Jokab Safety BT50, BT50T Catalog Page

www.jokabsafety.com
6:24
www.jokabsafety.com
Safety relay/expansion relay
BT50(T)
Approvals:
TÜV Nord
Safety relay for:
Emergency stop
Interlocked hatch
Expansion of Pluto
Features:
Single and “dual” channel
Test/"reset" input
Width 22.5 mm
LED indication
Safety relay/expansion relay to Pluto
The BT50 is designed to connect safety devices, such as emergency stops, directly in the voltage supply circuit to the relay. Despite a maximum built-in width of 22.5 mm the relay is very powerful. With 3NO safety outputs, 1NC output (for monitoring purposes), a test input and complete internal supervision, the BT50 is quite unique. In addition, delayed outputs (BT50T) can be ordered. In order for the safety outputs to close, the supply volt­age, e.g. by means of an emergency stop button, must be connected to A1 and A2 and the test input closed. After actuation of the relay the test input can be opened again. The test input is intended to supervise that contactors or valves have dropped/returned before a new start can be permitted.The test input can also be used for starting and the start button can be supervised (see the connec­tion example on the next page).
More outputs
By connecting a BT50 to a safety relay/PLC it is easy to increase the number of safe outputs. This means that an unlimited number of dangerous machine operations and functions can be stopped by using just one safety-PLC.
Safety level
BT50 have an internal redundant and monitored safety function. Power failure, internal component faults or exter­nal interference cannot result in dangerous functions. Input via A1 on its own is not protected from short
3 NO/1NC relay outputs
Supply 24 VDC
Quick release connector blocks
BT50 - Additional power terminals
BT50T - One changeover relay with a double informa­tion output (Y14)
BT50T - Delay times selec­table from 0 - 1.5 s
circuiting, and therefore installation is critical for the safe­ty level to be achieved. To achieve a higher safety level a screened cable can be used and/or connection made to both A1 and A2 (see the example on the next page).
Regulations and standards
The BT50 is designed and approved in accordance with appropriate directives and standards. See technical data.
Connection examples
For examples of how our safety relays can solve various safety problems, please see the chapter “Connection examples”.
www.jokabsafety.com
6:25
Technical data – BT50(T)
1 2 0
84
2 2 , 5
Manufacturer ABB AB/Jokab Safety, Sweden Article number/Ordering data
BT50 2TLJ010033R0000 BT50T 2TLJ010033R1000
Colour Black and beige Operational voltage 24 VDC + 15%/-25% Power consumption 1,4 W/1,8 W Relay Outputs 3 NO + 1 NC Max. switching capacity
Resistive load AC 6A/250 VAC/1500 VA Inductive load AC AC15 240VAC 2A Resistive load DC 6A/24 VDC /15 0 W Inductive load DC DC13 24VDC 1A
Max. res. load total switching capacity: 12A distributed on all contacts
Min. load 10mA /10 V(if load on contact has
Contact material Ag + Au flash Fuses Output (External) 5A gL/gG Conditional short-circuit current
(1 kA) 6A gG Max Input Wire res. at nom.
voltage 200 Ohms Response time at deactivation
(input - output)
not exceeded 100 mA)
Version B <20 ms or delayed ma x 1500 ms (old version of BT50 <60 ms)
Terminals (Max. screw torque 1 Nm)
Single strand: 2x1.5 mm Conductor with socket contact: 2x1mm2.
Mounting 35 mm DIN-rail Protection class enclosure/
terminals IP 40/20 IEC 60529 Impulse Withstand Voltage 2.5kV Pollution Degree 2 Operating temperature range -10°C to +55°C (with no icing or
Operating humidity range 35% to 85% LED indication Electrical Supply, Relay and X4 Weight 200 g Performance (max.)
Functional test: The relays must be cycled at least once a year.
Conformity 2006/42/ EC, 2006/95/EC,
condensation)
Category 4/PL e (EN ISO 13849­1:2 008) SIL 3 (EN 62061:2005) PFHd 1.22E-08
2004 /10 8/EC EN 954-1:1996, EN 62061:2005 EN ISO 13849-1:2008
Connector blocks are detachable (without cables having to be disconnected)
2
1
2
3
4
5
Technical description – BT50(T)
Supervision circuit
When supply voltage is connected to A1 and A2, relays K1 and K2 are activated. K1 and K2 drop if the supply voltage is discon­nected. Both relays K1 and K2 must drop for them to be activated again. Another require­ment is that the test circuit, A1 - X4, must be closed for the outputs to be activated. Thereafter A1 - X4 can either be open or constantly closed.
The supervising circuit ensures that both K1 and K2 have dropped before they can be reactivated. The stop function complies with the requirement that a component fault
Electrical connection – BT50(T)
K1
K2
or external interference cannot lead to a dangerous function.
The safety outputs consist of contacts from K1 and K2 connected internally in series across terminals 13 - 14, 23 - 24, and 33 - 34. These contacts are used to cut the power to components which stop or prevent hazardous movements/functions. It is recommended that all switched loads are adequately suppressed and/or fused in order to provide additional protection for the safety contacts.
The NC output 41 - 42 should only be used for monitoring purposes e.g. indication lamp for emergency stop pressed.
BT50T - Info. output
Max load 250 mA
BT50T - Delay times
A2 T1 T2 A2 T1 T2
0 s
0.5 s
1.0 s
1.5 s
6
7
8
9
10
*
Emergency stop with reset when emergency button returns.
*
Emergency stop with dual connection direct to the supply voltage.
* BT50 has additional power terminals A1 and A2.
*
Hatch with automatic reset. BT50 as emergency stop and control
relay with Start and Stop function.
A1 X4
Controlled monitoring of external contac­tor, relay, valve or ABB Jokab Safety’s expansion relays.
Monitoring to ensure that the On but-
A1 X4
ton is not stuck in pressed position. A short circuit over the closing contact is not monitored.
LOAD
11
12
13
14