Johnson Controls Unitary Products YH-15, YJ-12, YH-20, YJ-15, YH-25 Technical Manual

...
Page 1
R-410A SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS AND AIR HANDLERS
YH-07 thru -25 and YJ-10 thru -20
CONDENSING UNIT MODELS
PH-07 thru -15 and PJ-15 thru -20
HEAT PUMP UNIT MODELS
AIR HANDLING UNIT MODELS
7.5 - 25 Ton 60 Hertz
TECHNICAL GUIDE
TECHNICAL GUIDE
ISO 9001
Certified Quality
Management System
YH/YJ/PH Outdoor Units
YH/YJ/PH/PJ Outdoor Units
NH/NJ Indoor Units
505430-BTG-P-0316

Description

UP condensing units and heat pumps are completely assembled, piped and wired at the factory to provide a single-piece unit for shipment and rigging. Each unit is pressurized with a holding charge of refrigerant R-410A for storage and/or shipping.
The compact design, clean styling, small footprint, and quiet operation make these condensing units and heat pumps suitable for almost any outdoor location. On rooftops... because they weigh much less than a single package unit of similar capacity and are much easier to rig and support. On the ground... because the footprint is compact allowing a variety of applications.
Both the UP condensing units and heat pumps are equipped with reliable Simplicity® SE microprocessor controls to assure proper operation and unit protection for long product life. Products from 10 to 20 tons are available in single or dual (2 or 4 pipe) refrigerant circuits for redundancy in operation and various application choices such as one outdoor unit matched with two indoor units.
The UP air handling units are completely assembled units, including a well-insulated cabinet, a DX cooling coil with copper tubing, aluminum fins, expansion valve(s), distributor(s), 2” throwaway filters, a centrifugal blower, a blower motor, an adjustable belt drive, a blower
motor contactor and a small holding charge of nitrogen.
(Except YH-25)
Page 2
505430-BTG-P-0316
Units are shipped in the vertical position ready for field installation, but can be easily converted to horizontal position. An added benefit of the UP air handling units is they are
designed to operate with either a condensing unit or a heat pump and no field modification or special unit is required for heat pump applications.
2 Johnson Controls Unitary Products
Page 3
505430-BTG-P-0316

Table of Contents

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Condensing Unit Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Outdoor Unit Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Air Handling Unit Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Cooling and Heating Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Air Handling and Hot Water Coil Accessory Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Air Handling and Steam Coil Accessory Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Electrical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Weights And Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Johnson Controls Unitary Products 3
Page 4
505430-BTG-P-0316
Product Category
Y = Split System, Condenser, AC, R-410A
Product Identifier
H = Standard Efficiency, 2-Pipe, R-410A J = Standard Efficiency, 4-Pipe, R-410A
Nominal Cooling Capacity - MBH
-07 = 7.5 Ton
-10 = 10 Ton
-12 = 12.5 Ton
-15 = 15 Ton
-20 = 20 Ton
-25 = 25 Ton
C00 = Cooling Only
Product Options
T = 208/230-3-60 W = 460-3-60 X = 575-3-60
Configured Split Condenser Model Number Nomenclature
A = Standard Motor
Airflow
Product Generation
5 = Fifth Generation
Voltage
Heat Type & Nominal Heat Capacity
YH-20
C00 A
TAAA
5
A
Product Style
A = Style A
P = Split System, Condenser, HP, R-410A
AA = None AB = Phase Monitor AC = Coil Guard AE = Phase Monitor + Coil Guard EA = E-Coat Condenser Coil EB = E-Coat Condenser Coil + Phase Monitor EC = E-Coat Condenser Coil + Coil Guard EE = E-Coat Condenser Coil + Coil Guard
+ Phase Monitor LA = Low Ambient LB = Low Ambient + Phase Monitor LC = Low Ambient + Coil Guard LD = Low Ambient + Phase Monitor
+ Coil Guard LE = Low Ambient + Technicoat Cond. Coil LF = Low Ambient + Technicoat Cond. Coil
+ Phase Monitor LG = Low Ambient + Technicoat Cond. Coil
+ Coil Guard LH = Low Ambient + Technicoat Cond. Coil
+ Phase Monitor + Coil Guard LJ = Low Ambient + ElectroFin Cond. Coil LK = Low Ambient + ElectroFin Cond. Coil
+ Phase Monitor LL = Low Ambient + ElectroFin Cond. Coil
+ Coil Guard LM = Low Ambient + ElectroFin Cond. Coil
+ Phase Monitor + Coil Guard TA = Technicoat Condenser Coil TB = Technicoat Condenser Coil + Phase Monitor TC = Technicoat Condenser Coil + Coil Guard TE = Technicoat Condenser Coil + Coil Guard
+ Phase Monitor
Installation Options
A = None B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 2 & 3 J = Options 1, 2 & 3 K = Options 1 & 4 L = Options 2 & 4 M = Options 1, 2 &4 P = Options 3 & 5 Q = Options 1, 3 & 5 R = Options 4 & 5 S = Option 5 T = Options 1 & 5 V = Options 1, 4 & 5
1 = Disconnect 2 = Non Pwr’d Conv Outlet 3 = BACnet MS/TP on Simplicity SE 4 = Fault Detection Device 5 = Pwr’d Conv Outlet
Options
Product Category
N = Split System, Air Handler, AC & HP, R-410A
Product Identifier
H = Standard Efficiency, 2-Pipe, R-410A J = Standard Efficiency, 4-Pipe, R-410A
Nominal Cooling Capacity - MBH
-07 = 7.5 Ton
-10 = 10 Ton
-15 = 15 Ton
-20 = 20 Ton
-25 = 25 Ton
C00 = Cooling Only
Product Options
Installation Options
A = None
T = 208/230-3-60
2
W= 460-3-60
2
S = 208/230/460-3-60 X = 575-3-60
Configured Split Air Handler Model Number Nomenclature
B = 1.5 HP Motor C = 2.0 HP Motor D = 3 HP Motor E = 5 HP Motor F = 7.5 HP Motor N = None (Motor Drive Kit Req)
1
Airflow
Product Generation
1 = First Generation 2 = Second Generation 3 = Third Generation
Voltage
Heat Type & Nominal Heat Capacity
N
H
-20
C00 B
SAAA
3
A
Product Style
A = Style A
1. Motors are not shipped with 25 ton Air Handler Units.
AA = No Options Installed EJ = E-Coat Evaporator Coil TJ = Technicoat Evaporator Coil
2. NH/NJ-20 Airflow Option “F” Only.

Nomenclature

4 Johnson Controls Unitary Products
Page 5

Condensing Unit Features and Benefits

Features

• Meets or exceed s ASHRAE 90.1 standards.
• Scroll compressors provide both high efficiency and reliability.
• Simplicity
• Dual refrigerant circuits on PH and YJ models.
• Condensing unit coils are constructed of reliable and durable Micro-Channel aluminum tube and fins for long lasting, efficient operation. Mirco-Channel technology provides exceptional durability along with reduced product weight and less refrigerant charge. Heat pumps units are equipped with aluminum fin, copper tube coils providing durability, reliability and value.
• Multiple condensing unit and air handler match-ups provide a wide range of application choices from oversized indoor motors to dual indoor units matched­up with single outdoor units.
• Crankcase heaters that de-energize when compressors are operating.
• Bo th high and low pressure controls. Since these controls are self-contained, there are no capillary lines to be damaged.
• Internal compressor motor protection.
• Class 2, 24-volt thermostat control circuit protected by a re-settable breaker.
• Standard factory installed service valves.
• Filter-driers are shipped in the unit's control box for field installation in the liquid line leaving the outdoor unit.
• Copper stub-outs are factory mounted on the suction and liquid lines to simplify the field piping connections.
• Simplicity® SE Controls provide stable cooling operation at ambient temperatures down to 40°F with low ambient kits available for operation to 0°F.
• Capacity staging for more economical operation and stable temperature levels within the conditioned space.
• Simplicity® SE Controls control board uses a three times, you're out philosophy. The high, low-pressure switch, anti-freeze protection, low voltage or heating high limit must trip three times within two hours before the unit control board will lock out the associated compressor. An alarm message will be displayed on the LCD screen.
• Simplicity® SE Controls monitor each safety independently (High pressure, low pressure, low voltage) allowing ease of troubleshooting if any problems arise.
• Inh erently protected condenser fan motors.
• Technicoat or E-Coat coated outdoor coils for sea coast or corrosive environment applications.
• Factory installe d disconnect to allow power to be removed from the unit when performing periodic maintenance or for service.
• Factory installed powered or non-powered 115 volt GFI outlet.
®
SE Controls
505430-BTG-P-0316
• Factory installed pha se monitor to protect the unit from phase loss or phase reversal.

Benefits

The UP® condensing units and heat pumps can be applied on a rooftop or at ground level... due to their ample sub­cooling capacity which allows them to be located three or more stories below the evaporator coil.
After assembly, the unit is pressurized with a combination of Refrigerant R-410A and nitrogen for pressure testing and additional leak testing. During this pressure test, the operation of the high pressure control is checked. As the unit is being evacuated and dehydrated, the operation of the low pressure control is also checked.
Every compressor, condenser fan motor, crankcase heater, and electrical control circuit is checked to assure a trouble­free start-up and years of reliable operation. The condenser fan guards are vinyl-coated to provide additional rust protection and to enhance the appearance of the unit. Compressors are mounted on rubber isolators to reduce the transmission of vibration. Vertical discharge condenser fans direct sound upward and away from any surrounding structures.
All sheet metal parts are constructed of commercial grade galvanized steel. After fabrication, each part is thoroughly cleaned to remove any grease or dirt from its surfaces. The external parts are coated with a pow d er paint to assure a quality finish for many years. This UL approved coating system has passed the 1000 hour, 20% salt spray test per ASTM Standard B117.
All condensing unit and heat pump models include a 5-year limited warranty on the compressor(s) and 1-year limited warranty on all other parts. The matching line of air handling units carries a 1-year limited parts warranty.

Outdoor Unit Accessories

Coil Guards: Wireform coil guards for added protection of outdoor coils. Designed to mount on each side of the product if required to provide protection from minor impacts or large debris.
Hail Guards: Hood type hail guards designed to protect the outdoor coils from hail. Can be installed on a single side or both to provide protection from storms that may produce hail.
Low Ambient Kits: units to operate between 0°F and 40°F in the cooling mode. Standard cooling is allowed to 40°F. (Not designed for operation on heat pump units).
Kits designed to allow the cooling only

Air Handling Unit Features and Benefits

Features

These air handlers can be arranged for a variety of air discharge patterns in either the horizontal or vertical position. Refer to the unit installation instructions for other application possibilities.
Johnson Controls Unitary Products 5
Page 6
505430-BTG-P-0316

Benefits

Air handling units are designed with two distinct modules to provide maximum application flexibility. All are shipped as single packages with the blower module mounted on top of the coil module. The blower module can be repositioned in the field to meet a large number of vertical and horizontal applications.
The 7.5 thru 20 Ton blower module includes the blower wheels along with factory-mounted motor and drive. The 25 Ton blower module includes the blower wheels with field mounted motor and drives. All models offer two motor horsepower options to meet both standard and high static airflow requirements.
The coil module includes direct expansion coils, 2 in. throwaway filters with the option to accept 4” filters, liquid line solenoid valves for capacity reduction, thermal expansion valves, distributors and a non-corrosive, composite condensate drain pan.
Every air handling coil is pressurized with air and leak tested under water. After the headers are brazed onto the coil and the coil is installed in the unit, the coil is pressurized with nitrogen for pressure testing and additional leak testing. After the coil is evacuated and dehydrated, it is pressurized with a holding charge of nitrogen for storage and/or shipping.

Factory-Mounted Components

Part Load Operation:
These air handlers with DX (Direct Expansion) coils rated at 10 tons of capacity and above have multiple coils with pre-piped distributors, expansion valves and solenoid valves. Field modifications are not required for part load operations. Capacity reduction not only provides economical operation, but also maintains stable temperature and humidity levels in the conditioned space.
BAS Control:
Simplicity® SE with Communication Option Control - The York® Simplicity® SE with Communication Option Control is factory installed. It includes all the features of the Simplicity® SE control with an additional gateway to BACnet MS/TP (programmable to Modbus or N2 protocols).
Easy Service: Serviceable expansion valves are provided on every unit. These valves are factory-installed to provide many years of trouble-free operation. If service is required, it is not necessary to unbraze any joints. The expansion valves also include a tee fitting to allow easy installation of hot gas bypass if required.
Coil Protection:
The indoor coils of these air handlers can have factory applied Technicoat or Electrofin coating to provide extended life to the indoor coil in standard applications and additional corrosion protection on those applications in sea coast or corrosive environments.
These air handlers, combined with condensing units, provide years of quiet, efficient and dependable operation. These units are manufactured under ISO 9001 Quality System Certification.

