100, D-38116 Braunschweig, Germany
53
13 Appendix
54
Translation:
Physikalisch-Technische Bundesanstalt PTB
Braunschweig and Be rlin Supplement 1 to EC Type-Examination Certificate PTB 98 ATEX 2194
13 Appendix
Test and examination report:
Zertifizierungsstelle Explosionsschutz Brunswick, 5 April 2001 (Certifying Body for Explosion P rotection)
signed
Dr.-Ing. U. Gerlach
PTB Ex 01-20368
(stamp)
Page 2/2
EC Type-Examination Certificates are not valid without signature and stamp. The certificates may only be circulated without alteration. Extracts or alterations are subject to the approval by the Physikalisch-Technische Bundesanstalt.
Physikalisch-Technische Bundesanstalt, Bundesallee 100, D-38116 Braunschweig, Germany
55
13 Appendix

13.3 EU Declaration of Conformity ATEX

56
13 Appendix
Translation:
M. K. JUCHHEIM GmbH & Co. Street address: Moltkestraße 13 - 31 Phone:+49 (0) 6003-0 Delivery address: Mackenrodtstr. 14
36039 Fulda, Germany Fax: +49 (0) 6003-607
Postal address: 36035 Fulda, Germany e-mail: JUMO_de@e-mail.com
EU DECLARATION OF CONFORMITY
ATEX
Document No.: CE 346 Manufacturer: M. K. JUCHHEIM GmbH & Co Address: Moltkestr. 13 - 31
36039 Fulda, Germany
Product designation: Data Sheet No. 40.4385
Type (series) dTRANS p02 404385/...
We declare in sole responsibility that the product described fulfills the safety requirements of the
European Directive 94/9/EC.
The essential health and safety requirements are fulfilled through the compliance with the following standards:
Standard Date of issue EN 50 014 1997
EN 50 020 1994 EN 50 284 1998
and the EC Type-Examination Certificate:
PTB 98 ATEX 2194
Quality assurance system approved by:
TÜV Hannover, Am TÜV 1, D-30519 Hannover, Germany Identification No. 0032, Notification No. TÜV 99 A TEX 1454 Q.
Issued by: Company M. K. Juchheim, Fulda, Germany
Place, date: Fulda, 6 July 2000
Legally binding signature: Head of Sales and Production
signed: per procuram Günter Bott
57
13 Appendix

13.4 Settings

H
Function LCD display Factory
Min. value (peak-reading pointer) P min –– Max. value (peak-reading pointer) P max –– Density correction P0 1.000 Dimensional unit P1 bar
Measurement start P2 mA 4.00 Measurement end P3 mA 20.00 Damping P4 sec 0.1 Measurement start (blind setting) P5 %
Measurement span (blind setting) P6 % Zero adjustment P7 0.000
Individual settings can be recorded in this table.
setting
or mbar
1
0
1
100
Customer’s setting
not adjustable not adjustable
Current generator P8 mA 3.85 Output current in fault situation P9 mA 21.50 Key / function locking P10 0 Characteristic P11 Lin Starting point (EP = Entry Point) P12 % 9.400 Version display P13 01.12 Display unit for temperature P14 °C
1
Different factory settings are possible in accordance with customers’ specification!
not adjustable
58
M. K. JUCHHEIM GmbH & Co
Street address: Moltkestraße 13 - 31 36039 Fulda, Germany Delivery address: Macken ro d tstr aß e 1 4 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 60 03-0 Fax: +49 661 60 03-6 07 E-mail: mail@jum o.net Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House Temple Ban k, Riverw ay Harlow, Essex CM20 2TT, UK
Phone: +44 12 79 63 55 33 Fax: +44 12 79 63 52 62 E-mail:
sales@jumo.co.uk
JUMO PROCESS CONTROL INC.
885 Fox Chase, Suite 103 Coatesville, PA 19320, USA Phone: 610-380-8002
1-800-554-JUMO Fax: 610-380-8009 E-mail: Internet: www.JumoUSA.com
info@JumoUSA.com
Loading...