Engineering Data - Diagrams ................................................................B50
Catalog Ordering Data ..........................................................................B60
Series 5000 AC NEMA Rated Contactors.............................................B65
4
3
0
B1
Page 2
TM - NEMA Control
General Information
B
Auxiliary Contacts -Auxiliary contact blocks
may be added with the starter in place, without
tools. The same block is used on sizes 00
thru size 4 as either N.O. or N.C.. A total of 4
auxiliary contacts can be added. The addition
of side mounting kits allows a total of 8
auxiliary contacts throughsize 4.
Power Pole - Full rated
power poles, N.O. or N.C.
through NEMA size 4, may
be field added, without coil
change. A tie pole with 2 N.O.
contacts is available for twospeed single winding
(consequent pole)
motor applications.
Operating Coils - All coils are encapsulated. Size 00
thru 4 are plug-in type and each is factory tested twice,
for long reliable service. Coil changes are not required for any combination of add-on accessories.
Power Wiring - Up-front
terminals and straight
through design make power
wiring easy. As few as 3
connection points per pole
reduces the possibility of
loose connections and
contributes to the reliability of
the starter.
Contact Inspection - Loosen 2
captive screws and remove the
contact carrier, through size 4.
Adapter Plate - Allows use of Type TM
starters in place of other make s thru size
2, without drilling new mounting holes.
The adapter plate holes align with those
of most other starters thru size 2 - proof of
the TM compact design.
Reliability - The basic contactor design, using polysulphone and teflon
guides, melamine and rosite moldings along with stainless steel springs,
provides exceptional electrical and mechanical life. The operating state
is clearly visible from the front, indicated by the position of the contact
carrier.The contactor is easily operated from the front for circuit checking.
Overload Relay - Available with ambient compensation (green reset rod) or
non-ambient compensation (red
reset rod). An easily accessible +
15, adjust-ment knob can be locked
at the 100% setting. High accuracy
of repetitive trip is assured by
factory testing every unit twice.
Heaters - Heater numbers are stamped on the surface
for easy identification. The same heaters are used for
TM & HP series overload relays for both ambient and
non-ambient compensated overload relays.
3
8
0
Versatility - Uniform mounting dimensions Add-on auxiliary
contacts Plug-in coils Accessories, such as power pole,
mechanical interlock pro-vides maximum versatility and flexibility of
inventory panel layout and installation. Self-rising saddle-clamps
are included on all control terminals for quick wiring.
B2
Page 3
NEMA Control - TMGeneral Information
B
3
8
0
Compact Size - Integral overload relay design, with straight
through power cable design, provides compact overall size.
Straight through wiring reduces overall panel area for a
NEMA wired device. Uniform mounting dimensions, along with
mechanical interlock design, makes reversing devices and other
mechanically interlock devices the same height and depth as
nonreversing. This allows intermixing in rows and saves panel
space.
Uniform Mounting Dimensions - Only 2 mounting plate sizes for 00
through 4 starters. One mounting plate for sizes 00-2, the second for
sizes 3 & 4. This provides great flexibility for intermixing
starter sizes in rows and reduces panel layout time.
Pilot Device Kits - Operator devices may be added in the field. Push
button and pilot light kits for non-combination enclosures are suitable for
use in NEMA Type 1, 4 & 12. This simplifies selection and increases
flexibility.
B3
Page 4
B
TM - NEMA Control
Non-Reversing
Bulletin 6013 NEMA Starters.
Bulletin 7707 NEMA Contactors.
NEMA Size 00-6.
NEMA Type 1, 4 & 12 Enclosures.
NEMA Size 00-2.
NEMA Type 3R Enclosure.
Bulletin 6013 Starters are available single phase through
size 2P, 3 phase through size 6.
Bulletin 7707 Contactors are available 2 & 3 pole through
size 6 and 4 pole thru size 4.
Reversing
Bulletin 6030 NEMA Starters.
Bulletin 6031 NEMA Contactors.
NEMA Size 00-6.
NEMA Type 1, 4, 12 Enclosures
Bulletin 6030 reversing starters and Bulletin 6031
reversing contactors include mechanical and
electrical interlocks.
General Information
Multi-Speed
Bulletin 6050 NEMA Starters.
NEMA Size 0-5.
NEMA Type 1, 4 & 12 Enclosures.
Bulletin 6050 multi-speed starters are designed for two-speed,
single winding (consequent pole) and two-speed, two winding
(separate winding) motor applications.
Mechanical and electrical interlocks are included.
Starters for three and four speed motor applications can also
be supplied.
B4
3
8
0
Page 5
AC Contactors
AC Contactors - Bulletin 7707 TM
1-Pole, Single Phase
Maximum Motor
Horsepower Rating
NEMA
Size
00
0
1
115V 200V 230V uous
1
/3
1
2
2 Pole, Single Phase
00
0
1
2
3
1
/3
1
2
3
1
/2
7
3 Pole, Three Phase
NEMA
Size
00
0
1
2
3
4
5
6
200V 230V 575V uous
1
1
/2
1
3
7
10
25
40
75
150
3
1
7
/2
15
30
50
100
200
4 Pole, Three Phase
3
0
7
1
10
2
25
3
40
4
75
5
150
6
3
1
/2
7
15
30
50
100
200
----
----
----
----
----
----
----
----
1
2
/2
5
1
/2
10
25
50
100
200
400
5
1
/2
10
25
50
100
200
400
Starter
Amps.
Contin-
1
2
3
1
2
3
7
15
9
18
27
1
/2
45
90
460- Contin-
9
18
27
45
90
135
270
540
18
27
45
90
135
270
540
9
18
27
NEMA Type 1
General Purpose
Enclosure
Catalog No. Price
Use complete catalog number. Replace
the (*) with the suffix from coil table.
Discount Schedule JC10
Note:
1.
Price includes contactor complete with one N.O. control-circuit contact.
2.
This unit replaces T77 (size 5) and is not interchangeable.
Engineering Data - see Page B50
Modifications - see Page B36
Renewal Parts - see Page B42
Dimensions - see Page B43
Coil Volt/Hertz Suffix
24/60 or 24/50
110-120/60 or 110/50
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
200-208/60
-96
-76
-26
-46
-56
-86
B5
Page 6
B
TM - NEMA Control
AC Reversing Contactors
AC Reversing Contactors - Bulletin 6031 TM
3 Pole, Three Phase
2
Maximum Motor
Horsepower Rating
NEMA
Size
00
0
1
2
3
4
5
6
Notes:
Price includes contactor complete with one N.O. contact on each contactor. All
1.
contactors are mechanically and electrically interlocked.
2.
For plug-stop or jogging duty, where operations exceed 5 times a minute,
contactor size should be chosen in accordance with NEMA Standard ICS 2-321-3,
as listed in table.
3.
This unit replaces T77 (size 5) and is not interchangeable.
200V 230V 575V
1
/2
1
3
1
/2
7
10
25
40
2
75
150
1
3
7
15
30
50
100
200
460-
1
/2
2
5
1
/2
10
25
50
100
200
400
NEMA Type 1
General Purpose
Enclosure
Catalog No. Price
1. Includes starter complete with one N.O. contact on each contactor and 3 phase
overload relay less heaters. All starters are mechanically and electrically interlocked.
2. For plug-stop or jogging duty or where operations exceed 5 per minute, starter
sizes should be chosen in accordance with NEMA Standard ICS 2-321-3, as listed in
table.
3. This unit replaces T77 (size 5) and is not interchangeable.
4. For Ambient Compensated overload see B37.
Ordering Information
Use complete catalog number.
Replace the (*) with the suffix from coil
table. Order heaters at $18 each.
Engineering Data - see Page B50
Modifications - see Page B36
Renewal Parts - see Page B42
Heater Tables - see Page B33
Dimensions - see Page B45
B8
Plug-Stop or Jogging Duty NEMA ICS 2-321-3
Horsepower Ratings - Three Phase
NEMA
Size
0
1
2
3
4
5
6
200V
60 Hz
1
3
7
15
25
60
125
230V
60 Hz
1
/2
3
1
/2
10
20
30
75
150
380V
50 Hz
1
/2
1
1
5
15
30
50
125
250
460/575V
60 Hz
1
/2
2
5
15
30
60
150
300
Coil Volt/Hertz Suffix
24/60 or 24/50
110-120/60 or 110/50
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
200-208/60
-96
-76
-26
-46
-56
-86
Discount Schedule JC10
3
7
5
Page 9
AC Two Speed Starters
AC Two Speed Non Combination Starters - Bulletin 6050
2 Speed, Single Winding (consequent pole)
Maximum Motor
Horsepower Rating
Constant or Variable Torque
NEMA
Size
3
8
0
1.
(Constant Horsepower)
200V 230V 575V
0
1
2
3
4
5
3
(2)
(5)
10
(7 )
25
(20)
40
(30)
75
(60)
3
(2)
1
7
7
/2
(5)
15
1
/2
(10)
30
(20)
50
(40)
100
(75)
5
(3)
1
/2
10
(7 )
25
(20)
50
(40)
100
(75)
200
(150)
2 Speed, Double Winding (separate winding)
0
1
2
3
4
5
3
(2)
7
(50)
10
(7 )
25
(20)
40
(30)
75
(60)
Note:
Includes starter complete with one N.O. contact on each contactor and two 3 phase overload relays less heaters. All
starters are mechanically and electrically interlocked. Six (6) heaters are required, 3 for each speed rated for HP ratings.
