JOST TK 5 OPERATING MANUAL

OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 1 of 20
22.12/03/Siew
TK 5
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 2 of 20
22.12/03/Siew
1 ELECTRICAL SAFETY
THE TK5-CONTROL UNIT CONDUCTS DANGEROUS VOLTAGE WHEN CONNECTED TO THE MAINS POWER SUPPLY.
WHEN IN OPERATION, THE TK5-CONTROL UNIT MUST BE EARTHED VIA A GROUND CONDUCTOR CONNECTED TO THE PE MASS TERMINAL.
THE TK5-CONTROL UNIT CAN STILL BE UNDER OUTSIDE VOLTAGE EVEN WHEN IT IS SWITCHED OFF.
BEFORE STARTING WORK, CHECK THAT THE TK5-CONTROL UNIT IS NOT UNDER VOLTAGE BY MEASURING THE MAINS POWER CONNECTION TERMINALS WITH A VOLTMETER.
THE ELECTRICAL INSTALLATION MAY ONLY BE PERFORMED BY AN APPROVED ELECTRICIAN.
Warning symbols
For your own safety, please pay particular attention to the instructions marked with the symbols below:
Dangerous voltage
General warning
!
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 3 of 20
22.12/03/Siew

2 NOTES ON THE EMVG ACT

The CE-mark which has been applied refers to the German EMVG Act of 9/11/1992 concerning electro-magnetic compatibility (EMC).
The TK5-control unit must be installed by personnel trained in the requirements of EMC.
The TK5-control unit is compliant to the following standards / normed documents:
1. EN 50081-1
2. EN 50082-2
Providing the precautions detailed below are taken, the TK5­control unit may be deployed:
- in the home, businesses, trade premises and in small firms
- in industrial applications
Precautions to be taken:
(as detailed in the circuit diagram in the Annex)
All control lines must be screened and laid on one side of the
control unit.
The line which connects the TK5-control unit and the drive must
be screened and laid double-sided.
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 4 of 20
22.12/03/Siew

3 TABLE OF CONTENTS

1 ELECTRICAL SAFETY
2 NOTES ON THE EMVG ACT ...................................................................................................................3
3 TABLE OF CONTENTS .............................................................................................................................4
4 FOREWORD ................................................................................................................................................5
5 INTENDED USE ..........................................................................................................................................6
6 METHOD OF WORKING..........................................................................................................................6
7 INSTALLATION .........................................................................................................................................7
7.1 DESIGN ....................................................................................................................................................7
7.2 NOTES ON INSTALLATION .................................................................................................................7
7.3 CABLING .................................................................................................................................................8
7.4 CONNECTIONS .......................................................................................................................................8
7.5 PARTICULARITIES ................................................................................................................................9
7.5.1 Controller release...............................................................................................................................9
7.5.2 Output-side switching ........................................................................................................................9
7.5.3 Switching the target value signal .....................................................................................................9
7.5.4 Coarse/fine current applications ......................................................................................................9
7.5.5 Manual/automatic application...........................................................................................................9
7.5.6 Applications with multiple drives ....................................................................................................10
.....................................................................................................................2
8 COMMISSIONING ...................................................................................................................................10
8.1 CHECKS BEFORE TURNING ON THE MAINS VOLTAGE .............................................................10
8.2 TURNING ON THE MAINS VOLTAGE .............................................................................................. 10
9 ADJUSTMENT / RECONFIGURATION ...............................................................................................12
9.1 POSITION OF ADJUSTING ELEMENTS AND COMPONENTS.......................................................12
9.2 EXPLANTION OF ADJUSTING ELEMENTS .....................................................................................12
9.3 ADAPTING THE TARGET VALUE SOURCE ....................................................................................13
9.4 ADAPTING TO THE MAINS VOLTAGE ............................................................................................ 13
9.5 CALIBRATING THE CONTROL UNIT ...............................................................................................14
10 MAINTENENCE........................................................................................................................................14
11 NOTIFYING DEFECTS............................................................................................................................14
12 AUXILIARY DEVICES ............................................................................................................................16
13 ANNEX........................................................................................................................................................ 17
13.1 TECHNICAL DATA ..............................................................................................................................17
13.2 TYPE CODE ...........................................................................................................................................18
13.3 SCOPE OF SUPPLY ...............................................................................................................................19
13.4 FUSE .......................................................................................................................................................19
13.5 DIMENSIONS.........................................................................................................................................19
13.6 CIRCUIT DIAGRAM .............................................................................................................................20
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 5 of 20
22.12/03/Siew
4 FOREWORD
These instructions apply solely to TK5-control units.
It is essential that these instructions have been read and understood before starting installation and commissioning work.
The limit values stipulated in the technical data must be complied with when the control unit is deployed.
The guarantee given for the manufacturer's drives/machines does not include defects which are caused by misuse or false operation of this control unit.
The instructions are sub-divided into different chapters as detailed in the table of contents.
Please read chapter 1 "Electrical safety“ and chapter 2 "Notes on the EMVG Act“ before starting work with the TK5-control unit.
It is essential that the operator is familiar with the contents of these instructions before using the drive/machine or before making works­specific adjustments and settings.
In case you have any questions concerning the TK5-control unit, please contact the manufacturer directly.
The manufacturer reserves the right to make changes to products without giving prior notice.
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 6 of 20
22.12/03/Siew
5 INTENDED USE
The TK5-control unit is designed for operating oscillation equipment with the manufacturer's magnetic drives of type JD connected to an AC power system.
The TK5-control unit allows the amplitude of such equipment to be infinitely adjusted - virtually from 0 to the maximum.

