Safety timer
JSHT2
Approvals:
TÜV Nord
Safety relay for:
Time bypassing
Inching
Features:
Hardwire time selection
0.2 – 40 s
Selectable single or dual
channel input
Test input
Width 45 mm
The JSHT2A/B/C closes two independent relay outputs
during a guaranteed maximum period of time when
the inputs are closed.
Time bypassing
Sensors detect the autocarrier and are connected to the
JSHT2 which supervises the sensors and by pas ses the
light beam for a maximum predeter mined time.
Inching
Inching applications require safety outputs to be closed
for a predetermined maximum period of time, allowing the
machine to move only a short distance each time the inching control is activated. For each new motion the inching
control e.g. PB or pedal must be released and activated
again.
Operation
When the inputs close the output contacts close. The output contacts open when the input opens or when the time
period has expired. The time is hardwire selectable on the
terminals T1, T2 and T3. The time given is the maximum
time. Single or dual channel operation is also hardwire selectable.
LED indication for supply,
inputs and outputs
1+1 NO relay outputs
Supply 24 VDC, 24, 48, 115
or 230 VAC
Quick release connector
blocks
Connection examples
For examples of how our safety relays can solve various safety
problems, please see the section “Connection examples”.
Regulations and standards
The JSHT2A/B/C is designed and approved in accordance
with appropriate directives and standards. See technical data.
Light beam being bypassed
only for the time it takes the
auto carrier to pass.
Shaft only turns a small
amount each time the PB is
pressed.
Technical data – JSHT2 A/B/C
Manufacturer ABB AB/Jokab Safety, Sweden
Article number/Ordering data
JSHT2A 24 DC 2TLJ010012R0000
JSHT2B 24 DC 2TLJ010012R1000
JSHT2C 24 DC 2TLJ010012R2000
Colour Black and beige
Power supply 24 VDC ± 15 %
Power consumption 1,8 W/3,8 VA
Max Input Wire res. at nom
voltage/channel
Response time at activation < 30 ms
Response time at deactivation < 15 ms
Selectable time
(± 15 % at nom. V.)
Relay outputs 2 x 1 NO
Max. switching capacity
Resistive load AC 4A/250 VAC/10 00 VA
Inductive load AC AC15 250VAC 3A
Resistive load DC 4A/24 VD C/100 W
Inductive load DC DC13 24VDC 2A
Max. total switching capacity: 8A distributed on all contacts
Min. load 10m A /10 V (if load on contact has
Contact material AgCuNi
Fuses Output (External) 3A gL/gG or 4A fast
Max Input Wire res. at nom.
voltage 100 Ohm
24/48/115/230 VAC ± 15 %, 50 - 60 HZ
100/200 Ohm (1 Channel/
2 Channel)
JSHT2A: 0.2 - 0.5 - 0.7 - 1.0 sec
JSHT2B: 5 - 10 - 15 - 20 sec
JSHT2C: 5 - 15 - 30 - 40 sec
not exceeded 100 mA)
Terminals (Max. screw torque
1 Nm)
Single strand: 1 x 4 mm2 or 2 x 1,5 mm
Conductor with socket contact: 1 x 2,5 mm2 or 2 x 1 mm
Mounting 35 mm DIN-rail
Protection class enclosure/
terminals IP 20/IP 40 IEC 60529
Impulse Withstand Voltage 2.5kV
Pollution Degree 2
Operating temperature range –10°C to +55°C (with no icing or
Operating humidity range 35% to 85%
LED indication Electrical Supply, Inputs, Outputs
Weight 24 VDC: 310 g
Performance (max.)
Functional test: The relays must be
cycled at least once a year.
Conformity 2006/42/EC, 2006/95/EC,
condensation)
24/48/115/230 VAC: 410 g.
Safety Category 4/PL e (EN ISO
13849-1:2008)
SIL 3 (EN 62061:2005)
PFHd 4.42E-09
2004 /108/ EC
EN 954-1:1996, EN 62061:2005
EN ISO 13849-1:2008
Connector blocks are detachable
(without cables having to be disconnected)
2
2
1
2
3
4
5
6
Technical description – JSHT2 A/B/C
Connection and
monitoring circuit
**
The electrical supply is connected across
A1 and A2. The internal supervising circuit is
activated directly when the supply is on. The
inputs A and B must both be opened and
then closed. Thereafter K1 and K2 are activated and the outputs close. K1 and K2
are activated for hardwired selected time
Timer
** Only for AC-supply.
(set by connections on the terminals T1,
T2 and T3). If there is a short circuit between the inputs or the inputs are opened
again before the set time period has expired the outputs will open. In order to close
the outputs again both the inputs have to
be opened and both internal relays K1 and
Electrical connection – JSHT2 A/B/C
7
8
K2 deactivated (controlled by the supervising circuit) and then the inputs closed
again.
By external hardwire connectors the
JSHT2 can be made to operate from
either single or dual channel inputs. See
figure below.
Connection for dual channel inputConnection for single channel input
9
10
11
Selection of time by hardwire links
JSHT2A JSHT2B JSHT2C
* It is recommended that all switched loads are
adequately suppressed and/or fused in order
to provide additional protection for the safety
contacts. In the figure the monitoring of two
contactors in the test input is shown.
12
13
14