Please read this operating manual before commissioning the instrument. Keep the manual in a
E
place which is accessible to all users at all times.
Your comments are appreciated and may help us in improving this manual.
All necessary settings are described in this operating manual. Manipulations not described in the
manual or expressly forbidden will jeopardize your warranty rights. Please contact the nearest subsidiary or the head office, should you encounter problems.
When accessing the inner parts of the unit and returning modules, assemblies or components,
please observe the regulations accordings to EN 61340-5-1 and EN 61340-5-2 „Protection of
electrostatic sensitive devices“. Only use ESD packaging for transport.
Please note that we cannot accept any liability for damage caused by ESD.
This series of universal, freely configurable profile controllers/profile generators is available in the formats 96mm x 96mm and 96mm x 48mm (portrait
and landscape format). The instruments feature two 4-digit 7-segment displays, five or eight LEDs for indicating the switching status and the operating
modes, an 8-digit matrix display, as well as six keys for operation and configuration.
The user has flexibility in assigning the instrument slots, in accordance with
the block structure.
10 profile programs with up to 100 segments can be programmed; a total of
100 segments can be implemented.
Additional functions include self-optimisation, parameter set switching, a realtime clock, up to eight limit comparators and a maximum of eight operating
contacts. Linearisation for the usual transducers are stored in the memory,
and a customized linearisation table can be programmed. The instruments can
be adapted to the most diverse tasks with the aid of a maths module. The instruments can be integrated into a data network via a serial interface, or they
can be expanded through an external relay module. A setup program with a
program editor is available for easy configuration from a PC.
1 Introduction
The electrical connection is at the rear by screw terminals.
1.2Block structure
7
1 Introduction
1.3Typographical conventions
1.3.1 Warning signs
1.3.2 Note signs
V
E
H ActionThis sign refers to an action to be performed.
The signs for Danger and Warning are used
in this manual under the following conditions:
DangerThis sign is used when there may be danger
to personnel if the instructions are disregard-
ed or not followed accurately.
WarningThis sign is used when there may be damage
to equipment or data if the instructions are
disregarded or not followed accurately.
WarningThis sign is used when special care must be
taken when handling components that are
sensitive to electrostatic discharges.
NoteThis symbol is used when your attention is
drawn to a specific remark.
ReferenceThis sign refers to additional information in
other manuals, chapters or sections.
The individual steps are marked by this
asterisk, e. g.:
h Press I key
1.3.3 Presentation
E + IKey combination The depiction of keys together with a plus
sign means that first the E key has to be
pressed and held down, and then a further
key is pressed.
CONFIG 1Dot-matrix display Tex ts a nd m es sa ge s a re vi sualised in the dot-
matrix display.
8
2.1Type designation
703580/ 0––––/,
Format 96 mm x 96mm
703585/–0 0 –0 0 0 ––/,
Format 48 mm x 96 mm and 96mm x 48mm
2 Identifying the instrument version
(1)(2)(3)(4)(5)(6)(7)
(1) Basic type extension
Format:
96mm x 96mm0
48mm x 96mm portrait1
96mm x 48mm landscape2
Version:
Standard with factory default
settings8
Customized programming9
Language for instrument texts:
German1
English2
French3
for 2-wire transmitter6 6 6 6 6 6
Tw o l og i c i np u ts7 7 7 - - -
1111
(5) Interface
not assigned0 0
RS422/4855 4
PROFIBUS-DP
(no GL approval)
(6) Maths and logic module
not available0 0
available0 3
(7) Approvals
DIN EN 14597
Germanischer Lloyd (GL)
DIN EN 14597 and GL
DIN EN 14597 and UL
GL and UL
DIN EN 14597, GL and UL
* Type 703580 only
Delivery package
*
*
*
*
*
*
64
056
062
063
064
065
066
-Profile controller/generator
-2 mounting brackets
-seal
-Operating Manual B 703580
(4) Supply
110 — 240V AC +10/-15%
48 — 63Hz
20 — 30V AC/DC 48 — 63Hz 2235
9
2 Identifying the instrument version
2.2Accessories
External relay module ER8 (3A/230V)
Supply 110 — 240V AC
Part no. 00405292
(no GL approval)
External relay module ER8 (3A/230V)
Supply 20 — 53V DC/AC
Part no. 00405297
(no GL approval)
External logic module EL8 (0/12V)
Supply 110 — 240V AC
Part no. 00439131
(no GL approval)
External logic module EL8 (0/12V)
Supply 20 — 53V DC/AC
Part no. 00471459
(no GL approval)
PC interface for setup program
with USB/TTL converter, 2 adapters (socket, pins)
Part no. 00456352
Setup program and program editor for
Windows
Part no. setup program: 00379085
Part no. program editor: 00379547
Hardware requirements:
- 512 Mbyte RAM
- 50 Mbyte available on hard disk
- CD-ROM drive
- 1 free serial interface or USB interface
®
NT4.0/2000/XP/Vista/7 (32/64 bit)
10
3.1Location and climatic conditions
Setup plug
panel cut-out to
IEC 61554
The conditions at the instrument location must conform to the requirements listed under Technical data. The ambient temperature at the location should be between –5 and 55 °C, at a relative humidity of not more
than 95%.
3.2Dimensions
3.2.1 Type 703580/0...
3 Installation
11
3 Installation
Setup plug
panel cut-out to
IEC 61554
Setup
plug
panel cut-out to
IEC 61554
3.2.2 Type 703585/1...
3.2.3 Type 703585/2...
12
3.3Edge-to-edge mounting
Ty peh or i zo n ta lv er t ic a l
without setup plug:
703580/0...
the rear of the panel into the guides
at the sides of the housing.
The flat sides of the brackets must
be against the housing.
h Place the brackets against the rear
of the panel and tighten them evenly
with a screwdriver.
3.5Cleaning the front panel
The front panel can be cleaned with the usual rinsing and cleaning agents. It
has a limited resistance to organic solvents (e. g. methylated spirits, white spirit, P1, xylol, etc.). Do not use high-pressure cleaning equipment.
13
3 Installation
3.6Removing the controller chassis
The controller chassis can be removed from the housing for servicing.
h Press together the ribbed surfaces
top and bottom (or left and right with
the landscape format) and pull out
the controller chassis.
When inserting the controller chassis, care must be taken that the lugs
(underneath the ribbed surfaces) snap into position.
14
4.1Installation notes
❑ The choice of cable, the installation and the electrical connection of the in-
strument must meet the requirements of VDE 0100 “Regulations on the installation of power circuits with nominal voltages below 1000 V” or the appropriate local regulations.
❑ The electrical connection must only be carried out by qualfied personnel.
❑ The instrument shall be operated by mains protected with a branch circuitry
overcurrent protection device not more than 20 Amps.
For servicing/repairing a Disconnecting Device shall be provided to disconnect all conductors.
❑ A current-limiting resistor interrupts the supply circuit in the event of a short
circuit. The load circuit must be fused for the maximum relay current to prevent welding of the output relay contacts in the event of a short circuit.
❑ Electromagnetic compatibility conforms to the standards and regulations
specified under Technical Data.
❑ Input, output and supply lines should be run separately, not parallel to one
another.
4 Electrical connection
❑ All input and output cables without connection to the mains supply must be
arranged as twisted and screened cables. Earth the screen at one end at
the instrument terminal TE.
❑ Earth the instrument at terminal TE to the earth conductor. This line must
have at least the same cross-section as the supply lines. Earth lines should
be run in a star layout to a common earth point which is connected to the
earth conductor of the supply. Do not loop the earth connections, i. e. do
not run them from one instrument to another.
❑ Do not connect any additional loads to the supply terminals of the instru-
ment.
❑ The instrument is not suitable for installation in hazardous areas.
❑ Apart from faulty installation, there is a possibility of interference or damage
of controlled processes due to incorrect settings on the controller (setpoint,
data of parameter and configuration levels, internal adjustments). Safety
devices independent of the controller, such as overpressure valves or
temperature limiters/monitors, should always be provided and should be
capable of adjustment only by specialist personnel. Please refer to the
appropriate safety regulations in this connection. Since adaptation (selfoptimisation) cannot be expected to handle all possible control loops, there
is a theoretical possibility of unstable parameter settings. The resulting
process value should therefore be monitored for its stability.
❑ The maximum permitted voltage difference between the inputs of the con-
troller and TE is 30 V AC or 50 V DC.
15
4 Electrical connection
+
–
+
–
+
–
+
–
+
+
–
–
ϑ
ϑ
ϑ
ϑ
ϑ
ϑ
ϑ
ϑ
11109874321
S
EA
S
EA
1
Thermocouples
Logic inputs 1+2Analogue input 2Analogue input 1
Resistance
thermometer
(3-wire)
Resistance
thermometer
(2-wire)
Voltage
0/2—10V
Current
0/4—20mA
Potentiometer
BE1
BE2
V
The electrical connection must only be
made by suitably qualified personnel
The instrument version can be identified
by the type code.
PROFIBUS-DP:
v Interface Description B 703560.2.3
When a thermocouple with internal temperature compensation is wired up to the analogue inputs 1, 3 or 4, no Pt500, Pt1000 or KTY must be connected to analogue input 2.
v Section 12 “Retrofitting of cards”
Additional analogue input signals
SignalConnection like
0—1V0—10V
-1to +1V0 — 10V
-10 to +10V0 — 10V
0—100mVthermocouple
-100 to +100mVthermocouple
4.2Connection diagrams
4.2.1 Type 703580
16
+
–
+
–
+
–
ϑ
ϑ
ϑ
ϑ
12111054321
S
EA
RxD
(+)
RxD
()–
TxD
(+)
RxD/
TxD
(+)
TxD
()–
RxD/
TxD
()–
GND
GND
RS422
RS485/ER8
2
Thermocouples
Interface
Analogue input 3
(option)
Resistance
thermometer
(3-wire)
Resistance
thermometer
(2-wire)
Voltage
0/2—10V
Current
0/4—20mA
Potentiometer
B
A
GND
PROFIBUS DP
+5 V
20 mA
+–
+
–
+
–
ϑ
ϑ
ϑ
ϑ
121110876321
S
EA
3
Thermocouples
* Supply for
2-wire transmitter (22V)
Output 6
(Slot 6)
Output 5
(Slot 5)
Analogue input 4
(option)
Resistance
thermometer
(3-wire)
Resistance
thermometer
(2-wire)
Voltage
0/2—10V
Current
0/4—20mA
Potentiometer
+
+
–
–
i
i
+
+
–
–
u
u
+
+
–
–
230V/3A
230V/3A
5V(22V)/30mA*
5V(22V)/30mA*
230V/1A
230V/1A
-10/0/2—10V
-10/0/2—10V
-20/0/4—20mA
-20/0/4—20mA
The output must be configured accordingly.
v Section 10.4 “Outputs”
v Section 12 “Retrofitting of cards”
Additional analogue input signals
SignalConnection like
0—1V0—10V
-1 to +1V0 — 10V
-10 to +10V0 — 10V
0—100mVthermocouple
-100 to +100mVthermocouple
Earth the screen for the
interface cable at one
end only to TE.
