Juice Goose SCV-20001 Users Manual

UNISTAR V
120-230V 50/60Hz
1 to 3kVA
USER MANUAL
003-2519, Rev C
Staco Energy is highly specialized in the development and production of uninterruptible power
systems (UPS). The UPS’s of this series are high quality products, carefully designed and
manufactured to ensure optimum performance.
No reproduction of any part of this manual, even partial, is permitted without the authorization of Staco Energy Products Company. The Staco Energy Products Company reserves the right to modi fy the product described herein, in order to improve it, at any time and without notice.
301 Gaddis Boulevard • Dayton, Ohio 45403
U.S. Toll Free 866-261-1191
(937) 253-1191 • Fax: (937) 253-1723
Web site: www.stacoenergy.com
Thank you for choosing our product.
Page | ii
Table of Contents
1. Important Safety Wa rn ings ................................................................................................................... 1
1.1 Transportation ................................................................................................................................ 1
1.2 Preparation ..................................................................................................................................... 1
1.3 Installation ...................................................................................................................................... 1
1.4 Operation ....................................................................................................................................... 1
1.5 Maintenance, Service and Faults .................................................................................................... 2
2. Installation and setup ........................................................................................................................... 3
2.1 Rear panel view .............................................................................................................................. 3
2.1.1 1 kVA or 1.5kVA ....................................................................................................................... 3
2.1.2 2 kVA ....................................................................................................................................... 3
3 kVA ................................................................................................................................................ 4
2.2 Operating principle ......................................................................................................................... 5
2.3 Install the UPS ................................................................................................................................ 5
2.3.1 Rack-mount Installation ........................................................................................................... 6
2.3.2 T ow er Installation ..................................................................................................................... 6
2.4 Setup the UPS ................................................................................................................................ 7
2.5 Battery Replacement ...................................................................................................................... 9
2.6 Battery Kit Assembly (option) ........................................................................................................ 10
3. Operation ........................................................................................................................................... 12
3.1 Button operation ........................................................................................................................... 12
3.2 LCD Panel .................................................................................................................................... 13
3.3 Audible Alarm ............................................................................................................................... 14
3.4 LCD display wordings index ......................................................................................................... 14
3.5 UPS Settings ................................................................................................................................ 15
3.6 Operating Mode Description ......................................................................................................... 18
3.7 Faults Reference Code ................................................................................................................. 19
3.8 Warning indicator .......................................................................................................................... 19
4. Troubleshooting .................................................................................................................................. 20
5. Storage and Maintenance .................................................................................................................. 22
5.1 Operation ..................................................................................................................................... 22
5.2 Storage ......................................................................................................................................... 22
6. UPS Specifications ............................................................................................................................. 23
6.1 120V Specifications ...................................................................................................................... 23
6.2 230V Specifications ...................................................................................................................... 24
6.3 Battery Pack Specification ............................................................................................................ 25
Page | iii

1. Important Safety Warnings

Please strictly comply with all warnings and operating instructions in this manual. Save this manual and carefully read the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.

1.1 Transportation

Transport the UPS system only in the original package to protect against shock and impact.

1.2 Preparation

Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate to the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or near a heater.
Do not block ventilation holes in the UPS housing.

1.3 Installation

Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances such as hair dryers to UPS output sockets.
The UPS can be operated by individuals with no previous experience.
The UPS can be operated in TN & TT power distribution.
Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and
close to the UPS system.
Please use only UL-tested, UL-marked power cables to connect the loads to the UPS system.
When installing the equipment, ensure that the sum of the leakage current of the UPS and the
connected devices does not exceed 3.5mA.
Tempe rature Ra ting - Units are considered acceptable for use in a maximum ambient of 40°C (104°F).
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall be easily accessible.
CAUTION: The unit is heavy. Lifting the unit requires a minimum of two people.