Unit Installation

Units may be bottom-supported or ceiling-suspended and can be arranged to meet almost any space or duct requirements. Each unit is available with a choice of blower motors horsepower and other accessories to make them suitable for most applications.
Air Handling units are available in either two or four pipe configurations from 7.5 to 25 tons. The dual and single circuit options provide a wide variety of application and unit match­up possibilities.
Blower Motors:
Different HP motors are available for each unit to meet almost any air delivery requirement. All motors are UL approved, have permanently lubricated ball bearings and are mounted within the insul at ed cabinet of the units to minimize the transmission of sound to the surrounding space.
1.5-5 HP motors are inherently protected. 7.5 HP motors require motor overload protection.
Overload Relay (7.5HP):
These blower motors do not have inherent protection and require external motor overload protection. NH/NJ-20 "F" models Overload Relays are factory installed. NH-25 models Overload Relays are field installed. Power wiring for blower motor is supplied in the Overload Relay Kit. See details in Overload Relay Kit and Overload Relay Setting Tables on Page 70.

Accessories

Base Sections:
Base sections can be used to elevate units above the floor. If desired, a moderate percentage of outdoor air may be introduced through these sections by cutting an access opening to accommodate the outdoor air duct connection. These bases include a durable finish to match the evaporator blower unit. The base may have to be insulated for certain applications.
Hot Water Coils:
Drainable water coils are available for field installation between the blower and the coil modules of both horizontal and vertical units. Since their casings match the dimensions and the finish of the basic units, they become an integral part of the unit after installation. The coils slide out of their casings for easy installation. Hot water coils have copper tubes that have been mechanically expanded into aluminum fins. Both headers are located on the same end of the coil. Coils are leak-tested at 325 psig under water and dried before their connections are capped for storage and shipping.
Steam Coils:
Steam coils are available for installation between the blower and coil modules of both horizontal and vertical units. Since the casing matches the dimensions and the finish of the basic unit, it becomes an integral part of the unit after installation. The coil slides out of the casings for easy installation and is pitched in the casings to facilitate condensate drainage. The coil has copper tubes that have been mechanically expanded into aluminum fins. Both headers are located on the same end of the coil. The coil is leak-tested at 325 psig and dried before the connections are capped for storage and shipping.
6 Johnson Controls Unitary Products
Page 7
505430-BTG-P-0316
Bottom Return: Air handling unit can be quickly converted to bottom return for both vertical and horizontal applications. All that is required is the removal of several screws and a single panel on 7.5-15 ton and two panels on the 20 ton AHU. Optional painted panel can be ordered to cover the side return opening when utilizing the bottom return.
Supply Air Plenums: These fully insulated plenums are available for free standing units located within the conditioned space. They are shipped fully assembled for easy field installation, are finished to match the exterior of the basic unit, and include double deflection grills that can be adjusted to vary the throw, spread and drop of the supply air.

Guide Specifications

Split System Cooling Only Condensing Units Models: YH-07 thru -25, YJ-10 thru -20 & Split System Heat Pump Models: PH-07 thru -20, PJ-15 thru -20

General

• Factory assembled, single piece, air cooled condensing unit designed for outdoor installation.
• Factory wired, piped, and tested for leakage and functionality to assure trouble-free installation and start­up.
• Rated in accordance with AHRI Standard 340/360.
• Manufactured in a facility registered under the ISO 9002 manufacturing quality standard.
• Designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration and comply with NEC.
• Cooling performance rated in accordance with DOE and AHRI test procedures.
• CSA listed and classified to UL 1995/CAN/CSA No. 236- M90 standards.
• One year limited parts warranty on complete unit with an additional four year compressor warranty.

Unit Operating Characteristics

• The system shall have an EER of _____ Btuh/ Watt or greater at standard AHRI conditions.

Installer Shall

• Furnish UP™ air-cooled condensing units, heat pump or equivalent in accordance with the performance schedule shown on the plans, and
• Unit shall be stored and handled in accordance with unit manufacturer's instructions.
• Install each unit as shown on the plans in accordance with the manufacturer’s recommendations and all applicable national and local codes

Unit Construction

• Constructed of zinc-coated, galvanized steel.
• Exterior surfaces bonded and coated with baked enamel finish by a powder paint process capable of withstanding a minimum of 1000 salt spray hours according to ASTM B117.
• Cabinet screws that comply with ASTM B117 salt spray test for a minimum of 750 hours.
• Permanen tly attached heavy-gage perimeter base rails with forklift slots and lifting holes.
• Removable access panels to all internal components.
• Separate access panel to controls.
• Acce s s panels to allow outdoor coil cleaning.

Compressor(s)

• Hermetic scroll type, in ternally protected with high­pressure relief and over temperature protection.
• Two stage units operate in 50% capacity increments.
• Sucti on gas cooled
• Voltage range of ±10% of unit nameplate voltage.
• Neoprene isolators minimize sound transmission and vibration.
• Belly-band crankcase heaters keep refrigerant from diluting sump oil.
• Full charge of compressor oil
Operating Range shall be between 125° F to 40° F in cooling as standard from factory.
• The capacity of the condensing unit shall meet or exceed _____ Btuh at a suction temperature of _____ F. The power consumption at full load shall not exceed _____ kW.
• The combination of the condensing unit and the evaporator or fan coil unit shall have a total net cooling capacity of _____ Btuh or greater at conditions of _____ cfm entering-air temperature at the evaporator at _____ F wet bulb and _____ F dry bulb, and air entering the condensing unit at _____F.
Johnson Controls Unitary Products 7

Outdoor Condenser Unit Coils

• Draw thru configuration
• Constructed with Micro-chan nel aluminum fins and aluminum tubing. All refrigerant tubing must share a common header.

Heat Pump Unit Outdoor Unit Coils

• Draw thru configuration
• Constructed with aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed.
Page 8
505430-BTG-P-0316

Condenser Fans

• Direct driven propeller-type fans
• Statically and dynamically balanced
• Aluminu m blades riveted to corrosion resistant steel spider brackets.
• Arranged for vertical air discharge.
• Equip ped with PVC coated steel wire safety guards.
8 Johnson Controls Unitary Products
Page 9
505430-BTG-P-0316

Condenser Motors

• Totally enclosed, air over cooled.
• Inh erent overload protection.
• Pe r manently lubricated bearings.
• Must cycle to allow cooling operation down to 40°F.

Refrigerant Piping

• Solid core filter-drier(s) ship loose for field installation.
• Liquid and suction line service valves with gauge ports.
• Su ction and discharge line service ports accessible from unit. Ports capped for leak prevention.
• Liquid line magnetic check valves
• Holding charge of R410A refrigerant.

Electrical Requirements

• Si ngle-point connection electrical power.
• Nominal unit electrical characteristics shall be _____ v, 3-ph, 60 Hz. The unit shall be capable of satisfactory operation within voltage limits of ____ v to _____ v.
• C ondenser fan motors and secondary of transformers shall be grounded.

Unit Controls

• All 24-volt control circuit, powered by a 24 volt transformer(s) and protected by a resettable breaker.
• C onventional thermostat must provide operation for both condensing units and heat pumps without an “O” output from the thermostat.
• Low voltage terminal strip for simple hook-up.
• Compressor motor protection shuts down unit for motor over-current, over-temperature or low voltage conditions.
• Safety lockou ts provi de reset capability at the space thermostat or base unit should any of the following standard safety devices trip and shut off compressor:
a. Loss-of-charge/Low-pressure switch. b. High-pressure switch. c. Control board diagnostics and fault message display. d. Safety lockouts send a 24 volt signal to the control
board's "X" terminal, allowing notification to the user via the thermostat fault light (if present).
e. In the unlikely event any faults should occur, the unit
control board will store the faults in its internal memory. The LCD display will scroll the 5 MOST critical faults, however, all fault messages can be extracted via USB device, displayed real-time via the MAP Gateway as well as be broad-casted through a
BAS system (if applicable). The UCB will provide fault messages in plain English to ensure the user can easily understand the specific fault.

Non-fused Disconnect Switch

• Factory-installed, internally mounted.
• Accessible from outside the unit.
• NEC and UL approved non-fused switch.
• Provides power off lockout capability.

Convenience Outlet

• Factory-installed, internally mounted.
• Accessible from outside the unit.
• 115V, 15 amp GFI receptacle with independent fuse protection.
• Required voltage provided by factory-installed step­down transformer or field supplied 115v circuit.

Low-ambient Head Pressure Control

• Sta ndard operation down to 40 °F without a low ambient kit.
• Operation down to 0°F with a field-installed low ambient kit accessory. The controller modulates the fan motor speed in response to liquid line temperature or pressure.

Coil Guard

Factory or field installed decorative grille shall be placed on the units to protect condenser coil after installation.

Hail Guard Package

Field installed hail guard package shall protect coils against damage from hail and other flying debris.

Coated Condenser Coils

Special phenolic or epoxy polymer coating available as a factory option on both outdoor and indoor coils.

Each Unit Shall Be:

• Covered by a 1-year limited parts warranty on the complete unit and 5-year on compressor(s).
• In current production with published literature available to check performance, limitations, specifications, power requirements, dimensions, operation and appearance.
• Indoor un it shall be equipped with a V-belt drive option that will permit the blower RPM to be adjusted to meet the CFM requirements of the air delivery system. (Refer to Technical Guide for Airflow Capabilities.)
Johnson Controls Unitary Products 9
Page 10
505430-BTG-P-0316

Each Unit Enclosure Shall Have:

• Exterior panels of 18 gauge steel, finished with baked enamel to provide a long lasting quality appearance
• Removable panels to provide easy access to the internal components for maintenance and service on condensing units, heat pumps and air handlers
• Air handling units must have a filter rack that accepts both 2” and 4” filters.
• The dimensions of each unit shall not exceed those specified in the manufacture’s literature.
• The minimum application clearances for condensing units, heat pumps and air handlers must meet those specified in the manufacturer’s litera tu re .

The Blower Motor Shall:

• Be mounted within the insulated cabinet to minimize the transmission of sound to the surrounding space, and any motor 7.5 HP or greater must have a service factor of 1.15.

The Evaporator Coil Shall:

• Consist of copper tubes arran ged in staggered rows, mechanically expanded into aluminum fins,
• Be draw-through, and
• Include factory-mounted distributors, expansion valves and solenoid valves for capacity reduction.

The Blower Wheels Shall:

Be dynamically balanced to minimize the levels of sound and vibration generated by the unit.
10 Johnson Controls Unitary Products
Page 11
505430-BTG-P-0316

Physical Data

YH-07 thru -25 and YJ-10 thru -20 Physical Data

Single
Scroll
Models
Tandem
Scroll
Single
Scroll
Tandem
Scroll
Single
Scroll
Tandem
Scroll
Component
Nominal Tonnage 7.5101012.512.51515202025
REFRIGERANT
Refrigerant type R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A Holding charge (lb)
Operating Charge (lb)
DIMENSIONS (inches)
Length 59.1 59.1 59.1 59.1 59.1 59.1 59.1 59.1 59.1 59.1 Width 31.9 31.9 31.9 31.9 31.9 64.1 64.1 64.1 64.1 64.1 Height 44.5 50.0 50.0 50.0 50.0 44.5 44.5 50.0 50.0 50.0
WEIGHTS (lb)
Shipping 390 499 493 499 493 914 899 945 930 945 Operating 387 497 490 497 490 909 894 942 927 942
COMPRESSORS
Type Quantity 1121212121
Nominal Capacity (Tons)
Capacity Stages
SYSTEM DATA
No. Refrigeration Circuits 1121212121 Suction Line OD (in.) 1 1/8 1 3/8 1 1/8 1 3/8 1 1/8 1 5/8 1 1/8 1 5/8 1 3/8 2 1/8 Liquid Line OD (in.) 5/8 7/8 5/8 7/8 5/8 7/8 5/8 7/8 5/8 7/8
OUTDOOR COIL DATA
Face area (Sq. Ft.) 23.8 29.0 29.0 29.0 29.0 47.5 47.5 58.1 58.1 58.1 Rows 1111111111 Fins per inch 23 23 23 23 23 23 23 23 23 23 Tube diameter (in./MM) 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 Circuitry Type 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass Refrigerant Control --- --- --- --- --- --- --- --- --- ---
CONDENSER FAN DATA
No. Fans / Diameter (in.) 2/24 2/24 2/24 2/24 2/24 4/24 4/24 4/24 4/24 4/24 Type Axial Axial Axial Axial Axial Axial Axial Axial Axial Axial Drive type Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct No. speeds 1111111111
Number of motors Motor HP (ea.) 1/3 3/4 3/4 3/4 3/4 1/3 1/3 3/4 3/4 3/4
4
Rotation RPM 850 1100 1100 1100 1100 850 850 1100 1100 1100
Nominal CFM
1
Holding Charge is the amount in the unit as shipped from the factory.
2
Includes matched indoor blower unit with 25 ft of piping.
3
All compressors include crankcase heaters.
4
When viewing the shaft end of the motor.
1
(each system)
System #1 14.0 19.25 9.9 24.0 11.5 27.0 13.5 33.5 18.8 35
2
System #2 --- --- 9.9 --- 11.5 --- 13.5 --- 18.8 ---
3
System #1 7.5 10 5 12.5 6.3 15 7.5 20 10 25 System #2 --- --- 5 --- 6.3 --- 7.5 --- 10 --­System #11212121212 System #2 --- --- 1 --- 1 --- 1 --- 1 ---
System #12222242424 System #2 --- --- --- --- --- --- 2 --- 2 ---
System #1 7500 9800 9800 9800 9800 15000 7500 19600 9800 19600 System #2 --- --- --- --- --- --- 7500 --- 9800 ---
YH-07 YH-10 YJ-10 YH-12 YJ-12 YH-15 YJ-15 YH-20 YJ-20 YH-25
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Single
Scroll
Tandem
Scroll
CW CW CW CW CW CW CW CW CW CW
Single
Scroll
Tandem
Scroll
Johnson Controls Unitary Products 11
Page 12
505430-BTG-P-0316