A
B
Contact protection circuit for the relay outputs:
56Ω/15 nF between common-make/common-break
Typ e 70 35 80
4 Electrical connection
17
4 Electrical connection
TENL1321
5
+
–
i
+
–
u
+
–
230V/3A
Logic inputs 3+4
(Slot 1)
Mains supply
Output 1
(Slot 1)
5V(22V)/30mA*
230V/1A
* Supply for
2-wire transmitter (22V)
-10/0/2—10V
-20/0/4—20mA
20—30V
AC/DC
!
!
AC
110—240V
+
–
BE3
BE4
The output must be configured accordingly
v Section 10.4 “Outputs”
Type 70358 0
Contact protection circuit for the relay outputs:
56Ω/15 nF between common-make/common-break
18
4 Electrical connection
V
The electrical connection must only be
made by suitably qualified personnel.
The instrument version can be identified
by the type code.
* Supply for 2-wire
transmitter
The output must be configured accordingly.
v Section 10.4 “Outputs”
Earth the screen for the
interface cable at one
end only to TE.
B
A
Contact protection circuit for the relay outputs:
56Ω/15 nF between common-make/common-break
PROFIBUS-DP:
v Interface Description B 703560.2.3
4.2.2 Type 703585 (portrait and landscape format)
19
4 Electrical connection
+
–
+
–
+
–
+
–
+
+
–
–
ϑ
ϑ
ϑ
ϑ
ϑ
ϑ
ϑ
ϑ
11109874321
S
EA
S
EA
6
Thermocouples
Logic inputs 1+2Analogue input 2Analogue input 1
Resistance
thermometer
(3-wire)
Resistance
thermometer
(2-wire)
Voltage
0/2 10V
Current
0/4 20mA
Potentiometer
BE1
BE2
When a thermocouple with internal temperature compensation is wired up to analogue
input 1, no Pt500, Pt1000 or KTY must be connected to analogue input 2.
v Section 12 “Retrofitting of cards”
Additional analogue input signals
SignalConnection like
0—1V0—10V
-1to +1V0 — 10 V
-10 to +10 V0 — 10V
0—100mVthermocouple
-100 to +100mVthermocouple
* Supply for
2-wire transmitter
The output must be configured
accordingly.
v Section 10.4 “Outputs”
Contact protection circuit for the relay outputs:
56Ω/15nF between common-make/common-break
Type 703585
20
4.3Isolation
(Type 703580 only)
(Type 703580 only)
4 Electrical connection
For Type 703580 and Type 703585
21
4 Electrical connection
22
5.1Displays and keys
(1)
(2)
(3)
(4)
(5)
(6)
Ty peH ei gh t
70358013mm
70358510mm
Ty peH ei gh t
70358010mm
7035857mm
5 Operation
(1) configurable
7-segment display (display 1)
factory setting: process value
(2) configurable
7-segment display (display 2)
factory setting: setpoint
(3) configurable dot-matrix display
(display 3)
8-digit, green
factory setting:
profile program/segment number
1. no display for analogue outputs.
v Section 10.7 “Display”
(4) Setup interface
Position depending on model;
see dimensional drawings
v Section 3.2 “Dimensions”
(5) Status indicators
6 (3) yellow LEDs for the status
indication of the outputs
2 green LEDs to display the
operating modes “Manual”
and “Automatic”
(6) Keys
(see below)
1
Key designation
Keys from left to right:
PGM for programming
Exit/Hand for programming and for manual mode
Automaticto start programs
Decrement to decrease parameter values
Incrementto increase parameter values
Enterfor programming and display switching
1
1. In the description below the key is shown according to its function ( X or M ).
23
5 Operation
5.2Operating modes and states
Operating mode/
state
Basic statusThe displays represent the values according to
AutomaticProfile program is running.
ManualProcess variables (e. g. operating contacts) are
Program stopCurrent profile program is stopped.
StandstillCondition after supply failure when configured
DisplayNotes
the display configuration.
v Section 10.7 “Display”
factory setting:- process value
The active parameter set is indicated by an
additional decimal point.
v Chapter 9 “Parameter level”
v Chapter 6 “Profile program start”
being modified by hand.
v Section 5.5.2 “Manual operating mode”
v Section “Holding the profile program”
accordingly.
v Section 10.5 “Profile controller”
- setpoint of basic status
- text
BASIC ST
h Continue profile program with
or
h cancel profile program with
Self-optimisationSelf-optimisation is running.
v Section 11.1 “Self-optimisation”
Alarm messages-v Section 15.2 “Alarm messages and display
priorities”
- LED is off; - LED is on
A
E
24
5.3Principle of operation
■ = factory setting
Basic statusInitial status.
5 Operation
Profile program
start
Profile program
editor
Operating levelThis level is available for programming
Parameter
level
Configuration
level 1
Configuration
level 2
Profile programs are selected here,
and the instant of start as well as the
start conditions are defined.
Profile programs are created here.
setpoints, displaying process variables, altering system states and setting the time.
The profile controller is adapted to the
control loop with the aid of the parameters in this level.
This level is available for adapting the
profile controller to the control task.
The software version and the hardware
specifications of the profile controller
are indicated here.
ServiceOnly accessible to service personnel.
Time-outIf no key is pressed during a config-
urable period (factory-set: 30sec),
then the profile controller will automatically return to basic status.
Code requestIn order to access some levels, a code
has to be entered first. The codes can
be altered via the setup program.
Codes are entered digit by digit.
h Enter the digit with
h Step on to the next digit with E
I and D
25
5 Operation
(return to basic status)
■ = factory setting
Levels and
menus
Each level is divided into menus, thus creating a tree structure which has a selection or a value input at the end of each branch.
5.4Entering values and selecting settings
Value inputh Increase parameter value with I
Shifting the
decimal point
h Decrease parameter value with
The longer the key is pressed, the more quickly the value changes. Approx.
1sec after releasing the key, the entry is accepted automatically (display flashes briefly).
Parameters can be altered within their value range or within the maximum values that can be displayed (e. g. 2 decimal places: -99.99 to +99.99).
h Increase the decimal places with
D
E + I
h Decrease the decimal places with
E + D (last digit must be 0)
26
5 Operation
Code and time
input
Selectionh Step upwards in the selection list
Time inputs and codes are entered digit by digit.
h Increase or decrease value (digit)
with
I and D
h Confirm entry and select next
digit with
All digits must be confirmed with E.
The value is accepted automatically
when the last digit is entered.
with
h Step downwards in the selection list
with
The selection will be automatically
accepted after approx. 1 sec.
E
I
D
5.5Operating modes
The setpoint is provided through the menu “System state” (operating level) in
the active operating mode (basic status, manual operating mode, automatic
operating mode.
5.5.1 Basic status
Ex-factory, the controller is switched off (inactive) in basic status. No setpoint
input is possible.
The controller can be activated for the “basic status” operating mode via the
setup program. Only then can the setpoint be input.
27
5 Operation
System state
5.5.2 Manual operating mode
For start-up and testing, a setpoint, the states of the operating contacts and
the active parameter set can be input manually.
Operating levelThe settings can be made at the operating level, under the menu item “System
states”.
Setpoint of
manual mode
Operating contact
1—8
Parameter set
OPERATNG ➔ SYSSTATE
ParameterValue/
selection
➔ SETPOINT 0.
➔
OPCNTCT1 ON
OFF
➔
PARA.SET 1
Description
lower setpoint limit
… upper setpoint limit
ON
OFF
1—2
28
5.5.3 Automatic operating mode (program run)
Example:
(Display is configurable!)
5 Operation
Starting the
profile program
Altering the
segment setpoint in current
profile program
The profile program is started with the program no. that was selected under
Program start➜Program number.
h Start program with
h Cancel current program with A
A program can also be selected, started and cancelled via the logic functions.
The logic function “Program selection” has priority over the settings at the
“Program start” level.
During a program run (automatic
mode), the segment setpoint of the
subsequent segment can be altered
while the program is running.
h Alter the next segment setpoint
with
I and D
The segment setpoint is altered temporarily, which means that when the program is restarted, the alteration will be
lost.
a - Setpoint profile on alteration
in the current segment
A
Change of
segment
Holding the
profile program
b - Setpoint profile on restart,
after a supply failure or with
repeat cycles
By pressing the key combination for
segment change, the program continues at the start of the subsequent segment.
h Step on to the next segment with
P + D
or via the logic function
The current program can be held by changing over to the “Program stop”
state.
h Hold program with
h Continue program with X
or via the logic function
M
29
5 Operation
5.6Shifting the setpoint
Shifting the
profile
Relevant
settings
Using the “external setpoint with correction” function, the profile can be shifted upwards or downwards by the amount of the analogue input.
The external setpoint is provided via one analogue input or through mathematics.
Configuration level 1 r Controller r Controller inputs
Configuration level 1 r Inputs r Analogue input 1—4
Configuration level 1 r Maths/Logic r Mathematics 1+2
5.7Altering setpoints
In each operating mode, the setpoint can also be altered directly from the
keys.
Example:
h Alter setpoint in the manual mode
with I and D ;
shift decimal point with
E + I und E + D
(The entry is documented in the
matrix display)
30
5.8Setpoint switching
If setpoint switching has been programmed, the active setpoint is modified
from the keys.
Setpoint inputs via the interface have priority.
5 Operation
Predefined
external
setpoint
Relevant
settings
When predefining an external setpoint, setpoint switching takes place as
shown in the diagram below:
Operating level r Setpoints
Operating level r System state r Setpoint
Configuration level 1 r Controller r Controller inputs
Configuration level 1 r Controller r Setpoint limits
Configuration level 1 r Logic functions
31
5 Operation
Display 1: Process value
Display 2: Setpoint
Display 3: Program status
Display 1: Process value
Display 2: Setpoint
Display 3: Residual program
run-time
Configuration 1
Configuration 2
Example
5.9Display switching
Tw o d is p la y co nf ig ur ati on s ca n be d ef in ed w hi ch d et er mi ne t he d is pl a y o f va lues and process variables on the 7-segment displays and the dot-matrix display.