1.4 Operation

Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would cancel the protective earth of the UPS system and of all connected loads.
The UPS system features its own internal current source (batteries). The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button and disconnect the mains.
Prevent fluids or other foreign objects from getting inside the UPS system.
The EPO, RS-232 and USB circuits are IEC 60950 safety extra low voltage (SELV) circuits. This
circuit must be separated from any hazardous voltage circuits by reinforced insulation.
Page | 1
Manufacturer
Type
Rated
Toplite (Guangzhou) Technology Battery Co Ltd
NPW45-12
12 V dc, 9.0 Ah
NPW45-12 FR
12 V dc, 7.0 Ah
NPW36-12
12 V dc, 7.2 Ah
NPW36-12 FR
12 V dc, 7.0 Ah
UPS 12360 7 FR
12 V dc, 7.1 Ah
UPS 12460 F2FR
12 V dc, 9.0 Ah
HR 1234W FR
12 V dc, 8.5 Ah
NPW45-12
12 V dc, 8.0 Ah
NPW45-12FR
12 V dc, 8.0 Ah

1.5 Maintenance, Service and Faults

The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
CAUTION - Risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitors such as BUS-capacitors.
To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the battery.
Only persons that are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away fr om the batteries.
CAUTION - Risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, veri fy that no voltage is present!
When c hanging batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may
be toxic.
When replacing batteries, replace with the same type and number of batteries or battery packs.
(MH29104)
CSB Battery Co Ltd (MH14533)
Yuasa Battery (Guangdong) Co Ltd (MH29616)
Do not dismantle the UPS system.
WARNING - A battery can present a risk of electrical shock and high short-circ uit curr ent. T he
following precautions should be observed when working on batteries:
a) Remove watches, rings, or other metal objects.
b) Use tools with insulated handles.
c) Wear rubber gloves and boots. d) Do not lay tools or metal parts on top of batteries. e) Disconnect charging source prior to connecting or disconnecting battery
terminals. f) Determine if battery is inadvertently grounded. If inadvertently grounded, remove source
from ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance.
Page | 2

2. Installation and setup

Model No.
Type
Model No.
Type
SCV-1000x
SCV-1000x-LB
SCV-1500x
SCV-1500x-LB
SCV-2000x
SCV-2000x-LB
SCV-3000x
SCV-3000x-LB
120V version
120V version
240V version
240V version
NOTE: Bef or e installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. NOTE: There are two different types of online UPS: standard and long-run models. Please refer to the following model table.

2.1 Rear panel view

2.1.1 1 kVA or 1.5kVA

2.1.2 2 kVA

Standard
Model
Long-run
Model
Page | 3

3 kVA

120V version
240V version
1. Programmable outlets: connect to non-critical loa ds .
2. Output receptacles: connect to mission-critical loads.
3. AC input
4. Input circuit breaker
5. Emergency power off function connector (EPO)
6. USB communication port
7. RS-232 communication port
8. SNMP intelligent slot
9. External battery connector
10. Output circuit br eaker
11. Modem/phone/network surge protection
Page | 4

2.2 Operating principle

The UPS is composed of mains input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery charger, DC-to-DC converter, battery, dynamic bypass and UPS output.

2.3 Install the UPS

For safety consideration, the UPS is shipped out from factory without connecting battery wires. Before installing the UPS, please follow the below steps to re-connect battery wire.
Step 1 Step 2 Step 3
Step 1: Remove front panel. Step 2: Remove battery panel and re-connect battery wire. Step 3: Put battery panel and cover back to the unit.
This UPS can be either displayed on the desk or mounted in the 19” rack chassis. Please choose proper installation to position this UPS.
Page | 5

2.3.1 Rack-mount Installation CAUTION – Do NOT use the mounting brackets to lift the unit. The mounting brackets are only for

securing the unit to the rack. Install UPS alone
Install UPS and external battery

2.3.2 Tower Installation

Install UPS alone
Install UPS and external battery
NOTE: When installing the UPS or battery pack with feet, keep 2.76in distance from the edge of the unit.
Page | 6

