JUMO DICON touch Operating Manual

JUMO DICON touch
Two-channel process and program controller with
paperless recorder and touchscreen 8.9 cm (3.5")
Operating Manual
70357100T90Z004K000
V1.01/EN/00603327
Inhalt
1.1 Safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1.1 Warning symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1.2 Note signs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1.3 Display types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.3 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2 Identifying the device version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.1 Order Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.3 General accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.5 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.1 Mounting site and climatic conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.1.1 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.1.2 Environmental influences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.1.3 Case . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.3 Close mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.4 Insertion in panel cut-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.5 Care and treatment of the front cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
4.1 Installation notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.1.1 Cables, shielding, and grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.1.2 Electrical safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.1.3 Intended use, misuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.2 Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.3 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.3.1 Connection elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.3.2 Analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.3.3 Probes for air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.3.4 Probes for water and oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.3.5 Probes for water and oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.6 Probes for the operating medium water, oil, and air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.7 Analog outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3.8 Digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.3.9 Digital outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.3.10 Digital outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.3.11 Voltage supply (according to nameplate) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3
Inhalt
4.3.12 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
5.1 Display and operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.2 Device menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.3 Alarm and event list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.4 Function buttons, history and channel changeover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.5 Images in the operating loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.5.1 Controller screen 1, Controller screen 2 and Controller overview . . . . . . . . . . . . . . . . . . . . . . . . 38
5.5.2 Program controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.5.3 General screen 1.2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.5.4 Recording image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.5.5 Process screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6 Login . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
6.1 Logging on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.2 Logging out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.3 Change password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
7 User level (Log-In) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
7.1 Example 4 Transferring controller setpoint values to the user level . . . . . . . . . . . . . . . . . . . . . . 45
8 Program administration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
8.1 Enter program curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
8.1.1 On the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
8.1.2 About the setup program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
8.1.3 Section run time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
8.1.4 Setpoint values 1 and 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
8.1.5 Operating contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
8.1.6 Tolerance band . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
8.1.7 Number of repetitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
8.1.8 Start section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
8.1.9 Parameter block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
9 Device information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9.1.1 Version, motherboard, Ethernet information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9.2 Slots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
9.3 Inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
9.3.1 Digital and analog inputs, digital and analog outputs, external digital, and external analog inputs . 52
9.4 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
4
Inhalt
9.4.1 Mathematics, logic signal, limit value outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
9.4.2 Timer signal, digital controller signals, control contacts, controller, analog flag, digital flag . . . . 53
9.5 Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
9.6 PROFINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
10 Functional level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
10.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
10.1.1 Activate functional level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
11 Parameterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
11.1 Date and time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
11.2 Daylight saving time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
11.3 Controller/parameter blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
11.4 Setpoint values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
11.4.1 Entered on the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
11.4.2 Entered using the setup program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
12 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
12.1 Analog selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
12.2 Digital selector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
12.3 Basic settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
12.4 Digital inputs IN1 to 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
12.5 Analog inputs IN8, IN9, IN10, IN11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
12.5.1 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
12.6 Controller1, 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
12.6.1 Controller configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
12.6.2 Controller inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
12.6.3 Self-optimization controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
12.6.4 Start SO on device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
12.6.5 Control loop monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
12.6.6 Output level monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
12.6.7 Controller setpoint values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
12.6.8 Ramp function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
12.7 Digital outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
12.7.1 Switch digital outputs from fixed to logic level 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
12.8 Analog outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
12.9 Limit value monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
12.9.1 Function and hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
12.9.2 Hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
12.9.3 Start-up alarm suppression . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
12.9.4 Acknowledging self-locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
12.9.5 Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
12.10 Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
12.10.1General configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
5
Inhalt
12.10.2Configurating the screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
12.10.3Start screen and watermark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
12.10.4Operating loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
12.10.5Recording colors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
12.10.6Color for controller screens 1, 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
12.10.7Program controller screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
12.10.8General screens 1, 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
12.11 Recording . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
12.11.1Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
12.11.2Analog channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
12.11.3Digital channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
12.12 Program controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
12.12.1Controller signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
12.12.2Extended functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
12.12.3Basic status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
12.12.4Manual operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
12.12.5Behavior for out of range parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
12.12.6Weekly program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
12.13 Timer or week-time switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
12.14 Digital controller signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
12.14.1Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
12.15 Mathematics/logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
12.16 Flags/service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
12.16.1Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
12.16.2Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
12.17 External digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
12.18 External analog inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
12.18.1Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
12.19 Serial interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
12.20 Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
12.21 Modbus TCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
12.22 Relay module (accessories) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
12.23 PROFIBUS DP (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
13 Configuration – in setup program only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147
13.1 Installing the setup program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
13.1.1 Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
13.1.2 Software requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
13.2 Starting the setup program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
13.2.1 Establish the connection to the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
13.2.2 Setup data transfer on or from the external mass storage device . . . . . . . . . . . . . . . . . . . . . . . 149
13.3 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
13.4 Country settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
13.5 User list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
13.6 User level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
6
Inhalt
13.7 E-mail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
13.8 Web server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
13.9 Modbus frames for reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
13.10 Modbus frames for writing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
13.11 PROFINET-RT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
13.12 Customized linearization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
13.12.1Grid points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
13.12.2Formula . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
13.13 Process screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
13.13.1process screen editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
13.13.2Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
13.13.3Signal types for process screens (overview) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
13.13.4General object features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
13.13.5Preview screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
13.13.6Transfer process screen to device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
14 Special functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .167
14.1 Calibrating the touchscreen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
15 Online parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .169
15.1 Fine Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
15.2 Ethernet (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
15.3 Date and time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
15.4 Screenshot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
15.5 Deleting measurement data memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
15.6 Approval of extra codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
15.7 Testing calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
15.8 Various process values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
15.9 Startup program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
16 Error and alarm messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .177
16.1 Error messages in float values and on the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
16.2 Display of error messages for binary values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
17 Retrofitting optional boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .179
17.1 Safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
17.2 Identifying the modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
17.3 Installing modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
17.3.1 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
18 Approvals / approval marks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
18.1 UL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
7
Inhalt
18.2 GL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
18.3 DIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
19 China RoHS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .181
19.1 Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
8

1.1 Safety information

General information
This manual contains information that must be observed in the interest of your own safety and to avoid damage to assets. This information is supported by symbols which are used in this manual as indicated.
Please read this manual before commissioning the device. Keep the manual in a place acces­sible to all users at all times.
If difficulties occur during commissioning please refrain from carrying out any manipulations that could jeopardize your warranty rights.

1.1.1 Warning symbols

DANGER!
This symbol indicates that personal injury caused by electrical shock may occur if the re- spective precautionary measures are not carried out.
WARNING!
This symbol in connection with the signal word indicates that personal injury may occur if the respective precautionary measures are not carried out.

1 Introduction

CAUTION!
This symbol in connection with the signal word indicates that damage to assets or data loss will occur if the respective precautionary measures are not taken.
CAUTION!
This symbol indicates that components could be destroyed by electrostatic discharge (ESD = Electro Static Discharge) if the respective cautionary measures are not taken. Only use the ESD packages intended for this purpose to return device inserts, assembly groups, or assembly components.
READ DOCUMENTATION!
This symbol – placed on the device – indicates that the associated device documentation has to be observed. This is necessary to recognize the kind of the potential hazards as
well as the measures to avoid them.

1.1.2 Note signs

NOTE!
This symbol refers to important information about the product, its handling, or additional use.
REFERENCE!
This symbol refers to further information in other sections, chapters, or manuals.
9
1 Introduction
&
FURTHER INFORMATION!
This symbol is used in the tables and refers to further information in connection with the table.
DISPOSAL!
This device and the batteries (if installed) must not be disposed in the garbage can after use! Please ensure that they are disposed properly and in an environmentally friendly
manner.

1.1.3 Display types

Menu structure
The > symbol between words indicates a menu structure and enables the parameters to be quickly detected in the configuration level or for navigation in the setup program, such as the software version of the devices, for example:
D
EVICE MENU >GENERAL >VERSION >SW VERSION
Active input
The device has no buttons and is operated using a finger or a pen. The following instructions will therefore make references to "touching" and the images dis­played will show a hand operating the device.
10

1.2 Description

The DICON touch is a two-channel universal process and program controller that displays in­formation on a vibrant screen. The device is easy to operate via a touchscreen. Both control channels use the tried-and-tested JUMO control algorithm with two possible opti­mization options. These enable a simple and highly-accurate startup. It also enables multiple zone control, cascade control, or other complex control tasks. The block diagram below illustrates the various different hardware options offered by the mod­ular hardware concept. Four analog universal inputs and up to eight external inputs can record a variety of physical measured values with high precision. The actuators can be controlled di­rectly in the device with either an analog or digital setup. These can be expanded further through external digital outputs. Interfaces such as Modbus (master/slave), PROFIBUS, PRO­FINET-RT Class B or Ethernet with Web server can be used for the communication with higher­order systems. To ensure secure process operation, the device has a password-protected user administration with individual assignment of rights for different levels or control commands. Screen masks for controllers, program generators, recording, and for overview screens are ready-made and available. An individual process screen can be created using the configuration software. Using the extra-code recording function, important analog and digital process values can be saved so that they are tamper-proof, so that they can be graphically visualized, and so that they can be exported via interface or USB stick in a tamper-proof fashion to the PC. The configuration software ensures that the process controller can be easily programmed, that math or logical coherences can be described, and that customer-specific linearizations can be created. In addition, tools for simulating external signals or control paths are included. These tools can also record for the duration of the startup. A comprehensive alarm and limit-value concept as well as a flexible digital signal administration complete the "all-in-one" device.
1 Introduction
11
1 Introduction
Analog input ( In8universal)
Analog input (universal) In10
Relay output OUT1 (changeover contact)
703571
8 expansion slots
Voltage supply
- AC 110 to 240 V, +10/-15 %
- AC/DC 24 V, +30/-25 %
Interface
RS485)
Modbus master or slave
COM1
(
Relay output OUT2 (changeover contact)
Digital/analog outputs
OUT4
OUT3
Digital/analog outputs
OUT6
OUT5
Digital/analog outputs
OUT8
OUT7
Digital/analog outputs
OUT10
OUT9
Digital/analog outputs
OUT12
OUT11
Interface COM2
( Modbus master or slave, PROFIBUS-DP or PROFINET device
RS422/485)
Ethernet
USB interfaces
- USB device
- USB host
Available ex-works Option
7 In1 to 7 (potential free contact)
Digital inputs
Analog input (universal) In9
Analog input (universal) In11

1.3 Block diagram

12

2 Identifying the device version

2.1 Order Details

(1) Basic type
703571 JUMO DICON touch - two-channel process and program controller with RS485 interface
(2) Version
8 Standard with default settings
9 Customer-specific configuration (specifications in plain text)
(3) National language of display texts
01 German
02 English
03 French
(4) Input IN10
00 Not used
10 Analog input (universal)
(5) Input IN11
00 Not used
10 Analog input (universal)
(6) Outputs OUT3/4
00 None
11 1 relay (changeover contact)
12 2 relays (make contact)
13 1 solid-state relay 230 V, 1 A
14 1 logic output 0/22 V, max. 30 mA
15 2 logic outputs 0/12 V, 20 mA
16 1 analog output
17 Two PhotoMOS® relays
20 2 solid state relay 230 V, 1 A for motor actuator drives (double slot:OUT3/4 and OUT7/8)
(7) Outputs OUT5/6
00 None
11 1 relay (changeover contact)
12 2 relays (make contact)
13 1 solid-state relay 230 V, 1 A
14 1 logic output 0/22 V, max. 30 mA
15 2 logic outputs 0/12 V, 20 mA
1
16 1 analog output
17 2 PhotoMOS® relays
20 2 solid state relay 230 V, 1 A for motor actuator drives (double slot:OUT5/6 and OUT9/10)
(8) Outputs OUT7/8 (not available for assignment with module 20 on OUT3/4)
00 None
13
2 Identifying the device version
11 1 relay (changeover contact)
12 2 relays (make contact)
13 1 solid-state relay 230 V, 1 A
14 1 logic output 0/22 V, max. 30 mA
15 2 logic outputs 0/12 V, 20 mA
16 1 analog output
17 2 PhotoMOS® relays
(9) Outputs OUT9/10 (not available for assignment with module 20 on OUT5/6)
00 None
11 1 relay (changeover contact)
12 2 relays (make contact)
13 1 solid-state relay 230 V, 1 A
14 1 logic output 0/22 V, max. 30 mA
15 2 logic outputs 0/12 V, 20 mA
16 1 analog output
17 2 PhotoMOS® relays
(10) Outputs OUT11/12
00 None
11 1 relay (changeover contact)
12 2 relays (make contact)
13 1 solid-state relay 230 V, 1 A
14 1 logic output 0/22 V, max. 30 mA
15 2 logic outputs 0/12 V, 20 mA
16 1 analog output
17 2 PhotoMOS® relays
(11) Voltage supply
23 AC 110 ... 240 V +10/-15 %, 48 ... 63 Hz
39 AC/DC 24 V +30/-25 %, 48 ... 63 Hz
(12) COM2 interface
00 Not used
08 Ethernet
54 RS422/485 Modbus RTU
63 PROFINET
64 PROFIBUS-DP
(13) DIN-tested
000 Without approval
2
056 With DIN approval
(14) GL-tested
000 Without approval
062 With GL approval
14
2 Identifying the device version
(15) Extra code
000 None
213 Recording function
214 Math and logic module
223 Program controller
879 AMS2750/CQI-9
1
PhotoMOS is a registered trademark of Panasonic Corporation
2
In connection with PROFINET no GL and DIN approval
3
For the calibration certificate the channels to be checked are to be defined with the thermocouple type and the de­sired measuring points.
(1) / (2) - (3) - (4) (5) - (6) (7) (8) (9) (10) - (11) - (12) / (13) , (14) , (15)
3
Order code /-- - - - / , , ,
Order exam­ple
1
List extra codes in sequence and separate using commas.
703571/X-X-XX-XXXX X-X-X/X,X,X
...
1