The presentation in the dot-matrix display is only active in automatic mode.
h Switch display with E
or automatic changeover after an adjustable time period.
Display switching can be de-activated.
Relevant
settings
32
Configuration level 1 r Display r Configuration 1+2
Configuration level 1 r Display r Automatic display changeover
6.1Instant start of program
The program is started with the program no. that was selected under Program
start➜Program number.
6 Profile program start
h Start program with
h Cancel current program with A
A program can also be selected, started and cancelled via the logic functions.
The logic function “program selection” has priority over the settings at the
“program start” level.
6.2Delayed start of program
Tw o op ti on s a re a va il ab le f or s t ar ti ng a p ro gr am a t a sp ec if i c t im e:
Real-time clock
active
Real-time clock
inactive
1. With active real-time clock, by entering the start time and start day.
2. With inactive real-time clock, by entering the delay time.
v Chapter 8 “Operating level”
The settings are reset to their normal values after the start of the program.
A
Start/Cancel
delay of
program start
Program number
Start time
Start day
Delay time
Start segment
Residual segment
time
h Start program delay-time with
h Cancel program delay-time with A
The LED associated with automatic
operation blinks.
A
PGMSTART
ParameterValue/selectionDescription
➔
PROG.NO. 1.
➔
START00:00:00
➔
STARTDAY SO
➔
DLYTIME00:00:00
➔
STARTSEG 1.
➔
RESIDSEG 00:00:00
Factory settings are shown bold.
1—10
00:00:00—23:59:59
SO—SA
00:00:00—23:59:59
1—100
Segment number at which
a start is made
00:00:00—23:59:59
Residual run-time of the
start segment
33
6 Profile program start
34
7.1General
7 Profile program editor
10 profile programs with up to 100 segments can be programmed; a total of
100 segments can be implemented.
Profile programs are defined by programming setpoints and segment times or
gradients segment by segment.
The type of instrument programming (setpoint/segment time or setpoint/gradient) can be configured and applies to the entire programming procedure.
When creating profile programs via the setup program, the programming type
can be selected for each segment.
In addition, the states of the operating contacts 1 — 8 and the active parameter set can be defined for each segment.
The setpoint profiles can be output as ramps or steps (configurable).
The following diagrams show the output in the form of ramps.
Section 10.5 “Profile controller”
35
7 Profile program editor
■ = factory-set
Creating
profile
programs
When creating profile programs, the segments have to be edited one after another.
h Change to the program editor with 2x
Pand confirm with E
h Enter the code and confirm with E
h Enter the program number and confirm with E
Create program by entering the segment setpoint, segment time, etc. The
segment number starts at 1 and is incremented automatically.
Program editor
Edit segment
Segment number
Segment setpoint
Segment time
Gradient
Operating contact 1
…
Operating contact 8
Minimum limit of
tolerance band
Maximum limit of
tolerance band
Parameter set
number
Repeat cycles
Zielabschnitt
If the segment time is 0, the segment will not be accepted.
All digits must be confirmed with
E.
The time-out function is not active within the program editor.
v Arrangement of program entry (see cover page)
PGM EDIT➔ PGM NO. (1—10)
ParameterValue/selection Description
➔ SEG EDIT
➔ SEG NO.
➔ SETPOINT
➔ SEG TIME
➔ DEGC/MIN
➔ OPCNTCT1
…
➔ OPCNTCT8
➔ TOL.MIN
➔ TOL.MAX
➔ PARA SET
➔ CYCLES
➔ TARGTSEG
1.
0.
00:00:00
0.
OFF
OFF
-1999.
9999.
1
0.
1.
1 — 100
Value within the setpoint limits
00:00:00…99:59:59
0 — 999
ON
OFF
-1999 to 0 (0 = no limiting)
0 to 9999 (0 = no limiting)
1 — 2
-1 — 0 to +99 (-1= infinite)
1 — 100
36
Factory settings are shown bold.
Insert segment
Segment number
Segment setpoint
Segment time
Gradient
Operating contact 1
…
Operating contact 8
Minimum limit
of tolerance band
Maximum limit of
tolerance band
Parameter set
number
Repeat cycles
Ta rg et s e gm e nt
7 Profile program editor
PGM EDIT ➔ PGM NO. (1—10)
ParameterValue/selection Description
➔ SEG INS.
➔ SEG NO.
➔ SETPOINT
➔ SEG TIME
➔ DEGC/MIN
➔ OPCNTCT1
…
➔ OPCNTCT8
➔ TOL.MIN
➔ TOL.MAX
➔ PARA.SET
➔ CYCLES
➔ TARGTSEG
1.
0.
00:00:00
0.
OFF
OFF
-1999.
9999.
1
0.
1.
1—100
Value within the setpoint limits
00:00:00—99:59:59
0—999
ON
OFF
-1999 to 0 (0 = no limiting)
0 to +9999 (0 = no limiting)
1—2
-1—0 to +99 (-1 = infinite)
1—100
Copy segment
Segment number
Ta rg et s e gm e nt
Delete segment
Segment number
Delete program➔ PGM DEL. 0.-1—10 (-1=delete all programs)
➔ SEG COPY
➔ SEG NO.
➔ TARGTSEG
➔ SEG DEL.
➔ SEG NO. 1.1—100
1.
1.
Factory settings are shown bold.
1—100
1—100
factory-set code: 1001
7.2Editing segments
An existing segment can be edited.
The segment number entry is limited
by the segment that was defined last.
A segment is defined through the
input of a setpoint and a segment
time or gradient.
If the segment time is 0, then the segment will not be accepted.
All digits must be confirmed with
E.
37
7 Profile program editor
7.3Inserting segments
Segments can be inserted at any point
in the profile. The subsequent segments
will be automatically rearranged and renumbered. The parameters of the segment that was inserted (A02 in the example) are preconfigured to standard
default values.
h Select “Insert segment”
h Continue with
h Enter the segment number
(in this case: 2)
h Continue with
h Enter parameters
(at least setpoint and segment
time/gradient)
h Back with
7.4Copying segments
Segments which have already been defined can be copied to other segments,
or can be added to a series of defined
segments.
h Select “Copy segment”
h Continue with
h Enter the segment number of the
segment to be copied
(in this case: 1)
E
E
X
E
38
h Continue with
h Enter the segment number of that
segment to which the data to be
copied should be assigned
(in this case:4)
h Confirm with E
E
7.5Deleting segments
When a segment is deleted, the subsequent segments move up and are automatically renumbered. The profile will
change according to the preconfigured
setpoints.
h Select “Delete segment”
7 Profile program editor
h Continue with
h Enter the segment number of the
segment to be deleted
(in this case: 2)
h Confirm with
E
E
7.6Programming repeat cycles
A group of consecutive segments can be repeated up to 99 times or indefinitely (input: -1). Repeat cycles are programmed in the menu of the last segment
in the group. The first segment of the group is defined in the setting “Target
segment”.
ExampleA02 — A04 are to be repeated once.
h Edit segment 4
h Set the repeat cycles to “1”
h Set the target segment to “2”
39
7 Profile program editor
Example:
SegmentSegment
setpoint
Segment
time
A0171 h
A02101 h
A03504 h
A04501 h
7.7Temporary alterations
Te mp or ar y al te ra ti on s ar e al te ra t io ns to
the current profile program in the program editor. They are not stored in the
profile program store, which means
that the alterations will be lost after a
restart.
Curve a:
Setpoint profile after alterations in the
current segment
Curve b:
Setpoint profile for subsequent segments or in repeat cycles.
Alterating the
setpoint in
current
segment
Alterating the
setpoint in
subsequent
segment
When altering the setpoint at time t
the setpoint profile continues with the
setpoint that was entered. During the
residual segment time (= remaining runtime of the segment), the setpoint of
the subsequent segment is approached (curve a).
Example: Alteration in A03
Segment setpoint w03: 10 → 60
On alteration at time t
, the setpoint
0
that was entered will be approached
during the residual segment time. The
slope of the ramp changes (curve a).
Example: Alteration in A04
Segment setpoint w04: 50 → 60
,
0
Alterating the
segment time
of current
segment
40
After altering the segment time, the
subsequent setpoint will be approached with the remaining (residual)
segment time (curve a).
If the new segment time is smaller than
the one that has previously elapsed,
the setpoint profile will continue at the
start of the following segment.
Example: Alteration in A03
Segment setpoint: 4h → 3h
8 Operating level
GeneralAt the operating level, it is possible to display and modify additional setpoints,
indicate different process variables and program parameters and set the current system state.
Program run-time (1)
Residual program
run-time (2)
Max. program
run-time (3)
Segment run-time (4)
Residual segment
run-time (5)
Max. segment
run-time (6)
h pressing
OPERATNG
ParameterValue/selectionDescription
➔ SETPNTS
➔ W1
➔ W2
➔ W3
➔ W4
➔ PROCESS
➔ ANALOG 1
➔ ANALOG 2
➔ ANALOG 3
➔ ANALOG 4
➔ MATHS 1
➔ MATHS 2
➔ OUTPUT
➔ SYSSTATE
➔ SETPOINT
➔ OPCNTCT1
...
➔ OPCNTCT8
➔ PARA.SET1Value inputs
➔ PGM TIME
➔ P RUN-T
➔ P RES.T
➔ P MAX.T
➔ S RUN-T
➔ S RES.T
➔ S MAX.T
P 3x in the basic status or the manual operating mode.
Value input
0.
0.
0.
0.
0.
0.
0.
0.
0.
0.
0.
0.
OFF
...
OFF
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
00:00:00
within the defined setpoint limits
w1 has no significance
Value display
Value range as for setpoint limits
Off
On
Settings are only valid for the
current operating mode (basic
status or manual mode)
1 —2
Value display
Free segments➔ FREE SEG 100.
Real-time clock
Function
Time
Date
➔ CLOCK
➔ FUNCTION
➔ TIME
➔ DATE
ACTIVE
00:00:00
26.01.99
Factory settings are shown bold.