2.4 Setup the UPS

Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. CAUTION: For 1 and 2 kVA models, to reduce the risk of fire, connect only to a circuit provided with 20
amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70.
CAUTION: For 3 kVA models, to reduce the risk of fire, connect only to a circuit provided with 30 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA
70.
Step 2: UPS output connection
There two kinds of outputs: programmable outlets and general outlets. Connect non-critical devices to the programmable outlets and critical devices to the general outlets. During power failure, you may extend the backup time to critical devices by setting shorter backup time for non-critical devices.
Step 3: Communication connection Communication port:
USB port RS-232 port Intelligent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of the communication cable to the USB/RS-232 port and the other end to the communication port of your PC. With the monitoring software installed, you can perform these operations:
Remote Shutdown of UPS
Send shutdown commands to remote computers
Remotely set parameters of the UPS
Set-up the number of battery strings connected
Set-up voltage and frequency ranges
See manual for monitoring software for details.
The UPS is equipped with an intelligent slot perfect for either a SNMP or an AS400 card. Installing either a SNMP or AS400 card in the UPS will provide advanced communication and monitoring options.
NOTE: USB port and RS-232 port can’t work at the same time.
Step 4: Network connection Network/Fax/Phone surge port
Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel of the UPS unit. Connect from “OUT” outlet to the equipment with another modem/fax/phone line cable.
Page | 7
Step 5: Disable and enable EPO function
External Battery Pack
External Battery Pack
UPS
Short terminals for UPS normal operation.
Keep pin 1 and pin 2 closed for UPS normal operation. To activate EPO function, cut the wire between pin 1 and pin 2.
Step 6: External battery connection Connect one end of external battery cable to UPS unit and the other end to battery pack. See below chart for detailed connection.
CAUTION: Connection to External Battery shall be installed by SERVICE PERSONNEL only.
CAUTION – Risk of fire hazard. Step 7: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full
battery run capability during this initial charge period.
Step 8: Install software
Install UPS monitoring software to fully configure UPS shutdown. Follow the steps below to download and install monitoring software:
1. Go to the website http://www.power-software-download.com
2. Click ViewPower software icon and then choose your required OS to download the software.
3. Follow the on-screen instructions to install the software.
4. When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray , near the clock.
Page | 8

2.5 Battery Replacement

NOTICE: This UPS is equipped with internal batteries and only service personnel can replace the
batteries.
CAUTION!! Consider all warnings, cautions, and notes before replacing batteries. NOTE: Upon battery disconnection, equipment is not protected from power outages.
Step 1 Step 2 Step 3
Step 4 Step 5 Step 6
Step Step 7
Step 1: Remove front panel. Step 2: Disconnect battery wire and remove battery panel. Step 3: Pull out the battery box. Step 4: Remove the top cover of battery box and replace the inside batteries. Step 5: After replacing the batteries, put the battery box back to original location and screw in tightly. Step 6: Re-connect the battery wire and screw battery panel back on the unit. Step 7: Put the front panel back on the unit.
Page | 9

2.6 Battery Kit Assembly (option)

Tape
Tape
Blank Battery
NOTICE: Replacement battery pack comes fully assembled from the factory. Consult factory for details. 2-battery kit – 1kVA
Step 1 Step 2
Step 3 Step 4
Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below picture. Step 3: Put assembled battery packs on one side of plastic shells. Step 4: Cover the other side of plastic shell as shown below. Then, battery kit is fully assembled.
3-battery kit – 1.5kVA
Step 1 Step 2
Step 3 Step 4
Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below picture. Step 3: Put assembled battery packs on one side of plastic shells and insert one more defect battery in
the open space. (Blank battery is not connected) Step 4: Cover the other side of plastic shell as shown below. Then, battery kit is fully assembled
Page | 10
4-battery kit – 2kVA
Step 1 Step 2
Step 3 Step 4
Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below picture. Step 3: Put assembled battery packs on one side of plastic shells. Step 4: Cover the other side of plastic shell as shown below. Then, battery kit is fully assembled.
6-battery kit – 3kVA
Step 1 Step 2
Step 3 Step 4
Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below picture. Step 3: Put assembled battery packs on one side of plastic shells. Step 4: Cover the other side of plastic shell as shown below. Then, battery kit is fully assembled.
Page | 11

3. Operation

Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to
mode.
Turn off the UPS: Press and hold this button at least 2 seconds to turn off the
mode.
Switch LCD message: Press this button to change the LCD message for input
Down key: Press this button to display next selection in UPS setting mode.
Switch to bypass mode: When the main power is normal, press ON/Mute and
range.

