Jordan Valve Mark 25 User Manual

I & M Mark 25
3170 Wasson Road • Cincinnati, OH 45209 USA
Phone 513-533-5600 • Fax 513-871-0105
info@richardsind.com • www.jordanvalve.com
Please read these instructions carefully!
Your Jordan Valve product will provide you with long, trou­ble-free service if it is correctly installed and maintained. Spending a few minutes now reading these instructions can save hours of trouble and downtime later. When mak­ing repairs, use only genuine Jordan Valve parts, available for immediate shipment from the factory.
Installation & Maintenance Instructions for
Mark 25 TempilotTM Temperature Controller
ing the response time. Turning the screw counterclock­wise decreases the sensitivity by increasing the flow and reducing the response time.
Sensitivity
The sensitivity of the Tempilot controller is adjusted by turning the restriction screw. (The restriction screw is factory set for air operation.) For water operation, the re­striction screw should be opened a minimum of 1/2 turn and recalibrated. Restriction screw must NEVER be fully closed. Make adjustments slowly, allowing about two min­utes after each adjustment for the controller to balance.
NOTE: If sensitivity is changed, controller must be reca­librated.
Operation
A temperature change in the medium being controlled creates a change in length of the sensitive tube (1). An increase in temperature lengthens the sensitive tube (1) and moves the Invar rod (2) away from the lever (3). The lever (4), which pivots at Point A, is moved to close the exhaust valve (4) by spring (5). This permits the supply (air or water) (S) to increase the pressure in the control line (R) and close the normally open valve. A decrease in tem­perature shortens the sensitive tube (1) and moves the Invar rod against the lever (3). The lever (3) moves against the pressure spring (5), to open the exhaust valve (4). This exhausts the pressure in the control line and opens the valve.
The sensitivity adjustment screw (6) regulates the rate of flow of the supply air (or water) to the controller to a change in temperature. Turning the screw clockwise in­creases the sensitivity by reducing the flow and increas-
Installation
The Jordan Tempilot requires a clean, reliable supply of compressed air or cold water at 15 - 25 pounds pressure. Other fluids may be used, such as gas, oil, etc., providing provision is made for safe disposal.
AIR OPERATION — The Tempilot should normally be in­stalled in the horizontal position; however, other positions may be used if the supply and control connections are parallel with the ground and calibration is checked after installation.
WATER OPERATION — The Tempilot must be installed in the horizontal position with the drain connection at the bottom. Drain piping should be 3/8” minimum for posi­tive draining at all times.
1. Select the sensitive element location with care to as­sure satisfactory results. Bulb must project entirely into the water or air being controlled.
2. Flush or blow out all lines before making final con­nections. Put supply pressure through all control lines and check for leaks.
3. Always locate the Tempilot as close to the control valve as possible. Piping between the Tempilot and the control valve should be 1/8” brass pipe or 1/4”
PROTECT VALVES WITH LINE STRAINERS
O.D. copper tubing.
4. The difference in height between the Tempilot and the control valve should be kept to a minimum. When the regulator is below the control valve, the elevation cannot exceed 10’ with a 15 psi supply pressure. If the Tempilot is above the control valve, adjust springs on the valve to compensate for the static head pressure.
Positions “B” and “D” (dotted) show pivot point (B) and spring location (D) for reverse acting regulator.
A
B
3
C
D
2
Valve
(Normally
Open)
1
2. Install Lever (6). Tighten the Lever Pivot Screws (21) as required. The Lever must be in the exact center of the body and must move freely but without side play. (For Water only — seal Lever Pivot Screws with Loctite Grade E.)
3. Install Screws (22).
4. Install parts (8) and (9). (Note relationship for Direct and Reverse Acting.)
5. Back up Adjustment Screw (5) until Collar (19) touch­es the Pivots on Lever (6).
6. Install Cover Assembly (2).
7. Install Adjustment Knob (3). The notch on Knob (3) should be opposite the dial marking correspond­ing to the room temperature. Tighten the Knob Set Screw very firmly.
8. Turn the Adjustment Knob to the desired control temperature for an approximate calibration.
9. Recalibrate as required after the controller is installed and connected to the supply and control lines.
5
6
R
4
S
Figure 1
Calibration
1. To calibrate the Tempilot, turn the adjusting knob until a 7-1/2” psi control pressure shows on the gauge.
2. Read the temperature at the bulb with an accurate thermometer.
3. Loosen the set screw in the adjusting knob and turn the adjusting knob to indicate the temperature at the bulb.
4. Tighten the set screw.
5. Now set the Tempilot for the desired temperature for your process.
Both Air and Water Controller
A. Disassembly (Refer to Figure 4 on page 3)
1. Remove Knob (3) after loosening its Set Screw.
2. Remove Cover Assembly (2).
3. Remove Lever Spring Retainer (8) and Lever Spring (9).
4. Back up one Lever Pivot (21) and remove Lever (6).
5. Unscrew Sensitive Tube Assembly (20) from Body (1).
Lever Spring Retainer
Direct Acting spring in front of lever. For
Figure 2
Reverse Acting, place spring behind lever.
Please note Figure 2. This figure shows how the lever spring and the lever spring retainer should be assembled in front of the lever for direct acting regulators. Also note that the lever pivots and the lever pivot set screws are as­sembled in the top two pivots for a direct acting Tempilot
Reversing Tempilot Action
Please note Figure 3. Since this is a reverse acting Tem­pilot, the lever spring retainer is in front of the lever, and the lever spring is behind the lever. Also, the lever pivots and the lever pivot set screws are in the lower two pivot points.
Figure 3
B. Assembly
1. Install new Sensitive Tube Assembly (20) to body (1).
Set Screws (Reverse Acting)
-2-
Loading...
+ 2 hidden pages