PH-07 thru -20 and PJ-15 thru -20 Physical Data

Component
PH-07 PH-10 PH-15 PJ-15 PJ-20
Nominal Tonnage 7.5 10 15 15 20
REFRIGERANT
Refrigerant type R-410A R-410A R-410A R-410A R-410A Holding charge (lb)
Operating Charge (lb)
1
1.0 1.0 1.0 1.0 1.0
2
System #1 23.9 31.75 54.0 27.0 34.0 System #2 --- --- --- 27.0 34.0
DIMENSIONS (inches)
Length 59.1 59.1 59.1 59.1 59.1 Width 31.9 31.9 64.1 64.1 64.1 Height 44.5 50.0 44.5 44.5 50.0
WEIGHTS (lb)
Shipping 421 543 947 921 1090 Operating 430 574 968 942 1126
COMPRESSORS
3
Type Single Scroll Tandem Scroll Tandem Scroll Single Scroll Single Scroll Quantity 1 1 1 2 2
Cooling
Nominal Capacity (Tons)
Capacity Stages
System #1 7.5 10 15 7.5 10 System #2 --- - -- --- 7.5 10 System #112211 System #2 --- --- --- 1 1
Heating
Nominal Capacity (Tons) System #1 & #2 7.5 10 15 15 20 Capacity Stages System #1 & #2 1 1 1 1 1
SYSTEM DATA
No. Refrigeration Circuits 1 1 1 2 2 Suction Line OD (in.) 1 1/8 1 3/8 1 5/8 1 3/8 1 3/8 Liquid Line OD (in.) 5/8 7/8 7/8 5/8 5/8
OUTDOOR COIL DATA
Face area (Sq. Ft.) 23.8 29.0 47.5 47.5 58.1 Rows 22222 Fins per inch 20 20 20 20 20 Tube diameter (in./MM) 0.38 / 10 0.38 / 10 0.38 / 10 0.38 / 10 0.38 / 10 Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Refrigerant Control TXV TXV TXV TXV TXV
CONDENSER FAN DATA
No. Fans / Diameter (in.) 2/24 2/24 4/24 4/24 4/24 Type Axial Axial Axial Axial Axial Drive type Direct Direct Direct Direct Direct No. speeds 1 1 1 1 1
Number of motors Motor HP (ea.) 1/3 3/4 1/3 1/3 3/4
4
Rotation
System #122422 System #2 --- --- --- 2 2
CW CW CW CW CW
RPM 850 1100 850 850 1100 Nominal CFM
1
Holding Charge is the amount in the unit as shipped from the factory.
2
Includes matched evaporator unit with 25 ft of piping.
3
All compressors include crankcase heaters.
4
When viewing the shaft end of the motor.
System #1 7500 9800 15000 7500 9800 System #2 --- --- --- 7500 9800
Models
12 Johnson Controls Unitary Products
Page 13
505430-BTG-P-0316

NH-07 thru -20 and NJ-10 thru -20 Indoor Unit Physical Data

Component
Nominal Tonnage 7 1/2101015152020
DIMENSIONS (inches)
Length Width Height
WEIGHTS (lb)
Unit Shipping Unit Operating With Standard Motor and Drive High Static Motor and Drive
INDOOR BLOWER (Forward Curve)
Diameter x Width 12 x 12 15 x 15 15 x 15 18 x 18 18 x 18 15 x 15 15 x 15 Quantity 1111122
Face area (Sq. Ft.) 10.6 10.6 10.6 18.3 18.3 20.0 20.0 Rows 3443444 Fins per inch 15 15 15 15 15 15 15 Tube diameter 3/8 3/8 3/8 3/8 3/8 3/8 3/8 Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced Refrigerant Control TXV TXV TXV TXV TXV TXV TXV
No. Refrigeration Circuits 1121212 Suction Line OD (in.) 1 1/8 1 3/8 1 1/8 1 5/8 1 3/8 1 5/8 1 3/8 Liquid Line OD (in.) 5/8 7/8 5/8 7/8 5/8 7/8 7/8
Size and Quantity Per Model (In.)
Size and Quantity Per Model (In.)
INDOOR COIL
SYSTEM DATA
FILTERS
16 x 25 x 2 4 4 4 --- --- 8 8 20 x 24 x 2 --- --- --- 6 6 --- ---
FACE AREA (SQ. FT.) 11.1 11.1 11.1 20.0 20.0 22.2 22.2
16 x 25 x 4 4 4 4 --- --- 8 8 20 x 24 x 4 --- --- --- 6 6 --- ---
FACE AREA (SQ. FT.) 11.1 11.1 11.1 18.0 18.0 22.2 22.2
NH-07 NH-10 NJ-10 NH-15 NJ-15 NH-20 NJ-20
56.0 56.0 56.0 74.5 74.5 98.5 98.5
30.0 30.0 30.0 33.0 33.0 30.0 30.0
65.0 65.0 65.0 75.0 75.0 65.0 65.0
526 573 575 796 796 938 938
498 539 541 764 764 873 873 500 550 552 792 792 903 903
Models
Johnson Controls Unitary Products 13
Page 14
505430-BTG-P-0316

NH-25 Indoor Unit Physical Data

Component
Nominal Tonnage 25
DIMENSIONS (inches)
Length Width Height
WEIGHTS
Unit Shipping Unit Operating With 5 hp Motor and Drive
7.5 hp Motor and Drive
INDOOR BLOWER (Forward Curve)
Diameter x Width 18 X 18 Quantity 2
Face area (Sq. Ft.) 25.8 Rows 4 Fins per inch 16 Tube diameter 3/8 Circuitry Type Interlaced Refrigerant Control TEV
No. Refrigeration Circuits 1 Suction Line OD (in.) 2 1/8 Liquid Line OD (in.) 7/8
Size and Quantity Per
Face area (Sq. Ft.) 21.2 Rows 2 Fins per inch 12 Tube diameter (Copper) OD (In.) 1/2 Connections (Supply and Return) OD (In.) 1 3/8 Weight (lb) 150
Face area (Sq. Ft.) 18.2 Rows 1 Fins per inch 8 Tube diameter (Copper) (In.) 1 Connection, (NPTE) (In.) Inlet 2 Outlet 1-1/2 Weight (lb) 160
1
Motors, Drive and Overload Kits must be
INDOOR COIL
SYSTEM DATA
Model (In.)
FACE AREA (SQ. FT.) 34.7
ACCESSORY
HOT WATER COIL DATA
SYSTEM COIL DATA
FILTERS
1
(lb)
20 x 25 x 2 10
ordered separately for the NH-25. The Motor Drive and Overload Kits are to be field installed.
Models
NH-25
100.1
38.1
74.6
1067
1130 1157
14 Johnson Controls Unitary Products
Page 15

Unit Limitations

Condenser Unit limitations

Outdoor DB Temp
Size
-10
(10)
-10
(10)
-12
(12.5)
-15
(15)
-15
(15)
-20
(20)
-20
(20)
-25
(25)
Model
PH
YH/YJ
YH/YJ
PH/PJ
YH/YJ
PH/PJ
YH/YJ
YH
(Tons)
-07 (7.5) PH
-07 (7.5) YH
Unit Voltage
Applied Voltage
Min Max Max Min
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
208/230-3-60 187 252
575-3-60 540 630
1
Cooling (°F)
125 40 86 68 70 0 80 50460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 70 0 80 50460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 70 0 80 50460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 70 0 80 50460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
125 40 86 68 - - - -460-3-60 432 504
1. Rated in accordance with AHRI Standard 110, Range “A” Utilization Voltage. †. Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0°F.
Indoor DB Temp
†
Cooling (°F)
Max Min Max Min Max Min
Outdoor DB Temp
Heating (°F)
505430-BTG-P-0316
Indoor DB Temp
Heating (°F)
Johnson Controls Unitary Products 15
Page 16
505430-BTG-P-0316

Air Handling Unit Limitations

Entering Air Temperature Degrees °F
Model Power Supply Voltage
Voltage Variation Supply Air Range CFM
Cooling DB/WB
Min. Max. Min. Max. Min. Max. Min. Max.
208/230-3-60 187 253 2,250 3,750 65/57 90/77 40 80
NH-07
460-3-60 414 506 2,250 3,750 65/57 90/77 40 80 575-3-60 540 630 2,250 3,750 65/57 90/77 40 80
208/230-3-60 187 253 3,000 5,000 65/57 90/77 40 80
NH-10
460-3-60 414 506 3,000 5,000 65/57 90/77 40 80 575-3-60 540 630 3,000 5,000 65/57 90/77 40 80
208/230-3-60 187 253 3,000 5,000 65/57 90/77 40 80
NJ-10
460-3-60 414 506 3,000 5,000 65/57 90/77 40 80 575-3-60 540 630 3,000 5,000 65/57 90/77 40 80
208/230-3-60 187 253 4,500 7,500 65/57 90/77 40 80
NH-15
460-3-60 414 506 4,500 7,500 65/57 90/77 40 80 575-3-60 540 630 4,500 7,500 65/57 90/77 40 80
208/230-3-60 187 253 4,500 7,500 65/57 90/77 40 80
NJ-15
460-3-60 414 506 4,500 7,500 65/57 90/77 40 80 575-3-60 540 630 4,500 7,500 65/57 90/77 40 80
208/230-3-60 187 253 6,000 10,000 65/57 90/77 40 80
NH-20
460-3-60 414 506 6,000 10,000 65/57 90/77 40 80 575-3-60 540 630 6,000 10,000 65/57 90/77 40 80
208/230-3-60 187 253 6,000 10,000 65/57 90/77 40 80
NJ-20
460-3-60 414 506 6,000 10,000 65/57 90/77 40 80 575-3-60 540 630 6,000 10,000 65/57 90/77 40 80
208/230-3-60 187 253 8,000 12,000 65/57 90/77 40 80
NH-25
460-3-60 414 506 8,000 12,000 65/57 90/77 40 80 575-3-60 540 630 8,000 12,000 65/57 90/77 40 80
1
Heating Min/Max temperatures apply to steam and hot water coils. NOTE: Do not apply steam to hot water coils.
Heating DB
1
16 Johnson Controls Unitary Products
Page 17
505430-BTG-P-0316

