DC Control 146 Field Loss Relay
Series 146 Relays provide excellent protection against overspeeding on DC shunt or compound wound motors in the event of an open circuit in the
field. The relay coil is connected in series with the shunt field while the re-lay motor contacts are in the motor control circuit. The relay coil is de-energized if the field opens and the relay contacts open to disconnect the motor from line. Where shunt or compound wound motors are operated at light loads or not rigidly connected to the load, field loss relays provide protection against motor and load damage from overspeeding. The Series 146 Relay is a UL recognized component. Coils are designed to carry maximum field current continuously. Relays are factory adjusted to pick-up at one tenth of the maximum field current amps. listed. Drop-out is approximately 62% of the pick-up value. Other pick-up values on special order.
Field Loss Relays (DC) - 146 300V DC Max.
Max. Field Current Amps
.25 .5
1.0
1.5
2.0
2.5
3.0
4.0
5.0
6.0
7.0
Relay Pick-Up Amps
.025 .050 .100 .150 .200 .250 .300 .400 .500 .600 .700
Relay Drop-Out Amps
.0155 .031 .062 .093 .124 .155 .186 .248 .310 .372 .434
146-25 146-50 146-100 146-150 146-200 146-250 146-300 146-400 146-500 146-600 146-700
$
660.
660.
660.
660.
660.
660.
660.
660.
660.
660.
660.
Max. Field Current AmpsCatalog No. Price
8.0
9.0
10.5
12.0
13.5
15.0 22 27 35 65 80
Relay Pick-Up Amps
.800 .900
1.050
1.200
1.350
1.500
2.200
2.700
3.500
6.500 8
Relay Drop-Out Amps
.496 .559 .651 .744 .836 .930
1.320
1.620
2.100
4.000
4.96
Catalog No. Price 146-800
146-900 146-1050 146-1200 146-1350 146-1500 146-2200 146-2700 146-3500 146-6500 146-8000
$
1180.
660.
660.
660.
660.
660.
660.
764.
764.
764.
764.
Engineering Data:
Dimensions -Approximate
Ordering Information
Use complete catalog number when ordering. Contact Rating: Single pole double break normally open contacts, rated at 0.7 amps., 250 V DC Max.