Value display
Number of program segments
which are still free
inactive
active
00:00:00 — 23:59:59
Format: DD.MM.YY
41
8 Operating level
Setting the timeWhen the instrument is first switched
on, the matrix display will ask you to
set the real-time clock.
h Confirm the message with
The real-time clock is set at the operating level, under the menu Real-time
➔Time. The time is entered digit by digit.
clockh Increase or decrease the value
(digit) with
h Confirm the entry and select the
next digit with
I and D
E
E
42
GeneralTw o pa ra me te r s et s ca n be s to re d.
9 Parameter level
Access level
h pressing
P 4 times in basic status or the manual operating mode.
by ...
Access codeThe level is protected by a code.
factory-set code: 0001
Selecting the
Select the parameter set with
P.
parameter set
PARAMETR ➔ PARASET1
ParameterDisplayValue rangefactory-
set
Controller
structure
Proportional
band
Derivative timeTV10 — 9999 sec80 secInfluences the differential component of
Reset timeTN10 — 9999 sec350 secInfluences the integral component of the
Switching cycle
time
Contact spacingXSH0 — 999 digit0 digitSpacing between the two control contacts
Switching
differential
STR 1P, I, PD, PI, PID PIDStructure 2
STR 2P, I , P D , P I , P I DP I D
XP10—9999 digit 0 digitSize of the proportional band
XP20—9999 digit 0 digit
TV20—9999 sec80 sec
TN20—9999 sec350 sec
CY10—9999 sec20 secFor a switching output, the cycle time
CY20—9999 sec20 sec
XD10—999 digit1 digitDifferential for switching controllers
XD20—999 digit1 digit
Meaning
1
refers to the second output in
the case of a double-setpoint controller.
With modulating controllers, only PI and
PID are possible.
If Xp1,2 =0 the controller structure is not
effective! (limit comparator action)
For proportional controllers, Xp1,2 must be
>0
the controller output signal
controller output signal
should be selected so that the switched
energy supply does not lead to impermissible measurement fluctuations, while, at the
same time, not overloading the switching
devices
for double-setpoint controllers, modulating controllers and proportional controllers
with integral actuator driver
for Xp = 0..
Stroke timeTT5—3000 sec60 secUtilised stroke time of the control valve on
modulating controllers and proportional
controllers with integral actuator driver
Working pointY0-100 to +100% 0%Output for P and PD controllers
(y = Y0 at x = w).
1. Similarly, Xp2, Tv2, Tn2; Cy2; Xd2
43
9 Parameter level
PARAMETR➔ PARASET1
Output limitingY10—100%100%Maximum output limit
Y2-100 to +100% -100%Minimum output limit
Minimum relay
ON time
TK10—60sec0 secLimitation of the switching rate on
TK20—60sec0 sec
The parameter displays on the unit depend on the controller type
that was selected.
v Section 10.1 “Controller”
switching outputs.
Active
parameter set
When parameter set 2 is active, the
decimal point on the right of display 2
lights up.
44
10 Configuration level 1
GeneralThe following applies to the representation of parameters and functions on the
unit:
The parameter is not displayed when
-the instrument features do not permit the function assigned to
the parameter.
Example: Output 3 cannot be configured if output 3 is not available
to the instrument.
-the parameter is irrelevant to the function that was previously configured.
Example: Analogue input 1 is configured to “Pt100”, which means that
display start/end for standard signals will not be displayed.
Access level
h pressing
P 5 times in the basic status or in the manual operating mode
by ...
Access codeThe level is protected by a code.
factory-set code: 0002
Overview
r Controller
v Page 47
r Limit comparators
v Page 49
r controller type
control direction
controller inputs
setpoint limits
manual output
manual operating mode
self-optimisation
output 1+ 2 for
self-optimisation
dead band
fuzzy control 1
fuzzy control 2
r limit comparator 1—8r function
r
r
process value
external setpoint
external setpoint
with correction
stroke retransmission
additive disturbance
multiplying disturbance
setpoint start
setpoint end
action
switching differential
limit value
function on over/
underrange
switch-on delay
pulse function
LK inputs
limit comparator PV
r
limit comparator setpoint
➔ = press E !
45
10 Configuration level 1
r Inputs
v Page 52
r Outputs
v Page 57
r Profile controller
v Page 59
r analogue input 1—4
supply frequency
unit
r output 1—6r function
r function
restart
program start
setpoint input
time/gradient
programming
function control
programming
process value deviation
program end time
r transducer
linearisation
measurement correction
constant cold junction
temperature
external cold-junction
temperature
display start
display end
range start
range end
filter time constant
customized
recalibrationr start value
output signal
zero point
end value
output signal on
over/underrange
r controller
limit comparator 1—8
end value
r Maths/logic
v Page 62
r Display
v Page 67
r Logic function
v Page 70
r Interface
v Page 73
➔ = press E !
r mathematics 1+2
Logic 1+2
r configuration 1+2
time-out
automatic
display switching
r logic input 1—8
limit comparator 1—8
logic output 1+2
operating contact 1—8
tolerance band signal
program end signal
r protocol type
data format
unit address
minimum response time
r function
variable a
variable b
range start
range end
linearisation
r display 1—3r display value
decimal point
r baud rate
parity
stop bit
46
10 Configuration level 1
10.1 Controller
The following are set here: controller type and input variables of the controller,
setpoint limits, conditions for manual mode, presettings for self-optimisation
and the fuzzy logic.
CONFIG 1➔ CONTRL.
ParameterValue/selection Description
Controller type➔ CTR.TYPE1-SETPT
2-SETPT
MODULTNG
ACTUATNG
PROP.
Control direction➔ DIRECTN.DIRECT
INVERSE
single-setpoint controller
double-setpoint controller
modulating controller
proportional controller with integral
actuator driver
proportional controller
direct
inverse
Inputs of the
controller
process value
external setpoint
external setpoint
with correction
stroke
retransmission
additive disturbance
multiplying
disturbance
➔ INPUTS
➔ PV
➔ EXTSET
➔ EXTCORR
➔ Y RETRM
➔ ADD DIST
➔ MUL DIST
NO FUNCT
ANALOG 1
ANALOG 2
ANALOG 3
ANALOG 4
MATHS 1
MATHS 2
inverse:
The controller output Y is > 0 when
the process value is smaller than
the setpoint (e. g. heating).
direct:
The controller output Y is > 0 when
the process value is larger than the
setpoint (e. g. cooling).
Defines from which analogue inputs
or maths functions the controller
receives its signals.
In the case of a proportional controller with integral actuator driver,
stroke retransmission has to be
configured!
* factory-set for all, except process
value
** factory-set for process value
Factory settings are shown bold.
47
10 Configuration level 1
The setpoint limits are
ineffective with setpoint input
via the interface.
For external setpoint with correction, the correction value is
limited.
CONFIG 1➔ CONTRL.
ParameterValue/selection Description
Setpoint limits
setpoint start
setpoint end
Manual output➔ Y MANUAL 101. -100—100
Manual operating
mode
Self-optimisation➔ TUNEENABLED
Output 1 for
self-optimisation
➔ WLIMITS
➔ STARTVAL
➔ ENDVALUE
➔ HANDMODEENABLED
➔ TUNEOUT1RELAY
0.
400.
INHIBTD
INHIBTD
SSRELAY
ANOUTPUT
-1999—0 to +9999
-1999—400 to +9999
101 = last output
Defines the output on over/
underrange
enabled
inhibited
enabled
inhibited
Relay
solid-state relay and logic output
analogue output
type of controller output 1 fro
self-optimisation
Output 2 for
self-optimisation
Deadband➔DEADBAND 0. 0—999digit
Fuzzy control 1➔ FC1 0. 0 —100
Fuzzy control 2➔ FC2 30. 0—30—100
➔ TUNEOUT2RELAY
SSRELAY
ANOUTPUT
Relay
solid-state relay and logic output
analogue output
type of controller output 2 for
self-optimisation
serves to minimise the output
movement within the dead band;
e. g. with noisy signals.
The dead band is only effective
with controller structures with
I component.
0 = fuzzy control off
Intensity of the fuzzy signal added
to the controller output to improve
the control quality.
Influences the controller parameters
during activated fuzzy module to
improve the control quality.
48
Factory settings are shown bold.
10.2 Limit comparators
lk2
lk3
lk4
lk6
lk5
lk7
lk8
lk1 — lk6:
Monitoring referred to setpoint.
lk7/lk8:
Monitoring referred to a fixed
value AL
w = limit comparator setpoint, AL = limit value
x = limit comparator process value, X
Sd
= switching differential
On
On
On
On
On
On
On
On
Limit comparators (limit monitors, limit contacts) are used to monitor an input
variable (limit comparator process value) against a fixed limit value or another
variable (limit comparator setpoint). When a limit is exceeded, a signal can be
output or a function inside the controller initiated.
The limit comparator is reset automatically after an adjustable interval.
-1= The limit comparator has to be
reset with the
logic function (all displays off).
analogue input 1*
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint (present)**
ramp end value
control deviation
output
E key or the
Factory settings are shown bold.
50
* factory-set on LK process value
** factory-set on LK setpoint
10 Configuration level 1
AbsoluteAt the time of alteration, the limit comparator acts in accordance with its func-
tion.
RelativeThe limit comparator is in the OFF status.
An alteration of the limit value or the (limit comparator) setpoint could cause
the limit comparator to switch ON. Such a reaction will be suppressed, and
this condition maintained until the (limit comparator) process value has movedaway from the switch-on region (grey area).
Example:
Monitoring the (controller) process value x with function lk4
setpoint alteration w
a) Initial condition
1→w2
b) Condition at time of alteration.
The limit comparator remains “OFF” although the process value is within the
switch-on region.
c) Stabilised condition
The limit comparator again operates according to its function.
This function also prevents a limit comparator from being triggered during the
start-up phase.
51
10 Configuration level 1
H
The choice of the transducer depends on the hardware configuration of
the analogue inputs. -10/0/2—10V and -1—1V will only be indicated with
the appropriate hardware configuration.
v Chapter 12 “Retrofitting of cards”
10.3 Inputs
The analogue inputs are configured here.
CONFIG 1➔ INPUTS
ParameterValue/selection Description
Analogue input 1➔ ANALOG 1Configuration of the analogue inputs
......
Analogue input 4➔ ANALOG 4
Supply frequency➔PWRFREQ50 HZ
60 HZ
Unit➔ UNITDEGREE C
DEGREE F°C°F
Factory settings are shown bold.