3
(2)
1
/2
7
(5)
15
1
/2
(10)
30
(20)
50
(40)
100
(75)
5
(3)
1
/2
10
(7 )
25
(20)
50
(40)
100
(75)
200
(150)
460-
1
/2
1
/2
NEMA 1
General Purpose
Enclosure
Catalog No. Price
T50AA0C2 -
T50AA1C2 -
T50AA2C2 -
T50AA3C2 -
T50AA4C2 -
T50AA0S2 -
T50AA1S2 -
T50AA2S2 -
T50AA3S2 -
T50AA4S2 -
*
*
*
*
*
*
*
*
*
*
$
1848.
1992.
3624.
5472.
14616.
1320.
1488.
2664.
4176.
10248.
NEMA 4
Watertight
Enclosure
1
Catalog No. Price
T50WA0C2 -
T50WA1C2 -
T50WA2C2 -
T50WA3C2 -
T50WA4C2 -
T50WA0S2 -
T50WA1S2 -
T50WA2S2 -
T50WA3S2 -
T50WA4S2 -
NEMA Control - TM
NEMA 12
Industrial - Dust-tight
Enclosure
111
$
2220.
2364.
4152.
6672.
16992.
1692.
1860.
3192.
5376.
12624.
3000.
$
*
3120.
*
5016.
*
7536.
*
18840.
*
Consult Factory
2472.
*
2616.
*
4080.
*
6240.
*
14472.
*
Consult Factory
Catalog No. Price
T50TA0C2 -
T50TA1C2 -
T50TA2C2 -
T50TA3C2 -
T50TA4C2 -
T50TA0S2 -
T50TA1S2 -
T50TA2S2 -
T50TA3S2 -
T50TA4S2 -
*
*
*
*
*
*
*
*
*
*
Open Type
Catalog No. Price
1800.
$T50UO0C2 -
*
T50UO1C2 -
T50UO2C2 -
T50UO3C2 -
T50UO4C2 -
T50UO0S2 -
T50UO1S2 -
T50UO2S2 -
T50UO3S2 -
T50UO4S2 -
*
*
*
*
*
*
*
*
*
1920.
3408.
5136.
13296.
1272.
1416.
2472.
3840.
9624.
B
Ordering InformationCoil Volt/Hertz Suffix
Use complete catalog number.
Replace the (*) with the suffix from
coil table. Order heaters at $18 each.
Engineering Data - see Page B50
Modicications - see Page B36
Renewal Parts - see Page B42
Heater Tables - see Page B33
Dimensions - see Page B46
24/60 or 24/50
110-120/60 or 110/50
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
200-208/60
Discount Schedule JC10
-96
-76
-26
-46
-56
-86
B9
Page 10
B
TM - NEMA Control
Combination Starters & Contactors
General Information
Non-Reversing
Bulletin 6018 with disconnect switch, fusible
and non-fusible.
Bulletin 6020 with Circuit Breaker 250V thermal
magnetic trip breaker or 600V adjustable
magnetic trip MCP. breaker.
NEMA Size 0-6.
NEMA 1, 4 & 12 enclosures.
Choose standard, compact or extra-wide
enclosure style of enclosure for Sizes 0, 1 & 2.
All three styles are available in NEMA 1, 4 & 12
enclosure.
Sizes 3 & 4 are available in standard and extrawide enclosure styles.
Size 6 is supplied in the standard enclosure style
and includes Vacuum contactor.
Each starter includes disconnect device and TM
non-reversing starter.
Extensive field modification kits and factory
installed modifications are available.
Reversing
Bulletin 6038 with disconnect switch, fusible
and non-fusible.
Bulletin 6040 with circuit breaker.
250V thermal magnetic trip breaker or 600V
adjustable brip MCP. breaker.
NEMA Size 0-5.
NEMA 1, 4 & 12 Enclosures.
Each includes disconnect device and TM
reversing starter.
Extensive field modification kits and factory
installed modifications are available.
Multi-Speed
Bulletin 6058 with disconnect switch, fusible
and non-fusible.
Bulletin 6060 with Circuit Breaker.
600V MCP. breaker.
NEMA Size 0-6.
NEMA 1, 4 & 12 enclosures.
Each includes disconnect device and TM multispeed starter.
They are cataloged for two-speed, single winding
(consequent pole) and two speed, two
winding (seperate winding) motor application.
Starters for three and four speed motor
applications can also be supplied.
Extensive field modification kits and factory
installed modifications are available.
3
8
0
B10
Page 11
General Information
Combination Starters & Contactors
NEMA Control - TM
Disconnect Device
Disconnect switches are heavy duty,
visible blade type with positive drive
action and meet industrial with stand
requirements.
Above 100 amp., a non-automatic circuit
breaker with fuse clips is provided.
Mounting plates include drilling for field
conversion of fuse size and spacing.
Circuit breaker type starters use motor
circuit protectors with a single, seven-point
trip adjustment and manual trip feature. An
optional current limiter attachment provides
200,000 amp. rms symmetrical interrupting
capacity.
Door Swing
The concealed hinge design allows 150
door swing for interior accessibility.
Uniform Enclosure
One enclosure covers Size 0, 1 & 2, for
each enclosure style.
Sizes 3 & 4 are covered by a single
enclosure.
NEMA 1, 4 & 12 enclosure designs are
each the same basic size, for each
enclosure style. All this for flexibility, ease
of layout and ease of installation.
Grounding
A UL recommended type, green head
screw is provided for grounding the
enclosure.
A green ground wire is installed in the
non-fused leg of control transformers.
Door Gasketing
Standard on NEMA 4 & 12 and optional on
NEMA 1. Gasketing is neoprene, extruded,
closed cell type for increased life, sealing
qualities and safety for the installer.
o
Disconnect Operator
Flange mounted operating handle provides positive control of the disconnect.
Interlocking prevents opening the door
with the disconnect "ON" or turning the
disconnect "ON" with the door open.
Interlock defeaters are provided for
maintance.
The position of disconnect is clearly
visible to determine if controller is "ON" or
"OFF".
A red handle flag is visible in the "ON"
state.
Padlocking
Operating handles can be padlocked in
"OFF", with up to
Doors can be locked closed with one
shackle lock, thus providing security to
equipment and safety to personnel.
White Mounting Plate
Baked ANSI safety white enamel is used
for the mounting plate. This provides
increased visibility for safety.
Add-On Accessories
Most TM starter add-on accessories can
be installed in combination starters.
Mounting plates are pre-drilled for field
installation of additional control devices.
Quality Enclosure Construction
Painted surfaces are baked enamel for
long life.
All unpainted hardware is plated for
corrosion resistance.
Hinge pins are stainless steel.
NEMA 4 enclosures are #304 stainless
steel for appearance and corrosion
resistance.
3
/8" shackle locks.
3
/8"
B
Safety & Relibility
Flange mounted disconnect handle.
3
8
0
Disconnect state clearly visible.
Defined enclosure grounding method.
Padlocking for both door and disconnect handle.
Door swing for maximum interior accessories.
All contribute to safety for the installer and for
operating personnel.
Quality enclosure construction.
Careful selection of disonnect devices and the
basic TM starter all contribute to long, reliable
performance.
Space Savings
Uniform enclosure sizes allow mixing NEMA starter sizes
in a row.
Mount enclosures side-by-side, without restricted door swing.
Add most modifications without changing the enclosure.
Select an enclosure style for max. utilzation of available space.
Minimize additional control enclosures by using the space in
an extra-wide starter enclosure.
Space saving economy is built into TM combination
starters.
B1 1
Page 12
B
TM - NEMA Control
General Information
Choice of Enclosure Style
Choose from three enclosure styles, standard,
compact or extra-wide for non-reversing
starters through NEMA Size 2.
The compact style fits in low height areas and the
extra-wide has approximatley 200 square
inches inches of added panel space for mounting of auxiliary equipment.
Size 3 & 4 non-reversing starters are available
in standard and extra-wide.
Choice of enclosure style provides maximum
flexibility.
Versatility
Choose an enclosure style to meet the
application.
Check the enclosure sizes to simplify your
starter layouts.
Check the interchangeability of mounting
plates.
Choose add-on accessories for the basic TM
starter.
Select from a wide range of factory modifications
and field modification kits.
All of this to improve application flexibility with
minimum inventory requirements. This is the
versatility of TM combination starters.
B12
Pilot Devices
A complete selection of field modification kits or
factory installed operator devices are
available.
Most are arranged for mounting on the enclosure flange, eliminating the need for a flexible
wire harness to the door.
Control Transformer
Available factory installed or as a field modification kit.
All starters can accommodate a 100VA extra
capacity transformer in every enclosure style
and type.
Secondary fusing standard.
3
7
5
Page 13
AC Combination Starters
NEMA Control - TM
B
AC Combination Starters with Non-Fusible Disconnect Switch, 600V - Bulletin 6018
Standard - Vertical
NEMA Type 4
Watertight Enclosure
Catalog No. Price
$
T18WA30610 T18WA31610 T18WA32610 T18WA33610 -
-use extra wideConsult Factory
*
2244.
*
2304.
*
3600.
*
6132.
NEMA
Size
0
1
2
3
4
5
6
Maximum Motor
Horsepower Rating
200V 230V 575V
3
7
10
25
40
75
150
3
1
/2
7
15
30
50
100
200
460-
5
1
10
/2
25
50
100
200
400
Cont.