2.2 Scope of delivery

1 controller in the ordered version
1 Operating Manual
1 panel seal 4 retaining elements for panel installation

2.3 General accessories

Article Part no.
Program editor/startup 00607139
Setup/program editor 00606496
PCA3000/PCC JUMO software package 709701/709702 00431884
USB cable A-connector mini B-connector 3 m 00506252
15
2 Identifying the device version

2.4 Accessories

Item Parts no.
Modules for expansion slots:
One analog input (universal) 00581159
One relay output (changeover contact) 00581160
Two relay outputs (N/O contact) 00581162
One logic output DC 0/22 V, max. 30 mA 00581165
Two logic outputs DC 0/12 V max. 20 mA 00581168
One solid state relay AC 230 V, 1 A 00581164
Two solid state relays AC 230 V, 1 A for motor actuator
Two PhotoMOS® relays
DC 45 V, max. 200 mA,
AC 30 V, max. 200 mA
One analog output (universal) 00581169
Ethernet interface 00581174
Serial interface RS422/RS485 00581172
1
00621574
00581171
PROFIBUS-DP interface 00581173
1
PhotoMOS is a registered trademark of Panasonic Corporation
16

2.5 Nameplate

Position
The nameplate is affixed to the case.
2 Identifying the device version
Contents
The nameplates contain important information. This includes:
Description Designation on the nameplate
Device type (A) Type
Voltage supply, power consumption (B)
Fabrication number (C) F-No.
Part no. (D) TN
Device type (Typ)
Compare the specifications on the nameplate with the order. Identify the supplied device version using the order details (order code).
Part no. (TN)
The part no. uniquely identifies an article in the catalog. It is important for communication be­tween the customer and the sales department.
Fabrication number (F-No.:)
Among other things, the fabrication number contains the date of production (year/week). Example: F-No. = 1234567801013010000 The characters in question are digits 12, 13, 14, and 15 (from the left). The device was therefore produced in the 1st calendar week of 2013.
Identifying the optional modules
The device type also contains information about optional default modules, as in the following example of the Ethernet interface (Figure 08):
703571/8-01-00-00-00-00-00-00-00-25-08... (see type key) Further information on identifying optional modules is included in this chapter: Ö B 703571.0 - Chapter 9.2 "Slots", Page 51
17
2 Identifying the device version
18

3.1 Mounting site and climatic conditions

The mounting site should be free from vibration, dust and corrosive media. Install controllers as far away as possible from sources of electromagnetic fields, such as those created by fre­quency converters or high-voltage ignition transformers. Conditions at the mounting site must correspond to the following environmental influences:

3.1.1 Electrical data

Voltage supply
Connection
Volta ge
Power consumption At voltage supply 230 V: max. 15 VA / 7 W
Inputs and outputs
Connection
Conductor cross section
Electrical safety According to DIN EN 61010-1
At the back via screw terminals AC/DC 24 V +30/-25%, 48 to 63 Hz or AC 110 to 240 V +10/-15 %, 48 to 63 Hz
At voltage supply 24 V: max. 12 VA / 9 W
At the back via screw terminals Max. 2.5 mm
Overvoltage category III, pollution degree 2
2
, wire or strand with end sleeve

3 Mounting

Electromagnetic compatibility
Interference emission
Interference immunity
Memory data recorder Memory cycle Recording interval
When recording:
4 analog signals
3 digital signals
According to DIN EN 61326-1 Class A - For industrial applications only Industrial requirements
1 s approx. 44 days
5 s approx. 220 days
10 s approx. 441 days
60 s approx. 2646 days (7 years, 91 days)

3.1.2 Environmental influences

Ambient/storage temperature range -5 to +55 °C/-30 to +70 °C
Resistance to climatic conditions Humidity 3K3 (DIN EN 60721-3-3) with extended temperature
range, rel. humidity 95 % mid-year without condensation

3.1.3 Case

Site Altitude maximum 2000m above sea level
Case type Plastic front frame with metal case barrel (for indoor use only)
Front frame dimensions 96 mm × 96 mm
+0.8
Panel cut-out 92
Close mounting Spacing between the panel cut-outs, min. 35 mm horizontally and
mm × 92+
min. 80 mm vertically
0.8
mm according to DIN IEC 61554
19
3 Mounting
92
+0.8
92
+0.8
(22)
(20)
(21)
130.9 - panel thickness
Panel thickness
Panel thickness Max. 5 mm
Depth behind panel Max. 130 mm
Mounting Four mounting brackets
Operating position
(including the viewing angle of the TFT color screen)
Protection type Front IP66, rear IP20, according to DIN EN 60529
Weight (fully fitted) approx. 1000 g

3.2 Dimensions

Any
Horizontal ±65°, vertical +40 to -65°
(20) USB host interface (21) USB device interface for setup
(22) Panel cut-out
20

3.3 Close mounting

If several devices are mounted on a switch board above or next to each other, the panel cut­outs must be positioned 35 mm horizontally and at least 80 mm vertically away from each oth­er.

3.4 Insertion in panel cut-out

3 Mounting
Step Activity
1 Affix delivered panel seal (1) on the device from the rear
2 Insert the device into the panel cut-out from the front and ensure the panel seal is correctly
positioned so that no water or dirt can penetrate the case.
3 From the panel rear, slide the mounting brackets into the guides on the sides of the case. In
doing so, the flat faces of the mounting brackets must make contact with the case.
4 Place the mounting brackets against the panel rear and tighten evenly with a screwdriver
until the controller housing is firmly positioned in the panel cut-out.

3.5 Care and treatment of the front cover

The front plate can be cleaned with commercial detergents and cleaning agents.
21
3 Mounting
NOTE!
The resistive touchscreen cover reacts to finger pressure or can be operated using commer­cially available pens with a rounded plastic tip.
CAUTION!
Sharp tools can scratch and damage the cover. The front plate is not resistant to corrosive acids or lyes, abrasives, or cleaning with high­pressure cleaners. Do not use sharp objects near the device.
22

4.1 Installation notes

CAUTION!
The delivery status of the device at the first startup does not necessarily correspond to the intended application (for example, Controller 2 inactive). This may result in undefined plant behavior. Therefore, where possible during startup, no actuators should be connected and load cur­rent circuits should be isolated. The plant installer is essentially responsible for the startup process.

4.1.1 Cables, shielding, and grounding

When selecting the electrical wiring material as well as when installing and connecting the con­troller electrically, comply with the requirements of DIN VDE 0100 "Low-voltage electrical instal­lations" and the applicable country-specific regulations (for example, based on IEC 60364).
Where possible, route input, output, and supply cables separately and not parallel to one another.
Only use shielded and twisted probe and interface cables and where possible, route them at a distance from components or lines that are live.
For temperature probes, ground the shielding on one side in the control cabinet.
Do not perform loopthroughs on the grounding cables, but route the cables individually to a shared grounding point in the control cabinet; in doing so, ensure that the cables are as short as possible.
Ensure potential equalizer is correctly routed.
At maximum load, the cables must be heat resistant up to at least 80 °C.
When connecting the device to an external PELV electrical circuit, the existing internal SELV electrical circuit becomes a PELV electrical circuit whereby the protection against electrical shock is provided through double/reinforced insulation and voltage limitation – but here no connection to the protective ground is required.

4 Electrical connection

4.1.2 Electrical safety

The primary fuse protection for the voltage supply should not exceed a value of 20 A (pas­sive) and should not be less than 2 A.
In order to prevent the destruction of the relay or solid state relay outputs in the event of an external short circuit in the load circuit, the load circuit should be fused to the maximum ad­missible output current.
In addition to a faulty installation, incorrectly set values on the controller could also impair the correct function of the following process. Therefore, ensure that safety devices indepen­dent of the controller (for example, overpressure valves or temperature limiters/monitors) are available and that it is only possible for qualified personnel to define settings. Please observe the corresponding safety regulations in this context.
Since not all existing control paths can be controlled with the setting function, the stability of the actual value reached should be monitored.
For servicing/repairing a Disconnecting Device shall be provided to disconnect all conduc­tors.
23
4 Electrical connection

4.1.3 Intended use, misuse

The controller is intended for use in the industrial sector.
WARNING!
The controller is not suitable for installation in areas with an explosion hazard Explosion hazard. The device must only be used outside of areas with an explosion hazard.
24

4.2 Galvanic isolation

Voltage supply AC/DC 24 V
Analog output
Relay outputs
RS422/485
Ethernet, PROFINET
Digital 1input
Analog IN11input
Analog input IN8
DC 50 V
AC 30 V
»
1 solid state relay output AC 230 V, 1 A
AC 3600 V
»
Voltage supply AC 240 V
1 l DC 0/22 V, max. 30 mA (short-circuit proof)
ogic output
2 logic outputs DC 0/12 V, max. 20 mA (short-circuit proof)
Digital input (potential free contact)
7
DC 50 V
AC 30 V
»
DC 50 V
AC 30 V
»
DC 50 V
AC 30 V
»
AC 3600 V
»
AC 3600 V
»
AC 3600 V
»
DC 50 V
AC 30 V
»
DC 50 V
AC 30 V
»
2 PhotoMOS® solid state relay U = DC 45 V, I = 200 mA
max. max.
U = AC 30 V, I = 200 mA
max. max.
DC 50 V
AC 30 V
»
»
USB (host, device)
PROFIBUS
DC 50 V
AC 30 V
»
2 solid state relay outputs AC 230 V, 1 A for controlling motor actuators
AC 3600 V
»
»
4 Electrical connection
25
4 Electrical connection

4.3 Connection diagram

DANGER!
Works involving dangerous electrical voltage (230 V) are performed here. There is a risk of electric shock. Switch off all voltage circuits before routing. The electrical connection must only be carried out by qualified personnel.

