Mark 608DS (1-1/2" - 2”)
3170 Wasson Road • Cincinnati, OH 45209 USA
Phone 513-533-5600 • Fax 513-871-0105
info@richardsind.com • www.jordanvalve.com
Mark 608DS Gas Pressure Regulators
Installation Instructions for
Warning: Jordan Valve Pressure Regulators must only be used, installed and repaired in accordance with these Installation & Maintenance Instructions. Observe all applicable public and company codes and regulations. In the event
of leakage or other malfunction, call a qualified service person; continued operation may cause system failure or a
general hazard. Before servicing any valve, disconnect, shut off, or bypass all pressurized fluid. Before disassembling
a valve, be sure to release all spring tension.
Please read these instructions carefully!
4. If possible, install a relief valve downstream from
the valve. Set at slightly above the control point of
Your Jordan Valve product will provide you with long,
trouble-free service if it is correctly installed and maintained. Spending a few minutes now reading these instructions can save hours of trouble and downtime later.
When making repairs, use only genuine Jordan Valve
parts, available for immediate shipment from the factory.
the valve but below the maximum safety limit for
the tank.
5. It is strongly recommended that the installer read
and be thoroughly familiar with API 2000, Standard
Information for Tank Blanketing Regulator Selection
before installing and attempting to operate this
product.
Ideal Installation
Control Line
Conservation Vent
Emergency
Pressure Vent
Control Line
Gas Supply
Blanketing
Valve
IMPORTANT: IF THE INTENDED SET POINT OF THIS
VALVE IS BELOW 8 wc (20 mbar), THE VALVE MUST
BE MOUNTED IN THE INVERTED POSITION (SPRING
HOUSING DOWN).
1. To protect the valve from grit, scale, thread chips
and other foreign matter, ALL pipelines and piping
components should be blown out and thoroughly
cleaned before the installation process begins.
2. Shutoff valves, pressure gauges and by-pass piping are optional, and if installed should be in accordance with all applicable codes, standards, and
practices. They are recommended to provide easier
adjustment, operation, and testing.
3. The flow arrow on the valve body must be pointed
in the direction of flow. Ideally, the valve should be
installed in the highest horizontal line of piping.
A control line must be installed as follows:
1. Connect one end of a ¾” pipe to the fitting under
the diaphragm.
2. Connect the other end to an appropriate fitting on
the tank.
3. DO NOT locate the control line tap in any location
where turbulence or abnormal velocities may occur.
Control line should
slope downward toward
the tank to prevent
Condensation buildup.
1. Make the control line as short
and straight as possible.
2. Connect the control line to
the point where the pressure
is to be controlled.
3. Increase 1 pipe size for every
10 feet of control line, with
setpoints less than 5" w.c.
(0,012 bar).
Blanketing Gas
Control line
Vapor Pressure
Media
4. The control line should be sloped away from the
valve.
5. Install a pressure gauge to measure pressure in the
tank itself, not in the outlet piping or the control line
to aid in setting the valve.
Control Line Piping Recommendation
Keep the regulator as close to the tank as possible
and as high as possible.
Minimize the length of the downstream pipe com-
ing from the valve.
NEVER reduce the pipe size on the valve outlet to
the tank. This line must always be as large as the
valve size, or one pipe size larger to assure it does
not act as a restriction.
Any downstream isolation valve after the regulator
must be a full port type. The isolation valve cannot
act as a restriction.
The sensing line must be a minimum of 3/4" pipe.
A sensing line isolation valve is recommended.
Again, must be full ported.
Slope the sensing line to the sensing port on the
tank.
Keep the sensing line as short and straight as pos-
sible.
For each 10 feet of sensing line, increase the line
size by one pipe diameter. (Especially important on
the blanket pressures of less than 5 inches of water
column).
Keep the sensing port on the tank as far removed
as possible from the downstream pipe outlet going
into the tank.
Start-Up
With the inlet, outlet, and bypass shutoff valves closed,
and no pressure in the downstream line:
1. Slowly open the inlet valve just enough to start
flow through the valve. Observe the tank pressure
gauge. Increase the downstream pressure slowly
by gradually opening the inlet valve.
2. Do not fully open the inlet valve until you are sure
that the regulator has control of the system. Usually, the handwheel on the inlet valve will turn freely
when this is achieved.
3. To change the controlled pressure, adjust the
controlled pressure supplied to the top of the diaphragm.
A. Under Pressure: Controlled pressure too low; not
enough flow or no flow through valve.
B. Over Pressure: Valve will not close or controlled
pressure increases after valve closes.
C. Pressure Fluctuates: Controlled pressure rises and
falls, will not settle out under low loads.
The next step is to determine what could cause the
trouble. The third step is to locate and remedy the cause
by the process of elimination. Make no assumptions and
check the easy ones first. The guide below lists the controlled pressure action, common causes and procedure
for checking each cause.
Controlled pressure action UNDER PRESSURE:
Valve undersized for application. Check capacity
required and valve capacity.
Line strainer screen clogged. Blow down strainers
or visually check that they are clear.
Incorrect setting on range spring. Vary the setting
and check response.
Main valve diaphragm or balance diaphragm rup-
tured. See action on valve maintenance.
Malfunction of other piping components. Check
for leaking safety valves, inadvertently opened or
closed valves.
Controlled pressure action OVER PRESSURE:
Incorrect setting on range spring. Vary the setting
and check response.
Main valve seats leaking. Close inlet shut-off valve,
allow downstream pressure to bleed off, close outlet valve and remove loading pressure tubing. Back
out adjusting screw on valve until free. Crack open
inlet shut-off valve - if the fluid issues from the main
valve port, the main valve seats are leaking.
By-pass shut-off leaking. During period of leakage
close outlet shut-off valve, observe downstream
pressure gauge.
Controlled Pressure Fluctuates:
Valve oversized. Check capacity required and valve
capacity.
Note: Valve is NOT field repairable. Contact your local
representative or 800-543-7311 for repair information.
Trouble Shooting
The first step in troubleshooting a piloted pressure regulator is to classify the action of the controlled pressure
into one of the following categories:
Bulletin IM-MK608DS-1211
3170 Wasson Road • Cincinnati, OH 45209 USA
Phone 513-533-5600 • Fax 513-871-0105
info@richardsind.com • www.jordanvalve.com