Amps
Rating
18
27
45
90
135
270
540
Switch
Rating
Amps.
30
30
60
100
150
400
600
NEMA Type 1
General Purpose
Enclosure
Catalog No. Price
T18AA30610 T18AA31610 T18AA32610 T18AA33610 -
-use extra wide-
*
$
1092.
*
1152.
*
1824.
*
3036.
Compact - Horizontal
0
3
1
7
2
10
3
1
7
/2
15
5
1
/2
10
25
18
27
45
30
30
60
C18AA30610 C18AA31610 C18AA32610 -
1092.
*
1152.
*
1824.
*
C18WA30610 C18WA31610 C18WA32610 -
*
2244.
*
2304.
*
3600.
Extra Wide
0
3
1
7
2
10
3
25
4
40
3
8
0
Note:
1.
Includes starter complete with N.O. contact and 3 phase overload relay less heaters.
Renewal Parts - see Page B42
Engineering Data - see Page B50
For Plugging and Jogging Service - Page B8
Modifications - see Page B36
Heater Tables - see Page B33
Dimensions - see Page B48
24/60 or 24/50
110-120/60 or 110/50
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
200-208/60
*
*
*
*
*
*
*
*
*
*
*
$
3612.
3756.
5892.
9384.
17340.
18
18
18
27
27
27
27
45
45
90
135
270
Circuit
Breaker
Ampere
Rating
3
7
15
3
7
15
30
30
50
100
150
400
Magnetic
Trip Motor
Circuit
Protector
TEC
TJC4
Maximum Motor
NEMA
Size
3
8
0
Horsepower Rating
200V 230V 575V
1
1
1
3
1
3
7
7
15
30
50
100
1
/2
1
3
/2
5
1
1
/2
1
3
/2
5
1
10
/2
1
/2
10
25
50
100
200
/2
0
1
2
3
4
5
1
1
/2
3
1
/2
1
1
/2
3
1
7
/2
1
/2
7
10
25
40
75
Note:
1. Includes starter with N.O. contact, circuit breaker and 3 phase overload relays less heaters.
460/
Starter
Cont.
Amps
Rating
1
/2
Ordering Information
Use complete catalog number. Replace
the (*) with the suffix from the coil table.
Order heaters at $18 each.
Modifications - see Page B36
Engineering Data - see Page B50
Renewal Parts - see Page B42
Full-load Current Table - see Page B34
Heater Tables - see Page B33
Dimensions - see Page B48
NEMA Type 1
General Purpose
Enclosure
Catalog No. Price
T58AA0C2610 -
T58AA1C2610 -
T58AA2C2610 -
T58AA3C2610 -
T58AA4C2610 -
*
*
*
*
*
2976.
$
3120.
5064.
7296.
17136.
NEMA Type 4
Watertight Enclosure
1
Catalog No. Price
- use size 1 -
T58WA1C2610 -
T58WA2C2610 -
T58WA3C2610 -
T58WA4C2610 -
Consult Factory
*
*
*
*
*
$
4968.
7368.
11232.
23328.
NEMA Type 12
Industrial - Dust-tight
Enclosure
1
Catalog No. Price
- use size 1 -
T58TA1C2610 -
T58TA2C2610 -
T58TA3C2610 -
T58TA4C2610 -
*
*
*
*
*
$
3516.
5688.
8664.
21048.
1
2 Speed, Double Winding (separate winding)
3
0
(2)
7
1
(5)
10
2
(7 )
25
3
(20)
40
4
(30)
75
5
(60)
3
8
0
Note:
Includes starter complete with one N.O. contact on each contactor and two 3 phase overload relays less heaters. All starters
1.
are mechanically and electrically interlocked. Six (6) heaters are required, 3 heaters for each speed.
Ordering Information
Use complete catalog number. Replace
the (*) with the suffix from coil table.
Order heaters at $18 each.
5
3
(3)
(2)
7
(5)
15
(10)
30
(25)
50
(40)
100
(75)
1
/2
10
(7 )
25
(20)
50
(40)
100
(75)
200
(150)
1
/2
1
/2
18
27
1
/2
45
90
135
270
30
30
60
100
150
400
T58AA0S2610 -
T58AA1S2610 -
T58AA2S2610 -
T58AA3S2610 -
T58AA4S2610 -
*
*
*
*
*
2448.
2616.
4104.
6000.
12768.
- use size 1 -
T58WA1S2610 -
T58WA2S2610 -
T58WA3S2610 -
T58WA4S2610 -
Consult Factory
*
*
*
*
*
4464.
6432.
9936.
18960.
- use size 1 -
T58TA1S2610 -
T58TA2S2610 -
T58TA3S2610 -
T58TA4S2610 -
*
*
*
*
*
3012.
4728.
7368.
16680.
Coil Volt/Hertz Suffix
Engineering Data - see Page B50
Modification - see Page B36
Renewal Parts - see Page B42
Heater Tables - see Page B33
Dimensions - see Page B49
24/60 or 24/50
110-120/60 or 110/50
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
200-208/60
-96
-76
-26
-46
-56
-86
B20
Discount Schedule JC10
Page 21
AC Combination Starters
NEMA Control - TM
Fusible AC 2 Speed Starter with Disconnect Switch, 200-230V - Bulletin 6058
2 Speed, Single Winding (consequent pole)
Maximum Motor
NEMA
Size
0
1
2
3
4
5
Horsepower Rating
Constant or Variable
Torque ( Constant
Horsepower)
200V 230V
3
(2)
1
7
(5)
10
1
(7 )
25
(20)
40
(30)
75
(60)
/2
/2
3
(2)
7
(5)
15
(10)
30
(25)
50
(40)
100
(75)
Starter
Continue
Ampere
Rating
1
/
2
18
27
45
90
135
270
Disconnect
Switch
Ampere
Rating
30
30
60
100
150
400
NEMA Type 1
General Purpose
Enclosure
Catalog No. Price
T58AA0C2203 -
T58AA1C2203 -
T58AA2C2206 -
T58AA3C2201 -
T58AA4C2202 -
*
*
*
*
*
3168.
$
3312.
5160.
7920.
18960.
NEMA Type 4
Watertight Enclosure
1
Catalog No. Price
- use size 1 -
T58WA1C2203 -
T58WA2C2206 -
T58WA3C2201 -
T58WA4C2202 -
Consult Factory
*
*
*
*
*
5160.
$
7464.
11856.
25152
NEMA Type 12
Industrial - Dust-tight
Enclosure
1
Catalog No. Price
- use size 1 -
T58TA1C2203 -
T58TA2C2206 -
T58TA3C2201 -
T58TA4C2202 -
*
*
*
*
*
3708.
$
5784.
9288.
22506.
B
1
2 Speed, Double Winding (separate winding)
3
0
(2)
1
/
2
7
1
(5)
10
2
3
4
5
1
/
(7
2)
25
(20)
40
(30)
75
(60)
Note:
1.
Includes starter complete with one N.O. contact on each contactor and two 3 phase overload relays less heaters. All
starters are mechanically and electrically interlocked. Six (6) heaters are required, 3 heaters for each speed.
Ordering Information
Use complete catalog number. Replace
the (*) with the suffix from coil table.
Order heaters at $18 each.
3
(2)
7
(5)
15
(10)
30
(25)
50
(40)
100
(75)
18
1
/
2
27
45
90
135
270
30
30
60
100
150
400
T58AA0S2203 -
T58AA1S2203 -
T58AA2S2206 -
T58AA3S2201 -
T58AA4S2202 -
*
*
*
*
*
2640.
2808.
4200.
6624.
14592.
- use size 1 -
T58WA1S2203 -
T58WA2S2206 -
T58WA3S2201 -
T58WA4S2202 -
Consult Factory
*
*
*
*
*
4656.
6528.
10560.
20784.
Coil Volt/Hertz Suffix
Engineering Data - see Page B50
Modification - see Page B36
Renewal Parts - see Page B42
Heater Tables - see Page B33
Dimensions - see Page B49
24/60 or 24/50
110-120/60 or 110/50
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
200-208/60
- use size 1 -
T58TA1S2203 -
T58TA2S2206 -
T58TA3S2201 -
T58TA4S2202 -
*
*
*
*
*
3204.
4824.
7992.
18408.
-96
-76
-26
-46
-56
-86
Discount Schedule JC10
B21
Page 22
B
TM - NEMA Control
AC Combination Starters
Fusible AC 2 Speed Starter with Disconnect Switch, 600V - Bulletin 6058
2 Speed, Single Winding (consequent pole)
Maximum Motor
NEMA
Size
0
1
2
2
3
4
5
Horsepower Rating
Constant or Variable
Torque ( Constant
Horsepower)
460V 575V
5
(3)
10
(71/2)
15
(10)
25
(20)
50
(40)
100
(75)
200
(150)
5
(3)
10
1
(7
15
(10)
25
(20)
50
(40)
100
(75)
200
(150)
Starter
Continue
Ampere
Rating
/2)
18
27
45
45
90
135
270
Disconnect
Switch
Ampere
Rating
30
30
60
60
100
200
400
2 Speed, Double Winding (separate winding)
NEMA 1
General Purpose
Enclosure
Catalog No. Price
3168.
T58AA0C2603 -
T58AA1C2603 -
T58AA2C2603 -
T58AA2C2606 -
T58AA3C2601 -
T58AA4C2602 -
*
*
*
*
*
*
$
3312.
5160.
5160.
7440.
17664.