4.3.1 Connection elements

(1) Analog input IN8 (2) Analog input IN9
(3) Expansion slot for analog input IN10 (4) Expansion slot for analog input IN11
(5) Voltage supply
AC 240 V +10/-15 %, 48 to 63 Hz, max. 38.1 VA
AC/DC 24 V +30/-25%, 48 to 63 Hz,
max. 21.9 VA / 11.5 W
(7) Relay output OUT1 (8) Expansion slot for outputs OUT3/4
(9) Expansion slot for outputs OUT5/6 (10) Expansion slot for outputs OUT7/8
(11) Expansion slot for outputs OUT9/10 (12) Expansion slot for outputs OUT11/12
(13) COM1 interface RS485 (14) Expansion slot for COM2 interface
(15) Digital inputs IN1 to 7
(6) Relay output OUT2
26

4.3.2 Analog inputs

U
+
-
x
U
+
-
x
U
+
-
x
I
+
-
x
E
S
A
Input IN8, IN9 as standard
Two analog inputs can be added to input (IN10), (IN11) optional boards
4 Electrical connection
Connection (Connection ele-
ment) Input
Thermocouple (1) IN8
(2) IN9
(3) IN10
(4) IN11
RTD temperature probe Two-wire circuit
RTD temperature probe Three-wire circuit
Voltage DC 0(2) to 10 V 1
Symbol and terminal designation
3
4
2
4
2
3
4
4
Voltage DC0to1V 2
4
Voltage DC 0 to 100 mV 3
4
Current DC 0(4) to 20 mA 3
4
Resistance transmitter
A = Start
E = End
S = Slider
2
3
4
27
4 Electrical connection
Hinweis: Wegen der Ansprechgenauigkeit ist die Verwendung nur ohne Schutzhülsen (Tauchhülsen) zulässig.
aktuelle Typenbezeichnung alte Typen-
bezeichnung
Fühlerart Temperaturbereich Nennlänge mm Prozessanschluss
Widerstandsthermometer Typenblatt 90.2006
902006/65-228-1003-1-15-500-668/000 - 1 x Pt100 -170 ... +700°C 500
902006/65-228-1003-1-15-710-668/000 - 710
902006/65-228-1003-1-15-1000-668/000 - 1000
902006/55-228-1003-1-15-500-254/000 - 1 x Pt100 -170 ... +700°C 500
902006/55-228-1003-1-15-710-254/000 - 710
902006/55-228-1003-1-15-1000-254/000 - 1000
902006/65-228-2003-1-15-500-668/000 90.271-F01 2 x Pt100 -170 ... +700°C 500 Anschlagflansch
verschiebbar
902006/65-228-2003-1-15-710-668/000 90.272-F01 710
902006/65-228-2003-1-15-1000-668/000 90.273-F01 1000
902006/55-228-2003-1-15-500-254/000 - 2 x Pt100 -170 ... +700°C 500 verschiebbare
Klemmverschraubung G1/2
902006/55-228-2003-1-15-710-254/000 - 710
902006/55-228-2003-1-15-1000-254/000 - 1000
Thermoelemente Typenblatt 90.1006
901006/65-547-2043-15-500-668/000 90.019-F01 2 x NiCr-Ni, Typ „K“ -35 ... +800°C 500 Anschlagflansch
verschiebbar
901006/65-547-2043-15-710-668/000 90.020-F01 710
901006/65-547-2043-15-1000-668/000 90.021-F01 1000
901006/65-546-2042-15-500-668/000 90.019-F11 2 x Fe-CuNi, Typ „L“ -35 ... +700°C 500
901006/65-546-2042-15-710-668/000 90.020-F11 710
901006/65-546-2042-15-1000-668/000 90.021-F11 1000
901006/66-550-2043-6-500-668/000 90.023-F01 2 x NiCr-Ni, Typ „K“ -35 ... +1000°C 500
901006/66-550-2043-6-355-668/000 90.023-F02 355
901006/66-550-2043-6-250-668/000 90.023-F03 250
901006/66-880-1044-6-250-668/000 90.021 1 x PT10Rh-PT, Typ „S“ 0 ... 1300°C 250
901006/66-880-1044-6-355-668/000 90.022 355
901006/66-880-1044-6-500-668/000 90.023 500
901006/66-880-2044-6-250-668/000 90-D-021 2 x PT10Rh-PT, Typ „S“ 0 ... 1300°C 250 Anschlagflansch
verschiebbar
901006/66-880-2044-6-355-668/000 90-D-022 355
901006/66-880-2044-6-500-668/000 90-D-023 500
901006/66-953-1046-6-250-668/000 90.027 1 x PT30Rh-PT6Rh, Typ „B“ 600 ... 1500°C 250
901006/66-953-1046-6-355-668/000 90.028 355
901006/66-953-1046-6-500-668/000 90.029 500
901006/66-953-2046-6-250-668/000 90-D-027 2 x PT30Rh-PT6Rh, Typ „B“ 600 ... 1500°C 250
901006/66-953-2046-6-355-668/000 90-D-028 355
901006/66-953-2046-6-500-668/000 90-D-029 500
Hinweis: Wegen der Ansprechgenauigkeit ist die Verwendung nur ohne Schutzhülsen (Tauchhülsen) zulässig.
aktuelle Typenbezeichnung alte Typen-
bezeichnung
Fühlerart Temperaturbereich Nennlänge mm Prozessanschluss
Widerstandsthermometer (Typenblatt 90.2006)
90.2006/10-402-1003-1-9-100-104/000 1 x Pt100 -40 ... +400°C 100 Verschraubung G1/2
90.2006/10-402-2003-1-9-100-104/000 2 x Pt100 100
902006/54-227-2003-1-15-710-254/000 90.272-F02 2 x Pt100 -170 ... 550°C 65...670 verschiebbare Klemm-
verschraubung G1/2
902006/54-227-1003-1-15-710-254/000 90.272-F03 1 x Pt100 65...670
902006/10-226-1003-1-9-250-104/000 90.239 1 x Pt100 -170 ... 480°C 250 Verschraubung G1/2
902006/10-226-2003-1-9-250-104/000 90-D-239 2 x Pt100 250
Thermoelemente (Typenblatt 90.1006)
901006/54-544-2043-15-710-254/000 90.020-F02 2 x NiCr-Ni, Typ „K“ -35 ... 550°C 65...670 verschiebbare Klemm-
verschraubung G1/2
901006/54-544-1043-15-710-254/000 90.020-F03 1 x NiCr-Ni, Typ „K“ 65...670
901006/54-544-2042-15-710-254/000 90.020-F12 2 x FeCuNi, Typ „L“ 65...670
901006/54-544-1042-15-710-254/000 90.020-F13 1 x FeCuNi, Typ „L“ 65...670

4.3.3 Probes for air

4.3.4 Probes for water and oil

28

4.3.5 Probes for water and oil

Hinweis: Wegen der Ansprechgenauigkeit ist die Verwendung nur mit werkseitig mitgelieferten Schutzhülsen (Tauchhülsen) zulässig.
aktuelle Typenbezeichnung alte Typen-
bezeichnung
Fühlerart Temperaturbereich Nennlänge mm Prozessanschluss
Widerstandsthermometer (Typenblatt 90.2006)
902006/53-505-2003-1-12-190-815/000 90D239-F03
2 x Pt100
-40 ... +400 °C 190
902006/53-507-2003-1-12-100-815/000 90.239-F02 2 x Pt100
(im Schutzrohr untereinander angeordnet)
-40 ... +480 °C 100
902006/53-507-2003-1-12-160-815/000 90.239-F12 160
902006/53-507-2003-1-12-190-815/000 190
902006/53-507-2003-1-12-220-815/000 90.239-F22 220
902006/53-507-1003-1-12-100-815/000 90.239-F01 1 x Pt100 -40 ... +480 °C 100 Einschweisshülse
902006/53-507-1003-1-12-160-815/000 90.239-F11 160
902006/53-507-1003-1-12-220-815/000 90.239-F21 220
902006/53-505-1003-1-12-190-815/000 90.239-F03
1 x Pt100
-40 ... +400 °C 190
902006/53-505-3003-1-12-100-815/000 90.239-F07 3 x Pt100 -40 ... +400 °C 100
902006/53-505-3003-1-12-160-815/000 90.239-F17 160
902006/53-505-3003-1-12-220-815/000 90.239-F27 220
902006/40-226-1003-1-12-220-815/000 90.280-F30 1 x Pt100 -170 ... +480°C 220 Einschweisshülse
902006/40-226-1003-1-12-160-815/000 90.280-F31 160
902006/40-226-1003-1-12-100-815/000 90.280-F32 100
Thermoelemente (Typenblatt 90.1006)
901006/53-543-1042-12-220-815/000 90.111-F01 1 x Fe-CuNi Typ „L“ -35 ... 480°C 220 Einschweisshülse
901006/53-543-2042-12-220-815/000 90.111-F02 2 x Fe-CuNi Typ „L“ 220
Hinweis: Wegen der Ansprechgenauigkeit ist die Verwendung nur ohne Schutzhülsen (Tauchhülsen) zulässig.
aktuelle Typenbezeichnung alte Typen-
bezeichnung
Fühlerart Temperaturbereich Einbaulänge mm Prozessanschluss
Widerstandsthermometer (Typenblatt 90.2006)
90.2006/10-390-1003-1-8-250-104/000 90.210-F95 1 x Pt100 max. 300°C 250
Thermoelemente (Typenblatt 90.1006)
901006/45-551-2043-2-xxxx-11-xxxx 2 x NiCr-Ni, Typ „K“ max.
150°C 5
0...2000
+
-
xIx
U
,
4 Electrical connection

4.3.6 Probes for the operating medium water, oil, and air

4.3.7 Analog outputs

One analog output can be added to output OUT 3/4 to 11/12 using optional boards
Connection (Connection ele-
ment)
One analog output DC0/2to10V or DC0/ 4to20mA (configurable)
Input
(8) OUT3/4
(9) OUT5/6
(10) OUT7/8
(11) OUT9/10
(12) OUT11/12
Symbol and terminal designation
1
2
29
4 Electrical connection
P
P

4.3.8 Digital inputs

Input IN1 to 7 as standard (cannot be extended)
Connection (Connection ele-
ment) Input
Digital input, potential-free contact as standard
(15) IN1 to 7 3, 4, 5, 6, 7, 8, 9

4.3.9 Digital outputs

OUT1 and OUT2 as standard
The controller is fitted with two relay outputs (changeover contacts) as standard.
Connection (Connection
element) Output
Relay output (changeover contact)
(6) OUT2
(7) OUT1
Symbol and terminal designation
10
Symbol and terminal designation
1
2
3
Outputs OUT 3/4 to 11/12 are expandable using the following optional boards
Connection (Connection
element) Output
One relay output (changeover contact)
Two relay outputs (N/O con-
1
tact)
(8) OUT3/4
(9) OUT5/6
(10) OUT7/8
(11) OUT9/10
(12) OUT11/12
Symbol and terminal designation
1
2
3
1
2
3
4
30
4 Electrical connection
+
-
xIx
U
,
+
-
xIx
U
,
+
-
xIx
U
,
Connection (Connection
element) Output
One solid state relay AC230V, 1A
One logic output DC 0/22 V, max. 30 mA (short-circuit proof)
Two logic outputs DC 0/12 V max. 20 mA (short-circuit proof, not galvanically isolated from each other)
Two PhotoMOS® relays
2
max. DC 45 V, 200 mA max. AC 30 V, 200 mA (galvanically isolated)
Symbol and terminal designation
1
2
1
2
1
2
3
4
1
2
3
4
Two solid state relays AC230V, 1A (for controlling the left and right-hand motor actuators, galvanically isolated)
1
Combining a mains voltage circuit with a protective low-voltage circuit on the "dual normally open contact" option is not admissible.
2
PhotoMOS is a registered trademark of Panasonic Corporation.