CONFIG 1➔ INPUTS ➔ ANALOG 1
as in example “Analogue input 1”
below.
50Hz
60 Hz
ParameterValue/selection Description
Tra ns du ce r➔ PROBENO FUNCT
RTD
TC INTRN
TC EXTRN
TC CONST
RESTRANS
0 - 20mA
0 - 1 V
0 -100mV
-1 - 1V
+/-100mV
4 - 20mA
0 - 10V
2 - 10V
+/-10V
no function*
resistance thermometer**
thermocouple
(internal cold junction)
thermocouple
(external cold junction)
thermocouple
(constant cold junction)
potentiometer
0—20mA
0—1V
0—100mV
-1 to +1V
-100 to +100mV
4—20mA
0—10V
2—10V
-10V to +10V
* factory-set on analogue input 2, 3, 4
** factory-set on analogue input 1
Factory settings are shown bold.
52
10 Configuration level 1
CONFIG 1 ➔ INPUTS ➔ ANALOG 1
ParameterValue/selection Description
Linearisation➔ LINTABLINEAR
PT100
PT1000
PT500
PT50
CU50
KTY
PTK9
NI100
TC TPE J
TC TPE E
TC TPE K
TC TPE N
TC TPE T
TC TPE B
TC TPE R
TC TPE S
TC TPE U
TC TPE L
CUST LIN
W5RE W26
W3RE W25
W3RE W26
linear
Pt 100
Pt 1000
Pt 500
Pt 50
Cu 50
KTY21-6 (1kΩ at 25°C)*
Pt K9
Ni 100
Fe-Con J
NiCr-Con E
NiCr-Ni K
NiCrSi-NiSi N
Cu-Con T
Pt30Rh-Pt6Rh B
Pt13Rh-Pt R
Pt10Rh-Pt S
Cu-Con U
Fe-Con L
customized linearisation**
W5Re-W26Re
W3Re-W25Re
W3Re-W26Re
Measurement
correction
* for other types, see setup
program (extended configuration)
** for customized linearisation, up to
20 interpolation points can be
realised (with setup program only).
x = physical measured value
y = display value
➔ OFFSET 0.-1999—0 to +9999 digit
Measurement correction can be
used to correct a measured value by
a certain amount upwards or downwards.
Examples:
measured displayed
value offset value
294.7 +0.3 295.0
295.3 - 0.3 295.0
The controller uses the
Acorrected value (= displayed
value) for its calculation.
This value does not correspond to the actually measured
value.
If incorrectly applied, this can
result in impermissible values
of the control variable.
Factory settings are shown bold.
53
10 Configuration level 1
CONFIG 1 ➔ INPUTS ➔ ANALOG 1
ParameterValue/selection Description
Constant
cold-junction
temperature for
thermocouples
External
cold-junction
temperature for
thermocouples
Display start➔ DSPLSTRT 0. -1999— 0 to +9999 digit
Display end➔ DISPLEND 100.-1999—100 to +9999 digit
➔ CJTEMP 50.0—50 —100 digit
temperature of cold-junction
thermostat
➔ EXTTEMPANALOG 1
...
ANALOG 4
analogue input 1
...
analogue input 4
measurement of the cold-junction
temperature with a termperature
probe
On transducers with standard
signal and on potentiometers, a
displayed value is assigned to the
actual signal.
Example:
0—20mA " 0 — 1500°C.
The range of the physical signal can
be 20 % wider or narrower without
signalling over/underrange.
Range start➔ RNGESTRT-1999. -1999 to +9999 digit
Range end➔RANGEEND 9999. -1999 to +9999 digit
By restricting the measuring range,
the instrument will switch earlier to
the action defined for over/underrange.
Example:
Pt100 (range: -200 to +850°C).
An alarm message is to be output
for temperatures outside the range
15 — 200°C.
→ Range start: 15
Range end: 200
Filter time constant ➔ FILTER 0.60—0.6 —100 sec
To a d ju s t t he di g it a l i np u t fi lt er
(0 sec = filter off).
At a signal step, 63% of the changes
are covered after 2x filter time constant.
When filter time constant is large:
-high damping of disturbance
signals
- slow reaction of process value
display to process val. changes
-low limit-frequency
(2nd order low-pass filter)
54
Factory settings are shown bold.
Customized
recalibration
Start value
End value
10 Configuration level 1
CONFIG 1 ➔ INPUTS ➔ ANALOG 1
ParameterValue/selection Description
➔ RECAL
➔ STARTVAL
➔ ENDVALUE
0.
1.
Factory settings are shown bold.
-1999 — 0 to +9999 digit
-1999 — 1 to +9999 digit
(for explanation, see below)
factory-set access code: 0004
Different from all the other
settings, the input of the start and
end values is linked to the present
measured value at the appropriate
input.
These values cannot be readily
accepted by another instrument.
Customized
recalibration
A signal is processed electronically (conversion, linearisation …) to produce a
measured value via the analogue inputs of the controller. This measured value
enters into the calculations of the controller and can be visualised on the displays (measurement = displayed value).
This fixed relationship can be modified if required, this means that the position
and slope of the measurement characteristic can be altered.
55
10 Configuration level 1
ProcedureApply two measurement points ((1), (3)), one after another, to the controller;
they should be as far apart as possible.
At these measurement points, enter the required display value (start value, end
value) in the controller. A reference instrument is most convenient for determining the measured values M1 and M2.
Measurement conditions must remain stable during programming.
Programmingh Move to measurement point (1)
h Enter start value (2)
h Move to measurement point (3)
h Enter end value E (4)
1
1
56
If recalibration is carried out without reference instrument, the offset ∆
must be taken into account when moving to measurement point (3).
To ca nc el re ca li br a ti on , t he s ta rt a nd e nd v al ue s h a ve t o b e p ro gr am me d t o
the same value. This sets the start value to 0 and the end value to 1.
Any subsequent recalibration will otherwise be based on the corrected characteristic.
1. If start value=0 or end value=1 is to be set, then the value must first be altered with
I or D to enable correction.
10 Configuration level 1
10.4 Outputs
The outputs are configured here.
CONFIG 1➔ OUTPUTS
ParameterValue/selection Description
Output 1➔OUTPUT1-Configuration of the outputs as in
analogue input 1
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint
ramp end value
control deviation
output
setpoint 1
...
setpoint 4
controller output 1**
controller output 2
address value
limit comparator output 1
...
limit comparator output 8
operating contact 1
...
operating contact 8
logic input 1
...
logic input 8
logic 1
logic 2
program end signal***
tolerance band signal
manual operation
supply for 2-wire transmitter
*factory-set on all outputs
except output 1
** factory-set on output 1
***see also profile program end time
Factory settings are shown bold.
57
10 Configuration level 1
CONFIG 1 ➔ OUTPUTS ➔ OUTPUT1
ParameterValue/selection Description
Output signal for
analogue output
Zero point for
analogue signals
End value for
analogue signals
➔ SIGNAL0 - 10 V
➔ STARTVAL 0.-1999 — 0 to +9999 digit
➔ ENDVALUE 100.-1999 — 100 to +9999 digit
2 - 10 V
-10- 10V
0 - 20mV
4 - 20mA
-20-20mA
0—10V
2—10V
-10 to +10V
0—20mA
4—20mA
-20 to +20mA
A physical output signal is assigned
to the value range of an output
variable.
Example:
Setpoint 1 (value range:
150 — 500°C) is to be output via the
analogue output (0 — 20mA).
i.e.: 150 — 500°C " 0 — 20mA
zero: 150
end value: 500
Output signal for
over/underrange
H Setting for controller
outputs for cooling.
For double-setpoint
controllers, the following
settings must be predefined:
zero: 0
end value: -100
➔ RANGEFCT 0.0 — 101*
101= last output signal is
retained
The output produces a defined
signal.
H If the output is from a
controller, the profile controller
(when active) produces the
output that was selected under
“manual output”.
vSection 10.1 “Controller”
* for switching outputs:
0 = off, 1 — 100 = on
Factory settings are shown bold.
58
10 Configuration level 1
10.5 Profile controller
The profile controller/generator is configured here. In addition, the response to
a power failure, the profile run and the type of programming are defined here.
CONFIG 1➔ PROF CTR
ParameterValue/selection Description
Function➔PROGRFCTPROFCTRL
PROFGEN
CONTRL.
Restart after
power failure
Profile program
start
Setpoint input➔W INPUTW RAMP
➔ RESTARTPGMCANCL
CONTINUE
STDSTILL
CONT X%
CONT X
➔ PGMSTARTPGMSTART
START X
W STEP
profile controller
profile generator
fixed-setpoint controller
With the “fixed-setpoint controller“
setting, the instrument behaves as
for Type 703570/75.
v Operating Instructions B70.3570
abort profile program
continue
standstill
continue at deviation <x%
continue at process value
(for explanation, see next page)
start at beginning of profile
program (w01)
start at process value
setpoint ramp
setpoint step
Time/gradient
programming
➔ TIMEGRADTIME
DEGC/MIN
setpoint ramp:
setpoint step:
time
gradient
Defines in which way segments are
programmed when creating new
profile programs (profile program
editor):
- Time: setpoint/segment time
- Gradient: setpoint/gradient
Factory settings are shown bold.
59
10 Configuration level 1
CONFIG 1 ➔ PROF CTR
ParameterValue/selection Description
Response on
overrange/
underrange
➔ RANGEFCTCONTINUE
PGM STOP
continue
program stop
Program stop:
The program will be continued after
the end of the measurement
overrange/underrange.
Defines when the controller and the
limit comparators are active.
Generator control:
active in automatic mode;
otherwise according to defined
system state in setup program
Operating contact:
only active when operating contact
is in the ON condition.
relevant for restart
(continue at deviation <X%)
-1 = continuous signal
Duration of program-end signal
v Section 10.4 “Outputs”
Restart after a power failure
Abort
The program run is aborted; the instrument switches to basic status.
profile program
ContinueThe program continues from the point at which it was interrupted at the time of
the power failure.
StandstillOutputs, limit comparators, operating contacts and controller behave as de-
fined in the system state “Basic status”.
A key, or it can be cancelled
) does not exceed a program-
new
Continue at
deviation <X%
The program can be continued by pressing the
by using the
E key.
The program continues from the point at which it was interrupted at the time of
power-down, if the difference between the process value before power-down
) and the process value after power-on (X
(X
old
mable percentage (process value deviation). If this value is exceeded, the instrument goes into standstill.