NEMA 4
Watertight Enclosure
1
Catalog No. Price
- use size 1 -
T58WA1C2603 -
T58WA2C2603 -
T58WA2C2606 -
T58WA3C2601 -
T58WA4C2602 -
Consult Factory
*
*
*
*
*
*
$
5160.
7464.
7464.
11376.
23856.
NEMA 12
Industrial - Dust-tight
Enclosure
1
Catalog No. Price
- use size 1 -
T58TA1C2603 -
T58TA2C2606 -
T58TA2C2601 -
T58TA3C2602 -
T58TA4C2604 -
*
*
*
*
*
*
3708.
$
5784.
5784.
9288.
22776.
1
5
0
(3)
1
/2
7
1
(5)
10
2
2
3
4
5
1
(7 )
/2
25
(20)
50
(40)
100
(75)
200
(150)
Note:
1.
Includes starter complete with one N.O. contact on each contactor and two 3 phase overload relays less heaters. All starters
are mechanically and electrically interlocked. Six (6) heaters are required, 3 heaters for each speed.
Ordering Information
Use complete catalog number. Replace
the (*) with the suffix from coil table.
Order heaters at $18 each.
5
(3)
1
7
(5)
15
(10)
25
(20)
50
(40)
100
(75)
200
(150)
18
/2
27
45
45
90
135
270
30
30
30
60
100
200
400
T58AA0S2603 -
T58AA1S2603 -
T58AA2S2606 -
T58AA3S2601 -
T58AA3S2602 -
T58AA4S2604 -
*
*
*
*
*
*
2640.
2808.
4200.
4452.
6624.
14592.
- use size 1 -
T58WA1S2603 -
T58WA2S2603-
T58WA2S2606 -
T58WA3S2601 -
T58WA4S2602 -
Consult Factory
*
*
*
*
*
*
4660.
6530.
6530.
10080.
19490.
- use size 1 -
T58TA1S2603 -
T58TA2S2603 -
T58TA2S2606 -
T58TA3S2601 -
T58TA4S2602 -
Coil Volt/Hertz Suffix
Engineering Data - see Page B49
Modification - see Page B35
Renewal Parts - see Page B41
Heater Tables - see Page B32
Dimensions - see Page B42
24/60 or 24/50
110-120/60 or 110/50
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
200-208/60
*
*
*
*
*
*
-96
-76
-26
-46
-56
-86
3204.
4820.
4820.
7510.
17140.
5
0
2
B22
Discount Schedule JC10
Page 23
AC Combination Starters
NEMA Control - TM
AC 2 Speed Starters with Magnetic Trip Circuit Breaker, 200, 230, 460 and 575V
2 Speed, Single Winding (consequent pole), Bulletin 6060
NEMA
Size
0
1
2
3
4
5
Maximum Motor
Horsepower Rating
Constant or Variable Torque
( Constant Horsepower)
Constant or Variable Torque (
Constant Horsepower)
200V 230V 460V/575V
1
/2
1
/4
( )
1
/2
1
3
( )
/4
3
(2)
1
/2
1
( )
/4
1
/2
1
3
/4
( )
3
(2)
7
(5)
1
7
(5)
10
1
/2
(7 )
25
(20)
40
(30)
75
(60)
1
/2
1
/3
( )
1
/2
1
(1)
3
(2)
1
/2
1
( )
/3
1
/2
1
(1)
3
(2)
1
/2
/2
7
(5)
7
(5)
15
(10)
30
(25)
50
(40)
100
(75)
1
/2
1
/2
1
/2
1
(1)
3
(2)
5
(3)
1
1
(1)
3
(2)
5
(5)
10
1
(7 )
10
1
(7 )
25
(20)
50
(40)
100
(75)
200
(150)
/2
/2
/2
Starter
Continuous
Ampere
Rating
18
18
18
27
27
27
27
45
45
90
135
270
Circuit
Breaker
Ampere
Ratings
3
7
15
3
7
15
30
30
50
100
150
400
NEMA Type 1
General Purpose
Enclosure
Catalog No. Price
T60AA0S2671 -
T60AA0S2672 -
T60AA0S2673 -
T60AA1S2671 -
T60AA1S2672 -
T60AA1S2673 -
T60AA1S2674 -
T60AA2S2674 -
T60AA2S2675 -
T60AA3S2676 -
T60AA4S2677 -
*
*
*
*
*
*
*
*
*
*
*
3012.
3012.
3012.
3180.
3180.
3180.
3180.
4728.
4728.
6420.
14352.
NEMA Type 4
Watertight Enclosure
1
Catalog No. Price
- use size 1 -
- use size 1 -
- use size 1 -
T60WA1S2671 -
T60WA1S2672 -
T60WA1S2673 -
T60WA1S2674 -
T60WA2S2674 -
T60WA2S2675 -
T60WA3S2676 -
T60WA4S2677 -
Consult Factory
*
*
*
*
*
*
*
*
5028.
5028.
5028.
5028.
7056.
7056.
10356.
20478.
NEMA Type 12
Industrial - Dust-tight
Enclosure
1
Catalog No. Price
- use size 1 -
- use size 1 -
- use size 1 -
T60TA1S2671 -
T60TA1S2672 -
T60TA1S2673 -
T60TA1S2674 -
T60TA2S2674 -
T60TA2S2675 -
T60TA3S2676 -
T60TA4S2677 -
*
*
*
*
*
*
*
*
1
3576.
3576.
3576.
3576.
5352.
5352.
7788.
18168.
Note:
Includes starter complete with N.O. contact, on each contactor, and two 3 phase overload relays less heaters. All starters
1.
are mechanically electrically interlocked. Six (6) heaters are required, 3 heaters for each speed.
Ordering Information
Use complete catalog number.Replace the
(*) with the suffix from coil table. Order
heaters at $18 each.
Engineering Data - see Page 50
Modification - see Page 36
Renewal Parts - see Page 42
Heater Tables - see Page 33
Dimensions - see Page 49
Coil Volt/Hertz Suffix
24/60 or 24/50
110-120/60 or 110/50
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
200-208/60
-96
-76
-26
-46
-56
-86
B24Discount Schedule JC10
4
8
5
Page 25
AC Reduced Voltage Starters
Autotransformer Closed Transition
Reduced Voltage Starting of Squirrel Cage Motors
Highest Starting Torque per Ampere of Line Current
Available in Type 4 & 12 Enclosure
All Disconnect Types Available
Complete Line Factory Installed Modifications
NEMA Control - TM
Auto Transformer Starter
B
Two Step Part Winding
Part Winding Starters
Two Step Starting of Squirrel Cage Motors
Lowest Cost Method of Starting
NEMA Type 1, 4, & 12 Enclosures
Factory Installed Modifications
Open Transition
Wye-Delta Starters
Available Open or Closed Transition
Inrush Current
NEMA 1 Enclosure Standard
3
8
0
1
/3 Normal Line Starting
Wye Delta Starter
B25
Page 26
B
TM - NEMA Control
Autotransformer Closed Transition - Bulletin 6082
Wye-Delta Starters 3, NEMA 1 Enclosures - Bulletin 6095
Maximum horsepower ratings are in accordance with NEMA Standards ICS2-321C:20. Auto transformers are 3-Coil type, with voltage taps at
1.
50%, 65% and 80% rated in accordance with NEMA Standards ICS2-214.21 for medium-duty starting service.
Size 5 Starters are supplied in floor mounted enclosures without bottom cover plate for mounting against a wall. If not mounted against a wall, a
2.
rear cover plate must be ordered.
Wye-Delta Starters Overload Relay Heater Selected by dividing FLC by 1.73 and select Heaters from index.
3.
Ordering Information
Use complete catalog number.
Replace the (*) with the suffix from
the Coil Table. Heaters are
purchased seperately at $18
B26
each.
Modifications see Page B36
Engineering Data Page B50
Renewal Parts Page B42
Discount Schedule JC23
Coil Table
Volt/60Hz
220-240
440-480
Line
Voltage
-26
-46
Control
Transformer
-T26
-T46
0
3
3
Page 27
Reduced Voltage Starters
Part Winding Starters, Two Step - Bulletin 6090
NEMA Control - TM
B
Max. Motor Horsepower
Rating 2 or 3-Phase
Size
200V 230V 460/575V
1 PW
2 PW
3 PW
4 PW
5 PW
6 PW
Note:
Includes starter complete with two contactors, timing device
and two overload relays less heaters. (6 are required)
These starters are usually used with wye(star) connected
motors. They may also be used for delta connected motors
when the motors are so designed that neither delta winding
need be open during starting.
4
0
0
10
20
40
75
150
----
10
25
50
75
150
300
15
40
75
150
350
600
Type 1
General Purpose
Poles
Catalog No. Price
T90AA31 T90AA32 T90AA33 -
3
T90AA34 -
*
*
*
*
$
2628.
3744.
5280.
11292.
Type 4
Watertight
Catalog No. Price
4068.
T90WA31 T90WA32 T90WA33 T90WA34 -
$
*
5364.
*
7620.
*
14976.
*
Consult Factory
Overload Realy Heater Data
Heater elements should be selected for running current in each
winding. A total of 6 heater elements are required per controller.
Ordering Information
Use complete catalog number. Replace the
(*) with the suffix from the coil table.
Order heater elements at $18 each.
Modifications see Page B36
Renewal Parts see Page B50
Engineering Data see Page B42
Type 12
Industrial
Catalog No. Price
T90TA31 T90TA32 T90TA33 T90TA34 -
*
*
*
*
3828.