4.3.10 Digital outputs

Standard
Two relay outputs (changeover contact)
Switching capacity AC
Switching capacity DC
Contact life
AC 230V/24V; 3(0,5) A; cosφ=1(≥ 0,6); D300 DC 24V; 3(0,5; τ =7ms) A
250,000 operations at nominal load
31
4 Electrical connection
Per optional board
One relay output (changeover contact)
Switching capacity AC
Switching capacity DC
Contact life
Two relay outputs (N/O contact)
Switching capacity AC
Switching capacity DC
Contact life
One solid state relay
Switching capacity
Protection circuitry
Two solid state relay for motor actuators
Switching capacity
Protection circuitry
One logic output (voltage supply for transmitter)
1
AC 230V/24V; 3(0,5) A; cosφ=1(≥ 0,6); D300 DC 24V; 3(0,5; τ =7ms) A
250,000 operations at nominal load
AC 230V/24V; 3(0,5) A; cosφ=1(≥ 0,6); D300 DC 24V; 3(0,5; τ =7ms) A
250,000 operations at nominal load
1 A at AC 230 V, resistive load
Vari stor
1 A at AC 230 V,
RC combination
DC 0/22 V, max. 30 mA (short-circuit proof)
Two logic outputs DC 0/12 V max. 20 mA (short-circuit proof, not galvanically isolated)
Two PhotoMOS® relays
1
Combining a mains voltage circuit with a protective low-voltage circuit on the "dual normally open contact" option is not admissible.
2
PhotoMOS is a registered trademark of Panasonic Corporation.
2
DC 45 V, max. 200 mA, (galvanically isolated from each other, not short-circuit proof)
AC 30 V, max. 200 mA, (galvanically isolated from each other, not short-circuit proof)

4.3.11 Voltage supply (according to nameplate)

AC 230V (DC 24V)
Connection (Connection ele-
ment)
Protection conductor
Neutral conductor
Line conductor
PE
N (L-)
L1(L+)
Symbol and terminal designation
PE
N
L1
32

4.3.12 Interfaces

USB device, USB host and COM1 interfaces as standard
4 Electrical connection
Connection (Connection
element)
USB device interface (21)
USB host (20)
COM1 serial interface RS485 (galvanically isolated)
(13) 1 TxD+/RxD+
Symbol and terminal designation
2 TxD-/RxD-
Transmission/ received data +
Transmission/ received data -
33
4 Electrical connection
6
7
8
9
2
3
4
5
1
COM2 interface can be expanded using optional boards
Connection (Connection
Symbol and terminal designation
element)
Ethernet (14) 1 TX+
2 TX-
3 RX+
6 RX-
Serial interface RS422 (galvanically isolated)
1 RxD+
2 RxD-
3 TxD+
4 TxD-
Serial interface RS485 (galvanically isolated)
3 TxD+/RxD+
4 TxD-/RxD-
PROFIBUS-DP 3 RxD/TxD-P
(B)
5 DGND
6 VP (+5 V)
8 RxD/TxD-N (A)
Transmission data +
Transmission data -
Received data +
Received data -
Received data +
Received data -
Transmission data +
Transmission data -
Transmission/ received data +
Transmission/ received data -
Data wire B+
Ground
Voltage supply
Data wire (A) -
PROFINET-RT 1 TX+
2 TX-
3 RX+
6 RX-
Transmission data +
Transmission data -
Received data +
Received data -
34

5 Operation

35
5 Operation
Data recording and evaluation
213only available with option
Only available with option 223
Alarm/event list
Device settings menu
2 function keys
(Factory switched off)setting: (F )actory setting: switched off

5.1 Display and operating concept

The DICON touch is operated via a resistive touchscreen and also reacts to finger pressure. Commercially available pens with plastic tips can also be used.
36

5.2 Device menu

All the functions in the device menu are described in the following sections of the B703571.0de operating manual.
5 Operation
Chapter 6 "Login", Page 43
B 703571.0 - Chapter 7 "User level (Log-In)", Page 45
Chapter 8 "Program administration", Page 47
B 703571.0 - Chapter 10 "Functional level", Page 55
B 703571.0 - Chapter 11 "Parameterization", Page 57
B 703571.0 - Chapter 12 "Configuration", Page 65
Calibrating the touchscreen:
Chapter 14 "Special functions", Page 167

5.3 Alarm and event list

In these lists, alarms and events appear that are partly confirmed. Additional entries can be configured to appear in the lists.
Ö B 703571.0 - Chapter 12.9.5 "Alarm", Page 109 Ö B 703571.0 - Chapter 12.5.1 "Alarms", Page 77

5.4 Function buttons, history and channel changeover

Both these function buttons are set and configurable by default at "Operating level" and "Home" (back to Main view).
Ö B 703571.0 - Chapter 12.10.1 "General configuration", Page 110 The "History"(H) and "Channel changeover"(Ch) buttons enable navigation in the recorder im-
age and change their meaning according to the dialog. Ö Chapter 5.5.4 "Recording image", Page 42
37
5 Operation

5.5 Images in the operating loop

Start screen
After switch-on, the globe appears until the device software is started up.
Then Controller screen 1 appears (default setting). Using the icon in the bottom right-hand corner, all the images defined in the operating loop can be called up one after another.
Ö For the screen settings see B 703571.0 - Chapter 12.10 "Screen", Page 110 Ö To view the images displayed see B 703571.0 - Chapter 12.10.4 "Operating loop", Page
112

5.5.1 Controller screen 1, Controller screen 2 and Controller overview

You can change the color of these screens in the setup program. The basic structure cannot be changed however.
Default setting
Fixed-setpoint controller and Controller 1 are set up. In order to function properly, the controller requires an actual value, a setpoint value, and an
output to influence the actual value (for example, a heat source via a relay as a two-point con­troller). Autotuning can only detect new parameters using a closed control loop.
Ö Chapter 12.6.3 "Self-optimization controller", Page 83
If lines or arrows appear, check the configuration or the connection. Ö Chapter 16 "Error and alarm messages", Page 177
Enter setpoint values on the device for the fixed-setpoint controller
Ö Chapter 11.4 "Setpoint values", Page 62
Enter setpoint values for the fixed-setpoint controller with the setup program
Ö Chapter 11.4 "Setpoint values", Page 62
38
Start manual mode
In manual mode, the controller is fixed at a particular output level. First of all, the screens show the active controller, where the output is at approx. 40 %.
Step Activity
1 Touch the hand symbol (pencil appears at output level display)
2 Touch the pencil, enter the manual output level and confirm (green arrow)
5 Operation
3 The controller operation is interrupted and Controller 1 is now working with a fixed output
You can now manually influence the output level (by hand)
Exit manual mode
By touching the screen below the hand, you can exit manual mode and return to normal con­troller operation.
Autotuning
Ö B 703571.0- Chapter 12.6.3 "Self-optimization controller", Page 83
level of 20 % (the hand symbol appears next to the green setpoint value). You can view the difference between the fixed-setpoint controller and the program control­ler at the automatic operation icon in the top right-hand corner. The green setpoint value continues, as programmed.
39
5 Operation

5.5.2 Program controller

NOTE!
This screenshot is not available by default and only appears if the extra code for the program controller is enabled and configured.
Ö Chapter 2.1 "Order Details", Page 13
Default setting
There are no programs available. The following options are available for ordering a program:
Enter setpoint curves on the device
Ö Chapter 8.1.1 "On the device", Page 47
Enter setpoint curves using the setup program
Ö Chapter 8.1.2 "About the setup program", Page 48
Start, Stop
The black arrow starts an available program. A request appears asking which program should be started and the programmed setpoint curves are then synchronized for both controller chan­nels. The symbol for automatic operation appears in the center. Touching the black rectangle stops the program, adopting the conditions prior to the program starting.
Pause
Pauses the time base of a program in operation, whereby the current setpoint values and the conditions of the control contacts are maintained. Touching the pause button again resumes program operation.
Next section, previous section
The program in operation jumps to the next or previous section.
Temporary alteration
Allow one-time changes to the setpoint values for a program without storing it permanently in the program table. When you next run the program, the original setpoint values will be reacti­vated.
Start/stop manual mode (for program controller)
40
Using the program controller, manual mode can only be started by pressing the Hand button when the program is stopped. After touching the hand with the pencil, the dialog for entering setpoint values 1 and 2 opens. These setpoint value are controlled using the Ok button.
Autotuning
Ö B 703571.0- Chapter 12.6.3 "Self-optimization controller", Page 83

5.5.3 General screen 1.2

Default setting
Two general screens are available that do not contain any variables.
5 Operation
The variables displayed can be configured. Ö B 703571.0- Chapter 12.10.8 "General screens 1, 2", Page 116
41
5 Operation

5.5.4 Recording image

Default setting
Here the device is displaying up to four analog and three digital channels, like a line recorder. Extra code 213 is required for data to be recorded and evaluated.
You can view historical data (from previous recordings) with the H button and switch channels with the CH button. If the channels displayed are configured, the screen must still be active for the operating loop display.
Ö B 703571.0 - Chapter 12.11 "Recording", Page 117

5.5.5 Process screen

Default setting
This screen can be freely configured and is empty by default. A background image of your plant can be stored and animated with all the process values for the device.
The setup program is required to design the graphics. Ö B 703571.0 - Chapter 13.13 "Process screen", Page 159
42

6 Login

Some of the levels in the device menu are username- and password-protected. The level pro­tection is defined in the user list by the setup program, using five different users. On entering the password, each user is entitled to use the "rights" available.
If permitted, the rights and passwords can also be changed on the device.
Touching the screen in the bottom left-hand corner opens the device menu window. Touching the 'Login' function opens the Login window.
43
6 Login

6.1 Logging on

This sequence shows the logon process as the master user (with the default password 9200):
User 1 is now logged on and is permitted to access all functions listed under "Rights".

6.2 Logging out

As soon as you are logged on, the Log-Out button is no longer grayed out and touching it will enable you to log out. Consequently, your user rights will be limited.

6.3 Change password

You can change the user password that you are currently logged in with here. To do this, you must first enter the old password (for the master user) and then the new one. If the password is incorrect, the change will not be accepted.
44
NOTE!
This level is empty by default and parameters can only be defined using the setup program to appear in the device.
Up to 25 parameters of any type from the configuration or parameter level can be included in this level. These parameters, for example, often need to be changed or made available to op­erating personnel.
NLY SETUP >USER LEVEL
O
Setup dialog box

7 User level (Log-In)

7.1 Example 4 Transferring controller setpoint values to the user level

The four reversible controller setpoint values should be transferred to the user level. Double­clicking on the empty entry opens the selector window.
45
7 User level (Log-In)
Setup dialog box
Device display
Once the setup data has been transferred to the device, the setpoint values can be entered on the device.
46

8.1 Enter program curves

Ten programs can be entered on the device or in the setup program.

8.1.1 On the device

Step Activity
1 Enter program names and icons
2 Enter first section:
If the program memory is empty, the section will be highlighted in red.

8 Program administration

Each section consists of: target values 1 and 2, section time, control contacts, tolerance band, number of repetitions from start section, and parameter block.
3 Repeat section entries until the table is complete
4 Touching the pencil symbol enables additional editing functions.
Editing the program header
Copying and deleting the program
Creating a new section
Two program curves have now been programmed.
They can be started at any section at an adjustable time and run in parallel.
47
8 Program administration

8.1.2 About the setup program

Step Activity
1 Start the setup program and click on Program editor > Program administration in the menu
2 Enter sections in the table
3 The table is displayed as a graphic with the program simulation
4 Save the setup file and transfer the setup data to the device
48
Step Activity
5 If a green icon (smiley) appears, then the programs have been successfully transferred.
2 Programmkurven sind nun im Gerät und können an einem beliebigen Abschnitt zu einer
einstellbaren Zeit gestartet werden. The programs run in parallel.

8.1.3 Section run time

The period of time until the next section. Setpoint values varying from section to section create a ramp-like setpoint curve (with a nega­tive or positive slope).

8.1.4 Setpoint values 1 and 2

8 Program administration
Each program contains 2 setpoint value profiles which can be used to create 2 program con­trollers.

8.1.5 Operating contacts

Eight control contacts can be set at any one time. They are available in the digital selector and can switch on relays, for instance.
Ö Setup program:
C
ONFIGURATION LEVEL >DIGITAL OUTPUTS
They can also be logically linked or can trigger internal device functions.

8.1.6 Tolerance band

The tolerance band max. value is above the programmed setpoint value curve and the min. val­ue is below the curve. Both values can be variably adjusted for each section.
The function behaves in the same was as for the ramp function or the symmetrical program tolerance band. The tolerance band limit that is reached first stops the program.
Ö Chapter 12.6.8 "Ramp function", Page 98 and
Chapter 12.12 "Program controller", Page 120
49
8 Program administration

8.1.7 Number of repetitions

The number of repetitions is entered for a specific start section.

8.1.8 Start section

Repetition begins from this section.
Example

8.1.9 Parameter block

For each controller channel, parameter blocks 1 to 4 are available and can be switched in any combination
50

9 Device information

The device information function enables hardware and software modules to be displayed.

9.1 General

The type extra codes enabled in the device are displayed next to the device names.

9.1.1 Version, motherboard, Ethernet information

Software version, fabrication number, and testing ID are displayed. Displays the hardware on the motherboard. MAC address, IP address, gate address, DNS address, and transfer rate.

9.2 Slots

Assignment of expansion slots is displayed in the device.
51
9 Device information

9.3 Inputs/outputs

The switching statuses and measurement values are displayed here.

9.3.1 Digital and analog inputs, digital and analog outputs, external digital, and external analog inputs

52
9 Device information

9.4 Functions

9.4.1 Mathematics, logic signal, limit value outputs

9.4.2 Timer signal, digital controller signals, control contacts, controller, analog flag, digital flag

53
9 Device information

9.5 Ethernet

9.6 PROFINET

54

10.1 General

NOTE!
The functional level is faded out by default and must be activated using the setup program.