60
10 Configuration level 1
Continue at
process value
Restart after a
power failure
In the event of a power failure, the sign of the gradient (falling or rising) at the
time of the power failure is stored. After the supply voltage has been restored,
the program is checked from the beginning to find matching process values
and setpoints. The program is continued at the point at which the process value matches the setpoint and the sign of the gradient corresponds to the sign
that was stored.
Conditions prior to power-down(1)(2)(3)(4)(5)(6)(7)(8)
Profile program aborted(1)(2)(1)(1)(1)(1)(1)(1)
Continue
Process value within range
Process value out-of-range
Standstill(1)(2)(7)(7)(7)(6)(7)(8)
(1)
(1)
(2)
(2)
(3)
(7)
(4)
(4)
(5)
(5)
(6)
(6)
(7)
(7)
(8)
(8)
Continue at deviation <X%
(6)
(5)
(4)
(ABS (X
(ABS (X
Process value out-of-range
Continue at process value
Process value within range
Process value out-of-range
Conditions after power-on with
programmed function...
X%= process value deviation, X
= process value after power-on, ABS()= absolute value
X
new
(1) Basic status(5) Profile program stop
(2) Profile program sequence(6) Profile program end
(3) Continue at process value(7) Standstill
(4) Automatic mode(8) Manual mode
old
old
- X
- X
new
new
)/X
) x 100 ≤ X%
old
)/X
) x 100 > X%
old
= process value prior to power-down,
old
(1)
(1)
(1)
(1)
(1)
(2)
(2)
(2)
(2)
(2)
(3)
(7)
(7)
(3)
(7)
(7)
(7)
(3)
(7)
(7)
(7)
(3)
(7)
(6)
(6)
(6)
(6)
(7)
(7)
(7)
(7)
(7)
(8)
(8)
(8)
(8)
(8)
61
10 Configuration level 1
10.6 Maths and logic module
This menu is displayed only with enabled maths and logic module.
CONFIG 1➔ MATHSLOG
ParameterValue/selection Description
Mathematics 1➔MATHS 1-Configuration of mathematics as
Mathematics 2➔MATHS 2-
Logic 1 ➔ LOGIC 1NO FUNCT
FORMULA
Logic 2 ➔ LOGIC 2NO FUNCT
FORMULA
Factory settings are shown bold.
CONFIG 1➔ MATHSLOG ➔ MATHS 1
ParameterValue/selection Description
Function➔FUNCTIONNO FUNCT
DIFFERNC
RATIO
HUMIDITY
FORMULA
Variable a➔ VAR AANALOG1
...
ANALOG4
MATHS 1
MATHS 2
Variable b ➔ VAR BANALOG1
ANALOG2
ANALOG3
ANALOG4
MATHS 1
MATHS 2
Range start➔ RANGESTRT-1999.-1999 to +9999 digit
Range end➔RANGEEND 9999.-1999to +9999 digit
shown in example “Maths 1” below.
no function
logic formula (setup program)
no function
logic formula (setup program)
no function
difference (a-b)
ratio (a/b)
humidity (a;b)
maths formula
Definition of a value range for the
result of a mathematical calculation.
If the value range is infringed (above
or below), over/underrange will be
signalled.
v Section 15.2 “Alarm messages
and display priorities”
Factory settings are shown bold.
10 Configuration level 1
CONFIG 1 ➔ MATHSLOG ➔ MATHS 1
ParameterValue/selection Description
Linearisation➔ LINTABLINEAR
PT100
PT1000
PT500
PT50
CU50
KTY
PTK9
NI100
TC TPE J
TC TPE E
TC TPE K
TC TPE N
TC TPE T
TC TPE B
TC TPE R
TC TPE S
TC TPE U
TC TPE L
CUST LIN
W5RE W26
W3RE W25
W3RE W26
linear
Pt 100
Pt 1000
Pt 500
Pt 50
Cu 50
KTY21-6
Pt K9
Ni 100
Fe-Con J
NiCr-Con E
NiCr-Ni K
NiCrSi-NiSi N
Cu-Con T
Pt30Rh-Pt6Rh B
Pt13Rh-Pt R
Pt10Rh-Pt S
Cu-Con U
Fe-Con L
customized linearisation
W5Re-W26Re
W3Re-W25Re
W3Re-W26Re
Factory settings are shown bold.
Ratio controlThe control is always based on variable a.
The maths module forms the ratio of the measurements a and b (a/b) and provides the setpoint for the controller. The ratio of the measured values a and b
can be called up and displayed via the functions “Maths 1” or “Maths 2”.
The required ratio a/b is programmed in the setpoint input as setpoint (ratio
setpoint).
Humidity
control
The humidity controller receives the process value from a psychrometric humidity probe through the mathematical linkage of wet bulb and dry bulb temperatures.
Variable a - dry bulb temperature
Variable b - wet bulb temperature
63
10 Configuration level 1
Formula input-The formula character string consists of ASCII-characters and has a ma-
ximum length of 70 characters.
-The formula can only be entered via the setup program.
-The formulae can be entered freely according to the usual mathematical
rules.
-Spaces may be inserted in the formula character string without restriction.
No spaces are allowed within function designations, variable names and
constants.
no function
analogue input 1
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint (present)
ramp end value
control deviation
output
display of a storage address value
XXXX.—X.XXX
68
Display 3
Display value
10 Configuration level 1
CONFIG 1 ➔ DISPLAY ➔ DSPCONF1
ParameterValue/selection Description
➔ DISPLAY3
➔ DISPLVAL
NO FUNCT
ANALOG 1
...
ANALOG 4
MATHS 1
MATHS 2
PV
SETPOINT
RAMPENDV
CNTRLDEV
OUTPUT
VALDISPL
LIMITC
OPCONTCT
BARG Y
BARG XW
BARG PGM
TXTDISPL
PGMSTAT
PGM TIME
PGMRESID
SEG TIME
RESIDSEG
PGMNAME
TIME
no function
analogue input 1
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint (present)
ramp end value
control deviation
output
display of a storage address value
limit comparators (switching states)
operating contacts (switching states)
bar graph output
bar graph control deviation
bar graph program run-time
text display
current program no./segment no.
program run-time
residual program run-time
segment run-time
residual segment run-time
program name
time
switching states of the
limit comparators and operating
contacts: 8 7 6 5 4 3 2 1
00000000
bar graph output:
1-setpoint ctrl. 0% 100%
and prop. ctrl. ИИИИИИЙН
2-setpoint ctrl. -100% 0% 100%
ННННИННН
bar graph control deviation:
50%0% 50%
ННННИННН
bar graph program run time:
ИЙНННННН
The portion of the elapsed program
run time referred to the total run time
is shown.
Decimal point
➔ DECPOINT
XXXX.
XXXX.—X.XXX
Factory settings are shown bold.
Decimal pointIf the value to be displayed can no longer be represented with the pro-
grammed decimal place, then the number of decimal places will be automatically reduced. If, subsequently, the measurement becomes again smaller, then
the number will be increased to the programmed decimal point value.
69
10 Configuration level 1
10.8 Logic functions
Functions are assigned here to the logic signals of the logic inputs, limit comparators, operating contacts, tolerance band signal, profile program end signal
and of the logic module.
Operating contact 8 ➔ OPCNTCT8
To le r an c e ba n d
signal
Profile program
end signal
➔ TOLBAND
➔ PGM END
TUNESTRT
TUNESTOP
W SWITCH
X SWITCH
P SWITCH
KEYINHBT
LEVINHBT
TXTDISPL
DISPLOFF
AUTOHAND
PGMINHBT
PGMSTART
PGMSTOP
PGMABORT
PGMSELCT
FFWD
NEXTSEG
no function
start of self-optimisation
cancel self-optimisation
setpoint switching
process value switching
parameter set switching
key inhibit
level inhibit
text display*
all displays off/acknowledge LK
auto/manual changeover
programming inhibit
profile program start
profile program stop
profile program abort
profile program selection
fast forward**
change of segment
* A maximum of 10 texts is input and
assigned to the logic functions in the
setup program.
** The speed of the program run is
increased dynamically
The functions are active when the
contact is closed or the switching
status is “ON”.
Profile program start:
The program is started immediately.
The start day/start time and delay
settings (“program start” level) are
ineffective.
All displays off:
- all displays are off
- limit comparators are acknowledged
Te xt di s pl a y a nd al l d i sp l ay s o ff :
response according to priority list
Factory settings are shown bold.
70
10 Configuration level 1
Switching
action
Edge-triggered
functions
The logic functions are activated through logic inputs (floating contacts
(switches/relay contacts)), limit comparators, operating contacts or logic.
The functions are divided into two groups:
The logic functions react to switch-on edges.
The following functions are edged-triggered:
-start/stop self-optimisation
-start profile program
-abort profile program
- profile program selection via one logic input only
-acknowledge limit comparators
State-operated
functions
Combined
logic functions
The logic functions react to switch-on or switch-off states.
-all other functions
A combination of two operating variables (logic inputs, limit comparators,
logic and operating contacts) can be
used to implement the functions setpoint/process value switching.
The profile program selection is realised via three operating variables.
Any operating variable can be selected.
The states Z1 — Z2(Z3) are assigned to
the operating variables in descending
order (see list on the right).
71
10 Configuration level 1
Example:
The process value is to be selected via
one logic input and the state of one operating contact.
This results in the following assignment:
Z1 - logic input 1
Z2 - operating contact 1
Setpoint switchingProcess value
switching
Setpoint of
system state/
external setpoint
Setpoint 2Analogue input 2Program 2001
Setpoint 3Analogue input 3Program 3010
Setpoint 4Analogue input 4Program 4011
--Program 5100
--Program 6101
--Program 7110
--Program 8111
0 = contact open /OFF1 = contact closed /ON
Configured controller
process value
Profile program
selection
Program 1000
Z3Z2 Z1
72
If switching between two setpoints or process values only is required, then only one logic function has to be configured.
If more than two logic functions are configured to setpoint switching (process value switching), then only the first two (see list “operating variable - state”) are significant.