$
5244.
7080.
13692.
Coil Volt/Hertz Suffix
24/60 or 24/50
110-120/60 or 110/50
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
200-208/60
Open Type U
Catalog No. Price
T90U031 T90U032 T90U033 T90U034 -
-96
-76
-26
-46
-56
-86
*
*
*
*
$
2556.
3552.
4944.
10668.
B27Discount Schedule JC23
Page 28
B
TM - NEMA Control
Fused Disconnect Switch, NEMA 3R - Bulletin 6318
200 & 230 Volts
NEMA
Size
1
2
3
4
5
Dual Element Fuses
200V 230V
5
7
10
----25
----40
----75
460 & 575 Volts
Dual Element Fuses
460V 575V
1
2
3
4
5
10
---- 15
25
50
----100
----200
Maximum Motor Horsepower Rating
Non-Time Delay Fuses
200V 230V
1
7
1
/2
/2
----15
----30
----50
----100
10
---- 15
25
50
----100
----200
3
-----
---- 10
---- 25
---- 40
50
Non-Time Delay Fuses
460V 575V
1
7
10
---- 15
30
50
60
100
125
3
1
7
/2
---- 15
---- 30
---- 50
60
1
7
10
---- 20
40
50
75
100
150
/2
/2
Starter
Continuous
Ampere
Rating
27
45
90
135
270
27
45
90
135
270
Pump Control Panels
Disconnect
Ampere Rating
Switch
30
60
100
150
400
30
60
100
150
400
Fuse
Clips
60
60
100
100
200
200
400
400
60
30
60
100
200
200
400
400
NEMA Type 3R
Weatherproof
Enclosure
Catalog No. Price
Note:
Includes Pump Control Panel in NEMA 3R weather-resistant enclosure, complete with integral circuit breaker or fusible
1.
disconnect switch less fuses, start push button. Hand-Off-Auto selector switch and 3 phase ambient compensated overload
relay less heaters. Heaters are purchased separately at $9 each. For non ambient compensated overload relay delete "J"
from coil suffix.
Ordering Information
Use complete catalog number Replace the
(*) with the suffix from the coil table.
Order Heaters at $18 each.
Modifications see Page B36
Engineering Data see Page B50
Renewal Parts see Page B42
B28
Coil Volt/Hertz SuffixCoil Volt/Hertz Suffix
24/60 or 24/50
110-120/60 or 110/50
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
200-208/60
-96J
-76J
-26J
-46J
-56J
-86J
380/50
110/25
220/25
440/25
Discount Schedule JC13
-35J
-12J
-22J
-42J
4
8
5
Page 29
Pump Control PanelsNEMA Control - TM
Circuit Breaker, 200, 230, 460 and 575V - Bulletin 6320
240 Volts Thermal Magnetic Trip
Maximum Motor Horsepower Rating
NEMA
Size
1
2
3
4
5
7
10
----25
25
40
-----
2
1
/2
5
10
40
2
1
/2
7
15
25
30
50
460/575V200V 230V
-----
-----
-----
-----
-----
-----
-----
-----
600 Volts Adjustable Magnetic Trip M.C.P.
1
/2
1
/2
1
2
3
4
5
6
1
3
7
7
15
25
40
75
150
1
/2
1
/2
1
3
7
7
15
30
50
100
200
1
/2
1
/2
1
/2
1
/2
1
3
5
10
10
25
50
100
200
400
Starter
Continuous
Ampere
Rating
27
45
90
135
1
/2
27
45
90
135
270
540
Circuit Breaker
Ampere
Rating
40
50
50
70
100
150
150
3
7
15
30
30
50
100
150
400
600
Type
TEB
TED
TEC
TEC
TJC
NEMA Type 3R
Weatherproof
Enclosure
Catalog No. Price
Includes Pump Control Panel in NEMA 3R weather-resistant enclosure, complete with integral circuit breaker or fusible disconnect switch
less fuses, start push button. Hand-Off-Auto selector switch and 3 phase ambient compensated overload relay less heaters. Heaters are
purchased separately at $9 each.
2.
4
0
0
Specify HP if less than 5 HP
Ordering Information
Use complete catalog number Replace the
(*) with the suffix from the coil table. Order
Heaters at $18 each.
Modifications see Page B36
Engineering Data see Page B50
Replacement Parts see Page B42
Discount Schedule JC13
Coil Volt/Hertz Suffix
24/60 or 24/50
110-120/60 or 110/50
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
200-208/60
-96J
-76J
-26J
-46J
-56J
-86J
B29
Page 30
TM - NEMA ControlPump Panel Control
Factory Modifications For K18 & K20 Pump Panels
B
Description
Control Transformers
Standard Capacity
Primary Volts/Hertz:
220-240/60. or 220/50
440-480/60. or 440/50
550-600/60. or 550/50
220-208/60
380/50
220/25
440/25
100 Watts Extra
220-240/60. or 220/50
440-480/60. or 440/50
550-600/60. or 550/50
200-208/60
380/50
220/25
440/25
ORDERING EXAMPLE
K18RB34604 with 440/480 60 Hz . Std. Transformer,
Pilot Light (Options "B"), Grounded Service Entrance
Lug for size 4 (Option "E"), Backspin, Timer (Option "F")
and Lockout Relay (Option "H").
Catalog # is K18RB34604 - T46J-B-E-F-H
List Price is $6942 + 816 + 180 + 60 + 1068 + 360
Total Price $9426.
Add For NEMA Size
12345
162228336408462
246342504612612
288372468528588
432558702792882
Catalog
Number
Suffix
— T26J
— T46J
— T56J
— T86J
— T35J
— T22J
— T42J
— C26J
— C46J
— C56J
— C86J
— C35J
— C22J
Field Modifications Kits For Pump Panels
NEMACatalog
DescriptionSizeNumberPrice
Control Circuit
Control Transformers -50/60 hz.
600VKTR67-25
Pilot Lights With Red Lens
120VA63-435538A-1 132.
240V1-4A63-435538A-2
480VA63-435538A-3
600VA63-435538A-4
Fuse Block, 2 Pole, 30A, 250V,1-4A63-435539A 72.
Class H, With Two 1/2 A Dual
Element Fuses
Notes:
1.To complete Cat. No. of relay, add coil suffix from Suffix Table
Description
Control Circuit
Pilot Light, Standard Transformer Type,
Red Lens
Fused Control Circuit (includes 2 Fuses)
Power Circuit
Line Terminal Board, For Size 4 only.
4/0 Aluminum Wire
Grounded Service Conductor Service
Entrance Lug For:NEMA Size 1-3
NEMA Size 4
Relays
Time Delay Relay (Pneumatic) 0.2 Seconds to
3 Minutes Backspin (Includes Starter
Interlock)
Sequential Start timer
Lockout Control Relay
Substitute Non-Ambient Compensated
Overload Relay
Additional Specify As
Pr iceCat# Suffix
$ 180B
264C
252D
48E
60
$1068F
936G
360H
24Remove J
(Deduct)From
Suffix
Coil Suffix Table
VoltsHertzSuffix
110-12060-76
200-20860-86
220-24060-26
38050-35
440-48060-46
550-60060-56
DescriptionSizeNumberPrice
Power Circuit
Line Terminal Board For Size4A63-435540A$ 72.
4 Only, 4/0 Aluminum Wire
Grounded Service Conductor1-3A63-435541A 24.
Service Entrance Lug4A63-435542A 36.
1. Includes 3 - Phase Overload Relay complete, less heaters. Heaters
may be purchased at $18.00 each. See page B32.
1
Catalog N o.Price
1
B
Single Phase Application
A three phase overload relay is used
for single phase applications. Only
one heater is required and is to be
installed in the center phase cavity of
the relay.
Heater Selection
Select heaters based on motor namplate fullload current. Tables are for continuous rated
motors. Full-load current for a given horsepower motor will vary from one manufacturer
to another and will depend on RPM of motor.
Type Of Protection
Heaters selected directly from the table
provide a maximum of 125% protection at
40oC degree ambient, is suitable for motors
with a 1.15 service factor with a 40oC degree
rise or less and with motor and controller at
the same temperature.
For motors with a 1.0 service factor or with
a temperature rise greater then 40oC degree
without service factor rating, use one size
smaller heaters than in table. The ultimate trip
of the heater is approximately 125% of the
minimum current shown in the tables in a 40oC
degree ambient.
Ambient Correction
Not necessary when overload relay is ambient
compensated as identified by green reset rod.
For control at an ambient constantly less than
the motor ambient, correct by decreasing the
nameplate motor full-load curent by 1% per oC
difference in ambient in ambient for heater
selection.
For control at an ambient constantly greater
than the motor ambient, correct by increasing
the nameplate motor full-load current by 1%
per oC difference in ambient.
Branch Circuit Protection
Branch circuit protection should be provided
per National Electric Code (USA) or the
Canadian Standards Asociation rules.
Automatic Reset
Automatic reset operation should not be used
with two-wire control.
Overload Adjustment
These overload relays are manufactured with
an exclusive calibration process to assure
the ultimate in tripping accuracy and
repeatability. The overload allows a true + 15%
adjustment as a result of the process and is
well suited for use with unity service factor
motors requiring a shorter locked rotor
tripping time. The + 15% adjustment is easliy
made by means of a small dial on the bottom of
the relay. A quick field modification also
permits removal of the adjustment feature.