10.1.1 Activate functional level

The functional level is activated in the screen menu and subsequently appears in the device menu.
Ö Chapter 12.10 "Screen", Page 110

10 Functional level

The functional level is used primarily for testing and diagnostic purposes. Analog and binary values of the outputs can be controlled manually here. This may be useful, for instance, for checking an individual piece of equipment in a plant. For maintenance and repair works, for ex­ample, the timer, ramp function, and limit value monitoring can be operated and switching op­eration can be acknowledged.
Example for the timer
55
10 Functional level
56
NOTE!
The parameters described in this section can be entered either in the setup program or in DI­CON touch. This is where the parameters that are directly linked to the alignment of the con­troller with the control path are set, after the system has been commissioned.
You must be logged in to change the parameters.
Ö Device menu section > Login Ö Chapter 7 "User level (Log-In)", Page 45
Setup dialog box

11 Parameterization

11.1 Date and time

The following table shows the time settings for the device.
Parameter Setting Description
Current date 2011-01-01
2083-12-31
Current time 00:00:00
23:59:59

11.2 Daylight saving time

The following table shows the settings for daylight saving time.
Parameter Setting Description
Synchronization No function
Digital selector
Switch daylight saving time automatic
inactive
Enter the date here.
Enter the time here.
A digital signal can be selected here to syn­chronize the time.
Enables you to set the time to change auto­matically.
57
11 Parameterization
Parameter Setting Description
Start DST Month: March
Week: last week
Day: Sunday
Time: 02:00:00
End DST Month: October
Week: last week
Day: Sunday
Time: 03:00:00

11.3 Controller/parameter blocks

Setup dialog box
Toggling takes place at this time.
Toggling takes place at this time.
58
The following table shows the parameters in a parameter block. These parameters are also available for the other three parameter blocks. Four parameter blocks can be defined for each of the two controller channels. Switching the parameter blocks is performed separately for each controller channel via two digital signals.
Depending on the controller type configured, certain parameters may be omitted or ineffective. Parameters that appear in pairs such as Proportional band 1 and 2 refer to the first and second controller outputs (for instance, with three-state controllers).
The parameter blocks are assigned to both controllers in the configuration level. Ö B 703571.0 - Chapter 12.6.2 "Controller inputs", Page 81
11 Parameterization
Parameter Setting Description
Proportional band 1
(Xp1)
Proportional band 2
(Xp2)
Derivative time 1
(Tv1)
Derivative time 2
(Tv2)
Reset time 1
(Tn1)
Reset time 2
(Tn2)
Cycle time 1
(Cy1)
Cycle time 2
(Cy2)
Contact spacing
(Xsh)
Switching differ­ential 1
(Xd1)
Switching differ­ential 2
(Xd2)
Actuator time
(TT)
0 ... 9999 Value for the proportional band
The controller structure has no effect if Xp = 0 (behavior identical to limit value
0 ... 9999
0 ... 80 ... 9999 s The derivative time influences the differ-
0 ... 80 ... 9999 s
0 ... 350 ... 9999 s The reset time influences the integral
0 ... 350 ... 9999 s
0 ... 20 ... 999.9 s When using a switched output, the cycle
0 ... 20 ... 999.9 s
0 ... 999.9 Spacing between the two control con-
0 ... 1 ... 999.9 Hysteresis for a switching controller with
0 ... 1 ... 999.9
5 ... 60 ... 3000 s Control valve running time range used
monitoring)!
For a continuous controller, Xp must be > 0.
ential component (D component) of the controller output signal.
The greater the derivative time, the more effect the D component has.
component (I component) of the control­ler output signal.
The greater the reset time, the less effect the I component has.
time should be chosen so that the energy supply to the process is as con­tinuous as possible without overloading the switching elements.
tacts for a three-state controller, modu­lating controller, and continuous controller with integrated position con­troller
proportional band Xp = 0
for a modulating controller and continu­ous controller with integrated position controller
Working point
(Y0)
Max. output level limit
(Y1)
-100 ... 0 ... +100 % Working point correction for a P or PD controller (correction value for the output level)
If the actual value (x) has reached the setpoint value (w), the output level (y) corresponds to the working point (Y0).
0 ... 100 % Admissible maximum output level (only
effective if Xp > 0)
59
11 Parameterization
Parameter Setting Description
Min. output level limit
(Y2)
Minimum relay ON period 1
(Tk1)
Minimum relay ON period 2
(Tk2)
-100 ... +100 % Admissible minimum output level (only effective if Xp > 0)
0 ... 60 s Limits the switching frequencies for
switched outputs
0 ... 60 s
60
Transmission behavior
Xd1
0 %
100 %
y
w
x
Xd1
0 %
100 %
y
w
x
w-Xd1
Y0 = 0 %
Xd1
0 %
100 %
y
w
x
w+Xd1
Y0 = 100 %
Xd1
0 %
100 %
y
w
x
w-Xd1
Y0 = -100 %
Xd1
w-2*Xd1
The transmission behavior (controller structure) is determined by the configuration of the pa­rameters for the proportion band (P component), derivative time (D component), and reset time (I component).
Two-state controller
This controller has a switched output and can be parameterized with P, PI, PD, or PID trans­mission behavior. The proportional band Xp must be greater than 0 for the controller structure to take effect.
If Xp = 0, the behavior corresponds to the function of limit value monitoring with switching dif­ferential Xd1 (working point Y0 = 0 %):
Influence of working point Y0 on the switching behavior
11 Parameterization
61
11 Parameterization
Xd1
0 %
100 %
y
w
x
Xsh
Xd2
-100 %
Three-state controllers
This controller has two outputs, which can be configured as continuous (analog output) or switched (digital output). In both cases, the controller can be parameterized with P, PI, PD, or PID transmission behavior. The proportional bands Xp1 and Xp2 must be greater than 0 for the controller structure to take effect.
If Xp1 = 0 and Xp2 = 0, the behavior corresponds to the function of limit value monitoring with switching differential Xd1 and Xd2, and contact spacing Xsh (working point Y0 = 0 %):
Modulating controllers
This controller has two switched outputs and can be parameterized with PI or PID transmission behavior. The proportional band Xp must be greater than 0 for the controller structure to take effect.
The modulating controller is used for actuator drives with three switching statuses (actuator open, closed, hold). If output level feedback is available, the active output is deactivated when the output level limits are reached.
Continuous controller
This controller has a continuous output (analog output) and can be parameterized with P, PI, PD, or PID transmission behavior. The proportional band Xp must be greater than 0 for the con­troller structure to take effect (the setting Xp = 0 is normally used in practice).
Position controllers
This controller is a continuous controller with integrated position controller and two switched outputs (digital outputs) with PI or PID transmission behavior.
The position controller is used for actuator drives with three switching statuses (actuator open, closed, hold). An output level feedback is required.

11.4 Setpoint values

Four switchable setpoint values are assigned to a fixed-setpoint controller and can be entered on the device or in the setup program. The following table shows the setpoint changeover for fixed-setpoint controllers using two dig­ital signals that can be Chapter 12.6.7 "Controller setpoint values", Page 96 set.
For program controllers
Ö Chapter 8.1 "Enter program curves", Page 47
62
11 Parameterization
Type Signal 2 (Bit 1)
setpoint changeover
Fixed-setpoint controller
Program control­ler
00Setpoint 1 Setpoint 1
0 1 Setpoint value 2 Setpoint value 2
1 0 Setpoint value 3 Setpoint value 3
1 1 Setpoint value 4 Setpoint value 4

11.4.1 Entered on the device

Signal 1 (Bit 0) setpoint changeover
Setpoint value, Controller 1
W1 and W2 are predefined by the program generator
Setpoint value, con­troller 2
The setpoint values in the parameter level are entered on the device.

11.4.2 Entered using the setup program

The setpoint values are entered in the setup dialog parameter level.
63
11 Parameterization
64
NOTE!
The parameters described in this section can be edited using either the setup program or DI­CON touch. The settings (for example, measured value recording, outputs, Ethernet, and con­troller type) that are required immediately for commissioning in a specific plant and therefore that seldom need to be changed, are set here. Depending on the configuration, signals which are not in use are grayed out. Functions available in both selectors are highlighted in a specific color.

12.1 Analog selection

The analog selector contains all analog signals available in the configuration dialogs of a tree structure in the DICON touch.
All analog signals are shown in the following table. The entry in the "Type" column indicates the source of the signal:
Internal: Internal signal for the DICON touch (including signals from the analog inputs)
External: External input, for example, one that can be transmitted via an interface

12 Configuration

Category Signal Type Description
No function No signal selected
Analog inputs Analog input (IN8) Internal Messwerte der Analogeingänge
1...4
Ö See Chapter 12.5 Analog
inputs IN8, IN9, IN10, IN11 Page: 74
geingangs 1...8
External analog inputs
Analog input (IN9) Analog input (IN10)
Analog input (IN11)
External Analog Inputs 1 ... 8 External Analogwert des externen. Analo-
Ö See Chapter 12.18 External
analog inputs Page: 139
Mathematics Mathematik 1 ... 8 Internal Ergebnis der Mathematikfunktion
1...8
Ö See Chapter 12.15 Mathemat-
ics/logic Page: 134
65
12 Configuration
Category Signal Type Description
Controller 1 Actual value controller 1 Internal
Controller 2 Actual value, Controller 2
Setpoint values Ramp end value, Controller 1 Internal Sollwert für Reglerkanal 1 ... 2
Program setpoints Program setpoint 1, 2 Internal Sollwert für Reglerkanal 1 ... 2
Section end values Abschnittsendwert 1 ... 2 Internal Flags Merker 1 ... 8 Internal Analog value of the analog flag
Service Terminal temperature Internal Measured value (internal Pt100) Sampling rate Sampling rate Internal Measured value, sampling rate
Setpoint value, Controller 1
Controller differential, Control­ler 1
Output level display, Control­ler 1
Output 1, Controller 1
Output 2, Controller 1
Cascade output level, Control­ler 1
Setpoint value, Controller 2
Controller differential, Control­ler 2
Output level display, Control­ler 2
Output 1, Controller 2
Output 2, Controller 2
Cascade output level, Control­ler 2
Setpoint specification, Control­ler 1
Sollwert 1 ... 4 Regler 1 Ramp end value, Controller 2
Setpoint specification, Control­ler 2
Sollwert 1 ... 4 Regler 2
Ö See Chapter 12.6.1 Controller
configuration Page: 78
als Festwertregler
Ö See Chapter 12.6.7 Controller
setpoint values Page: 96
als Programmregler
Ö See Chapter 12.12 Program
controller Page: 120
Ö See Chapter 12.16 Flags/ser-
vice Page: 136