3.1 Button operation

Button Function
ON/Mute Button
OFF/Enter Button
Button View
turn on the UPS.
Mute the alarm: After the UPS is turned on in battery mode, press and hold
this button for at least 5 seconds to disable or enable the alarm system.
Up key: Press this button to display previous selection in UPS setting mode. Switch to UPS self-test mode: Press ON/Mute button for 5 seconds to enter
UPS self-testing while in AC mode, ECO mode, AECO mode, or converter
UPS in battery mode. UPS will be in standby mode under power normal or transfer to bypass mode if the Bypass is enabled.
Confirm selection key: Press this button to confirm selection in UPS setting
Select Button
ON/Mute + Select
Button
voltage, input frequency, battery voltage, output voltage, output frequency.
Setting mode: Press and hold this button for 5 seconds to enter UPS setting
mode when in Standby and Bypass mode.
Select buttons simultaneously for 5 seconds. UPS will enter bypass mode. This action will be ineffective when the input voltage is out of acceptable
Page | 12

3.2 LCD Panel

Indicates the remaining backup time in numbers. H: hours, M: minute, S: second
Indicates the warning and fault codes. The codes are listed in detail in section 3-5.
Display Function
Remaining backup time information
Indicates the remaining backup time in pie chart.
Fault information
Indicates that warning and fault occurred.
Mute operation
Output & Battery voltage information
Load information
Mode operation information
Indicates that the UPS alarm is disabled.
Indicates the output voltage, frequency or battery voltage. Vac: output voltage, Vdc: battery voltage, Hz: frequency
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%. Indicates overload. Indicates the load or the UPS output is short circuit.
Indicates the UPS is connected to the mains. Indicates the battery is working. Indicates the bypass circuit is working.
Programmable outlets information
Page | 13
Indicates the ECO mode is enabled. Indicates the Inverter circuit is working.
Indicates the output is working.
Indicates that programmable outlets have output voltage.
Battery infor mation
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ESC
Escape
HLS
High loss
LLS
Low loss
BAT
Battery
CF Converter
TP Temperature
CH Charger
SF Site Fault
EP EPO
FU Bypass frequency unstable
EE EEPROM error
Input & Battery voltage information
Indicates the Battery level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the battery is at fault. Indicates low battery level and low battery voltage.
Indicates the input voltage or frequency or battery voltage. Vac: Input voltage, Vdc: battery voltage, Hz: input frequency

3.3 Audible A larm

3.4 LCD display wordings index

Page | 14

3.5 UPS Settings

Parameter
3
Parameter 1
Parameter 2
There are three parameters to set up the UPS.
Interface
Setting
For 200/208/220/230/240 VAC models, you may choose the
120: presents output voltage is 120Vac
Interface
Setting
Interface
Setting
01: Output voltage setting
Parameter 1: Program alternatives. Refer to below table. Parameter 2 and Parameter 3 are the setting options or values for each program.
following output voltage: 200: presents output voltage is 200Vac 208: presents output voltage is 208Vac 220: presents output voltage is 220Vac 230: presents output voltage is 230Vac 240: presents output voltage is 240Vac For 100/110/115/120VAC models, you may choose the following output voltage: 100: presents output voltage is 100Vac 110: presents output voltage is 110Vac 115: presents output voltage is 115Vac
02: Frequency Converter enable/disable
CF ENA: converter mode enable CF DIS: converter mode disable(Default)
03: Output frequency setting
You may set the initial frequency on battery mode: BAT 50: presents output frequency is 50Hz BAT 60: presents output frequency is 60Hz If converter mode enable, you may choose the following output frequency: CF 50: presents output frequency is 50Hz CF 60: presents output frequency is 60Hz
Page | 15
04: ECO enable/disable
Interface
Setting
Interface
Setting
Interface
Setting
Interface
Setting
ENA: ECO mode enable DIS: ECO mode disable(Default)
05: AECO enable/disable
ENA: Advanced ECO mode enable DIS: Advanced ECO mode disable(Default)
06: Bypass mode enable/disable when UPS is off
ENA: Bypass mode is enabled when UPS is off DIS: Bypass mode is disabled when UPS is off (Default)
07: Programmable outlets enable/disable
ENA: Programmable outlets enable DIS: Programmable outlets disable(Default)
Page | 16
08: Programmable outlets setting
Interface
Setting
Interface
Setting
For 200/208/220/230/240 VAC models, you may choose the
85V to 135V.
0-999: setting the backup time limits in minutes from 0-999 for programmable outlets which connect to non-critical devices on battery mode.
09: Acceptable input voltage range setting
following selection for acceptable input voltage range: 110/300 flashing in turns: The acceptable input voltage range is from 110V to 300V. 160/260 flashing in turns: The acceptable input voltage range is from 160V to 260V. 170/270 flashing in turns: The acceptable input voltage range is from 170V to 270V. For 100/110/115/120 VAC models, you may choose the following selection for acceptable input voltage range: 55/150 flashing in turns: The acceptable input voltage range is from 55V to 150V. 80/130 flashing in turns: The acceptable input voltage range is from 80V to 130V. 85/135 flashing in turns: The acceptable input voltage range is from
00: Exit setting
Page | 17