6 METHOD OF WORKING

Using the supplied potentiometer or an external 0/ - 20 mA or a voltage signal 0 – 10 V DC as the source of the target value, the amplitude can be infinitely adjusted, and thus also the conveying performance of magnetic oscillation equipment within determined limits (minimum and maximum values).
The target value signal which has been set arrives at a smooth start­up and linearisation stage and is subsequently compared to the actual value signal. The actual value signal here is the voltage output by the control unit to the drive. The differential signal (control deviation) is passed to a controller, thereby generating the actuating signal for controlling the phase angle. The actuating signal determines the point in time at which the thyristor triggers.
For the purpose of galvanic separation, the triggering pulses are fed to the thyristor via an optocoupler. Triggering takes place within the positive sinusoidal half-wave. The phase angle in the sinusoidal half­wave controls the electrical power made up of voltage and current which is fed to the oscillation system. Fluctuations of ± 10 % in the mains voltage are thus compensated to approx. ± 2 % whilst the amplitude remains more or less constant.
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 7 of 20
22.12/03/Siew
7 INSTALLATION
7.1 DESIGN
The main components of the TK5-control unit are shown below:
1 Plexi-glass cover 2 Connecting terminals for mains power/drive/control signals
(removable) 3 Semi-conductor fuse 4 Thyristor with cooling element 5 Rating plate 6 Mounting holes
7.2 NOTES ON INSTALLATION
Cooling
The TK5-control unit is cooled by natural convection. In order to ensure a sufficient flow of air, the unit should be installed in the vertical position allowing for the minimum spacings stated in the figure opposite. The cooling air should be as clean as possible and not contain aggressive substances. If the cooling air contains dust, the cooling surfaces must be cleaned regularly.
:
15 mm
TK5-
Cont rol­unit
10 mm
Fastening:
The TK5-control unit can be fastened to a normal profile rail using a rapid-fastening rail clip.
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 8 of 20
22.12/03/Siew
7.3 CABLING
Dimensions of power and drive cables:
A cable length of 150 m between the control unit and the drive has been foreseen. If the distance is greater, the cable cross section must be increased accordingly.
Type of
control unit
TK 5 /... 10 1.5
1)
Observe the local regulations for earthing and cables.
NOTE: The German EMVG Act states that the cable between
the control unit and the drive must be screened sheath must have a large area on both sides and be laid short to protective conductor potential.
Control cables:
The control cables must be screened. We recommend sheathed, multi-strand, flexible cables with a conductor cross-section of 0.5 /
0.75 mm² for the control lines.
NOTE: Connect the cable sheath one-sided on the TK5-control
unit to the protective conductor potential . Arrange control cables so that there is at least 0.5m spacing to the drive cable to prevent interference.
7.4 CONNECTIONS
1,5mm² is the cable cross-section able to be connected to both terminal strips. Please refer to the circuit diagram in the Annex or to the note packed in with the control unit for the connection assignment of the power, drive and control cables.
Pre-fuse [A, delayed action]
Cross-section of power and drive cables 1) [mm²]
. The
NOTE: If the target value potentiometer is used, please ensure
that the connections are made in the correct sequence.
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 9 of 20
22.12/03/Siew
7.5 PARTICULARITIES
7.5.1 Controller release
The TK5-control unit is equipped with an input for releasing the controller (control terminals 14/15).
The controller is blocked when the terminals are open. The drive is at standstill.
The controller is released when the terminals are bridged. The drive vibrates.
If the drive is switched off via controller release, the mains power is not cut off to connection terminals 3/4.
If the technical process requires the drive to be switched on and off frequently, then "controller release“ should be used instead of line-side switching. The control unit remains connected to the mains voltage in this case.
7.5.2 Output-side switching
Switching in the output is only admissible when the control unit is switched off (line-side or via controller release). Switches or fuses with the corresponding maximum loading then need to be deployed.
The V-fuse unit switching between the control unit and the drive. It must remain on the drive when the control unit is switched off.
7.5.3 Switching the target value signal
If switching is to take place in the target value lines, then relays with gold contacts or hermetically encapsulated relays should be used due to the low switching voltage (U 10V=, I 20mA). In the case of mA signals, ensure that the load resistor is built into the TK5-control unit.