10.9 Interface
CONFIG 1 ➔ INTERFCE
ParameterValue/selection Description
Protocol type➔ PROTOCOLMODBUS
MODINT
Data format
Baud rate
➔ DATAFMT
➔ BAUDRATE
1200
2400
4800
9600
19200
10 Configuration level 1
MODbus/Jbus
MODbus int
1200 bps
2400 bps
4800 bps
9600 bps
19200 bps
Parity
Stop bit
Unit address ➔ UNITADDR 0.0—1 —254
Minimum
response time
➔ PARITY
➔ STOP BIT
➔ MIN TIME 0.0—500msec
NONE
ODD
EVEN
ZERO
1
2
Factory settings are shown bold.
no parity
odd parity
even parity
zero parity
1 stop bit
2 stop bits
Minimum period of time which
elapses between the request of an
instrument within a data network
and the response of the controller
Interface description B 703570.2
Interface description B 703560.2.3
73
10 Configuration level 1
74
11 Optimisation
a) SO in the start-up phase
b) SO at setpoint
Start of SO
Start of SO
Switching
line
11.1 Self-optimisation
ProcedureSelf-optimisation (SO) establishes the optimum controller parameters for PID
or PI controllers.
Depending on the controller type, the following controller parameters can be
defined:
Reset time (Tn1, Tn2), derivative time (Tv1, Tv2), proportional band (Xp1, Xp2),
switching cycle time (Cy1, Cy2), filter time constant (dF)
The controller selects one of two procedures (a or b), depending on the size of
the control deviation:
Start of selfoptimisation
The controller output types have to be defined for selfoptimisation.
v Section 10.1 “Controller”
Self-optimisation is started from the
manual mode and is automatically terminated, or can be cancelled.
It is not possible to start self-optimisation with activated level inhibit.
75
11 Optimisation
Xp too large
Xp too small
Tn, Tv too large
Tn, Tv too small
optimum
setting
Cy too large
11.2 Checking the optimisation
Start-up
procedure
Control
response
The optimum adjustment of the controller to the process can be checked by
recording the start-up with the control loop closed. The diagrams below indicate possible maladjustments and how these can be corrected.
The control response of a third-order control loop of a PID controller is shown
as an example. However, the procedure for adjusting the controller parameters
can also be applied to other control loops.
76
11.3 Fuzzy parameters
x
In addition to the algorithms for the
various controller structures, the controller software also includes a fuzzy
module. This can be used to improve
both the control and the disturbance
response of controllers with I-action.
When the fuzzy module is activated,
the output y is made up of the controller output and the output signal of the
fuzzy module.
The parameter Fc1 affects the intensity of the fuzzy signal:
Fc1 = 0:Fuzzy module not activated
0<Fc1≤ 100: Fuzzy module activated
If the fuzzy module activated by Fc1 makes corrections to the output y,
the reset time T
The parameter Fc2 is used to adjust the degree of influence on the reset time
T
.
n
Fc2 = 0:no influence on T
0<Fc2≤ 100: influence on T
is influenced during correction.
n
n
n
11 Optimisation
When supplied, and also after self-optimisation, the fuzzy parameters are set
to Fc1 = 0 and Fc2 = 30.
The fuzzy module can be activated at any time by setting Fc1 > 0.
The setting Fc2 = 30 is suitable for many applications. The optimum setting
can be determined with the help of the table below.
77
11 Optimisation
Action Reaction
Fc1disturbance amplitude
reduced, stabilisation time
increased
Fc1disturbance amplitude
increased, stabilisation
time reduced
Fc2stabilisation time reduced
Fc2stabilisation time
increased
↑
↑
↑
↑
If the fuzzy module is not activated (Fc1=0), Fc2 is also ineffective.
The action and sensitivity of the fuzzy parameters depend largely on
the process to be controlled.
The influence is greater on proportional controllers than on switching
controllers.
78
12 Retrofitting of cards
The following steps are necessary for retrofitting cards:
Only qualified personnel are permitted to retrofit cards.
The cards can be damaged by electrostatic discharges. Avoid elect-
E
rostatic charges during fitting and removal. Carry out the card change
on a workbench which is earthed.
Identifying the
card
h Identifiy the card by the sales no. or part no. that is glued to the packaging
The instrument is fitted from device software version 50.02.XX on with a
new type of analog input card. If analog input cards are retrofitted, it
must be noted that they cannot be operated together with the older type
of card (i.e. do not mix card types). Please note also that an update of
the setup program may be required in order to carry out the configuration through the setup program.
The Software-Version appears on the Display if the keys PGM +“arrow
up“ are pressed.
CardsCode Sales No.Card No.
Analogue input 3 and 4:
Universal input
up to software version 50.01.XX
from software version 50.02.XX on
Outputs/logic inputs:
Relay (changeover contact)
Solid-state relay 230V 1A
Logic 0/5V
Logic 0/22V
Analogue output
Supply for
2-wire transmitter
Tw o l og i c i np u ts
The retrofitable analogue inputs 3 and 4 are supplied ex-factory as universal
input. They can be reconfigured as voltage input for certain measuring ranges
(-10/0/2—10V and -1V—1V).
h Re-arrange push-on jumpers as in the diagram
The standard analogue inputs 1 and 2 are configured ex-factory as universal input or as voltage input for certain measuring ranges (see type
designation or order details). They can also be reconfigured:
80
12 Retrofitting of cards
Typ e 70 35 80 o nl y
Removing the
controller
chassis
Assigning the
slot
h Pull off setup plug
h Press together the ribbed surfaces
on the panel top and bottom (or left
and right with landscape format)
and pull out the controller chassis.
h Determine the corresponding slot for the card
81
12 Retrofitting of cards
Inserting the
card
Inserting the
controller
chassis
h Pull off the guide plate (1)
h Insert card into the guide until the projections on the card snap into the
notches provided (2)
h Fit on the guide plate
h Push the controller chassis into the case until the lugs (underneath the
ribbed surfaces) snap into place.
82
13.1 RS422/485 interfaces
The controller can be integrated into a data network via the interface. Functions which can be implemented include:
- process visualisation
- system control
- recording/logging
13 Interfaces
The bus system is based on the master-slave principle. A master computer
can address up to 31 controllers and instruments (slaves). The interface is a
serial interface to RS422 and RS485 standards.
The following data protocols are available:
- MOD/Jbus protocol
Interface description B 703570.2
83
13 Interfaces
13.2 PROFIBUS-DP
FieldbusThe controller can be incorporated into a fieldbus system according to the
PROFIBUS-DP standard, via the PROFIBUS-DP interface. This PROFIBUS
variant has been especially designed for the communication between automation systems and distributed peripheral devices at the field level, and is optimised for speed.
Data
transmission
GSD generatorWith the aid of the project design tool included in the delivery (GSD generator;
Data transmission is performed serially, according to the RS485 standard.
GSD = Device Base Data), a standardised GSD file is created, which serves to
integrate the controller into the fieldbus system, through the selection of characteristic controller features.
84
Interface description B 703560.2.3
14 Accessories
Error
Power
(L+) (L-)
L1PEN
97
TxD
RxD RxD
TxD GND
98 99
K5K6K7K8
4
4
1
4
4
2
4
4
3
2
4
1
2
4
2
2
4
3
1
4
1
1
4
2
1
4
3
K1K2K3K4
3
4
1
3
4
2
3
4
3
31323
3
8
4
1
8
4
2
8
4
3
7
4
1
7
4
2
7
4
3
6
4
1
6
4
2
6
4
3
5
4
1
5
4
2
5
4
3
Ty pe 7 03 58 0: Ter mi na l st ri p 2, t e rm in al3 4 5
Ty pe 7 03 58 5: Ter mi na l st ri p 2, t e rm in al3 4 5
14.1 External relay module/logic module ER8/EL8
By using the external relay module ER8 or logic module EL8, the controller can
be expanded by eight relay outputs (changeover contacts) or logic outputs (0/
12 V). Communication with the controller occurs via the RS422/485 interface.
All controller signals for switching outputs can be output by the module.
Configuration is only possible through the setup program.
v Section 7.4 “Outputs”
If the module ER8/EL8 is connected to the interface, then no further
communication is possible via the interface.
ConnectionThe electrical connection is carried out like the connection to an RS485 inter-
face (the figure below shows ER8; see also
B703564
).
Operating Manual ER8/EL8,
Configuring
the module
h Activate the relay module via the setup program
Edit r Settings only via setup r Expanded configuration
This activates the menu EditrExternal relay module.
h Configure the module
The functions are related to the relay module, but they also apply to the
logic module (Off = 0 V; On = 12 V).
If the setup plug is connected to the profile controller, the module will
not be operated and the outputs are in idle position (logic outputs:
0V).
85
14 Accessories
14.2 Setup program with commissioning software
Setup programA setup program for Windows® NT4.0/2000/XP/Vista/7 (32/64 bit) is available
for easy configuration of the profile controller.
Hardware requirements:
- 512 Mbyte RAM- CD-ROM drive
- 50 Mbyte available on hard disk- 1 free serial interface or USB interface
The program shows the current configuration as a list in the background. The
corresponding entry template is called up by double-clicking on the list, or via
the menus.
Commissioning
software
Some functions of the profile controller can only be configured via the setup
program:
-Customized linearisation (input of a linearisation table)
-Display brightness of display 3
- Switching off code request (expanded configuration)
-Configuring relay module
-Modifying passwords
-Profile program selection only via one logic input
-Profile program table (any profile program with corresponding start times
and conditions can be allocated to 10 program positions, and can then be
run through in sequence).
-System states
-Controller active in basic status
The commissioning software is a part of the setup program and is available for
adapting the controller to the control loop, optimally and conveniently.
Different process variables (e.g. setpoint, process value, control deviation, signals from the controller outputs) can be displayed graphically. The controller
parameters can be altered and transferred to the profile controller via the
setup/RS422/485 interfaces.
86
Data recording is limited to 48 hours.