3.6 Operating Mode Description

Operating mode
Description
LCD display
When the input voltage is within acceptable
Online mode
range, UPS will provide pure and stable AC power to output. The UPS will also charge the battery in online mode.
ECO mode (Efficiency Corrective Optimizer)
AECO mode (Advanced Efficiency Corrective Optimizer)
Frequency Converter mode
When the input voltage is within setting range (±3%Vo max), UPS will bypass voltage to output for energy saving. PFC and INVERTER are still active in this mode.
When the input voltage is within setting range (±3%Vo max), UPS will bypass voltage to output for energy saving. PFC and INVERTER are off in this mode.
When input frequency is within 40 Hz to 70 Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz. T he UPS will still charge battery under this mode.
Battery mode
Bypass mode
Page | 18
When the input voltage is beyond the acceptable range or power failure occurs and alarm is sounding every 4 seconds, UPS will backup power from battery.
When input voltage is within acceptable range but UPS is in overload, UPS will enter bypass mode or bypass mode can be set by front panel. Alarm sounds every 10 seconds.
Standby mode
Fault event
Fault code
Icon
Fault event
Fault code
Icon
Bus start fail
01
x
Inverter voltage Low
13
x
Bus over
02
x
Inverter output short
14
Bus under
03
x
Battery voltage too high
27
Bus unbalance
04
x
Battery voltage too low
28
Bus short circuited
05
x
Over temperature
41
x
Inverter soft start fail
11
x
Over load
43
Inverter voltage high
12
x
Warning
Icon (flashing)
Alarm
Battery is not connected
Sounding every second
EPO enable
Sounding every second
Over temperature
Sounding every second
Charger failure
Sounding every second
EEPROM error
Sounding every second
Fault mode
UPS is powered off and without output power, but the battery still can be charged.
The UPS is in fault mode when no output power is supplied from the UPS and the fault icon flashes on the LCD display, although the UPS information can be displayed on the screen.

3.7 Faults Reference Code

3.8 Warning indicator

Low Battery Overload
Over Charge Site Fault
Battery fault Out of bypass voltage range Bypass frequency unstable
Sounding every second Sounding twice every second
Sounding every second Sounding every second
Sounding every second Sounding every second Sounding every second
Page | 19

4. Troubleshooting

Symptom
Possible cause
Remedy
No indication and alarm even though
The AC input power is not
connected properly.
Check if input power cord
firmly connected to the mains.
The AC input is connected to
the UPS output.
Plug AC input power cord to
AC input correctly.
second.
sounding every second.
every second.
Fault code is shown as 27 and the
and alarm is continuously sounding.
Fault code is shown as 28 and the
and alarm is continuously sounding.
Remove excess loads from
UPS output.
UPS is overloaded. Devices
network via the Bypass.
After repetitive overloads, the
fed directly by the mains.
Fault code is shown as 43 and The
and alarm is continuously sounding.
Fault code is shown as 14 and the
The UPS shut down
output.
Fault code is shown as 01, 02, 03, 04,
A UPS internal fault has
If the UPS system does not operate correctly, use the table below to check problem.
the main is normal.
The icon is flashing and the warning code is lighting on LCD
display. Alarm is sounding every
The icon is flashing and is lighting on LCD display. Alarm is
The icon and flashing on LCD display and alarm is sounding
icon is lighting on LCD display
icon is lighting on LCD display
The icon and is flashing on LCD display and alarm is sounding twice every second.
EPO function is activated.
Line and neutral conductors of
UPS input are reversed.
The external or internal
battery is incorrectly
connected.
Battery voltage is too high or
the charger is at fault.
Battery voltage is too low or
the charger is fault.
UPS is overloaded
connected to the UPS are fed
directly by the electrical
Set the circuit in closed position to disable EPO
function.
Rotate mains power socket by 180° and then connect to UPS
system.
Check if all batteries are
connected properly.
Contact the manufacturer.
Contact the manufacturer.
Remove excess loads from
UPS output.
icon is lighting on LCD display
icon is lighting on LCD display. Alarm is continuously sounding.
11, 12, 13 and 41 on LCD display and alarm is continuously sounding.
Page | 20
UPS is locked in the Bypass
mode. Connected devices are
The UPS shut down
automatically because of
overload at the UPS output.
automatically because short
circuit occurs on the UPS
occurred. There are two
possible results:
1. The load is still supplied,
but directly from AC power via
bypass.
2. The load is no longer supplied by power.
Remove excess loads from UPS output first. Then shut
down the UPS and restart it.
Remove excess loads from
UPS output and restart it.
Check output wiring and if
connected devices are in short
circuit status.
Contact the manufacturer
Symptom
Possible cause
Remedy
Battery backup time is shorter than
nominal value
Charge the batteries for at
manufacturer.
Contact the manufacturer to
replace the batteries.
Fault code is shown as 05 on LCD
cut off.
Consult the manufacturer. If
mosfet will be damaged.
Batteries are not fully charged
Batteries defective
least 5 hours and then check
capacity. If the problem still
persists, consult the
display. At the same time, alarm is continuously sounding and output is
A UPS internal fault has
occurred and BUS is short
circuited.
the UPS power is on again
before repair, the DC/DC
Page | 21