Cooling and Heating Ratings

Cooling And Heating Rating

Condensing Unit Only
Outdoor Unit
PH-07 PH-10 PH-15 PJ-15 PJ-20
YH-07 85 6.8 12.4 NH-07 94 11.2 13.0 --- N/A N/A N/A N/A 3000 YH-07 85 6.8 12.4 NH-10 99 11.9 13.0 --- N/A N/A N/A N/A 3000 YH-10 110 9.3 11.9 NH-10 124 11.4 12.5 12.9 N/A N/A N/A N/A 4000
YJ-10 108 9.1 11.8 NJ-10 124 11.2 11.2 11.6 N/A N/A N/A N/A 4000
YH-12 133 11.6 11.5 NH-15 150 11.0 13.3 13.8 N/A N/A N/A N/A 5000
YJ-12 136 11.5 11.8 NJ-15 150 11.0 12.1 12.3 N/A N/A N/A N/A 5000 YH-15 160 13.4 12.0 NH-15 181 11.2 12.2 12.5 N/A N/A N/A N/A 6000 YH-15 160 13.4 12.0 NH-20 190 11.7 12.7 12.5 N/A N/A N/A N/A 6000
YJ-15 166 12.3 13.4 NJ-15 181 11.2 11.6 12.4 N/A N/A N/A N/A 6000
YJ-15 166 12.3 13.4 (2)NH-07 187 11.2 -- -- N/A N/A N/A N/A 6000
YJ-15 166 12.3 13.4 (2)NH-10 187 11.2 -- -- N/A N/A N/A N/A 6000
YJ-15 166 12.3 13.4 NJ-20 190 11.7 13.4 11.2 N/A N/A N/A N/A 6000 YH-20 233 17.5 13.2 NH-20 242 11.3 13.6 13.1 N/A N/A N/A N/A 8000
YJ-20 222 17.3 12.8 NJ-20 242 11.3 11.9 12.6 N/A N/A N/A N/A 8000
YJ-20 222 17.3 12.8 (2)NH-10 240 11.6 -- -- N/A N/A N/A N/A 8000 YH-25 271 23.7 11.4 NH-25 299 10.2 12.2 -- N/A N/A N/A N/A 10000
1
Certified in accordance with the Unitary Large Equipment certification program, which is based on AHRI Standard 340/360.(Except YH-25)
2
Condensing unit only ratings are at 45°F SST and 95°F entering-air temperature.
3
Gross capacity does not include heat added by blower motor. Refer to appropriate table for blower horsepower.
4
Heat Pumps designed for matched systems only.
Gross Capacity
(MBH)
4
4
4 4 4
2
KW EER
N/A N/A N/A NH-07 92 11.0 11.4 --- 82 3.3 49 2.3 3000 N/A N/A N/A NH-10 124 11.0 11.4 11.8 109 3.3 63 2.1 4000 N/A N/A N/A NH-15 180 10.6 11.5 12.4 168 3.3 104 2.3 6000 N/A N/A N/A NJ-15 180 10.6 11.5 12.0 168 3.4 103 2.4 6000 N/A N/A N/A NJ-20 238 10.6 11.7 12.1 220 3.4 124 2.2 8000
Indoor
Unit
System Cooling Capacity
Gross Capacity
(MBH)
3
EER IEER IPLV
1
Capacity
Heating Capacity
High Outdoor Low Outdoor
Gross
2
(MBh)
COP
Gross
Capacity
(MBh)
1
2
COP
Rated
Airflow
(CFM)
LEGEND EER = Energy Efficiency Ratio AHRI = Air Conditioning and Refrigeration Institute IPLV = Integration Part-Load Value IEER = Integrated Energy Efficiency Ratio
Johnson Controls Unitary Products 17
Page 18
505430-BTG-P-0316