Heaters selected directly from the table provide a
maximum of 125% protection at 40
ambient, is suitable for motors with a 1.15 service
factor with a 40oC degree rise or less and with
motor and controller at the same temperature. For
motors with a 1.0 service factor or with a temperature rise greater then 40oC degree without service
factor rating, use one size smaller heaters than in
table. The ultimate trip of the heater is approximately 125% of the minimum current shown in the
tables in a 40oC degree ambient.
o
C degree
Single Phase - Size 00, 0, 1, 1P, 2 $18.00 List each
Not necessary when overload relay is ambient
compensated as identified by green reset rod.
For control at an ambient constantly less than
the motor ambient, correct by decreasing the
namplate motor full-load curent by 1% per oC
degree difference in ambient. For control at an
ambient constantly greater than the motor
ambient, correct by increasing the nameplate
motor full-load current by 1% per oC degree
difference in ambient.
Three Phase - Size 00, 0, 1, 1P, 2 $18.00 List each
Motor Ampere Rating - Type TM, HP
Enclosed Starter
Non-Ambient and
Open or Enclosed
Starters Ambient
Compensated Relay
Min. Max.
Open Starter
Bimetallic
Relay
Min. Max.
.44
.49
.55
.60
.68
.74
.82
.92
.99
1.08
1.17
1.28
1.45
1.64
1.89
2.06
2.27
2.56
2.77
3.11
3.36
3.76
4.07
4.65
5.24
5.80
6.21
6.97
7.72
8.16
8.80
9.66
10.7
12.3
13.8
15.8
17.7
19.2
21.0
24.4
26.1
29.4
31.5
34.9
40.2
43.7
Automatic Reset
Automatic reset operation should not be used
with two-wire control.
Heater Selection
Select heaters based on motor nameplate
full-load current. Tables are for continuous
rated motors. Full-load current for a given
horsepower motor will vary from one
manufacturer to another and will depend on
RPM of motor.
Enclosed Starter
Non-Ambient and
Open or Enclosed
Starters Ambient
Compensated Relay
Non-Ambient and
Open or Enclosed
Starters Ambient
Compensated Relay
Min. Max.
7.4
8.0
10.0
10.6
12.0
13.6
16.8
18.9
20.4
22.8
24.8
28.6
31.7
35.3
39.2
42.4
46.5
50.9
57.4
63.8
70.8
77.4
83.2
91.0
97.7
106.1
115.5
124.0
7.9
9.9
10.5
11.9
13.5
16.7
18.8
20.3
22.7
24.7
28.5
31.6
35.2
39.1
42.3
46.4
50.8
57.3
63.7
70.7
77.3
83.1
90.9
97.6
106.0
115.4
123.9
135.0
B34Discount Schedule JC16
Page 35
Motor Full Load Current DataNEMA Controls - TM
The full load currents listed below are "average values" for motors of several manufacturers. These "average values" are as listed in the
National Electrical Code 1996 and must only be used as a guide for selecting suitable branch circuit components.
The rated full load current shown on the motor nameplate is likely to vary from the values listed below .
The NAMEPLATE full load current should always be used in determining the rating of devices.
When using a design "E" Motor Special considerations apply refer to NEC 1996 tables 430 -151A & B & 430-152, page 70-453/454.
TECL Current Limiter Attachment for TEC
Motor Circuit Protectors, 100,00 AIC Max.
Class J Fuse Clips, In place of Class H
Class R Fuse Clips, In place of Class H
For
BulletinEncl.
NumberType
6018-20
6018-20All
6038-40
6058-60
All1,4,12
All ExceptAll
6031&7707
All ExceptAll
6031&7707 1,4,12
All ExceptAll
6031&7707 1,4,12
6020-40,
6060
6018-38
6058
1,4,12
Add to NEMA Size
0 1 2 3 4 5&6
120. 120. 192. 264. 456. 792.38
216. 216. 312. 264. 456. 792.39
216. 216. 312. 264. 456. 396.40
80.80.80.80.80.80.
24.24.24.24.24.24.41
48.48.48.48.48.48.43
(96.) (96.) (144.)(180.) (276.) (1444.)44
360. 360. 360. 960. 1950. N/A45
N/C N/CN/C N/C N/CN/C
B
Control transformer
Description
Standard Capacity
Primary Volts/Hertz:
220-240/60, or 220/50
440-480/60, or 440/50
550-600/60, or 550/50
200-208/60
380/50
2
220/25
2
440/25
100 Watts Extra
Primary Volts/Hertz:
220-240/60, or 220/50
440/480/60, or 440/50
550-600/60, or 550/50
200-208/60
280/50
2
220/25
2
440/25
Fused Primary (Includes 2 Fuses)
Ungrounded Secondary with 2 Dual
5
1
2
Element Fuses
Special Voltage on Transformer (Not Std.)
Dual Voltage Secondary
1
324. 324. 456. 672. 816. 924.-T46
372. 372. 612. 876. 1116. 1284.
492. 492. 684. 1008. 1224. 1224.
All1,4,12
576. 576. 744. 936. 1056. 1176.-C56
864. 864. 1116. 1404. 1584. 1764.
112. 112. 112. 112. 112. 112.47
N/C N/CN/C N/C N/C N/C4 8
Add 10% to Price of Transformer49
-T26
-T56
-T86
-T35
-T22
-T42
-C26
-C46
-C86
-C35
-C22
-C42
T18AA31603-T46
Notes:
UL Listed for field modification. Other modifications listed factory installed.
1. Single or Dual (200-240 & 440-480) Voltage primary with 110-120V secondary. Standard primary
voltages are 110-120, 200-205, 220-240, 277, 380, 440-480 and 550-600. Prices included 1 panelmounted, dual-element secondary fuse, with other side of secondary connected to cabinet ground.
2. Price includes extra-wide enclosure when used with any Bulletin 6018-20 starter.
Discount Schedule JC 14B37
Page 38
B
NEMA Control - TMFactory Modifications
Factory Installed Modifications For Reduced Voltage Starters
Cat.
Suffix
#
Special Enclosure
Add to NEMA 1 Enclosed Starter for:
(Note back & bottom cover plates are required for
sizes 5 & 6.)
Disconnect Devices
Add to NEMA 1 Enclosed Starter for:
Non-Fusible Disconnect Switch
Combination
Add to NEMA 1 Enclosed Starter for:
Fusible Disconnect Switch
Combination
Add to NEMA 1 Enclosed Starter for :
Molded Case Circuit Breaker or
MCP Combination
NEMA Size
345
NEMA 4 Enclosure$3720. $6840. $6840. 61
NEMA 12 Enclosure 2280. 2880. 3240. 62
NEMA 1 Enclosure1824. 2520. 4512. 63
NEMA 4 Enclosure6856. 11328. 13320. 64
NEMA 12 Enclosure2136. 5736. 8232. 65
Ammeter & 1-Current Transformer
Ammeter, Switch & 3-Current Transformer
Voltmeter
Voltmeter & Switch
Elasped Time Meter
Wattmeter
Watthour meter
Convenience Recepticle Mounted on Side
Cylinder Lock on Door
Space Heater with N.C. Auxiliary
NEMA 1 & 12 Encl.612.612.612. 82
NEMA 4 Enclosure936.936.936. 83
NEMA 1 & 12 Encl.1008. 1008. 1008. 84
NEMA 4 Encl.1320. 1320. 1320. 85
NEMA 1;4, & 12 Encl.1152. 1152. 1152. 87
1680. 2376. 2376. 88
4440. 4440. 4440. 89
2376. 2376. 2376. 90
NEMA 1,4 & 12 Encl.3600. 3600. 3600. 91
696.696.696. 92
4864. 4864. 4864. 93
5040. 5040. 5040. 94
240.240.240. 95
600.600.600. 96
NEMA 1,4 & 12 Encl.924. 1488. 2208. 97
T 82 A A 4JB—26
B38Discount Schedule JC 14
Page 39
Field ModificationsNEMA Control - TM
Modification Kits
Cover Control
For
Description
Push Buttons
(Momentary)
Selector
Switches
(Maintained)
2
Pilot Lights
(Include Red Lens)
Reset Buttons
(One Reset Per Kit)
Start-Stop
Forward-Reverse-Stop
Hand-Off-Auto
120V
240V
120V
480V
240V
600V
480V
120V
600V
240V
120V
480V
240V
600V
480V
120V
600V
240V
480V
120V
600V
240V
120V
480V
240V
120V
480V
240V
600V
480V
For Bulletin
Number
6013 & 7707
6018-20
6030-31
6038-40
6013 & 7707
6030-31-50
6018-20-38,
6040-58-60
6013-30,
6031-50,
7707
6018-20,
6038-40,
6058-60
6013-30,
6050 (2 Req)
Mounting
Location
Case
Cover
Flange
Cover
Flange
Cover
Case
Case
Flange
Cover
Flange
Enclosure
Type
1, 4 & 12
1
1
1, 4 & 12
1
1
1, 4 & 12
1
1
1
1, 4 & 12
1
1
6018-20-38-40,
External Reset for NEMA Type 1, 4 & 12
Enclosed Standard Starters
6058-60 (2 Req)
6013-30,
6050 (2 Req)
Cover
1, 4 & 12
6018-20-38-40,
6058-60 (2 Req)
External Reset for #ETM032-1 & ETM031-1
NEMA Type 3R Enclosure
6013
3R
External Reset - For use with Joslyn Clark panel mounted overload kits in NEMA 1, 4 & 12 Enclosures. Dimensions from outside surface of
enclosure cover to device mounting surface must fall in the range:
1. For Bulletins 6018, 6020, 6038, 6040, 6058, & 6060, NEMA 4 & 12 enclosed, use 30 mm. units.
2. Kits may be changed in the field from 3-position to 2-position operation. In addition to HAND-OFF-AUTO,
four labels are included, marked: FORWARD-OFF-REVERSE; HIGH-OFF-LOW; TEST-LAG-HEAD; ON-OFF.