5. Storage and Maintenance

Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C (-13°F - 104°F)
Every 3 months
1-2 hours
40°C - 45°C (104°F - 113°F)
Every 2 months
1-2 hours

5.1 Operation

The UPS system contains no user-serviceable parts. If the battery service life (3-5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact the manufacturer for replacement battery packs.

5.2 Storage

Before storing, charge the UPS for 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:
Be sure to deliver the spent battery to a rec yc l ing facility.
Page | 22

6. UPS Specifications

VA
1000 VA
900 VA
1500VA
1250VA
2000 VA
1700 VA
3000 VA
2500 VA
W
900 W
810 W
1350W
1125W
1800 W
1530 W
2700 W
2250 W
INPUT
Low Line
Comeback
High Line
Transfer
High Line
Comeback
Frequency Range
50Hz/ 60Hz
Power Factor
0.99 @normal voltage
OUTPUT
Output Voltage
100*/110*/115*/120VAC
AC Voltage Regulation
± 1%
Frequency Range
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range
50Hz ± 0.5% or 60Hz ± 0.5% (Bat. Mode)
Current Crest Ratio
(CF)
AC to DC
Zero
Inverter to
Bypass
EFFICIENCY
AC Mode
86% (typical), 88% (peak)
88% (typical), 90% (peak)
Battery Mode
83% (typical), 86% (peak)
85% (typical), 88% (peak)
BATTERY
Numbers
2 3 4
6
Typical Recharge Time
4 hours recover to 90% capacity (for standard model only)
Charging Current (max.)
1 A
6A or 4A
1 A
6A or 4A
1 A
6A or 4A
1 A
6A or 4A
Charging Voltage
27.4 VDC ± 1%
41.1 VDC ± 1%
54.7 VDC ± 1%
82.1VDC ± 1%
INDICATORS
LCD
UPS status, Load level, Battery level, Input/Output/battery info, Discharge time and Fault indicators
ALARM
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
PHYSICAL
Dimension, DxWxH (in)
16.44 x 17.24 x 3.45
20.38 x 17.24 x 3.45
20.38 x 17.24 x 3.45
27.74 x 17.24 x 3.45
Net Weight (lbs)
29
20
42
26
47
28
65
33
ENVIRONMENT
Humidity
20-90 % RH @ 0- 40°C (non-condensing) (32°F - 104°F)
Noise Level
Less than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USB
Supports Windows 2000/2003/XP/Vista/2008/7, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser

6.1 120V Specifications

MODEL (SCV) 10001 10001-LB 15001 15001-LB 20001 20001-LB 30001 30001-LB
Capacity
Rated
voltage
Low Line
Transfer
80 VAC/70 VAC/60 VAC/55 VAC ± 5 %
(based on load percentage 100%-80% / 80%-70% / 70%-60% / 60%-0)
100VAC-120VAC
Voltage
Range
85 VAC/75 VAC/65 VAC/60 VAC ± 5 %
150 VAC ± 5 % 142 VAC ± 5 %
5:1 (max.)
Harmonic Distortion
(THDU)
8% max (Batt. mode before shut down)
2% (Linear load)
Transfer
Time
4 ms (Typical)
Waveform (Batt. Mode) Pure Sine wave
Battery Type 12V/9Ah
Depending
on application
12V/9Ah
Depending on
application
12V/9Ah
Depending
on application
12V/9Ah
*Derate capacity to 95% when the output voltage is adjusted to 115VAC. Derate capacity to 90% when the output voltage is adjusted to 110VAC. Derate capacity to 80% when the output voltage is adjusted to 100VAC.
Page | 23
Depending
on application

6.2 230V Specifications

VA
1000 VA
1500VA
2000 VA
3000 VA
W
900 W
1350W
1800 W
2700 W
INPUT
Low Line
Comeback
High Line
Transfer
High Line
Comeback
Frequency Range
40Hz ~ 70Hz
Power Factor
0.99 @normal voltage
OUTPUT
Output Voltage
200/208/220/230/240 VAC
AC Voltage Regulation
± 1%
Frequency Range
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range
50Hz ± 0.5% or 60Hz ± 0.5% (Bat. Mode)
Current Crest Ratio
(CF)
AC to DC
Zero
Inverter to
Bypass
Waveform (Batt. Mode)
Pure Sine wave
EFFICIENCY
AC Mode
87%
87%
88%
88%
Battery Mode
85%
85%
86%
85%
ECO Mode
94%
94%
95%
97%
BATTERY
Numbers
2 3 4
6
Typical Recharge Time
4 hours recover to 90% capacity (for standard model only)
Charging Current
(max.)
1A/2A/
4A/8A
1A/2A/
4A/8A
1A/2A/
4A/8A
1A/2A/
4A/8A
Charging Voltage
27.4 VDC ± 1%
41.1 VDC ± 1%
54.7 VDC ± 1%
82.1VDC ± 1%
INDICATORS
LCD
UPS status, Load level, Battery level, Input/Output/battery info, Discharge time and Fault indicators
ALARM
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
PHYSICAL
Dimension, DxWxH (in)
16.44 x 17.24 x 3.45
20.38 x 17.24 x 3.45
20.38 x 17.24 x 3.45
25.10 x 17.24 x 3.45
Net Weight (lbs)
29
20
42
26
47
28
65
33
ENVIRONMENT
Humidity
20-90 % RH @ 0- 40°C (non-condensing) (32°F - 104°F)
Noise Level
Less than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USB
Supports Windows 2000/2003/XP/Vista/2008/7, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
MODEL (SCV) 10002 10002-LB 15002 15002-LB 20002 20002-LB 30002 30002-LB
Capacity
Low Line
Transfer
Voltage
Range
Harmonic Distortion
Transfer
Time
Rated
voltage
(THDU)
220-240 VAC
160 VAC/140 VAC/120 VAC/110 VAC ± 5 %
(based on load percentage 100%-80% / 80%-70% / 70%-60% / 60%-0)
170 VAC / 150 VAC / 130 VAC / 120 VAC ± 5 %
300 VAC ± 5 % 290 VAC ± 5 %
5:1 (max.)
2% (Linear load)
6% max (Batt. mode before shut down)
4 ms (Typical)
Battery Type 12V/9Ah
Depending
on application
1 A
* Derate capacity to 80% when the output voltage is adjusted to 200VAC/208VAC.
12V/9Ah
1 A
Depending on
application
12V/9Ah
1 A
Depending
on application
12V/9Ah
1 A
Depending
on application
Page | 24

6.3 Battery Pack Specification

Model
SCV-BAT-1K
SCV-BAT-1.5K
SCV-BAT-2K
SCV-BAT-3K
Used with UPS Models
Battery Type
12V 9Ah
12V 9Ah
12V 9Ah
12V 9Ah
Battery Numbers
4 6 8
12
Dimensions (DxWxH)
Net Weight(LBS)
37.7
54.6
63.9
90.8
1K 1.5K 2K 3K
15.78 x 17.24 x 3.45 19.72 x 17.24 x 3.45 19.72 x 17.24 x 3.45 24.44 x 17.24 x 3.45
NOTE: Battery cabinet should be used with corresponded UPS.
Page | 25