Capacity Performance

Condenser and Air Handling Cooling Capacities YH-07/NH-07
Air on
Evaporator Coil CFM
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
(°F)
Total
WB
Capacity
(MBh)
77 110.8 6.0 51.5 42.0 32.6 - - - 107.2 6.5 49.8 40.4 30.9 - - ­72 103.3 5.7 66.5 57.0 47.6 38.1 - - 99.9 6.3 64.9 55.4 46.0 36.5 - ­67 95.9 5.5 81.5 72.0 62.6 53.1 43.6 - 92.6 6.2 80.0 70.5 61.0 51.6 42.1 ­62 88.0 5.4 88.0 86.3 76.8 67.3 57.8 48.3 84.8 6.1 84.8 83.9 74.5 65.0 55.5 46.1 57 77.7 5.2 77.7 77.7 72.2 62.8 53.3 43.8 80.1 6.0 80.1 80.1 73.1 63.6 54.2 44.7 77 114.0 6.0 56.3 45.6 34.8 - - - 110.2 6.5 54.6 44.0 33.3 - - ­72 106.3 5.7 72.3 61.6 50.9 40.1 - - 102.7 6.3 70.8 60.2 49.6 38.9 - ­67 98.7 5.4 88.4 77.6 66.9 56.2 45.5 - 95.2 6.2 87.1 76.4 65.8 55.2 44.5 ­62 90.6 5.4 90.6 89.7 82.2 71.9 60.7 50.0 87.1 6.1 87.1 86.7 80.3 69.6 59.0 48.3 57 79.9 5.2 79.9 79.9 77.2 67.3 55.8 45.0 82.3 6.0 82.3 82.3 78.8 68.2 57.5 46.9 77 117.2 5.9 61.0 49.1 37.1 - - - 113.1 6.5 59.4 47.5 35.7 - - ­72 109.3 5.7 78.1 66.2 54.2 42.2 - - 105.4 6.4 76.8 65.0 53.1 41.3 - ­67 101.4 5.4 95.2 83.2 71.3 59.3 47.3 - 97.7 6.2 94.2 82.4 70.5 58.7 46.9 ­62 93.1 5.4 93.1 93.1 87.5 76.5 63.6 51.6 89.5 6.1 89.5 89.5 86.1 74.2 62.4 50.6 57 82.2 5.2 82.2 82.2 82.2 71.7 58.3 46.3 84.5 6.0 84.5 84.5 84.5 72.7 60.8 49.0 72 109.2 5.8 83.0 70.2 57.3 44.4 - - 105.4 6.4 81.6 68.8 56.0 43.2 - ­67 101.3 5.5 98.2 88.2 75.3 62.5 49.6 - 97.7 6.3 96.0 87.2 74.3 61.5 48.7 ­62 93.0 5.5 93.0 93.0 90.2 77.8 64.5 51.6 89.5 6.2 89.5 89.5 87.8 75.0 62.1 49.3 57 82.1 5.3 82.1 82.1 82.1 70.0 56.4 43.5 84.5 6.1 84.5 84.5 84.5 71.7 58.9 46.0 72 109.1 5.9 87.9 74.2 60.4 46.6 - - 105.5 6.5 86.5 72.6 58.8 45.0 - ­67 101.2 5.6 101.2 93.2 79.4 65.7 51.9 - 97.8 6.3 97.8 91.9 78.1 64.3 50.5 ­62 92.9 5.6 92.9 92.9 92.9 79.1 65.3 51.6 89.5 6.2 89.5 89.5 89.5 75.7 61.9 48.1 57 82.0 5.4 82.0 82.0 82.0 68.2 54.4 40.7 84.5 6.1 84.5 84.5 84.5 70.7 56.9 43.1
77 103.7 6.9 48.1 38.7 29.2 - - - 99.2 8.0 47.5 38.1 28.6 - - ­72 96.5 6.9 63.3 53.8 44.4 35.0 - - 92.2 8.0 62.1 52.6 43.2 33.7 - ­67 89.4 6.9 78.4 69.0 59.5 50.1 40.7 - 85.2 8.0 76.6 67.2 57.7 48.3 38.8 ­62 81.6 6.7 81.6 81.6 72.1 62.7 53.3 43.8 77.9 7.7 77.9 77.9 69.2 59.7 50.3 40.9 57 82.5 6.7 82.5 82.5 74.0 64.5 55.1 45.7 78.8 7.8 78.8 78.8 70.0 60.5 51.1 41.6 77 106.4 7.0 52.9 42.3 31.8 - - - 101.7 8.1 53.5 41.7 31.1 - - ­72 99.0 7.0 69.4 58.8 48.2 37.7 - - 94.5 8.1 68.1 57.5 46.9 36.3 - ­67 91.7 6.9 85.8 75.3 64.7 54.1 43.6 - 87.3 8.0 82.8 73.3 62.7 52.1 41.5 ­62 83.7 6.8 83.7 83.7 78.4 67.3 57.2 46.7 79.9 7.8 79.9 79.9 75.2 64.4 54.0 43.4 57 84.6 6.7 84.6 84.6 80.4 69.1 59.2 48.7 80.7 7.9 80.7 80.7 76.1 65.1 54.8 44.2 77 109.0 7.1 57.7 46.0 34.3 - - - 104.1 8.1 59.4 45.4 33.6 - - ­72 101.5 7.0 75.5 63.8 52.1 40.4 - - 96.8 8.1 74.2 62.5 50.7 38.9 - ­67 94.0 7.0 93.3 81.5 69.8 58.1 46.4 - 89.4 8.1 89.0 79.5 67.8 56.0 44.3 ­62 85.8 6.8 85.8 85.8 84.6 72.0 61.2 49.5 81.8 7.9 81.8 81.8 81.2 69.0 57.7 46.0 57 86.8 6.8 86.8 86.8 86.8 73.6 63.4 51.7 82.7 7.9 82.7 82.7 82.1 69.6 58.6 46.9 72 101.7 7.1 80.2 67.5 54.7 41.9 - - 96.9 8.1 79.2 66.3 53.5 40.7 - ­67 94.2 7.0 93.8 86.1 73.3 60.5 47.7 - 89.5 8.1 89.4 83.7 71.5 58.7 45.8 ­62 86.0 6.8 86.0 86.0 85.4 72.1 59.8 47.0 82.0 7.9 82.0 82.0 81.7 68.6 56.0 43.2 57 86.9 6.8 86.9 86.9 86.9 73.4 61.4 48.6 82.8 7.9 82.8 82.8 82.6 69.3 56.9 44.1 72 101.9 7.1 85.0 71.1 57.3 43.4 - - 97.1 8.1 84.1 70.2 56.3 42.4 - ­67 94.3 7.0 94.3 90.7 76.8 62.9 49.1 - 89.7 8.1 89.7 87.9 75.3 61.4 47.4 ­62 86.1 6.9 86.1 86.1 86.1 72.3 58.4 44.5 82.1 7.9 82.1 82.1 82.1 68.2 54.3 40.4 57 87.1 6.9 87.1 87.1 87.1 73.2 59.4 45.5 83.0 7.9 83.0 83.0 83.0 69.1 55.2 41.2
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
18 Johnson Controls Unitary Products
Page 19
505430-BTG-P-0316
YH-07/NH-07 (Continued)
Air on
Evaporator Coil CFM
2250
2625
3000
3375
3750
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
WB (°F)
77 94.7 9.0 46.9 37.5 28.0 - - - 90.2 10.1 46.3 36.9 27.4 - - ­72 87.8 9.1 60.9 51.4 42.0 32.5 - - 83.4 10.2 59.7 50.2 40.8 31.3 - ­67 80.9 9.1 74.8 65.4 55.9 46.5 37.0 - 76.7 10.3 73.0 63.6 54.1 44.6 35.2 ­62 74.3 8.8 74.3 74.3 66.2 56.8 47.3 37.9 70.6 9.9 70.6 70.6 63.3 53.8 44.3 34.9 57 75.0 8.9 75.0 75.0 66.0 56.5 47.0 37.6 71.3 10.0 71.3 71.3 61.9 52.5 43.0 33.5 77 97.0 9.1 54.0 41.1 30.5 - - - 92.3 10.1 54.6 40.5 29.8 - - ­72 89.9 9.1 66.9 56.3 45.6 35.0 - - 85.3 10.2 65.7 55.0 44.3 33.7 - ­67 82.8 9.2 79.8 71.4 60.8 50.2 39.5 - 78.4 10.3 76.8 69.5 58.9 48.2 37.5 ­62 76.1 8.8 76.1 76.1 72.0 61.4 50.8 40.1 72.2 9.9 72.2 72.2 68.9 58.4 47.5 36.9 57 76.8 9.0 76.8 76.8 71.7 61.1 50.5 39.8 72.9 10.1 72.9 72.9 67.4 57.1 46.1 35.4 77 99.2 9.1 61.1 44.7 32.9 - - - 94.3 10.2 62.8 44.1 32.2 - - ­72 92.0 9.2 72.9 61.1 49.3 37.5 - - 87.2 10.3 71.7 59.8 47.9 36.1 - ­67 84.8 9.2 84.8 77.5 65.7 53.9 42.1 - 80.2 10.3 80.2 75.5 63.6 51.8 39.9 ­62 77.8 8.9 77.8 77.8 77.8 66.0 54.2 42.4 73.8 9.9 73.8 73.8 73.8 63.0 50.7 38.8 57 78.6 9.0 78.6 78.6 77.5 65.7 53.9 42.1 74.5 10.1 74.5 74.5 72.9 61.8 49.1 37.3 72 92.2 9.2 78.1 65.2 52.3 39.4 - - 87.4 10.2 77.0 64.1 51.2 38.2 - ­67 84.9 9.2 84.9 81.3 69.7 56.8 44.0 - 80.3 10.3 80.3 78.9 67.9 55.0 42.1 ­62 78.0 8.9 78.0 78.0 78.0 65.1 52.2 39.3 74.0 9.9 74.0 74.0 74.0 61.5 48.4 35.4 57 78.7 9.0 78.7 78.7 78.2 65.3 52.4 39.5 74.6 10.1 74.6 74.6 73.8 61.3 47.9 35.0 72 92.3 9.1 83.3 69.3 55.4 41.4 - - 87.5 10.2 82.4 68.4 54.4 40.4 - ­67 85.1 9.2 85.1 85.1 73.8 59.8 45.8 - 80.4 10.3 80.4 80.4 72.2 58.2 44.2 ­62 78.1 8.9 78.1 78.1 78.1 64.1 50.2 36.2 74.1 9.9 74.1 74.1 74.1 60.1 46.1 32.1 57 78.9 9.0 78.9 78.9 78.9 64.9 51.0 37.0 74.8 10.0 74.8 74.8 74.8 60.8 46.8 32.8
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
Johnson Controls Unitary Products 19
Page 20
505430-BTG-P-0316
YH-07/NH-10
Air on
Evaporator Coil CFM
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
Total
WB
(°F)
77 105.1 6.0 49.2 40.2 31.1 - - - 108.2 6.6 50.3 41.2 32.1 - - ­72 100.1 5.8 63.3 54.2 45.1 36.0 - - 101.4 6.5 63.6 54.6 45.5 36.4 - ­67 95.1 5.7 77.3 68.2 59.1 50.0 40.9 - 94.6 6.3 77.0 67.9 58.8 49.7 40.7 ­62 87.9 5.6 87.9 80.9 71.8 62.7 53.7 44.6 87.7 6.2 87.7 80.9 71.8 62.7 53.7 44.6 57 83.1 5.5 83.1 83.1 76.8 67.7 58.6 49.5 84.1 6.2 84.1 84.1 77.2 68.2 59.1 50.0 77 109.8 6.0 53.6 43.4 33.2 - - - 112.0 6.7 54.5 44.3 34.1 - - ­72 104.5 5.9 68.6 58.3 48.1 37.9 - - 105.0 6.5 68.6 58.4 48.3 38.1 - ­67 99.3 5.7 83.5 73.3 63.1 52.9 42.6 - 97.9 6.4 82.8 72.6 62.4 52.2 42.1 ­62 91.8 5.6 91.8 86.9 76.7 66.8 56.2 46.0 90.7 6.2 90.7 86.4 76.2 66.0 55.8 45.7 57 86.7 5.6 86.7 86.7 82.0 72.3 61.5 51.3 87.1 6.2 87.1 87.1 82.0 71.8 61.6 51.4 77 114.5 6.1 58.0 46.6 35.3 - - - 115.8 6.7 58.7 47.4 36.1 - - ­72 109.0 5.9 73.9 62.5 51.2 39.8 - - 108.5 6.6 73.6 62.3 51.1 39.8 - ­67 103.5 5.8 89.8 78.4 67.1 55.7 44.4 - 101.2 6.4 88.6 77.3 66.0 54.7 43.4 ­62 95.7 5.7 95.7 92.9 81.5 70.8 58.8 47.5 93.8 6.3 93.8 91.9 80.6 69.3 58.0 46.7 57 90.4 5.6 90.4 90.4 87.1 76.9 64.4 53.1 90.0 6.3 90.0 90.0 86.7 75.4 64.1 52.8 72 110.2 6.0 77.6 65.3 53.1 40.8 - - 110.3 6.6 77.7 65.4 53.2 40.9 - ­67 104.6 5.8 94.1 81.8 69.5 57.3 45.0 - 102.9 6.5 93.3 81.0 68.8 56.5 44.3 ­62 96.7 5.7 96.7 95.3 84.5 72.6 60.0 47.7 95.3 6.3 95.3 94.4 84.0 71.7 59.5 47.2 57 91.4 5.6 91.4 91.4 89.8 78.0 65.2 53.0 91.5 6.3 91.5 91.5 89.8 77.6 65.3 53.1 72 111.4 6.0 81.3 68.1 54.9 41.8 - - 112.1 6.6 81.7 68.5 55.3 42.1 - ­67 105.8 5.9 98.4 85.2 72.0 58.8 45.6 - 104.5 6.5 97.9 84.7 71.5 58.3 45.1 ­62 97.8 5.7 97.8 97.8 87.5 74.3 61.1 47.9 96.8 6.4 96.8 96.8 87.3 74.1 60.9 47.7 57 92.4 5.7 92.4 92.4 92.4 79.2 66.0 52.8 93.0 6.3 93.0 93.0 93.0 79.8 66.6 53.4
77 111.4 7.2 51.3 42.3 33.2 - - - 107.2 8.2 49.9 40.9 31.8 - - ­72 102.8 7.1 64.0 54.9 45.9 36.8 - - 99.1 8.0 62.6 53.5 44.5 35.4 - ­67 94.2 7.0 76.7 67.6 58.5 49.5 40.4 - 90.9 7.9 75.3 66.2 57.1 48.1 39.0 ­62 87.4 6.8 87.4 80.9 71.8 62.7 53.6 44.6 84.0 7.8 84.0 79.3 70.2 61.1 52.0 43.0 57 85.2 6.8 85.2 85.2 77.7 68.6 59.6 50.5 82.3 7.7 82.3 82.3 74.9 65.8 56.8 47.7 77 114.2 7.3 55.3 45.2 35.0 - - - 110.2 8.3 53.9 43.8 33.6 - - ­72 105.4 7.2 68.7 58.5 48.4 38.2 - - 101.8 8.1 67.4 57.2 47.0 36.9 - ­67 96.6 7.0 82.1 71.9 61.8 51.6 41.5 - 93.4 8.0 80.8 70.6 60.5 50.3 40.1 ­62 89.6 6.9 89.6 85.9 75.8 65.3 55.5 45.3 86.3 7.9 86.3 83.7 74.3 63.9 53.9 43.8 57 87.4 6.8 87.4 87.4 82.0 71.3 61.7 51.6 84.6 7.8 84.6 84.6 79.3 68.8 58.9 48.8 77 117.1 7.3 59.3 48.1 36.9 - - - 113.1 8.3 58.0 46.7 35.5 - - ­72 108.0 7.2 73.4 62.2 50.9 39.7 - - 104.5 8.2 72.1 60.9 49.6 38.4 - ­67 99.0 7.1 87.5 76.2 65.0 53.8 42.5 - 95.9 8.1 86.3 75.0 63.8 52.5 41.3 ­62 91.9 6.9 91.9 91.0 79.7 67.9 57.3 46.0 88.6 7.9 88.6 88.2 78.3 66.8 55.8 44.6 57 89.6 6.9 89.6 89.6 86.3 74.0 63.8 52.6 86.9 7.8 86.9 86.9 83.6 71.8 61.1 49.8 72 110.4 7.2 77.7 65.5 53.3 41.1 - - 106.7 8.2 76.4 64.2 52.0 39.7 - ­67 101.2 7.1 92.5 80.2 68.0 55.8 43.6 - 97.9 8.1 91.3 79.0 66.8 54.6 42.3 ­62 93.9 7.0 93.9 93.4 83.4 70.9 59.0 46.8 90.5 8.0 90.5 90.3 82.0 69.7 57.6 45.3 57 91.5 6.9 91.5 91.5 89.9 77.1 65.5 53.2 88.7 7.9 88.7 88.7 87.1 74.6 62.6 50.4 72 112.8 7.3 82.1 68.9 55.7 42.4 - - 108.9 8.3 80.8 67.6 54.3 41.1 - ­67 103.3 7.1 97.4 84.2 71.0 57.8 44.6 - 100.0 8.1 96.3 83.0 69.8 56.6 43.4 ­62 95.9 7.0 95.9 95.9 87.1 73.9 60.7 47.5 92.4 8.0 92.4 92.4 85.8 72.5 59.3 46.1 57 93.5 6.9 93.5 93.5 93.5 80.3 67.1 53.9 90.5 7.9 90.5 90.5 90.5 77.3 64.1 50.9