12.2 Digital selector

The digital selector contains all digital signals that are available in the configuration dialogs of a tree structure in the DICON touch.
All the digital signals are shown in the following table. The entry in the "Type" column indicates the source of the signal:
66
12 Configuration
Internal: Internal signal for the DICON touch (including digital input signals)
External: External value is transferred via the interface, for example
Category Signal Type Description
No function No signal selected
Controller 1 1st output, Controller 1 Internal Switching outputs, Controller 1
2nd output, Controller 1
Self-optimization, Control­ler 1
Manual mode, Controller 1
Controller 1, off Controller cycle alarm 1
Output level alarm 1
Controller 2 1st output, Controller 2 Internal Switching outputs, Controller 2
2nd output, Controller 2
Self-optimization, Control­ler 2
Manual mode, Controller 2 Controller 2, off
Controller cycle alarm 2
Output level alarm 2
digital inputs Digitaleingang 1 ... 7 Internal Logic level for connected floating
External digital inputs
Digital controller sig­nals
Limit value outputs Grenzwertausgang 1 ... 16 Internal Logic level of the limit value moni-
Timers Timer output 1 Internal Logic level of the output signals for
Logic output Logikausgang 1 ... 8 Internal Ergebnis der Logikfunktion 1 ... 8
externer Digitaleingang 1 ... 8
Digitalsteuersignale 1 ... 8 Internal Logikpegel der definierten Digital-
Timer end signal 1
Timertoleranceband 1
Timerstopsignal 1 Timer output 2
Timer end signal 2
Timertoleranceband 2 Timerstopsignal 2
External Logic level for the external digital
Logic level "0", function inactive
Logic level "1", function inactive
Ö See Chapter 12.6.1 Controller
configuration Page: 78
Logic level "0", function inactive
Logic level "1", function inactive
Ö See Chapter 12.6.1 Controller
configuration Page: 78
contacts 1to7
Ö See Chapter 12.4 Digital inputs
IN1 to 7 Page: 73
inputs 1to8
Ö See Chapter 12.17 External
digital inputs Page: 138
steuersignale 1 ... 8
Ö See Chapter 12.14 Digital con-
troller signals Page: 131
toring 1to16
Ö See Chapter 12.9 Limit value
monitoring Page: 104
Timer 1, 2
Logic level "0", function inactive
Logic level "1", function inactive
Ö See Chapter 12.13 Timer or
week-time switch Page: 128
Ö See Chapter 12.15 Mathemat-
ics/logic Page: 134
67
12 Configuration
Category Signal Type Description
Ramp signals Rampendsignal 1 Internal Logic level "0", function inactive
Program controller Program end signal Internal
Operating contacts Steuerkontakt 1 ... 8 Internal Logic level of the control contacts,
Flags Digitalmerker 1 ... 8 Internal Logic level of the digital flag
Service Service signal Internal
Function buttons Funktionstaste 1 ... 2 Internal
Analog input alarm MinAlarm IN8 Internal Alarmsignale Min und Max der
Tolerancebandsignal 1
Rampendsignal 2
Tolerancebandsignal 2
Programautosignal
Tolerancebandsignal
Programstopsignal
MaxAlarm IN8
MinAlarm IN9 MaxAlarm IN9
MinAlarm IN10
MaxAlarm IN10 MinAlarm IN11
MaxAlarm IN11
Logic level "1", function inactive
Ö See Chapter 12.6.8 Ramp func-
tion Page: 98
Logic level "0", function inactive
Logic level "1", function inactive
Ö See Chapter 12.12 Program
controller Page: 120
for example in automatic mode.
Ö See Chapter 8.1.5 Operating
contacts Page: 49
Ö See Chapter 12.16 Flags/ser-
vice Page: 136
Logic level of the service signal
Ö See Chapter 12.16 Flags/ser-
vice Page: 136
Logic level of the two function but­tons
Ö See Chapter 5.1 Display and
operating concept Page: 36
Analogeingänge 1 ... 4
Ö See Chapter 12.5 Analog
inputs IN8, IN9, IN10, IN11 Page: 74
68
12 Configuration
Category Signal Type Description
Ext. analog entry alarm
Math alarm MinAlarm Math 1 Internal
Digital alarms Digitalalarm 1 ... 7 Internal Alarms for connected floating con-
Ext. digital alarms ext. Digitalalarm 1 ... 8 External Alarms for ext. digital inputs
Digital control alarms Digitalsteueralarm 1 ... 8 Internal Alarme der definierten Digital-
MinAlarm Ext. AE 1 Internal Alarmsignale Min und Max der
ext. Analogeingänge 1 ... 8 MaxAlarm Ext. AE 1
MinAlarm Ext. AE 2
MaxAlarm Ext. AE 2 MinAlarm Ext. AE 3
MaxAlarm Ext. AE 3
MinAlarm Ext. AE 4
MaxAlarm Ext. AE 4 MinAlarm Ext. AE 5
MaxAlarm Ext. AE 5
MinAlarm Ext. AE 6 MaxAlarm Ext. AE 6
MinAlarm Ext. AE 7
MaxAlarm Ext. AE 7 MinAlarm Ext. AE 8
MaxAlarm Ext. AE 8
MaxAlarm Math 1
MinAlarm Math 2
MaxAlarm Math 2 MinAlarm Math 3
MaxAlarm Math 3
MinAlarm Math 4 MaxAlarm Math 4
MinAlarm Math 5
MaxAlarm Math 5 MinAlarm Math 6
MaxAlarm Math 6
MinAlarm Math 7 MaxAlarm Math 7
MinAlarm Math 8
MaxAlarm Math 8
Ö See Chapter 12.18 External
analog inputs Page: 139
Ö See Chapter 12.15 Mathemat-
ics/logic Page: 134
tacts 1to7
Ö See Chapter 12.4 Digital inputs
IN1 to 7 Page: 73
Ö See Chapter 12.17 External
digital inputs Page: 138
steuersignale 1 ... 8
Ö See Chapter 12.14 Digital con-
troller signals Page: 131
69
12 Configuration
Category Signal Type Description
Limit value alarms Grenzwertalarm 1 ... 16 Internal Alarms for the limit value monitor-
Logic alarms Logikalarm 1 ... 8 Internal Alarme der Logikfunktion 1 ... 8
Alarms and internal signals
ing 1to16
Ö See Chapter 12.9 Limit value
monitoring Page: 104
Ö See Chapter 12.15 Mathemat-
ics/logic Page: 134
Collective alarm Internal Collective alarm of the controller is
active, starting with the collective
alarm event to the end of the alarm
(as long as the red alarm line
flashes) Collective alarm acknowl-
edged
Memory alarm Memory alarm limit exceeded
Is active, starting with the collective
alarm event to the acknowledge-
ment of the alarm (as long as the
red bell is illuminated)
Ö See Chapter 12.3 Basic set-
tings Page: 71 Fault
Field bus error Is active if Profibus or PROFINET
report an error
Battery empty Buffer battery must be replaced by
JUMO Service
Pre-alarm battery Back-up battery voltage under
2.6 V
Login Logic level "0", user not logged on
Logic level "1", user logged on
USB inserted Logic level "0" USB not inserted
Logic level "1", USB inserted
Temp. in Fahrenheit Logic level "0", temp. not °F
Logic level "1", temp. in °F
Inside temperature too high Logic level "0", inside temperature
not too high
Logic level "1", inside temperature too high
70

12.3 Basic settings

on the device:
The settings are applicable for the entire device.
Setup dialog box
12 Configuration
Parameter
Parameter Selection/settings Description
Device name Name 20 characters of editable text
National language 1.German 2.English The device can save up to two languages.
Additional languages can only be added using the setup program: E
ONLY > COUNTRY SETTINGS.
DIT > SETUP
Ö Chapter 13.4 "Country settings", Page
151 Language selection after "power on"
& Not selected (empty); no The device starts without language selec-
tion
Selected (); yes The language selection appears
Mains frequency 50 Hz
60 Hz
Temp. of device Deg. Celsius Temperature unit for displaying the tem-
Deg. Fahrenheit
Temp. of interface Deg. Celsius Temperature unit for displaying the tem-
Read out data using: (only setup)
Deg. Fahrenheit Interface Secure recording data using the interface USB
perature in the device
perature values using the interface
Secure recording data on the stick
Ö Chapter 12.11 "Recording", Page 117
Memory alarm limit (in the device)
Setup quick info - Any text may be transferred to the device
0...20%...100% If the enabled memory data recorder does not reach this limit in the device, an alarm will be issued.
during the data transfer.
71
12 Configuration
Parameter Selection/settings Description
Online version vis. (only setup)
Comparison criteria Compatible Setup software<->device software
(setup only) Equal to or greater than Software version
(only setup)
Language selection after power ON
This setting means that language selection appears following "power on", which gives the user the opportunity to select their preferred language.
Standard online visualization Software version of the webserver soft-
No online visualization
Example 333.01.01-13 If relevant, additional versions are listed
Standard software The device software version is available
ware
that can be selected in the version library and can be specifically selected for the software update.
here
Memory alarm limit
If 20 % of the enabled memory is not used during recording, for example, an entry will be made in the alarm list. This enables the user to recover the recording data using the USB stick or the interface (as indicated). The value of the free memory only returns to 100 % when the data has been recovered. If the remaining 20 % is used up, the oldest recorded data is overwritten and replaced with the new data. In this case, there will be a recording gap.
72

12.4 Digital inputs IN1 to 7

Es stehen maximal sieben Digitaleingänge (IN 1 ... 7) zum Anschluss an potenzialfreie Kontak­te mit gemeinsamer Masse zur Verfügung.
Setup dialog box
12 Configuration
Parameter
Parameter Selection/settings Description
Channel name Digital input 01 (15 characters) of editable text that indicates,
Alarm type
Alarm active at Signal level that triggers an alarm or an event. High Contact closed: high (logic "1") (setup only) Low Contact open: low (logic "0")
Alarm text (only setup)
Alarm active at
An alarm is only displayed for as long as the signal level (closed contact) is also selected. If the contact is opened, the alarm entry disappears automatically.
for example, what the signal will be used for.
Off Alert switched off.
Alarm A message will be entered in the alarm list
depending on the signal level that has been set.
Event A message will be entered in the events list
depending on the signal level that has been set.
Alarm Digitaleing. 01 20 characters of editable text which is entered
into the alarm or event list.
Alarm text
The setup program is required to view and edit the texts.
73
12 Configuration

12.5 Analog inputs IN8, IN9, IN10, IN11

Analog inputs IN8 and IN9 are installed by default as universal measuring inputs for RTD tem­perature probes, thermocouples, resistance transmitters/resistance potentiometers, and stan­dard signals. Two additional analog inputs, IN10 and IN11, can be retrofitted.
Setup dialog box
Parameter
Parameter Selection/settings Description
Channel name Analog input IN8, IN9, IN10, IN11 (15 characters) of editable text
Probe Selection of measuring probe for the relevant analog input
No function No sensor selected Res.three-wire RTD temperature probe
in three-wire circuit
Res.two-wire RTD temperature probe
in two-wire circuit
Int. thermocouple Internal thermocouple
Cold-junction temperature
Ext. thermocouple External thermocouple
Cold-junction temperature
Constant thermocouple Constant thermocouple
Cold-junction temperature
Resistance transmitter Resistance transmitter 0 ... 20 mA Standard signal
0 ... 10 V Standard signal
0 ... 1 V Standard signal 0 ... 100 mV Standard signal
4 ... 20 mA Standard signal
2 ... 10 V Standard signal
74
12 Configuration
Parameter Selection/settings Description
Linearization Available options and default settings depend on the measuring probe
selected.
RTD probe Linear
Pt100 DIN EN 60751
Ni100 DIN EN 60751 Pt500 DIN EN 60751
Pt1000 DIN EN 60751
Ni1000
Pt100J JIS 1604 Pt50 GOST 6651-94
Cu50 GOST 6651-94
KTY11-6 Type KTY11-6 Pt100 Gost
Pt50 Gost
Cu100 Gost Cu50 Gost
Thermocouples CRCopel
Fe-CuNi L Gost Cu-CuNi T
Fe-CUNi J
Cu-CuNi U Fe-CuNi L
NICr-Ni K
Pt10Rh-Pt S Pt13Rh-Pt R
Pt30Rh-Pt6Rh B
NiCrSi-NiSi N NiCr-CuNi E
W5Re-W26Re C
W3Re-W25Re D In40-Rh
Pt10Rh-Pt
Customer-spec. 1 Customer-spec. 2
Customer-spec. 3
Customer-spec. 4 Customer-specific linearization with 4th
order polynomial
Unit 5 characters (%) Unit for numerical representation of
measured value
Decimal place XXXXX. No decimal place
XXXX.X 1 decimal place XXX.XX 2 decimal places
XX.XXX 3 decimal places
X.XXXX 4 decimal places
75
12 Configuration
Parameter Selection/settings Description
Measured value off­set
Measured value fac­tor
Filter time constant0 ... 0.6 ... 100 Time constant for adjusting the digital
Start of scaling
Scaling end
Line resistance 0 Ω The line resistance is entered here with
Ext. compensation temperature
Fixed compensation temperature
KTY at 25 °C/77 °F
Resistance measur­ing range
-100 ... 0 ... +100 Parallel translation of all measured val­ues
1,000 Slope
input filter (0 s = filter off)
Default setting depends on sensor and linearization.
-99999 ... +99999 Start value of display range for standard signals
Default setting depends on sensor and linearization.
-99999 ... +99999 End value of display range for standard signals
a two-wire circuit.
No selection -
Analog selection The measurand used to record the cold-
junction temperature is set here.
0 to 50 to 100 °C If the cold junction has a fixed tempera-
ture, this is entered here.
0to2000to10000Ω Basic resistance of a KTY probe at
20 °C
0to400Ω The following measuring ranges are
available for a customer-specific linear-
0to4000Ω
ized resistance measurement
Linearization
Linearization is dependent upon the probe that is connected (measuring probe). The predefined linearizations can be supplemented with customer-specific linearization. Ö Setup program:
S
ETUP ONLY >CUSTOMER-SPECIFIC LINEARIZATION
Measuring value offset, measuring value factor
The value for the measuring value offset provides parallel translation of all measured values and the value for the measuring value factor influences the increase in the values displayed.
Filter Time Constant
The filter time constant is used to adjust the digital input filter (2nd order filter). If the input signal changes suddenly, approx. 26 % of the change is recorded following a period that corresponds to the filter time constant (2× filter time constant: approx. 59 %; 5× filter time constant: approx. 96 %). A large filter time constant means: high attenuation of interference signals, slow reaction to the actual value display, low limit frequency (low-pass filter).
Scaling start, end
The maximum measuring range limits are displayed here, depending on the probe selected and the linearization. These limits only affect the recording. If, for example, the scaling end for a Pt100 is reduced from 850 °C to 400 °C, the recording only displays values up to 400 °C.
76
Line resistance
On connecting a RTD temperature probe in a two-wire circuit, longer lines may lead to measur­ing errors. This value is used to compensate the resistance of the probe line and depends on the line length. Enter the ohmic resistance of the probe line here to achieve the best possible temperature measurement.

