Safety relay/expansion relay
BT51(T)
Approvals:
TÜV Nord
Safety relay for:
Emergency stop
Interlocked hatch
Expansion of Pluto
Features:
Single and “dual” channel
Test/"reset" input
Width 22.5 mm
LED indication
Safety relay/expansion relay to Pluto
The BT51 is designed to connect safety devices, such as
emergency stops, directly in the voltage supply circuit to
the relay. Despite a maximum built-in width of 22.5 mm the
relay is very powerful.
With 4 NO safety outputs, test input and complete internal supervising, the BT51 is quite unique. In addition
you can order delayed outputs (BT51T).
In order for the safety outputs to close, the supply voltage, e.g. by means of an emergency stop button, must be
connected to A1 and A2 and the test input closed. After
actuation of the relay the test input can be opened again.
The test input is intended to supervise that contactors
or valves have dropped/returned before a new start can
be permitted.The test input can also be used for starting
and the start button can be supervised (see connection
example on next page).
More outputs
By connecting BT51 to a safety relay/PLC it is easy to
increase the number of safe outputs. This means that an
unlimited number of dangerous machine operations and
functions can be stopped from one safety relay/PLC.
4 NO relay outputs
Supply 24 VDC
Quick release connector
blocks
BT51 - Additional power
terminals
BT51T - One changeover
relay with a double information output (Y14)
BT51T
Delay times selectable from
0 - 1.5 s
Safety level
BT50 have an internal redundant and monitored safety
function. Power failure, internal component faults or external interference cannot result in dangerous functions.
Input via A1 only is not protected from short circuiting,
and therefore installation is critical for the safety level to be
achieved. To achieve a higher safety level a screened cable can be used and/or connection made to both A1 and
A2 (see example overleaf).
Regulations and standards
The BT51 is designed and approved in accordance with
appropriate directives and standards. See technical data.
Connection examples
For examples of how our safety relays can solve various safety
problems, please see the chapter “Connection examples”.
Technical data – BT51(T)
Manufacturer ABB AB/Jokab Safety, Sweden
Article number/Ordering data
BT 51 2TLJ010033R2000
BT 51T 2TLJ010033R3000
Colour Black and beige
Operational voltage 24 VDC + 15%/-25%
Power consumption 1,4 W/1,8 W
Relay Outputs 4 NO
Max. switching capacity
Resistive load AC 6A/250 VAC/1500 VA
Inductive load AC AC15 240VAC 2A
Resistive load DC 6A/24 VD C/150 W
Inductive load DC DC13 24VDC 1A
Max. res. load total switching
capacity: 12 A distributed on all contacts
Min. load 10mA /10 V (if load on contact has
Contact material Ag + Au flash
Fuses Output (External) 5A gL/gG
Conditional short-circuit current
(1 kA) 6A gG
Max Input Wire res. at nom.
voltage 200 Ohms
Response time at deactivation <20 ms or delayed max 1500 ms
Terminals (Max. screw torque 1 Nm)
Single strand: 2x1.5 mm
Conductor with socket contact: 2x1mm
not exceeded 100 mA
(B T51T)
2
2
Mounting 35 mm DIN-rail
Protection class enclosure/
terminals IP 40/20 IEC 60529
Impulse Withstand Voltage 2.5kV
Pollution Degree 2
Operating temperature range -10°C to +55°C (with no icing or
Operating humidity range
LED indication Electrical Supply, Relay and X4
Weight 200 g
Performance (max.)
Functional test: The relays must be
cycled at least once a year.
Conformity 2006/42 /EC, 2006/95/EC,
condensation)
35% to 85%
Category 4/PL e (EN ISO 138491:2 008)
SIL 3 (EN 62061:2005)
PFHd 1.63E-08
2004/108/EC
EN 954-1:1996, EN 62061:2005
EN ISO 13849-1:2008
Connector blocks are detachable
(without cables having to be disconnected)
1
2
3
4
5
Technical description – BT51(T)
Supervision circuit
When supply voltage is connected to A1
and A2, relays K1 and K2 are activated. K1
and K2 drop if the supply voltage is disconnected. Both relays K1 and K2 must drop for
them to be activated again. Another requirement is that the test circuit, A1 - X4, must
be closed for the outputs to be activated.
Thereafter A1 - X4 can either be open or
constantly closed.
The supervising circuit ensures that both
K1 and K2 have dropped before they can
be reactivated. The stop function complies
with the requirement that a component fault
Electrical connection – BT51(T)
or external interference cannot lead to a
dangerous function.
The safety outputs consist of contacts
from K1 and K2 connected internally in
series across terminals 13 - 14, 23 - 24, 33
- 34 and 43 - 44. These contacts are used
to cut the power to components which stop
or prevent hazardous movements/functions.
It is recommended that all switched loads
are adequately suppressed and/or fused in
order to provide additional protection for the
safety contacts.
BT51T - Info. output
BT51T - Delay times
A2 T1 T2 A2 T1 T2
0 s
0.5 s
1.0 s
1.5 s
Max load
250 mA
6
7
8
9
10
*
Emergency stop with reset when emergency
button returns.
*
Emergency stop with dual connection direct
to the supply voltage.
* BT51 has additional power terminals A1 and A2.
*
Hatch with automatic reset. BT51 as emergency stop and control
relay with Start and Stop function.
LOAD
A1 X4
Controlled monitoring of external contactor, relay, valve or ABB Jokab Safety’s
expansion relays.
Monitoring to ensure that the On button is not stuck in pressed position. A
short circuit over the closing contact is
not monitored.
A1 X4
11
12
13
14