3. Not suitable for enclosed starters with transformer.
Discount Schedule JC14B39
Page 40
TM-NEMA ControlField Modification
B
Enclosure Kits
For Use With
Bulletin No.
of Open
Type Devices
6013 &7707
6030, 6031,
& 6050
6013-7707
6013-7707
1
NEMA Type 4
Stainless Steel
(Watertight - Dust tight)
Kit Number Price
120.
192.
240.
192.
312.
336.
168.
168.
ETM042-1
ETM042-2
ETM044-1
ETM042-2
-----ETM044-2
NEMA
Size
00-2
3 & 4
00-2
3 & 4
00-1
2
NEMA Type 1
(General Purpose)
Kit Number Price
ETM012-1
ETM012-2
ETM014-1
ETM012-2
ETM012-3
ETM014-2
NEMA Type 3R
(Rainproof-Sleet Resistance)
ETM031-1
ETM032-1
2
2
2 & 3
2 & 3
$$$
Transformer Mounting Plate
Bulletin No.
of Open
Type Devices
6013 & 7707
NEMA
Size
00-220A
3 & 4
Use with
Enclosure
Kit No.
ETM012-2
ETM014-1
ETM044-1
ETM124-1
Kit Numbers Price
KTM-28
KTM4-54
$$
24.
30.
Bulletin No.
of Open
Type Devices
7707-PM
6030-31
& 6050
Control Circuit Kits
Auxiliary contacts for cavity mounting in starter and contactors.
One Normally Open, Convertible
One Normally Closed, Convertible
For side mounting on starters and contactors
Two Normally Open, Non-Convertible
Transformer Kits: Complete J Fused primary a midget single fused 120V secondary
Note:
Can be used in NEMA 1, 4 & 12
enclosures that have available space. See
enclosure kits to determine those with
available space.
Fuse Block, 2 Pole, 30 Amp., 250V, Class H, with two 1/2 Amp. Dual Element Fuses.
Universal Starter Adaptor Kit. NEMA Size 1 Type TM starter with an assortment of
heaters, auxiliary contacts, and coils and A60-300999 adaptor plate. For rush and
emergency repairs; can replace most NEMA Size 00-1 starters
Notes:
1. For use with the listed open type devices. Each kit includes external "Reset" button(s)
and "Reset" plug(s), either of which may be installed in the predrilled enclosure cover.
All enclosures have sufficient space to allow mounting a transformer or other equipment of similar size, unless otherwise noted.
2. Does not have space for transformer.
3. External "Reset" not included. For external "Reset", add Kit Number KTM32-20.
4. Will not fit standard enclosures.
5. Not applicable to NEMA 1 - Bulletin 6018, 6038 & 6058
6018-20-38,
6040-58-60
All
0-2
00-1
KTM2-1
KTM-USA
B40Discount Schedule JC 14
72.
1584.
4
9
2
Page 41
Field Modification KitsNEMA Control - TM
Power Circuit
Fuse Clips - Kit includes 6 clips and mounting screws,without base for lower clips.
Fuse
Class
30 amp. 250 volt (incl. 3 adaptor plates)
30 amp. 600 volt & 60 amp. 250 volt
60 amp. 600 volt
100 amp. 250 volt & 600 volt
Fuse Clip Lower Mounting Base - required only when converting a non-fusible starter to fusible or when
changing from 60 to 100 amp.30 & 60 amp. 250 & 600V
H
H & J
H & J
H
Switch
Amp. Size
30 & 60
60 & 100
100 amp. 250 & 600 volt
* Add series letter from catalog # on the label on the door of Enclosure Series “A”, “B” or “C”
N.O. Type
Power Pole - Auxiliary pole for side-mounting
on starter or contactor.
NC. Type
Tie Pole - Auxiliary 4th & 5th power pole, both N.O. with 3-terminal connection
for side-mounting on starter or contactors.
Power Take Off - For multiple sets of overload relays.
Power Pole Insulator - Required when a power pole or tie pole is added to a
device in a 6
3
/4" wide enclosure.
Accessories
Cavity Cover (when auxiliary contact is not used)
Adapter Plate - Used to enable replacement of competitive starters with type TM.
Adjusting Knob Wedges - Package of 25. Used in overload adjustment knob to
Heater Rack - Designed for stocking heaters for all TM starters. Rack has 25
compartments and will hold 900 of the #2400 series heaters or 600 of the #2500
series heaters or a combination there of.
Enclosure
BW
NEMA 12 Enclosure Dimensions Modified for Outdoor Use
Joslyn Clark NEMA 12 enclosures may be field modified for outdoor use as follows:
NEMA 3
1. Watertight conduit hubs shall be used at all conduit entrances.
NEMA 3R
1. Watertight conduit hubs shall be used at all conduit entrances when the
conduit enters at a level higher than the lowest live part.
2. Drain holes of 1/8 inch diameter shall be added to the bottom of the enclosure.
Power Contact Kit, For 3 Pole Type TM Starter Or Contactor (Movable And Stationary Contacts
& Springs)
Power Contact Kit, For 2 Pole TM5 Starter Or Contactor (Movable And
Stationary Contacts & Springs)
Power Contact Kit, 1 Pole, For Type TM6 Starter or Contactor (Movable And Stationary
Contacts & Springs)
(3 Required for 3 Pole Devices)
Power Contact Kit, For Type TM Normally Open Auxillary Side-mounted Power Pole on 1 & 2
Pole Starters And Contactors (1 Kit Required Per Pole-Movable And Stationary Contacts &
Springs)
Power Contact Kit, For Normally Closed Type TM Auxillary Side-mounted Power Pole
(Movable And Stationary Contacts & Springs)
Power Contact Kit, For Type TM Auxillary Side-mounted Tie Pole
(Movable And Stationary Contacts & Springs
Arc Shield Cover Kit (1 Required Per Power Pole) TM6
Replacement Overload Relay, Standard Bimetallic, Less Heaters, For Single Phase Type TM
Starter. Non Ambient Compensated
Replacement Overload Relay, Non Ambient Compensated, Less Heaters, For 2 or 3 Phase
Type TM Starter
Replacement Overload Relay, Ambient Compensated, Less Heaters, For 2 or 3 Phase
Type TM Starter
Replacement Current Transformer Assembly, For Use with
KTM35-13 & KTMA35-13 Kits
Power Contact Kit, 3 Pole Type “U” Size 5 Starter or Contactor
(Movable & Stationary Contacts & Springs)
Continuous ampere and maximum horsepower ratings are
in accordance with the following NEMA Standards:
Starters ICS 2-32 1B, ICS 2-321F
Contactors ICS 2-211.23, ICS 2-211.24
B
Power Wiring Accommodation - Type TM1
NEMALoadWireTerminalTerminal Scre w
Size 2LineContactorOverloadTypeTypeWidth, In. Size
Contactor orTransformer SizesStarterVolt-Amperes, 60 Hertz
NEMANo. ofStandard100W Extra
SizePolesCapacityCapacity
00.0.
1 & 2
3 & 42-4250500
52-3350500
2
6
2 For starter with control relay; starter coil is full voltage.
2-450150
2-350150
B
3 This table does not apply to transformers in resistance welding service.
4 This table applies to contactors used with transformers having an inrush of not more than
(20) times their full-load current, irrespective of the nature of the secondary load.
Kilowatt Ratings Of Low-Voltage Transformers
For Resistive-Heating Loads Other Than Infrared-Lamp Loads 5
Per NEMA ICS 2.210-1
1 O, 2-Pole Contactors3 O, 3-Pole Contactors8-Hour Rating
(Open or Closed)(Open or Closed)of Contactor
Contactor Heating Load, KWHeating Load, KWAmperes
Size115V230V460V575V230V460V 575VOpenEnclosed
Automatic reset operation should not
be used with two wire control.
Separate Control
Remove wire "A" when it is supplied.
Connect separate control lines to the
"1" terminal on the pilot device and
the "4" terminal on the starter.
Coil Terminal wire to be #14 AWG
maximum.
Page 53
Engineering DataNEMA Controls - TM
For Starters 6030-TM;
Contactors 6031-TM
Elementary Diagram
Seperate Control
Remove wire "A" when it is supplied
Connect seperate control lines to the
"1" terminal on the pilot device and
the "8" terminal on the starter. Coil
terminal wire to be No. 14 AWG
maximum.
Pushbutton Control
B
Wiring Diagram Front View
Contactors "F" & "R" Are
Mechanically Interlocked
When Limit Switches Are
Used
Omit Wires "C" and "D" and
Connect Per Dotted Lines
B53
Page 54
TM - NEMA ControlsEngineering Data
For Starters 6050-TM
B
Elementary Diagram
Three Phase
Two Speed
Two Winding
Motor
Separate
Winding
Separate Control
Remove wire "A" when it is supplied
Connect separate control lines to the
"1" terminal on the pilot device and
the "8" terminal on the starter. Coil
terminal wire to be No. 14 AWG
maximum.