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
20 Johnson Controls Unitary Products
Page 21
505430-BTG-P-0316
YH-07/NH-10 (Continued)
Air on
Evaporator Coil
CFM
2250
2625
3000
3375
3750
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
WB (°F)
77 103.1 9.1 48.5 39.5 30.4 - - - 98.9 10.1 47.1 38.0 29.0 - - ­72 95.4 9.0 61.2 52.1 43.1 34.0 - - 91.6 9.9 59.8 50.7 41.7 32.6 - ­67 87.6 8.9 73.9 64.8 55.8 46.7 37.6 - 84.4 9.8 72.5 63.4 54.4 45.3 36.2 ­62 80.6 8.7 80.6 77.7 68.6 59.5 50.4 41.4 77.2 9.7 77.2 76.0 67.0 57.9 48.8 39.8 57 79.5 8.6 79.5 79.5 72.1 63.0 54.0 44.9 76.6 9.5 76.6 76.6 69.3 60.2 51.2 42.1 77 106.1 9.2 52.6 42.4 32.2 - - - 102.1 10.2 51.2 41.0 30.8 - - ­72 98.2 9.1 66.0 55.9 45.7 35.5 - - 94.6 10.1 64.7 54.5 44.3 34.2 - ­67 90.3 9.0 79.5 69.3 59.1 49.0 38.8 - 87.1 9.9 78.2 68.0 57.8 47.7 37.5 ­62 83.0 8.8 83.0 81.5 72.8 62.6 52.4 42.3 79.7 9.8 79.7 79.3 71.2 61.2 50.9 40.7 57 81.8 8.7 81.8 81.8 76.5 66.3 56.2 46.0 79.0 9.6 79.0 79.0 73.7 63.8 53.4 43.2 77 109.2 9.3 56.6 45.3 34.1 - - - 105.3 10.3 55.2 44.0 32.7 - - ­72 101.0 9.2 70.8 59.6 48.3 37.0 - - 97.5 10.2 69.5 58.3 47.0 35.7 - ­67 92.9 9.1 85.1 73.8 62.5 51.3 40.0 - 89.8 10.1 83.9 72.6 61.3 50.0 38.7 ­62 85.4 8.9 85.4 85.4 76.9 65.7 54.4 43.1 82.2 10.0 82.2 82.2 75.5 64.5 53.0 41.7 57 84.2 8.8 84.2 84.2 80.9 69.6 58.4 47.1 81.5 9.8 81.5 81.5 78.2 67.4 55.6 44.3 72 103.1 9.2 75.2 62.9 50.7 38.4 - - 99.4 10.2 73.9 61.6 49.3 37.1 - ­67 94.7 9.1 90.1 77.8 65.6 53.3 41.1 - 91.5 10.1 88.9 76.6 64.4 52.1 39.8 ­62 87.1 9.0 87.1 87.1 80.7 68.4 56.2 43.9 83.7 10.0 83.7 83.7 79.3 67.2 54.7 42.5 57 85.9 8.8 85.9 85.9 84.2 72.0 59.7 47.5 83.0 9.8 83.0 83.0 81.4 69.4 56.8 44.6 72 105.1 9.2 79.5 66.2 53.0 39.8 - - 101.3 10.2 78.2 64.9 51.7 38.4 - ­67 96.6 9.1 95.1 81.9 68.6 55.4 42.1 - 93.2 10.1 93.2 80.7 67.4 54.2 40.9 ­62 88.8 9.0 88.8 88.8 84.4 71.2 57.9 44.7 85.3 10.0 85.3 85.3 83.1 69.8 56.5 43.3 57 87.6 8.8 87.6 87.6 87.6 74.3 61.1 47.8 84.6 9.8 84.6 84.6 84.6 71.3 58.1 44.8
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
Johnson Controls Unitary Products 21
Page 22
505430-BTG-P-0316
YH-10/NH-10
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
3000
3500
4000
4500
5000
WB (°F)
77 142.3 7.5 64.7 52.6 40.5 - - - 139.4 8.5 67.1 54.6 42.1 - - ­72 133.9 7.4 84.4 72.2 60.1 48.0 - - 129.5 8.4 85.3 72.8 60.3 47.8 - ­67 125.5 7.3 104.0 91.9 79.8 67.7 55.6 - 119.6 8.3 103.4 90.9 78.5 66.0 53.5 ­62 115.0 7.3 115.0 109.5 94.2 82.0 69.9 57.8 111.3 8.2 111.3 108.6 96.1 83.6 71.1 58.6 57 111.2 7.2 111.2 111.2 99.9 87.8 75.7 63.6 108.8 8.3 108.8 108.8 99.2 86.7 74.2 61.7 77 151.4 7.5 72.3 58.7 45.2 - - - 147.0 8.5 74.2 60.2 46.1 - - ­72 142.4 7.4 94.1 80.6 67.0 53.5 - - 136.6 8.4 94.1 80.0 66.0 51.9 - ­67 133.4 7.3 116.0 102.5 88.9 75.4 61.8 - 126.1 8.3 114.0 99.9 85.9 71.8 57.8 ­62 122.3 7.3 122.3 119.6 105.0 92.1 77.9 64.4 117.4 8.3 117.4 116.1 105.2 91.1 77.1 63.1 57 118.3 7.2 118.3 118.3 111.3 98.6 84.2 70.7 114.8 8.3 114.8 114.8 108.6 94.6 80.5 66.5 77 160.5 7.5 79.8 64.9 49.9 - - - 154.6 8.6 81.3 65.7 50.1 - - ­72 150.9 7.4 103.9 88.9 73.9 59.0 - - 143.7 8.5 102.9 87.3 71.7 56.1 - ­67 141.4 7.3 128.0 113.0 98.0 83.0 68.1 - 132.7 8.4 124.5 108.9 93.3 77.7 62.1 ­62 129.6 7.3 129.6 129.6 115.9 102.2 86.0 71.0 123.5 8.3 123.5 123.5 114.3 98.7 83.1 67.5 57 125.4 7.2 125.4 125.4 122.8 109.5 92.8 77.8 120.7 8.3 120.7 120.7 118.0 102.4 86.8 71.2 72 154.4 7.5 110.8 94.3 77.8 61.4 - - 148.2 8.5 110.7 93.7 76.6 59.6 - ­67 144.7 7.4 138.0 119.7 103.2 86.8 70.3 - 136.9 8.4 132.8 116.7 99.7 82.6 65.6 ­62 132.6 7.3 132.6 132.6 124.4 108.6 91.5 75.0 127.4 8.3 127.4 127.4 122.1 105.1 88.0 70.9 57 128.3 7.3 128.3 128.3 127.0 111.4 94.0 77.6 124.6 8.3 124.6 124.6 123.2 106.1 89.1 72.0 72 157.9 7.5 117.6 99.7 81.7 63.8 - - 152.7 8.5 118.6 100.0 81.5 63.0 - ­67 148.0 7.4 148.0 126.4 108.5 90.5 72.6 - 141.1 8.4 141.1 124.6 106.1 87.6 69.1 ­62 135.6 7.3 135.6 135.6 132.9 114.9 97.0 79.1 131.3 8.3 131.3 131.3 129.9 111.4 92.9 74.4 57 131.2 7.3 131.2 131.2 131.2 113.2 95.3 77.4 128.4 8.4 128.4 128.4 128.4 109.9 91.4 72.8
77 136.4 9.5 69.6 56.7 43.8 - - - 127.0 10.7 66.5 53.5 40.6 - - ­72 125.1 9.4 86.2 73.3 60.5 47.6 - - 117.1 10.7 83.6 70.6 57.7 44.8 - ­67 113.7 9.3 102.9 90.0 77.1 64.2 51.3 - 107.2 10.6 100.7 87.8 74.8 61.9 48.9 ­62 107.7 9.2 107.7 107.7 98.1 85.2 72.3 59.4 100.8 10.5 100.8 100.8 93.7 80.8 67.9 54.9 57 106.5 9.3 106.5 106.5 98.6 85.7 72.8 59.9 100.2 10.6 100.2 100.2 91.6 78.7 65.8 52.8 77 142.6 9.5 76.1 61.6 47.1 - - - 133.4 10.8 75.3 58.7 44.1 - - ­72 130.7 9.4 94.0 79.5 64.9 50.4 - - 123.1 10.7 92.0 77.3 62.7 48.1 - ­67 118.9 9.4 111.9 97.4 82.8 68.3 53.7 - 112.7 10.6 108.7 96.0 81.3 66.7 52.0 ­62 112.6 9.2 112.6 112.6 105.3 90.2 76.3 61.7 106.0 10.5 106.0 106.0 101.9 86.9 72.6 57.9 57 111.3 9.4 111.3 111.3 105.9 90.5 76.8 62.3 105.3 10.6 105.3 105.3 99.5 84.5 70.3 55.6 77 148.8 9.6 82.7 66.5 50.3 - - - 139.9 10.8 84.1 63.9 47.6 - - ­72 136.4 9.5 101.8 85.6 69.4 53.2 - - 129.0 10.7 100.4 84.0 67.7 51.3 - ­67 124.0 9.4 120.9 104.7 88.5 72.3 56.1 - 118.2 10.6 116.6 104.1 87.8 71.5 55.1 ­62 117.4 9.2 117.4 117.4 112.6 95.1 80.2 64.0 111.1 10.5 111.1 111.1 110.0 93.0 77.3 60.9 57 116.1 9.4 116.1 116.1 113.2 95.3 80.8 64.6 110.5 10.6 110.5 110.5 107.4 90.2 74.7 58.4 72 142.0 9.5 110.7 93.0 75.4 57.7 - - 133.3 10.7 109.1 91.2 73.2 55.2 - ­67 129.1 9.4 127.5 113.8 96.1 78.5 60.8 - 122.1 10.6 121.3 112.3 95.0 77.0 59.0 ­62 122.2 9.3 122.2 122.2 119.8 101.5 84.5 66.9 114.8 10.5 114.8 114.8 114.3 96.0 78.3 60.4 57 120.8 9.4 120.8 120.8 119.4 100.9 84.1 66.4 114.1 10.6 114.1 114.1 112.6 94.2 76.7 58.7 72 147.5 9.5 119.5 100.4 81.3 62.2 - - 137.7 10.7 117.9 98.3 78.7 59.1 - ­67 134.1 9.4 134.1 122.8 103.7 84.6 65.5 - 126.1 10.7 126.1 120.4 102.1 82.5 62.9 ­62 127.0 9.3 127.0 127.0 127.0 107.9 88.8 69.7 118.5 10.5 118.5 118.5 118.5 99.0 79.4 59.8 57 125.6 9.4 125.6 125.6 125.6 106.5 87.4 68.3 117.8 10.6 117.8 117.8 117.8 98.2 78.7 59.1
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
22 Johnson Controls Unitary Products
Page 23
505430-BTG-P-0316
YH-10/NH-10 (Continued)
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
1
WB (°F)
77 117.5 12.0 63.4 50.4 37.4 - - - 108.0 13.2 60.3 47.2 34.1 - - ­72 109.1 11.9 81.0 68.0 55.0 41.9 - - 101.2 13.2 78.4 65.3 52.2 39.1 - ­67 100.8 11.9 98.6 85.6 72.6 59.5 46.5 - 94.3 13.1 94.3 83.4 70.3 57.2 44.1 ­62 94.0 11.8 94.0 94.0 89.4 76.4 63.4 50.4 87.2 13.0 87.2 87.2 85.1 72.0 59.0 45.9 57 94.0 11.8 94.0 94.0 84.7 71.7 58.7 45.7 87.8 13.1 87.8 87.8 77.8 64.7 51.7 38.6 77 124.2 12.0 74.4 55.8 41.1 - - - 115.1 13.2 73.6 53.0 38.1 - - ­72 115.4 11.9 89.9 75.2 60.4 45.7 - - 107.7 13.2 87.9 73.1 58.2 43.4 - ­67 106.6 11.9 105.5 94.6 79.8 65.1 50.3 - 100.4 13.1 100.4 93.2 78.3 63.5 48.6 ­62 99.4 11.8 99.4 99.4 98.4 83.6 68.9 54.1 92.8 13.0 92.8 92.8 92.8 80.4 65.2 50.3 57 99.4 11.8 99.4 99.4 93.2 78.5 63.7 49.0 93.5 13.1 93.5 93.5 86.9 72.4 57.2 42.3 77 131.0 12.0 85.5 61.3 44.8 - - - 122.1 13.2 86.9 58.7 42.1 - - ­72 121.7 11.9 98.9 82.4 65.9 49.5 - - 114.3 13.2 97.5 80.8 64.2 47.6 - ­67 112.3 11.9 112.3 103.5 87.1 70.6 54.1 - 106.5 13.1 106.5 103.0 86.3 69.7 53.1 ­62 104.8 11.8 104.8 104.8 107.3 90.8 74.4 57.9 98.5 13.1 98.5 98.5 98.5 88.7 71.4 54.8 57 104.8 11.8 104.8 104.8 101.7 85.2 68.7 52.2 99.2 13.1 99.2 99.2 95.9 80.1 62.7 46.0 72 124.7 11.9 107.6 89.3 71.0 52.8 - - 116.1 13.2 106.1 87.5 68.9 50.3 - ­67 115.2 11.9 115.2 110.8 93.8 75.5 57.2 - 108.2 13.1 108.2 108.2 92.6 74.0 55.4 ­62 107.4 11.8 107.4 107.4 108.7 90.4 72.1 53.8 100.0 13.1 100.0 100.0 100.0 84.9 65.9 47.3 57 107.4 11.8 107.4 107.4 105.9 87.6 69.3 51.0 100.7 13.1 100.7 100.7 99.1 80.9 61.9 43.3 72 127.8 12.0 116.3 96.2 76.1 56.1 - - 117.9 13.2 114.7 94.1 73.6 53.0 - ­67 118.0 11.9 118.0 118.0 100.5 80.4 60.4 - 109.9 13.1 109.9 109.9 98.9 78.4 57.8 ­62 110.1 11.8 110.1 110.1 110.1 90.0 69.9 49.8 101.6 13.0 101.6 101.6 101.6 81.0 60.4 39.9 57 110.1 11.9 110.1 110.1 110.1 90.0 69.9 49.8 102.3 13.1 102.3 102.3 102.3 81.7 61.2 40.6
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