7.5.4 Coarse/fine current applications
A target value specification for coarse/fine current can be enabled for dosing and weighing applications. If a potentiometer is used for specifying the target value, a second potentiometer is required (-> order separately). The first potentiometer then specifies the target value for coarse current and the second specifies the target value for fine current. An example circuit is shown in the circuit diagram in the Annex. Terminals 26/27 then serve solely as support terminals for the sliders, and are thus not used on the control unit. An external target value signal (mA or V) can likewise be used for the aforesaid applications. For example, a signal of 2V corresponds to the fine current value and 8V to the coarse current value.
(see chapter "Auxiliary devices“) must be used when
7.5.5 Manual/automatic application
Manual/automatic application is understood to mean that the actual target value (->automatic) comes from an external source (controller / PLC as mA or V). A target value can be supplied from a manual potentiometer instead of the automatic target value from the control unit by switching over (-> manual). An example circuit is shown in the Annex "circuit diagram".
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 10 of 20
22.12/03/Siew
The S3 selector switch (target value source) must then be set to the automatic target value signal.
7.5.6 Applications with multiple drives
If more than one drive is to be connected to the control unit, this is possible in the majority of cases by simply switching the drives in parallel. The admissible nominal current for the control unit may then not be overshot. In certain applications it is necessary to run the individual drives via separating diodes Please consult the manufacturer.
8 COMMISSIONING
8.1 CHECKS BEFORE TURNING ON THE MAINS VOLTAGE
The TK5-control unit is set in the manufacturer's works to the oscillation equipment supplied and can therefore be deployed without needing any further adjustments. An exception to this is if the notice plate on the control unit refers to a resetting.
(see chapter "Auxiliary devices“).
The setting trimmer Umin / Umax and the S1 selector switch in the TK5-control unit may not be altered.
!
Should it be necessary to make settings other than those delivered, please read the chapter "Adjustment/reconfiguration".
Check the following points before switching on the mains power supply:
1. The control unit must be connected to the associated oscillation equipment.
2. The specifications made on the control unit's rating plate must agree with those for the drive. It is especially important that the control unit's output frequency agrees with the oscillation frequency of the drive.
3. The nominal mains power voltage must lie within the voltage range stated on the rating plate (entered under "V" on the rating plate).
4. The control unit must be earthed via the PE terminal.
5. Action must be taken to comply with the EMVG Act (see chapter 2)
6. The mains power cable must be connected to terminals 1/2/PE.
7. The drive cable must be connected to terminals 3/4/PE.
8. The appropriate target value transmitter must be connected (see the type designation on the rating plate and the explanation of the type code in the Annex)
9. Set the target value transmitter to minimum ( 0/4 mA, 0V, / target value potentiometer to 0)
10. Terminals 14/15 must be bridged if an external Controller release is not connected. Only when an external controller release is connected: Connect a make contact to terminals 14/15 and remove the jumper
8.2 TURNING ON THE MAINS VOLTAGE
The points listed under 8.1 must have been performed before the mains voltage is turned on.
The Mains voltage can now be switched on.
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 11 of 20
22.12/03/Siew
The TK5-control unit now conducts voltage which can cause fatal injuries.
The green LED above terminal 27 should now be lit.
The oscillation equipment should now operate at minimum amplitude. The target value signal can now be slowly adjusted to maximum. Once the maximum target value has been reached, the oscillation equipment should operate at the amplitude stated in the technical documentation for the machine.
When increasing the target value signal, pay attention
!
Once running smoothly, the target operating value can be set and material fed to the conveyor.
If it is necessary to make subsequent adjustments to the control unit to take account of the prevailing conditions, please refer to the chapter "Adjustment/reconfiguration".
to the operating noise made by the oscillation equipment. If knocking sounds can be heard, turn the oscillation equipment off immediately. The equipment can be switched back on once the error has been found and rectified.
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 12 of 20
22.12/03/Siew