Pushbutton Control
Wiring Diagram Front View
Contactors "HI" and "LO" Are
Mechanically Interlocked
B54
Page 55
Engineering DataNEMA Controls - TM
For Starters 6050-TM
Wiring Diagram Front View
Elementary Diagram
Momentary Contact Pushbuttons
Figure 1Figure 2
B
Connections Of Motor And Pushbotton
Terminals To Starter Terminals
Three Phase Two Speed One Winding
Motor Connection Data
Figure 1 Constant Horsepower
L1 L2 L3 OpenTogether Speed
T1 T2 T3T4,T5,T6Low
T6 T4 T5 T1,T2,T3High
Figure 2 Constant TorqueFigure 3 Variable Torque
L1 L2 L3 OpenTogether Speed
T1 T2 T3 T4,T5,T6Low
T6 T4 T5T1,T2,T3High
L1 L2 L3 OpenTogetherSpeed
T1 T2 T3 T4,T5,T6Low
T6 T4 T5T1,T2,T3 High
B55
Page 56
B
TM - NEMA ControlsEngineering Data
For Starters 6018-TM, 6020-TM Combination
Dual voltage transformer is shipped as
shown connected for higher voltage.
Reconnect jumpers "J" per table for
lower voltage.
VoltageConnectL1L2
230
460H2 to H3H1H4
All SingleH1H2
Primary Transformers
H1 to H3H1H4
H2 to H4
B56
Page 57
Engineering DataNEMA Controls - TM
For Starters 6038-TM, 6040-TM Combination
Automatic reset operation
should not be used with
two wire control
When limit switches are used
omit wire "C" and "D" and
connect per dotted lines
B
Connections For Flange Mounted Or Remote Pilot Devices
Dual voltage transformer is shipped as
shown connected for higher voltage.
Reconnect jumpers "J" per table for
lower voltage.
VoltageConnectL1L2
230
460H2 to H3H1H4
All SingleH1H2
Primary Transformers
H1 to H3H1H4
H2 to H4
B57
Page 58
TM - NEMA ControlsEngineering Data
Standard A-C Wiring Diagrams
Two-Speed, Two Winding (Separate Winding)
For Starters 6058-TM, 6060-TM Combination
B
Elementary Diagram:
Wiring Diagram - Front View
Two Speed
Two Winding
Motor
Contactors
"HI" and "LO" are
Mechanically
Interlocked
Common Control
When control circuit obtains power
from the line side of the starter as
shown, and control conductors
extend beyond the enclosure, they
must have overcurrent protection
rated not in excess of 500% of the
control circuit conductor ampacity.
Such protection should be installed in
the field if starter does not have
control fuses.
B58
Separate Control
Remove wire "A" when it is supplied.
Connect separate control lines as
follows:
With internally mounted fuses,
connect to fuse block.
Without internal fuses, an external
fuse must be mounted immediately
adjacent to the controller. Connect to
"1" terminal on pilot devices and "6"
terminal on starter.
Page 59
Engineering DataNEMA Controls - TM
Wiring Diagrams
Two-Speed, One Winding (Consequent Pole)
For Starters 6058-TM, 6060-TM Combination
Elementary Diagram
Two Speed
One Winding
Motor
Wiring Diagram - Front View
B
Contactors "M1" and "M2"
Mechanically interlocked
Three Phase Two Speed One Winding
Motor Connection Data
MotorPushbutton ABCDEFM1 M2
Figure 1 Figure 2T6 T4 T5 T1 T2 T3 Low Hi
Figure 2 Figure 1T1 T2 T3 T6 T5 Hi Low
Figure 3 Figure 1T1 T2 T3 T6 T4 T5 HiLow
Figure 3 Variable Torque
L1 L2 L3 OpenTogetherSpeed
T1 T2 T3 T4,T5,76Low
T6 T4 T5T1,T2,T3 High
Accessory And Replacement Kits
KTM and KTR accessories can;
be used with this controller.
Other replacement coil by Part No. on
coils.
For other renewal parts information,
refer to S.B. 6000 TM.
Auxiliary contacts "W"
rated for standard duty
600 volts maximum.
Contact Cat. No.
H1 H2
1 N.O.KTM-10
1 N.C.KTM-11
B59
Page 60
B
TM - NEMA ControlNumbering System
Contactors & Non Combination Starters
Type of Starter or Contactor
T -
Standard unit with standard TM size 00 -4 starter or contactor.
V -
Standard unit with standard Vacuum starter or contactor.
U -
Standard unit with standard TM size 5 starter or contactor.
A -
Standard unit except with ambient compensated overload relays.
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
208/60
380/50
220/25
440/25
Suffix
Standard
Capacity
- T26
- T46
- T56
- T86
- T35
- T22
- T42
100 Watt
Extra
Capacity
Suffix Without Transformer
Coil Volts & Hertz Suffix
110-120/60 or 110/50
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
208/60
- 76
- 26
- 46
- 56
- 86
- C26
- C46
- C56
- C86
- C35
- C22
- C42
4
9
2
B62
Page 63
Numbering SystemNEMA Control - TM
Reduced Voltage Auto Transformer Starters
Type of Starter or Contactor
Standard unit with standard Type TM starter or contactor.
T -
Standand unit with vacum starter or contactor.
V -
Standard unit with standard TM size 5 starter or contactor.
U -
Standard unit except with ambient compensated overload relays.
A -
Enclosure Type
A -
NEMA 1
U -
Open Type
W -
NEMA 4
T -
NEMA 12
T 82 A A 4 M E - 46
Product Code
82- Non Combination
83- Fused Combination
84- C.B. Combination
Cover Control
Reset button in cover for overloads.
A -
Reset button and Hand-Off-Auto selector switch.
B -
Reset button and Start-Stop push button
C -
None (no reset button in cover)
O -
Size of Starter
0 1 2 3 -
Size 0
Size 1
Size 2
Size 3
4 5 6 -
Size 4
Size 5
Size 6
B
Motor Horsepower
A B C D E F G H J K L -
5 HP
7 1/2 HP
10 HP
15 HP
20 HP
25 HP
30 HP
40 HP
50 HP
60 HP
75 HP
M N P Q R S T U V W X -
100 HP
125 HP
150 HP
200 HP
250 HP
300 HP
400 HP
450 HP
500 HP
600 HP
Other
Line Voltage
A -
208V/60Hz
B -
230V/60Hz
C -
220V/50Hz
D -
380V/50Hz
Suffix With Transformer
(secondary 110-120V with single fuse)
Transformer Primary
Volts & Hertz
220-240/60 or 220/50
440-480/60 or 440/50
550-600/60 or 550/50
208/60
380/50
220/25
440/25
460V/60Hz
E -
440V/50Hz
F -
575V/60Hz
G -
Suffix
Standard
Capacity
- T26
- T46
- T56
- T86
- T35
- T22
- T42
100 Watt
Extra
Capacity
- C26
- C46
- C56
- C86
- C35
- C22
- C42
Suffix Without Transformer
Coil Volts & Hertz Suffix
110-120/60 or 110/
50
220-240/60 or 220/
50
440-480/60 or 440/
50
550-600/60 or 550/
50
208/60
- 76
- 26
- 46
- 56
- 86
B63
Page 64
B
General Information5000 - AC Control
Application
The 5000 Space Savers in NEMA Sizes 00 thru 5 offer versatile and compact AC contactors for industrial motor, heating and other
power circuit switching. Simplified design coupled with built-in reliability assures the user long, trouble-free operation in machine tools, process controls, air-conditioning, custom panels and other demanding applications.
Description
All 5000 magnetically operated contactors incorporate a modern, modular design compatible with other control component
modules. Terminal location make them ideal for straight-through wiring and for wire-channel layouts. Accessible, up-front
pressure-type terminals are standard.
The hot molded, high arc resistant two or three piece housings not only totally enclose contacts and operating coils for environmental protection; but also separate them as added protection against internal phase-to-phase short circuits.
Generous size, long wearing double break contacts are furnished on all sizes. Contacts are made of silver cadmium oxide for
"anti-weld" protection under high inrushes. Contacts do not require adjustment or periodic dressing (filing).
Coil Data
Standard coils for continuous duty service are equipped with pressure type terminals. Molded coil constrution resists moisture;
thermal and mechanical stress.
Typical User Benefits:
Modern Modular Design - makes contactors compatible with
other control panel components. Ideal for wire-channel layouts.
Compact Size - 5000 Contactors conserve control panel area
without sacrificing accessibility or reliability. The 100 amp. Size 3
contactors occupy less than 19.0 sq. in. of panel space.
Only 15 Basic Parts - This simple design affords longer operating
life and greater reliability than more complex units.
Fast Installation - Accessible up-front pressure type
terminals on both power and control circuits, take unlugged
stripped wire. Design permits straight-through wiring.
Quick, Easy Inspection - Simply withdraw the front
housing piece, after removing two screws, all main contacts are in full view. No need to disturb wiring or remove
contactor from panel for complete inspection of all parts.
N.O. Std.
N.C. Std.
N.O. & N.C. Std.
N.O. Low Power
N.C. Low Power
N.O. & N.C. Low Power
N.O. Std. & N.C. Low Power
N.O. Low Power & N.C. Std.
N.C. Std. Early Close
N.O. Low Power & N.C. Std.
Late Break
N.C. Low Power - Late Break
N.O. Std. & N.C. Low Power
Late Break
N.O. Low Power & N.C. Low Power
Tandem Mounting Kit