12.5.1 Alarms

Limit value monitoring with one or two alarms and various alarm types can be activated for each analog input. In addition, this function is required in order to trigger the collective alarm of the controller module if the event of deviation above or below the measuring range (out of range).
This limit value monitoring is available in addition to the functions described in Chapter 12.9 "Limit value monitoring", Page 104 and is independent of these.
Setup dialog box
12 Configuration
Parameter
Parameter Selection/settings Description
IN 8 Analog input 1, IN9 Analog input 2
Minimum alarm Off Monitoring is not active.
Alarm Alarm results in an entry in the alarm list.
Event Alarm results in an entry in the event list.
Minimum value -99999 ... 0 ... +99999 Limit value at which an alarm is issued. Minimum alarm
text
Maximum alarm Off Monitoring is not active.
Maximum value -99999 ... 0 ... +99999 Limit value at which an alarm is issued.
Maximum alarm text
Underrange AE1 Text which is entered into the alarm or
event list in the event of deviation.
Alarm Alarm results in an entry in the alarm list. Event Alarm results in an entry in the event list.
Overrange AE1 Text which is entered into the alarm or
event list in the event of deviation.
77
12 Configuration

12.6 Controller1, 2

Two controllers (controller channels) are available. The parameters listed here can be config­ured independently of each other for controller 1 to controller 2.

12.6.1 Controller configuration

The controller type, the control direction, the output level for changeover to manual mode and for deviation above or below the measuring range, as well as the output level standardization and the deadband width are specified here.
Setup dialog box
Parameter
78
Parameter Selection/settings
Controller 1, Controller 2
Controller type Off Controller channel is switched off
Two-state controller Controller with a switched output
Three-state controllers Controller with two continuous or switched outputs (for
Modulating controllers Controller with two switched outputs (for motor actuator)
Continuous controller Controller with a continuous output (analog signal) Position controllers Continuous controller with integrated position controller
Control direc­tion
Direct (2) The controller output level is positive if the actual value
Inverse (1) The controller output level is positive if the actual value
1
Description
(default setting for Controller 2)
(default setting for controller 1)
example, for heating/cooling)
(for motor actuator)
is greater than the setpoint value (cooling).
is smaller than the setpoint value (heating).
12 Configuration
Parameter Selection/settings
Manual mode
Y in manual mode Defines the output level (%) that the controller should
Y with error Defines the output level (in %) that the controller should
Y manual mode 0...100%
Y substitute value
Time for manual aver­age value
Time for substi­tute average value
Start of cascade standardization
End of cascade standardization
Deadband (neutral zone)
Additional functions not selected (empty) (setup only) () Expansion 1 Reserved functions for service
1
Bold: default setting
Enabled Manual mode possible on the device
Disabled Manual mode disabled
Y manual mode The value set below for Y manual mode is adopted.
Current value The current controller output level before switching to
Average value The average value calculated using the set time below
Y substitute value The Y substitute value set below is adopted.
Current value The current output level before deviation above or below
Average value The average value calculated using the set time below
0...100%
1 to 3600 min Time for the average value when "Y in manual mode"
1 to 3600 min Time for averaging of values if the "Y with error" average
0....100 % Hier kann der Stellgrad normiert werden (nur für Kas-
0...100 %
0.00...100 % Output level movements within the deadband are sup-
() Expansion 2 () Expansion 3 () Expansion 4
1
Description
adopt after switching to manual mode.
manual mode is adopted.
is adopted.
display, if one of the analog values relevant for the con­troller is invalid (incorrect actual value, setpoint value, output level feedback, etc).
the measuring range is adopted.
is adopted.
average value is set
value is is set
kadenregler).
pressed, for example by noisy signals. The deadband is only effective for controller structures with I-component.
Control direction
Is set inversely by default (1) for heating mode.
79
12 Configuration
(1) (2)
100%
-100%
Y
XW
Deadband
Manual mode
Bei Einstellung gesperrt ist kein Handbetrieb mehr am Gerät möglich. Die Schaltfläche für Handbetrieb ist grau hinterlegt.
Deadband
Default is 0, i.e. no distance between heating and cooling contact.
80

12.6.2 Controller inputs

The analog inputs for the controller are configured in this menu – including the signals for switching off the controller and switching on the parameter block – as well as the parameters for manual mode.
Setup dialog box
12 Configuration
Parameter
Parameter Selection/settings Description
Controller 1, Controller 2
Controller actual value IN8 analog input 1 Analog signal for actual value
Analog selector
Controller setpoint value Setpoint specification for
Controller 1
Analog selector Output level feedback No selection
Manual output level Analog signal for manual output level
Additive variable distur­bance
Multiplicative variable dis­turbance
Analog selection
Analog signal for setpoint value
Analog signal for output level feedback
Analog signal for additive variable distur­bance
Analog signal for multiplicative variable disturbance
81
12 Configuration
Parameter Selection/settings Description
Manual signal/auto-switch­ing
Locking signal for manual mode
Signal 1 Parameter block switching
Signal 2 Parameter block switching
Signal for actual value switching
Controller signal off The controller can be switched to On or
Controller signal on
Actual value switching
Provided that no signal is selected for switching the actual value, the actual values set from the analog selector for the controller configuration are active. If, however, a signal is set for switch­ing the actual value, then the High signal level (logic "1"), is switched to the actual value out­lined in red. Controller 1 is then linked to IN9 (analog input 2) and Controller 2 to IN10 (analog input 3).
No selection
Digital selector
This signal switches between manual mode and automatic mode.
This signal locks manual mode
The parameter blocks entered in the Chapter 11.3 "Controller/parameter blocks", Page 58 are switched using both these signals.
The analog inputs (actual value inputs) are switched using this digital signal.
Off using this signal.
82

12.6.3 Self-optimization controller

Self-optimization (abbreviation: SO) determines the optimum controller parameters for a PI or PID controller.
Setup dialog box
12 Configuration
Parameter
Parameter Selection/settings
Method Oscillation Oscillation method
Step response step response method Lock Enabled Self-optimization can be started on the device
Disabled Self-optimization is disabled
Exit type 1, 2 Automatic Output level is recognized automatically. Relay Output level is displayed using the relay...
Solid state, logic ... using the solid state relay or digital signal...
Analog ... using the analog output.
Standby output 0...100% Output level for step
method
Acquisition of switch­ing period (Cy)
Signal start/stop No selection
Locking signal No selection
1
Bold: default setting
0... 30...100% Output level for step response level
Yes Cy is detected during self-optimization
No Cy is not detected
Digital selector
Digital selector
1
Description
Start/stop signal for self-optimization
Signal for locking self-optimization
Method
The standard method is the oscillation method, whereas the step response method is used specifically in the plastics industry.
83
12 Configuration
With the oscillation method, the output level is set alternately to 100 % and 0 %, which produc­es oscillation of the control variable. With the step response method, a step of a specified size is made from the standby output. In both cases, the controller determines the optimum control­ler parameters from the response of the actual value.
Ö See description of the oscillation method or step response method on the following pages.
Exit type 1, 2
The cycle time is calculated on the basis of the type of controller output.
Optimized controller parameters
With both self-optimization methods, certain parameters are optimized according to the config­ured controller type and configured parameters. The controller structure is derived from the type of the optimized parameters: Proportional band Xp (P component), derivative time Tv (D component), and reset time Tn (I component).
The cycle time Cy and the filter time constant dF are also optimized.
Configured con­troller type
Two-state control­ler
Three-state con­trollers
Modulating con­trollers
Continuous con­troller
Position control­lers
Configured parameter Optimized parameter Optimized
controller structure
Xp1 = any; Tv1 = 0; Tn1 > 0
All other settings Xp1, Tv1, Tn1 Cy1, dF PID
Xp1 = Xp2 = any; Tv1 = 0; Tn1 > 0
All other settings Xp1, Xp2, Tv1, Tn1, Cy1, Cy2, dF PID
Xp1 = any; Tv1 = 0; Tn1 > 0
All other settings Xp1, Tv1, Tn1, dF PID
Xp1 = any; Tv1 = 0; Tn1 > 0
All other settings Xp1, Tv1, Tn1, dF PID
Xp1 = any; Tv1 = 0; Tn1 > 0
All other settings Xp1, Tv1, Tn1, dF PID
Xp1, Tn1, Cy1, dF PI
Xp1, Xp2, Tn1, Cy1, Cy2, dF PI
Xp1, Tn1, dF PI
Xp1, Tn1, dF PI
Xp1, Tn1, dF PI
For first-order control paths, the parameters required for the PI controller structure are opti­mized, independently of the configured parameters.
Error handling
If the actual value deviates above or below the measuring range during self-optimization, self­optimization is aborted. In this case, the configured parameters are not changed.
WARNING!
During self-optimization according to the oscillation method, output level limits Y1 and Y2 are not active for switched outputs or solid state outputs. The output level may exceed or fall below the set limits. It must be ensured that this does not result in damage to the plant.
84
NOTE!
t
x
w
t1
S
w
x
t1
t
Optimization must be performed under genuine operating conditions and requires a closed control loop, whose actuator influences the actual value(heating controlled by relay output). It can be performed as many times as required.
Start of self-optimization
Self-optimization can be started using any signal from the digital selector. Any other signal from the digital selector can be used to abort (stop) autotuning.
Optimization according to the oscillation method
In the case of a large control deviation between the setpoint value and actual value (for exam­ple, in the startup phase), the controller determines a switching line around which the control variable performs a forced oscillation during self-optimization. The switching line is determined so that the actual value does not exceed the setpoint value if possible.
In the case of minor control deviation (for example, if the control loop is in a steady state during operation), oscillation is forced around the setpoint value. Here, the setpoint value is exceeded in any case.
The controller automatically chooses between two procedures depending on the extent of the control deviation:
12 Configuration
Self-optimization in during the startup phase Self-optimization during operation
x Actual value w Setpoint value
S Switching line t1 Start of self-optimization
85
12 Configuration
t
y
S
y
t
x
w
t1
t2
t3
}
Dy
{
y
x
y
S
t1
t2
t3
Dy
t
t
w
Optimization according to the step response method
Initially, a configurable standby output is produced until the actual value "settles" to a constant. This is automatically followed by a configurable output level step (step size) to the control path.
Main applications of the step response method:
Optimization immediately after "power on" during startup (considerable time saving, stand­by output setting = 0 %)
Control path does not oscillate easily (for example, extremely well insulated furnace with low losses, long oscillation period)
Actual value must not exceed the setpoint value If the output level is known for the corrected setpoint value, overshooting is prevented with the following setting: Standby output + step size output level in corrected state
The progression of the output level and actual value depends on the status of the process at the point when self-optimization starts:
Self-optimization in during the startup phase
y Output level ΔyStep size
Standby output t1 Start of self-optimization
y
S
x Actual value t2 Point of output level step
w Setpoint value t3 End of self-optimization
Self-optimization during operation
86
Checking the optimization
You can check for optimum adjustment of the controller to the control path by recording the startup process (with "Startup", for example) with a closed control loop. The diagrams below indicate possible incorrect adjustments and correction of these.
Here, the transient behavior of a third-order control path for a PID controller is recorded as an example. The procedure for setting the controller parameters can also be applied to other con­trol paths.
Proportional band Xp too large Reset time Tn and derivative time Tv too short
12 Configuration
Proportional band Xp too small Reset time Tn and derivative time Tv too long
Cycle time Cy too great Optimum setting
87
12 Configuration