9 ADJUSTMENT / RECONFIGURATION

9.1 POSITION OF ADJUSTING ELEMENTS AND COMPONENTS
Thyristor + heat sink
Choke
Fuse
Mains trans­former
Terminal strip
View with the plexi-glass cover removed.
LED: Green for "voltage “on
9.2 EXPLANTION OF ADJUSTING ELEMENTS
IMPORTANT NOTE:
!
Uncontrolled changes to the adjusting elements can cause the control unit to malfunction.
Before settings are changed, it is essential to read the following points through carefully.
Trimming potentiometers:
2 Trimming potentiometers are arranged on the control card.
Function of the trimming potentiometers:
Umax: Setting for the maximum output voltage *)
Umin: Setting for the minimum output voltage *)
*) Both trimmers are locked and may not
be altered without
consultation.
S3 selector switch (DIP switch):
There is a 4-way selector switch (S3) – a so-called DIP switch – fitted to the control card.
Each of these switches is a slide switch which are number 1-4 from left to right.
S1 slide switch:
SW 3
SW 3
SW 3
9.3 ADAPTING THE TARGET VALUE SOURCE
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
This switch serves to adapt the mains voltage and has two positions. The switch position is locked. Changing this incorrectly can lead to the destruction of the control unit! See 9.4
The S3 selector switch serves to adapt the control unit to the various target value sources.
Do not touch the slide switches until the mains voltage
!
Position of SW 3 (1-3):
OFF
OFF
OFF
has been switched off. The plexi-glass cover must be removed from the control unit to change their positions.
does not
1234
1234
1234
require the trimmers Umax/Umin to be reset.
(Installation set)
Target value 0...10 V via terminal 7/8 and/or target value potentiometer on 5/7
Target value 0...20 mA via terminal 7/8
Target value 4...20 mA via terminal 7/8
NOTE: Changing the setting of S3
S-TK5001 13 of 20
22.12/03/Siew
9.4 ADAPTING TO THE MAINS VOLTAGE
There is a slide switch (S1) on the control card to select the mains voltage.
The power to the control unit must before switch S1 is operated. Make sure there is no voltage ! The plexi-glass cover must be removed from
!
NOTE: Changing the mains voltage requires the trimmers
the control unit.
Selecting a false mains voltage will destroy the control unit. The drive must be selected to suit the mains voltage.
Umax/Umin to be reset
manufacturer's service department.
. Should only be done by the
be switched off
9.5 CALIBRATING THE CONTROL UNIT
10 MAINTENENCE
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
Switch position for mains voltage between 100V and 120VAC.
Switch position for mains voltage between 200V and 240VAC.
An amplitude measuring gauge and a TRMS voltmeter are required to calibrate the control unit. Consult with the manufacturer's service department.
The TK5-control unit generally does not require any maintenance.
However, in particularly dusty environments regular cleaning is essential. The drive's power draw should be measured at each service with a TRMS ammeter (real-effective value). The maximum amplitude of the oscillation equipment should also be checked (nominal values are stated in the drive documentation).
S-TK5001 14 of 20
22.12/03/Siew
11 NOTIFYING DEFECTS
Before notifying defects to our service department, please make a note of the following data:
Type designation of the control unit (see rating plate)
No. of the control unit (see rating plate)
Mains voltage (measured)
Drive data
Noticeable defects
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 15 of 20
22.12/03/Siew
This page has been left blank on purpose
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 16 of 20
22.12/03/Siew
12 AUXILIARY DEVICES
The following auxiliary devices are available for the TK5-control unit:
Fault warning unit "H“:
Current monitor to monitor the drive current. A fault warning contact is made if a limit value is undershot because of a wire break, for example
Target voltage source "Q":
Provides a constant voltage of 10V= to feed target value potentiometers
Fuse unit "V":
Required to protect the drive if switching is made between the control unit and the drive.
Separating diodes "F":
If more than one drive is connected to the control unit, it can be necessary to deploy this component in order to prevent mutual electrical interference
Protective device "N":
Required to limit the current for explosion-protected drives. It must be connected between the control unit and the explosion­protected drive.
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 17 of 20
22.12/03/Siew
13 ANNEX
13.1 TECHNICAL DATA
Nominal mains voltage 115, 230 V AC
(1Ph+N), switchable
Mains voltage ranges 100 - 120 V AC
200 - 240 V AC
Admissible voltage fluctuations + 5 %, (ref. to nominal voltage)
- 10 %, (ref. to nominal voltage)
Nominal mains frequency 50/60 Hz; ± 1 %
Max. output current 5 A
Output frequency As nominal mains frequency
Power loss Pv (W) max. 6 W
Internal voltages ± 12V stabilised, short-circuit
proof +10V stabilised, short-circuit proof for max. 2 target value potentiometers (5 KΩ)
Target value input 0/4 - 20 mA, load 250 Ω;
0 - 10 V; selectable via DIP switch
Target value integrator Permanently set
Target value linearisation Permanently set
Warning lights 1 x LED; for operating voltage
Controller release Via potential-free external make
contact,
OTHER DATA
Approvals EN 50081-1, EN 50082-2
VBG4
Semi-conductor fuse 10 AFF (superflink), 5x20mm
Cooling method Air self-cooling
Max. installation altitude 1000 m (over 1000m consult
the manufacturer)
Admissible humidity DIN 40040 F
Protection system DIN 40050 IP 21
Operating temperature 0°C to + 45°C
13.2 TYPE CODE
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
Storage and transport temperature - 10°C to + 85°C
Installation position Vertical Cont. admissible vibration level 0.5 G
Weight 700 g
Dimensions 110 112 x 197 mm (WxD) base area
The designation on the rating plate of the TK5-control unit is composed as follows:
(Installation set)
40 mm high
Only for special models yyy stands for 000 - 999
Additional connection 0 = No separating diodes 1 = Separating diode connection
Target value signal 1 = Potentiometer 2 = 0 - 10 V 3 = 0 - 20 mA 4 = 4 - 20 mA 5 = Special signal 6 = Universal device, 1 and 2 pre-set
Type of control unit K = Voltage return
Output frequency = mains power frequency 50, 60 Hz
Exxx = installation set if installed always E000
Nominal mains power voltage 115, 230 V
Max. output current 5 = 5 A
Type of control unit
S-TK5001 18 of 20
22.12/03/Siew
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 19 of 20
22.12/03/Siew
13.3 SCOPE OF SUPPLY
The following items are supplied with the TK5-control unit:
1 x target value potentiometer with scale and rotary knob
1 x circuit diagram
1 x spare fuse 10A FF
13.4 FUSE
Turn off the mains power before changing the fuse
The pre-installed fuse (superflink)
serves to protect the thyristor in case of a short circuit. Only use the same type when changing the fuse.
Fuse: 10 A FF (superflink) 5 x 20 mm
13.5 DIMENSIONS
TK5-control unit:
198
110
Potentiometer 5 K with scale and rotary knob:
O 28mm
a
b
c
M10
O 6mm
16
88
Scale : 64 x 64 mm Centre hole: 11 mm
Rotary knob : 36 mm Height : 20 mm
OPERATING INSTRUCTIONS FOR
TK5 – CONTROL UNIT
(Installation set)
S-TK5001 20 of 20
22.12/03/Siew
CIRCUIT DIAGRAM
MAINS
The EMVG Act states that
screened lines, as shown, must
be deployed.
Target value
(see below)
Controller release
OPEN : STOP
DRIVE
TARGET VALUE CONNECTION
MANUAL-AUTO SWITCHOVER
INPUT
NOTES:
POTI R1: APART PROVISION WITH SCALE AND KNOB ADMISSIBLE CABLE LENGTH 150 m
POTI R2: ORDER SEPARATELY
Fine
Coarse
Customer supply
Loading...