Johnson Controls Unitary Products 23
Page 24
505430-BTG-P-0316
YJ-10/NJ-10
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
3000
3500
4000
4500
5000
WB (°F)
77 138.1 7.5 63.6 51.7 39.9 - - - 132.8 8.6 62.9 50.8 38.7 - - ­72 130.1 7.4 82.9 71.0 59.2 47.4 - - 124.4 8.4 81.7 69.6 57.5 45.4 - ­67 122.0 7.2 102.2 90.4 78.5 66.7 54.8 - 115.9 8.3 100.6 88.5 76.4 64.3 52.2 ­62 112.3 7.2 112.3 108.5 94.8 83.0 71.1 59.3 106.3 8.2 106.3 104.4 92.3 80.2 68.1 56.0 57 108.2 7.1 108.2 108.6 99.9 88.0 76.2 64.3 105.7 8.2 105.7 105.7 95.1 83.0 70.9 58.8 77 147.1 7.5 70.5 57.3 44.0 - - - 141.3 8.6 70.1 56.5 42.8 - - ­72 138.4 7.4 91.8 78.6 65.3 52.0 - - 132.4 8.4 91.0 77.3 63.6 50.0 - ­67 129.8 7.3 113.1 99.9 86.6 73.3 60.0 - 123.4 8.3 111.9 98.2 84.5 70.8 57.1 ­62 119.5 7.2 119.5 117.6 104.6 91.9 78.0 64.7 113.2 8.2 113.2 112.2 102.1 88.5 74.8 61.1 57 115.1 7.2 115.1 115.4 110.1 97.8 83.6 70.3 112.5 8.2 112.5 112.5 105.3 91.6 77.9 64.2 77 156.0 7.6 77.5 62.8 48.1 - - - 149.9 8.6 77.4 62.1 46.9 - - ­72 146.8 7.4 100.8 86.1 71.4 56.7 - - 140.4 8.4 100.3 85.0 69.8 54.5 - ­67 137.7 7.3 124.1 109.4 94.6 79.9 65.2 - 130.9 8.3 123.2 107.9 92.6 77.4 62.1 ­62 126.8 7.2 126.8 126.8 114.3 100.8 84.9 70.2 120.0 8.2 120.0 120.0 112.0 96.7 81.4 66.2 57 122.1 7.2 122.1 122.1 120.4 107.5 91.0 76.3 119.3 8.2 119.3 119.3 115.4 100.1 84.9 69.6 72 152.4 7.5 108.1 92.0 76.0 60.0 - - 145.8 8.5 107.7 91.1 74.5 57.9 - ­67 142.9 7.3 136.1 116.8 100.8 84.8 68.8 - 135.9 8.3 132.1 115.5 98.9 82.3 65.7 ­62 131.5 7.2 131.5 131.5 123.1 107.7 91.1 75.1 124.6 8.2 124.6 124.6 119.5 102.9 86.3 69.7 57 126.7 7.2 126.7 126.7 125.9 110.8 93.9 77.8 123.9 8.2 123.9 123.9 121.9 105.3 88.7 72.1 72 157.9 7.5 115.3 98.0 80.7 63.4 - - 151.2 8.5 115.2 97.2 79.2 61.2 - ­67 148.1 7.4 148.1 124.3 107.0 89.7 72.4 - 141.0 8.3 141.0 123.1 105.1 87.2 69.2 ­62 136.3 7.3 136.3 136.3 132.0 114.6 97.3 80.0 129.3 8.3 129.3 129.3 127.1 109.1 91.1 73.1 57 131.3 7.3 131.3 131.3 131.3 114.0 96.7 79.4 128.5 8.2 128.5 128.5 128.5 110.5 92.5 74.6
77 127.4 9.6 62.2 49.8 37.4 - - - 122.1 10.8 60.4 48.0 35.6 - - ­72 118.7 9.5 80.6 68.2 55.9 43.5 - - 112.7 10.7 78.3 65.8 53.4 41.0 - ­67 109.9 9.3 99.0 86.6 74.3 61.9 49.5 - 103.2 10.6 96.1 83.7 71.2 58.8 46.4 ­62 100.4 9.2 100.4 100.4 89.8 77.5 65.1 52.7 95.0 10.5 95.0 95.0 86.6 74.1 61.7 49.3 57 103.2 9.2 103.2 102.8 90.4 78.0 65.7 53.3 98.1 10.5 98.1 97.9 85.4 73.0 60.5 48.1 77 135.6 9.6 69.7 55.6 41.6 - - - 129.2 10.8 70.6 53.8 39.6 - - ­72 126.3 9.5 90.2 76.1 62.0 47.9 - - 119.2 10.7 87.9 73.7 59.5 45.3 - ­67 116.9 9.3 110.6 96.6 82.5 68.4 54.3 - 109.2 10.6 105.2 93.6 79.4 65.2 51.0 ­62 106.8 9.2 106.8 106.8 99.7 85.0 71.5 57.4 100.5 10.5 100.5 100.5 96.5 82.0 68.1 53.9 57 109.9 9.2 109.9 109.6 100.4 85.4 72.2 58.1 103.8 10.5 103.8 103.6 95.2 80.5 66.8 52.6 77 143.8 9.6 77.3 61.5 45.7 - - - 136.2 10.8 80.8 59.7 43.7 - - ­72 133.9 9.5 99.8 84.0 68.2 52.3 - - 125.7 10.7 97.5 81.6 65.6 49.6 - ­67 124.0 9.3 122.3 106.5 90.6 74.8 59.0 - 115.1 10.6 114.3 103.5 87.5 71.6 55.6 ­62 113.3 9.2 113.3 113.3 109.6 92.6 78.0 62.2 106.0 10.5 106.0 106.0 106.4 89.8 74.4 58.5 57 116.5 9.2 116.5 116.5 110.3 92.7 78.7 62.9 109.4 10.5 109.4 109.4 104.9 88.1 73.0 57.1 72 139.2 9.5 107.4 90.2 72.9 55.7 - - 131.0 10.7 105.2 87.7 70.3 52.8 - ­67 128.9 9.3 128.0 114.2 97.0 79.7 62.5 - 120.1 10.6 119.6 111.2 93.7 76.3 58.8 ­62 117.7 9.2 117.7 117.7 115.9 98.1 81.4 64.2 110.5 10.5 110.5 110.5 110.7 92.9 75.8 58.3 57 121.1 9.2 121.1 121.1 118.0 99.9 83.5 66.3 114.1 10.5 114.1 114.1 111.8 93.9 76.9 59.4 72 144.5 9.5 115.0 96.3 77.7 59.0 - - 136.4 10.7 112.9 93.9 74.9 56.0 - ­67 133.8 9.3 133.8 121.9 103.3 84.6 66.0 - 125.0 10.6 125.0 118.9 99.9 81.0 62.0 ­62 122.2 9.2 122.2 122.2 122.2 103.5 84.9 66.2 115.0 10.5 115.0 115.0 115.0 96.1 77.1 58.1 57 125.7 9.2 125.7 125.7 125.7 107.0 88.4 69.7 118.7 10.5 118.7 118.7 118.7 99.8 80.8 61.8
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
24 Johnson Controls Unitary Products
Page 25
505430-BTG-P-0316
YJ-10/NJ-10 (Continued)
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
1
WB (°F)
77 116.8 12.1 58.7 46.2 33.7 - - - 111.5 13.3 57.0 44.4 31.8 - - ­72 106.7 11.9 75.9 63.4 50.9 38.4 - - 100.7 13.2 73.6 61.1 48.5 35.9 - ­67 96.6 11.8 93.2 80.7 68.2 55.7 43.2 - 89.9 13.1 89.9 77.7 65.1 52.6 40.0 ­62 89.7 11.7 89.7 89.7 83.3 70.8 58.3 45.8 84.4 12.9 84.4 84.4 80.0 67.5 54.9 42.3 57 93.0 11.7 93.0 92.9 80.4 67.9 55.4 42.9 87.9 12.9 87.9 87.9 75.5 62.9 50.3 37.8 77 122.7 12.1 71.5 52.0 37.7 - - - 116.2 13.3 72.4 50.2 35.8 - - ­72 112.1 11.9 85.6 71.3 57.0 42.7 - - 105.0 13.2 83.3 68.9 54.5 40.1 - ­67 101.4 11.8 99.7 90.6 76.3 62.0 47.7 - 93.7 13.1 93.7 87.6 73.2 58.8 44.4 ­62 94.2 11.7 94.2 94.2 93.2 78.9 64.6 50.3 88.0 12.9 88.0 88.0 88.0 75.8 61.1 46.7 57 97.7 11.7 97.7 97.6 90.0 75.7 61.4 47.1 91.5 13.0 91.5 91.5 84.8 70.9 56.0 41.6 77 128.6 12.1 84.3 57.8 41.7 - - - 120.9 13.3 87.7 56.0 39.7 - - ­72 117.4 11.9 95.3 79.2 63.1 46.9 - - 109.2 13.2 93.0 76.8 60.5 44.2 - ­67 106.3 11.8 106.3 100.5 84.4 68.3 52.2 - 97.4 13.1 97.4 97.4 81.3 65.0 48.8 ­62 98.8 11.7 98.8 98.8 103.1 87.0 70.9 54.8 91.5 12.9 91.5 91.5 91.5 84.2 67.3 51.1 57 102.3 11.7 102.3 102.3 99.6 83.5 67.3 51.2 95.2 13.0 95.2 95.2 94.2 78.8 61.7 45.4 72 122.9 12.0 103.0 85.3 67.6 49.9 - - 114.7 13.2 100.8 82.9 65.0 47.0 - ­67 111.2 11.8 111.2 108.2 90.5 72.8 55.1 - 102.4 13.1 102.4 102.4 87.3 69.3 51.4 ­62 103.3 11.7 103.3 103.3 105.5 87.8 70.1 52.4 96.1 12.9 96.1 96.1 96.1 82.6 64.4 46.5 57 107.1 11.7 107.1 107.1 105.7 88.0 70.3 52.6 100.0 13.0 100.0 100.0 99.5 82.0 63.6 45.7 72 128.3 12.0 110.8 91.5 72.2 52.9 - - 120.2 13.3 108.7 89.0 69.4 49.8 - ­67 116.1 11.9 116.1 115.9 96.6 77.3 58.0 - 107.3 13.2 107.3 107.3 93.3 73.7 54.1 ­62 107.9 11.7 107.9 107.9 107.9 88.6 69.3 50.0 100.7 13.0 100.7 100.7 100.7 81.1 61.5 41.9 57 111.8 11.8 111.8 111.8 111.8 92.5 73.2 53.9 104.8 13.0 104.8 104.8 104.8 85.2 65.6 46.0
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
Johnson Controls Unitary Products 25
Page 26
505430-BTG-P-0316
YH-12/NH-15
Air on
Evaporator Coil
CFM
3750
4375
5000
5625
6250
3750
4375
5000
5625
6250
WB (°F)
77 178.5 10.2 87.6 71.1 54.7 - - - 172.2 11.3 84.0 67.6 51.2 - - ­72 168.2 9.9 111.9 95.4 78.9 62.4 - - 161.2 11.0 108.3 91.9 75.5 59.2 - ­67 157.9 9.6 136.1 119.6 103.1 86.7 70.2 - 150.1 10.7 132.5 116.2 99.8 83.4 67.1 ­62 144.8 9.4 144.8 144.8 129.3 112.8 96.3 79.8 138.9 10.6 138.9 138.9 126.4 110.1 93.7 77.3 57 149.7 9.5 149.7 149.7 137.7 121.2 104.7 88.3 143.9 10.7 143.9 143.9 130.6 114.3 97.9 81.5 77 184.7 10.2 94.2 77.2 58.5 - - - 177.6 11.3 92.4 73.7 55.0 - - ­72 174.0 9.9 121.8 103.1 84.4 65.7 - - 166.2 11.0 118.4 99.8 81.1 62.4 - ­67 163.4 9.6 149.5 129.0 110.3 91.6 72.9 - 154.7 10.8 144.5 125.8 107.1 88.4 69.8 ­62 149.9 9.4 149.9 149.9 138.2 119.8 100.8 82.1 143.2 10.6 143.2 143.2 135.7 117.0 98.4 79.7 57 154.9 9.5 154.9 154.9 147.3 129.1 109.8 91.1 148.4 10.7 148.4 148.4 140.2 121.6 102.9 84.2 77 190.9 10.3 100.7 83.2 62.3 - - - 182.9 11.3 100.8 79.8 58.8 - - ­72 179.9 9.9 131.8 110.8 89.9 68.9 - - 171.2 11.0 128.6 107.6 86.6 65.6 - ­67 168.8 9.6 162.9 138.4 117.5 96.5 75.5 - 159.4 10.8 156.5 135.5 114.5 93.5 72.5 ­62 154.9 9.4 154.9 154.9 147.2 126.8 105.3 84.3 147.5 10.6 147.5 147.5 145.0 124.0 103.0 82.0 57 160.1 9.6 160.1 160.1 156.9 137.0 114.9 94.0 152.9 10.7 152.9 152.9 149.8 128.8 107.8 86.8 72 182.3 10.1 142.7 119.7 96.7 73.7 - - 174.1 11.2 139.0 116.1 93.1 70.2 - ­67 171.1 9.8 168.1 149.4 126.4 103.4 80.4 - 162.1 10.9 160.6 146.0 123.1 100.1 77.2 ­62 157.0 9.6 157.0 157.0 153.1 130.4 107.1 84.1 150.0 10.7 150.0 150.0 148.8 125.8 102.9 79.9 57 162.2 9.7 162.2 162.2 160.6 138.1 114.6 91.6 155.5 10.8 155.5 155.5 153.9 131.0 108.1 85.1 72 184.7 10.2 153.7 128.6 103.6 78.5 - - 177.0 11.3 149.4 124.5 99.7 74.8 - ­67 173.4 9.9 173.4 160.4 135.4 110.4 85.3 - 164.8 11.0 164.8 156.6 131.7 106.8 81.9 ­62 159.0 9.7 159.0 159.0 159.0 134.0 108.9 83.9 152.5 10.8 152.5 152.5 152.5 127.6 102.7 77.8 57 164.4 9.8 164.4 164.4 164.4 139.3 114.3 89.2 158.1 10.9 158.1 158.1 158.1 133.2 108.3 83.4