12.6.4 Start SO on device

This example describes the start of autotuning for a program controller. The following points must be taken into consideration, checked and, if necessary, adjusted:
Is the appropriate controller type configured?
Check or adjust controller direction.
It must be possible to adequately influence (closed control loop) the actual value, e.g. by a change to the output level in manual mode.
Adjust autotuning setting to the type of outputs.
Before starting autotuning for PID structure, the lead time must not be set to 0.
If the lead time = 0, optimization is for the PI structure.
Is the oscillation method suitable or is it necessary to change to the step response method? (not possible with every controller).
Only for step response methods: meaningful specifications for standby output and step height.
Only for continuous controller: The output function must be configured for the 1st controller output and scaled to 0...100%. This means: Function = 1st controller output, zero point = 0, end value = 100).
Only for three-step controller: determine actuator time and adjust in the parameter level.
Step Activity
1 The device is in the operating loop. Logon as a master from there
2 From the basic status, switch the program controller to manual mode
88
Step Activity
3 Enter program setpoint value for manual mode
4 Return to the controller screen by pressing OK
12 Configuration
5 Click on the symbol at the bottom for the SO and start by pressing OK
6 The symbol on the right-hand side shows that the SO has started
Result: The SO stores the determined control parameters in control parameter block 1.
89
12 Configuration

12.6.5 Control loop monitoring

Control loop monitoring monitors the control response during startup of a plant and in the event of a setpoint value step by analyzing the change of the actual value during an output level change. An alarm is issued if the actual value does not respond according to the specifications.
The alarm signal is available from the digital selector and can be processed further at any time.
Setup dialog box
Parameter
Parameter Selection/settings Description
Function
&
Response time 0 ... 1999 Time period in which the actual value must leave the
Monitoring band 0.0000 ... 1999 Monitoring band width that must leave the actual value
Inactive Control loop monitoring is generally not permitted
Active Control loop monitoring is generally permitted
monitoring band.
"0 s" setting means: Response time = reset time Tn
within the response time
"0" setting means: Monitoring band = 0.5 × proportional band (Xp)
90
Description of the function
y
M
t
y
x
t
T
R
Dx
x
y
t1 t2
Monitoring starts as soon as the maximum output level is produced in heating mode (see ex­ample) or as soon as the minimum output level is produced in cooling mode. Starting from this point, the actual value must leave the monitoring band – the range around the current value at the start of monitoring – within the response time. If it is not, an alarm is triggered.
On leaving the monitoring band, the actual value at the time is used as a reference value for a new monitoring band. The response time starts over.
Monitoring ends as soon as the maximum or minimum output level is no longer produced.
12 Configuration
x Actual value Δx Monitoring band
y Output level y
t1 Start of monitoring T t2 End of monitoring
Max. output level (for example, 100 %)
M
Response time
R
91
12 Configuration
t
t
x
y
Dx
x
y
M
y
T
R
T
A
t1
t2
If the actual value does not leave the monitoring band within this timeframe, an alarm signal is generated. The alarm signal is maintained for as long as the maximum or minimum output level is produced and the actual value is within the monitoring band.
x Actual value Δx Monitoring band y Output level y
t1 Start of monitoring T
Alarm period t2 End of monitoring
T
A
Max. output level (for example, 100 %)
M
Response time
R
An alarm may be caused by:
Partial or total failure of heating elements or other parts in the control loop
Reversal of the control direction (for example, "cooling" instead of "heating")
92

12.6.6 Output level monitoring

Output level monitoring monitors the output level in the corrected state. The output level must be within a definable range around a mean output level. If it is not, an alarm is issued.
The alarm signal is available from the digital selector and can be processed further at any time.
Setup dialog box
12 Configuration
Parameter
Parameter Selection/settings Description
Lock Inactive Output level monitoring generally not permitted
Active Output level monitoring generally not permitted Determination time 0 s ... 350 s ... 9999 s Calculation time for the mean output level
Output level band 0 % ... 10 % ... 100 % Monitored output level band (admissible range
around the mean output level)
Alarm delay 0 s ... 9999 s Delay time for alarm triggering Controller differential
band
0 ... 1 ... 1999 Controller differential band (admissible range
around the actual value in corrected state)
93
12 Configuration
y
x
t
t
T
D
T
A
Dy
Dx
Description of the function
Once the output level monitoring has been activated, determination of the mean output level starts as soon as the actual value is within the controller differential band. When the mean out­put level has been determined, the current output level must be within the monitored output lev­el band. If it is not, an alarm is triggered.
In the event of a setpoint value change, the output level monitoring is temporarily deactivated until the actual value returns to the control differential band. The mean output level is then de­termined again.
x Actual value Δx Controller differential band y Output level Δy Monitored output level band
Alarm delay TAAlarm period
T
D
Application examples:
Monitoring of signs of aging and faults on heating elements
Reporting of faults during operation
Functional limitations
Output level monitoring is not active in the following cases:
Proportional band Xp = 0
Self-optimization active
Manual mode
Ramp function active
Controller operating as program controller
Modulating controller without output level feedback (or output level feedback in "out of range" state)
Position controller with output level feedback in "out of range" status
94
Parameter dimensioning
w
t
t
0.5 x Tn
y
x
Dx
Dy
T
C
y
A
Appropriate dimensioning of parameters used for determining the mean output level is required for the output level monitoring to function correctly.
The controller differential band around the actual value defines the corrected state. It should be dimensioned so that it is adhered to during normal operation. The progression of the actual value can, for example, be recorded with the recording function on the device or with the startup function of the setup program. Determination of the mean output level starts when the actual value enters the control differential band. Calculation of the mean output level starts over if there is temporary deviation from the control differential band during output level determination or if the setpoint value is changed by more than 0.5 × control differential band Δx.
An average output level is calculated over the determination time by a sliding average. The time selected should be sufficiently long to ensure as accurate a calculation as possible. A wait­ing time of 0.5 × reset time Tn is connected to the determination time, during which time the actual value and output level are checked to see if they are within in the specified limits. If the limits are exceeded, the calculation will restart. Once the calculation is successful, the output level monitoring will be activated.
12 Configuration
x Actual value w Setpoint value
y Output level y
Determination time rt Reset time
T
C
Δy Output level band Δx Controller differential band
Average output level
A
95
12 Configuration

12.6.7 Controller setpoint values

With this separate setpoint value function, the setpoint values and the ramp function can be configured flexibly for both controller channels (Controller 1 to 2).
Up to four setpoint values are available for each controller channel and can be switched using two digital signals.
The analog signal for the setpoint specification (external setpoint value 1 to 2) is selected from the analog selector. This signal can be impinged by a correction value (setpoint value 1 to 4). If no analog signal is selected (inactive), the correction values serves as the fixed setpoint val­ue.
NOTE!
The active setpoint value is not automatically used as a setpoint value for the controller chan­nel; it must first be assigned in the controller configuration (see Chapter 12.6.2 "Controller inputs", Page 81).
NOTE!
If an analog signal is used as a setpoint value without a correction value, it can also be directly assigned in the controller configuration. In this case, setpoint value limitation, setpoint changeover, and the ramp function are not available. Equally, a fixed setpoint value can be assigned directly in the controller configuration (see Chapter 12.6.2 "Controller inputs", Page 81).
Setup dialog box
Parameter
Parameter Selection/settings Description
Signal for ext. setpoint value
External setpoint value No offset There is no ext. setpoint offset
No function Signal source for ext. setpoint value.
Analog selection
Offset The external setpoint value is added to the
internal setpoint value of the fixed setpoint controller or program controller.
96
12 Configuration
Parameter Selection/settings Description
Program setpoint value Program setpoint value 1 The source for the program setpoint value is Program setpoint value 2
Set point 1 ... 4 start -99999 ... +99999 Setpoint limit start
Set point 1 ... 4 end -99999 ... +99999 Setpoint limit end
Boost function No function Boost function switched off & Delta value Setpoint value is increased by a Delta value.
Percentage value Setpoint value is increased by a percentage
Boost value 0.0000..99999 Amount by which the setpoint value is
Boost signal No selection -
Digital selector The boost function is switched on using this
Boost duration 0...999 Duration of boost period (in s)
Signal 1 setpoint change­over
Signal 2 setpoint change­over
No selection
Digital selector
selected here for the active program control­ler.
value.
increased (in K or % by the setpoint value)
signal.
Signal 1 is selected here for the setpoint changeover for the fixed-setpoint controller.
Signal 2 is selected here for the fixed-setpoint changeover
Program setpoint value
This setting is only available if the program controller is configured. The setpoint values can then be read off the program curves that are entered.
Boost function
The boost function is used to release tools in the plastics industry during the production pro­cess. The setpoint values for all heating zones are thereby increased by a specific Delta or per­centage value for a specific time period.
Setpoint changeover
The setpoint values 1 to 4 for both fixed-setpoint controllers are located in the parameter level and can be entered as follows:
Ö Chapter 11.4 "Setpoint values", Page 62 Switching can be performed using digital signals from the digital selector.
Signal 2 (Bit 1) setpoint changeover
0 0 Setpoint value 1 Setpoint value 1
0 1 Setpoint value 2 Setpoint value 2
1 0 Setpoint value 3 Setpoint value 3 1 1 Setpoint value 4 Setpoint value 4
Signal 1 (Bit 0) setpoint changeover
Active setpoint value, Con­troller 1
Active setpoint value, Con­troller 2
97
12 Configuration

12.6.8 Ramp function

The ramp function enables the setpoint value to be continually changed up to the ramp end value (active setpoint value).
A tolerance band can be set around the setpoint value curve to monitor the actual value. If the actual value deviates from the tolerance band, a digital signal (tolerance band signal) is acti­vated.
Setup dialog box
Parameter
Parameter Selection/settings Description
Ramp function
Positive gradient
Negative gradient
Tolerance band
Signal for ramp stop
Signal for ramp off No selection The ramp can be switched off with this
Ramp off
Ramp in minutes
Ramp in hours
Ramp in days
0.00...999.00 In the event of a setpoint value step, the
0.00...999.00 In the event of a setpoint value step, the
0.00...999.00 The tolerance band monitors deviation of
No selection The ramp can be stopped with this signal
Digital selector
Digital selector
Ramp function switched off
Ramp function switched on
ramp rises depending on the time unit that has been set.
ramp declines depending on the time unit that has been set.
the actual value from the current setpoint value (tolerance band = admissible devi­ation)
(see t4 in image)
signal
98
Parameter Selection/settings Description
t1
(1) (2)
w1
J
w2
t2 t3 t4 t5 t6 t
w
t
(1)
w1
w2
(2)
Restart signal No selection The ramp can be restarted with this sig-
Signal actual value input
Additional func­tions (only setup)
Ramp function
This function creates a ramp-like setpoint curve out of a step-like setpoint curve, where the ris­ing and declining slopes can have different gradients.
12 Configuration
Digital selector
Analog selector/Controller 1 This actual value is monitored by the tol-
Actual value controller 1
0.00...999.00 Reserved functions for service
nal
erance band
t1 Power ON (1) Setpoint value
t2...t3 Power failure, manual mode, probe break (2) Actual value
t3 Ramp start at current value
t4 to t5Ramp stop by digital input t6 Setpoint changeover to w2
Tolerance band function
For a program controller/generator and ramp function, a tolerance band can be laid to monitor the actual value of the setpoint value curve. If the upper and lower limits are exceeded, a tol­erance band signal is triggered, which can be processed further internally or issued via an out­put.
(1) Tolerance band (2) Ramp
99
12 Configuration

12.7 Digital outputs

Depending on how the expansion slots have been equipped, two fixed digital outputs called OUT1 and OUT2 and 10 additional digital outputs (OUT3/4 to OUT11/12) are available.
Setup dialog box
Parameter
Parameter Selection/settings Description
Description Relay [OUT 1] (15 characters) editable text
For example, for the signal that is issued via the digital output.
Signal source Digital selector/controller This signal is issued at the digital output.
1st output, Controller 1
Inversion No Switching behavior remains unchanged
Yes Inverts the switching behavior
Manual mode Not permitted
Permitted Digital output can be edited in manual
mode.
Description Relay [OUT 2] Signal designation issued via the digital
output.
Inactive = output inactive
Signal source Digital selector/controller This signal is issued at the digital output.
2nd output, Controller 1
Inversion No Switching behavior remains unchanged
Yes Inverts the switching behavior
Manual mode Not permitted
Permitted Digital output can be edited in manual
mode.
100
Loading...