15 Appendix
15.1 Technical data
Thermocouple input
DesignationRange
Fe-Con L
Fe-Con JEN 60 584
Cu-Con U
Cu-Con TEN 60 584
NiCr-Ni KEN 60 584
NiCr-Con E
NiCrSi-NiSi NEN 60 584
Pt10Rh-Pt SEN 60 584
Pt13Rh-Pt REN 60 584
Pt30Rh-Pt6Rh BEN 60 584
W5Re-W26Re
W3Re-W25Re
Cold junctionPt100 internal , external or constant
1. The specifications refer to an ambient temperature of 20°C.
Pt100EN 60 7512-wire/3-wire-200 — +850°C≤0.05%50 ppm per °C
Pt 50,500, 1000 EN 60 7512-wire/3-wire-200 — +850°C≤0.1%50 ppm per °C
Cu50 2-wire/3-wire-50 — +200 °C≤0.1%50 ppm per °C
Ni100 DIN 437602-wire/3-wire-60 — +250°C≤0.05%50 ppm per °C
KTY21-62-wire-50 — +150°C≤1.0%50 ppm per °C
PtK9
Sensor lead resistancemax. 30Ω per conductor in 2-wire/3-wire circuit
Measuring current250µA
Lead compensationnot required for 3-wire circuit. For 2-wire circuit, lead compensation can be provided in the software
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
temperature error
Standard signal input
DesignationRangeMeas. accuracyAmbient
Volta ge0 — 10 V,input res istance RE > 100kΩ
Current4 — 20mA, voltage drop ≤ 1V
Potentiometer
Measurement circuit monitoring
TransducerOver/underrangeProbe/lead short-circuit
Thermocouple•-•
Resistance thermometer•••
Volta ge 2 — 10 V
0—10V
Current 4 — 20mA
0—20mA
-10 to +10V,input resistance RE > 100kΩ
-1 to + 1 V,input resistance RE > 100kΩ
0— 1V,input resistance RE > 100kΩ
0—100mV, input resistance RE > 100kΩ
-100 to +100mV, input resistance
RE > 100kΩ
0—20mA, voltage drop ≤ 1V
min. 100Ω, max. 10kΩ
1
•
•
•
•
≤
0.05%
≤0.05%
≤0.05%
≤0.05%
≤0.05%
≤0.05%
≤0.1%
≤0.1%
1
•
-
•
-
Probe/lead break
temperature error
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
100 ppm per °C
•= recognised -= not recognised
1. In the event of an error, t he outp uts move to defined states (configurable).
Standard version
•
-
•
-
87
15 Appendix
Outputs
Relay
contact rating
contact life
contact protection circuit
Logic
current limiting
Solid-state relay
contact rating1A at 230 V
Volta ge
output signals
load resistance
Current
output signals
load resistance
Supply for
2-wire transmitter
voltage
current
0/5V
20mA
56Ω/15nF between common-n.o. make/common-n.c. break
Controller structuresP/PD/PI/PID/I
A/D converterresolution better than 15 bit
Sampling time210msec
proportional controller with integral actuator driver
changeover contact
3A at 250 VAC resistive load
150 000 operations at rated load
or0/22V
-10 to +10V / 0 — 10V / 2 — 10V
R
500Ω min.
load
R
450Ω max.
load
22V
30mA
30mA
Electrical data
Supply (switched mode power supply)110 — 240V AC +10/-15% 48 — 63Hz
20 — 30V AC/DC, 48 — 63Hz
Te st vo l ta ge s ( t yp e t e st )t o E N 6 10 10 , P a rt 1
Power consumption24VA max. for Type 703580
Data backupEEPROM
Electrical connectionat the rear via screw terminals,
Electromagnetic compatibility
Interference emission
Immunity to interference
Safety standardsto EN 60730-1 for Type 703580
overvoltage category II, pollution degree 2
14VA max. for Type 703585
conductor cross-section up to 2.5mm
and core-end sleeve (length: 10mm)
EN 61326-1
Class A - only for industrial use -
Industrial requirements
to EN 61010-1 for Type 703585
2
Housing
Housing typeplastic housing for panel-mounting (indoor use) acc. to IEC 61554
Ty pe7 03 5 85 / 1. . .7 03 5 85 / 2. . .7 03 5 80 / 0. . .
Bezel in mm48 x 96 (portrait)96 x 48 (landscape)96 x 96
Depth behind panel in mm130130130
+0.6
Panel cut-out in mm45
Ambient/storage temperture range-5 to 55°C / -40 to +70° C
Climatic conditions rel. humidity not exceeding 95% annual mean, no condensation
Site altitudeupto2000m above sea level
Operating positionunrestricted
Protectionacc. to EN 60529, front IP65, rear IP20
Weight (fully fitted)approx. 420gapprox. 420gapprox. 730g
GL - Software
c UL usUnderwriters LaboratoriesE 201387UL 61010-1
Te st i ng l ab o ra t or yC er ti f ic a te s /c er ti f ic a ti on
numbers
Germanischer LloydCertificate
No. 15 694-00 HH
Te st ba si sv a li d fo r
GL-Baumusterprüfung
Kategorie C, EMC1
CAN/CSA-C22.2 No.61010-1
DICON 501
DICON 401/501
89
15 Appendix
15.2 Alarm messages and display priorities
PriorityDisplayPossible error/
Matrix7-segment
high
ИИИИИИИИ
+LEDs
(no display)(no display)
BREAK E1
…
8888.
8888. (blinks)
9999. (blinks)
or ( )*
BREAK E4
ORANGE 1
…
9999. (blinks)
or ( )*
ORANGE 4
URANGE 1
…
URANGE 4
-1999.
(blinks)
or ( )*
ORANGEM1( )*
ORANGEM2
URANGEM1( )*
URANGEM2
MATH1 ERR ( )*
MATH2 ERR
LOG1 ERR( )*
LOG2 ERR
ER8 ERR( )*
BUSERROR( )*
SETCLOCK( )*
SYS ERR( )*
MEM FULL( )*
NO PGM( )*
notes
watchdog or power-on
will trigger initialisation (reset)
-logic function “All displays off” is
configured and active
-controller faulty
-supply faulty
-probe/lead break of resistance
thermometer (connection 1.9,
1.11, 1.4, 1.8, 2.10, 2.12, 3.20,
3.12) or standard-signal input
-probe/lead short-circuit at
standard-signal input
-overrange at standard-signal
input
-underrange at standard-signal
input
-overrange of resistance
thermometer and thermocouple
input
-probe/lead break of thermocouple input
-underrange of resistance
thermometer and thermocouple
input
-probe/lead short-circuit of
resistance thermometer
-probe/lead break of resistance
thermometer 1.10, 1.7, 2.11,
3.11
overrange (maths module)
(calculation result > range end)
underrange (maths module)
(calculation result < range start)
mathematical error
(violation of mathematical rules;
impermissible values )
logic error
(violation of mathematical rules)
error on relay module-no communicationperipherycheck periphery
buffer battery emptycontrollerset real-time clock
buffer battery emptycontrollerrestart program
program memory is fullcontrollerdelete programs
program is not availablecontrollercreate program
Assignment Error handling
controllerreplace controller when
-no error
-controller
-supply
external
signal
generator
external
signal
generator
controllercheck maths formulae
controllercheck logic formulae
check/repair/replacement
initialisation is longer than 5sec
-open logic input
-replace controller
-check supply
-check probe for break or shortcircuit
-check probe connection and
terminals
-check lead
-is the medium to be measured
within the measuring range (too
hot - too cold?)
-check probe for break or shortcircuit
-check probe connection and
terminals
-check lead
1
1
1
1
1
90
low
* display according to configuration
1. can be acknowledged
(continued on next page)
15 Appendix
PriorityDisplayPossible error/
Matrix7-segment
high
low
(Text)
…
(Text)
(Text)
…
(Text)
(Text)( )*
(Text)( )*
SOACTIVE( )*
----
(display according to configuration)--* display according to configuration
( )*
( )*
----
( )*
notes
text (logic input 1)
…
text display (logic input 8)
text display (limit comparator 1)
…
text display (limit comparator 8)
text display (logic 1)-text display (logic 2)-self-optimisation has been
activated
measurement input not available
or not configured
Alarm messages with acknowledgement
On pressing the E key, the message disappears.
Assignment Error handling
check/repair/replacement
--
--
--
controller- configure measurement input
-retrofit input card
91
15 Appendix
Measurement inputResponse of the outputs in the event of error
No. Transdu-
cer
Measuring
range
Measurement
site
Output 1Output 2Output 3Output 4Output 5Output 6
1
2
3
4
Example:
1Pt10020—500°CMachinery room
boiler
temperature 1
Output
100%
Limit com-
parator off
Ta bl e: A ss ig nm en t of t he m ea su re m en t in pu ts/response of the outputs in the event
of an error (to be filled in by the user)
92
15.3 Character set for matrix display
The special characters for text entry in the setup program are shown here.
They are entered from the keys using the key combination Alt + XXX.
15 Appendix
200 — 210 reserved for bar graph display
93
15 Appendix
15.4 Instrument features (configuration level 2)
The software version and the hardware features of the profile controller are
shown here.
CONF 2
ParametersValue/selectionDescription
Version➔ VERSION50.0X.0Xversion number
VDN number➔VDN NO.STANDARD
relay
solid-state relay
analogue output
logic output 5V
logic output 22V or
voltage output for
2-wire transmitter
two logic inputs
not connected
connected
not available
RS 422/485
PROFIBUS-DP
charged
discharged
not available
available
94
15 Appendix
15.5 Notes for instruments with Germanischer Lloyd (GL) approval
The information below is intended to supplement or replace the details that
have already been given.
15.5.1 Technical data
Ambient conditions according to application category C for enclosed areas
Te mp e ra t ur e-5 to 55°C
Relative humidity≤100% r. h.
Vibration≤0.7g
Electromagnetic compatibility
The electromagnetic compatibility corresponds to the GL guidelines for
type examinations (10.97).
15.5.2 Alarm messages
vSection 15.2
15.5.3 Inhibits
All levels are inhibited by codes. Alterations, whether accidental or deliberate,
cannot be made easily. The operating level is not inhibited by a code. In this
case, it is possible to lock the entire keypad via a logic contact (e.g. keyswitch).
v Section 5.3
15.5.4 Manual mode
The user can pause the program by pressing the M key. The program continues when the key is pressed again.
The output (control) cannot be influenced directly.
In the event of an instrument failure, manual operation is no longer possible.
15.5.5 Additional notes
The instrument has to be sent back to the main factory for servicing.
In accordance with the regulations of the Germanischer Lloyd, certain applications require the availability of a reserve instrument.
95
15 Appendix
The instrument can only be used with restrictions on the bridge,
since a continuous dimming of the display brightness is not possible!
it is recommended that a print-out of the setup program be kept on
site, together with the technical documentation for the controller
(can be requested, if necessary).
96
16 Index
A
Accessories 10, 85
Action
49
Alarm messages
Alteration, temporary
Altering
segment time of current segment
setpoint in current segment
setpoint in subsequent segment
Analogue input
configuring
Approvals
90
40
9, 94
80
9
B
Basic status 24–25, 27
Basic type extension
Block structure
9
7
C
Card
identifying
retrofitting
Character set
Clock, setting of
Code request
Conditions