77 166.0 12.3 80.3 64.1 47.8 - - - 159.9 14.1 79.0 62.8 46.6 - - ­72 154.1 12.1 104.7 88.4 72.2 55.9 - - 148.2 13.8 102.8 86.6 70.4 54.2 - ­67 142.3 11.9 129.0 112.7 96.5 80.2 64.0 - 136.4 13.5 126.7 110.5 94.2 78.0 61.8 ­62 132.9 11.7 132.9 132.9 123.6 107.4 91.1 74.9 130.6 13.4 130.6 130.6 122.0 105.8 89.6 73.4 57 138.2 11.8 138.2 138.2 123.6 107.3 91.1 74.8 134.7 13.5 134.7 134.7 119.4 103.2 87.0 70.8 77 170.5 12.3 90.6 70.2 51.6 - - - 163.0 14.0 91.5 68.6 50.0 - - ­72 158.3 12.1 115.0 96.4 77.8 59.1 - - 151.0 13.7 112.8 94.2 75.6 56.9 - ­67 146.1 11.9 139.5 122.6 104.0 85.3 66.7 - 139.1 13.5 134.2 119.8 101.2 82.5 63.9 ­62 136.5 11.7 136.5 136.5 133.2 114.3 95.9 77.3 133.1 13.4 133.1 133.1 130.9 112.1 93.6 75.0 57 142.0 11.8 142.0 142.0 133.2 114.0 95.9 77.3 137.3 13.5 137.3 137.3 128.1 109.2 90.9 72.2 77 175.0 12.3 100.8 76.3 55.3 - - - 166.1 13.9 104.0 74.4 53.4 - - ­72 162.5 12.1 125.4 104.4 83.4 62.3 - - 153.9 13.7 122.9 101.8 80.7 59.6 - ­67 150.0 11.9 150.0 132.5 111.5 90.4 69.4 - 141.7 13.4 141.7 129.1 108.1 87.0 65.9 ­62 140.1 11.7 140.1 140.1 142.8 121.2 100.7 79.7 135.6 13.3 135.6 135.6 139.8 118.5 97.7 76.6 57 145.7 11.8 145.7 145.7 142.8 120.7 100.7 79.7 140.0 13.4 140.0 140.0 136.9 115.3 94.8 73.7 72 165.9 12.2 135.3 112.4 89.5 66.7 - - 157.7 13.8 133.0 110.0 87.1 64.2 - ­67 153.1 12.0 153.1 142.6 119.7 96.8 73.9 - 145.2 13.5 145.2 138.0 116.6 93.7 70.8 ­62 143.1 11.8 143.1 143.1 144.4 121.2 98.6 75.7 138.9 13.4 138.9 138.9 141.0 118.0 95.2 72.3 57 148.7 11.9 148.7 148.7 147.3 123.9 101.5 78.6 143.4 13.5 143.4 143.4 141.8 118.6 96.0 73.1 72 169.3 12.3 145.2 120.5 95.7 71.0 - - 161.4 14.0 143.0 118.3 93.5 68.7 - ­67 156.3 12.1 156.3 152.7 128.0 103.2 78.5 - 148.6 13.7 148.6 146.9 125.2 100.4 75.6 ­62 146.0 11.9 146.0 146.0 146.0 121.3 96.5 71.8 142.2 13.6 142.2 142.2 142.2 117.5 92.7 67.9 57 151.8 12.0 151.8 151.8 151.8 127.0 102.3 77.6 146.8 13.7 146.8 146.8 146.8 122.0 97.2 72.5
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
26 Johnson Controls Unitary Products
Page 27
505430-BTG-P-0316
YH-12/NH-15 (Continued)
Air on
Evaporator Coil
CFM
3750
4375
5000
5625
6250
1
WB (°F)
77 153.8 15.8 77.6 61.4 45.3 - - - 147.7 17.5 76.3 60.1 44.0 - - ­72 142.2 15.5 101.0 84.8 68.7 52.5 - - 136.2 17.2 99.2 83.0 66.9 50.8 - ­67 130.5 15.1 124.4 108.2 92.0 75.9 59.7 - 124.7 16.8 122.1 105.9 89.8 73.7 57.6 ­62 128.2 15.1 128.2 128.2 120.4 104.2 88.0 71.9 125.8 16.8 125.8 125.8 118.7 102.6 86.5 70.4 57 131.2 15.2 131.2 131.2 115.2 99.0 82.8 66.7 127.8 17.0 127.8 127.8 111.0 94.9 78.7 62.6 77 155.5 15.7 92.3 67.0 48.4 - - - 148.1 17.3 93.2 65.4 46.8 - - ­72 143.8 15.3 110.6 92.0 73.4 54.7 - - 136.5 17.0 108.4 89.8 71.2 52.5 - ­67 132.0 15.0 128.9 117.0 98.3 79.7 61.1 - 125.0 16.6 123.7 114.2 95.5 76.9 58.3 ­62 129.7 15.0 129.7 129.7 128.6 110.0 91.3 72.7 126.2 16.7 126.2 126.2 126.2 107.8 89.1 70.4 57 132.7 15.1 132.7 132.7 123.1 104.4 85.8 67.2 128.1 16.8 128.1 128.1 118.0 99.7 80.8 62.1 77 157.3 15.5 107.1 72.6 51.5 - - - 148.4 17.1 110.2 70.7 49.6 - - ­72 145.4 15.2 120.3 99.2 78.1 57.0 - - 136.8 16.8 117.7 96.6 75.4 54.3 - ­67 133.5 14.9 133.5 125.8 104.7 83.6 62.5 - 125.2 16.4 125.2 122.4 101.3 80.1 59.0 ­62 131.1 14.9 131.1 131.1 136.9 115.8 94.7 73.6 126.6 16.5 126.6 126.6 126.6 113.1 91.6 70.5 57 134.2 15.0 134.2 134.2 131.0 109.9 88.8 67.7 128.5 16.6 128.5 128.5 125.1 104.5 82.8 61.7 72 149.5 15.4 130.6 107.6 84.7 61.7 - - 141.3 17.0 128.2 105.2 82.3 59.3 - ­67 137.3 15.1 137.3 133.4 113.5 90.6 67.6 - 129.3 16.6 129.3 128.8 110.4 87.5 64.5 ­62 134.8 15.1 134.8 134.8 137.7 114.7 91.8 68.8 130.7 16.7 130.7 130.7 130.7 111.5 88.4 65.4 57 138.0 15.2 138.0 138.0 136.4 113.4 90.5 67.5 132.6 16.8 132.6 132.6 130.9 108.2 84.9 62.0 72 153.6 15.6 140.9 116.1 91.3 66.5 - - 145.7 17.2 138.7 113.9 89.1 64.3 - ­67 141.0 15.3 141.0 141.0 122.4 97.6 72.8 - 133.4 16.8 133.4 133.4 119.6 94.8 69.9 ­62 138.5 15.3 138.5 138.5 138.5 113.7 88.9 64.1 134.7 16.9 134.7 134.7 134.7 109.9 85.1 60.2 57 141.8 15.4 141.8 141.8 141.8 117.0 92.2 67.4 136.7 17.1 136.7 136.7 136.7 111.9 87.1 62.3
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
Johnson Controls Unitary Products 27
Page 28
505430-BTG-P-0316
YJ-12/NJ-15
Air on
Evaporator Coil
CFM
3750
4375
5000
5625
6250
3750
4375
5000
5625
6250
WB (°F)
77 170.2 10.0 80.1 64.2 48.3 - - - 173.7 11.0 81.5 65.4 49.3 - - ­72 164.1 9.7 106.1 90.2 74.3 58.4 - - 161.9 10.8 105.7 89.6 73.5 57.5 - ­67 157.9 9.5 132.0 116.1 100.2 84.3 68.5 - 150.1 10.6 129.8 113.8 97.7 81.7 65.6 ­62 142.4 9.3 142.4 140.8 122.7 106.8 90.9 75.1 139.3 10.4 139.3 138.5 122.4 106.4 90.3 74.2 57 141.3 9.3 141.3 141.3 129.9 114.0 98.1 82.2 140.0 10.4 140.0 140.0 127.0 111.0 94.9 78.8 77 182.4 10.0 89.5 72.3 53.8 - - - 182.2 11.1 91.1 72.7 54.3 - - ­72 175.5 9.7 119.7 101.2 82.7 64.2 - - 169.8 10.9 117.7 99.3 80.8 62.4 - ­67 168.7 9.5 149.8 130.0 111.5 93.0 74.5 - 157.4 10.7 144.3 125.9 107.4 89.0 70.5 ­62 152.3 9.4 152.3 151.5 136.6 118.9 99.7 81.2 146.1 10.5 146.1 145.7 134.6 116.1 97.7 79.2 57 151.2 9.3 151.2 151.2 144.6 126.8 107.6 89.1 146.8 10.5 146.8 146.8 139.7 121.2 102.8 84.3 77 194.5 10.0 98.9 80.4 59.3 - - - 190.7 11.1 100.8 80.0 59.2 - - ­72 187.0 9.8 133.3 112.2 91.1 70.0 - - 177.7 10.9 129.8 109.0 88.2 67.3 - ­67 179.5 9.5 167.6 143.9 122.8 101.7 80.6 - 164.8 10.7 158.8 138.0 117.1 96.3 75.5 ­62 162.2 9.4 162.2 162.2 150.6 131.0 108.4 87.3 152.9 10.5 152.9 152.9 146.8 125.9 105.1 84.3 57 161.1 9.4 161.1 161.1 159.2 139.6 117.0 95.9 153.7 10.5 153.7 153.7 152.3 131.4 110.6 89.8 72 187.6 9.8 141.9 119.6 97.2 74.8 - - 180.7 11.0 140.5 117.9 95.3 72.8 - ­67 180.3 9.6 174.3 153.5 131.1 108.7 86.4 - 167.5 10.8 164.6 149.3 126.7 104.1 81.5 ­62 162.8 9.5 162.8 162.8 156.9 135.3 112.2 89.8 155.4 10.6 155.4 155.4 152.4 129.8 107.2 84.7 57 161.6 9.4 161.6 161.6 160.7 139.0 115.9 93.5 156.3 10.6 156.3 156.3 155.6 133.0 110.4 87.8 72 188.2 9.9 150.6 126.9 103.3 79.6 - - 183.7 11.0 151.2 126.8 102.5 78.2 - ­67 181.0 9.7 181.0 163.0 139.4 115.7 92.1 - 170.3 10.8 170.3 160.6 136.2 111.9 87.6 ­62 163.3 9.5 163.3 163.3 163.3 139.7 116.0 92.3 158.0 10.6 158.0 158.0 158.0 133.7 109.4 85.1 57 162.1 9.5 162.1 162.1 162.1 138.5 114.8 91.1 158.8 10.6 158.8 158.8 158.8 134.5 110.2 85.9
77 177.3 12.0 82.9 66.6 50.4 - - - 162.9 13.7 78.3 62.1 45.9 - - ­72 159.8 11.9 105.3 89.0 72.8 56.6 - - 149.2 13.5 101.4 85.2 69.0 52.8 - ­67 142.3 11.8 127.7 111.4 95.2 79.0 62.7 - 135.4 13.3 124.6 108.4 92.2 76.0 59.7 ­62 136.2 11.5 136.2 136.2 122.1 105.9 89.7 73.4 128.0 13.0 128.0 128.0 118.2 102.0 85.7 69.5 57 138.7 11.5 138.7 138.7 124.1 107.9 91.7 75.5 131.1 13.1 131.1 131.1 116.6 100.4 84.2 68.0 77 182.1 12.1 92.8 73.1 54.7 - - - 168.7 13.7 90.6 68.8 50.3 - - ­72 164.1 12.0 115.8 97.4 79.0 60.6 - - 154.5 13.5 112.8 94.2 75.6 57.1 - ­67 146.2 11.9 138.8 121.7 103.3 84.9 66.5 - 140.3 13.4 134.9 119.6 101.0 82.4 63.9 ­62 139.8 11.6 139.8 139.8 132.5 113.4 95.7 77.3 132.6 13.1 132.6 132.6 129.5 110.6 92.4 73.8 57 142.5 11.6 142.5 142.5 134.7 115.6 97.9 79.5 135.8 13.2 135.8 135.8 127.7 108.8 90.6 72.1 77 186.8 12.2 102.7 79.6 59.0 - - - 174.5 13.8 103.0 75.6 54.7 - - ­72 168.4 12.1 126.4 105.8 85.2 64.7 - - 159.9 13.6 124.1 103.2 82.3 61.3 - ­67 150.0 12.0 150.0 132.0 111.5 90.9 70.3 - 145.2 13.4 145.2 130.8 109.9 88.9 68.0 ­62 143.5 11.7 143.5 143.5 142.9 120.8 101.8 81.2 137.2 13.1 137.2 137.2 140.9 119.2 99.0 78.1 57 146.2 11.7 146.2 146.2 145.3 123.3 104.2 83.6 140.5 13.2 140.5 140.5 138.9 117.2 97.1 76.2 72 173.8 12.1 139.0 116.3 93.5 70.7 - - 164.1 13.6 136.3 113.3 90.3 67.2 - ­67 154.8 12.0 154.8 145.1 122.3 99.5 76.7 - 149.0 13.5 149.0 141.4 120.5 97.5 74.5 ­62 148.1 11.7 148.1 148.1 147.8 124.3 102.3 79.5 140.7 13.2 140.7 140.7 142.6 119.2 96.6 73.5 57 150.9 11.7 150.9 150.9 150.4 126.9 104.9 82.1 144.2 13.2 144.2 144.2 143.4 120.0 97.3 74.3 72 179.2 12.1 151.7 126.8 101.8 76.8 - - 168.3 13.7 148.5 123.4 98.3 73.1 - ­67 159.6 12.0 159.6 158.1 133.1 108.1 83.2 - 152.8 13.5 152.8 152.0 131.2 106.1 81.0 ­62 152.7 11.7 152.7 152.7 152.7 127.7 102.8 77.8 144.3 13.2 144.3 144.3 144.3 119.2 94.1 69.0 57 155.6 11.7 155.6 155.6 155.6 130.6 105.6 80.6 147.8 13.3 147.8 147.8 147.8 122.7 97.6 72.5
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
28 Johnson Controls Unitary Products
Page 29
505430-BTG-P-0316
YJ-12/NJ-15 (Continued)
Air on
Evaporator Coil
CFM
3750
4375
5000
5625
6250
1
WB (°F)
77 148.6 15.3 73.8 57.6 41.4 - - - 134.2 17.0 69.2 53.1 36.9 - - ­72 138.6 15.1 97.6 81.4 65.3 49.1 - - 128.0 16.7 93.8 77.6 61.5 45.3 - ­67 128.6 14.8 121.5 105.3 89.1 72.9 56.7 - 121.7 16.3 118.3 102.2 86.0 69.9 53.7 ­62 119.7 14.5 119.7 119.7 114.2 98.0 81.8 65.7 111.5 16.0 111.5 111.5 110.2 94.1 77.9 61.8 57 123.4 14.7 123.4 123.4 109.0 92.8 76.7 60.5 115.7 16.3 115.7 115.7 101.5 85.3 69.2 53.0 77 155.4 15.4 88.5 64.6 45.9 - - - 142.1 17.0 86.4 60.4 41.5 - - ­72 145.0 15.1 109.7 91.0 72.3 53.6 - - 135.4 16.6 106.7 87.8 68.9 50.0 - ­67 134.5 14.8 130.9 117.4 98.7 80.0 61.2 - 128.7 16.3 127.0 115.2 96.4 77.5 58.6 ­62 125.3 14.5 125.3 125.3 126.5 107.8 89.0 70.3 118.0 16.0 118.0 118.0 118.0 105.0 85.7 66.8 57 129.1 14.7 129.1 129.1 120.7 102.0 83.3 64.6 122.4 16.3 122.4 122.4 113.8 95.2 76.0 57.1 77 162.3 15.4 103.2 71.6 50.3 - - - 150.0 16.9 103.5 67.6 46.0 - - ­72 151.3 15.1 121.8 100.6 79.3 58.0 - - 142.8 16.6 119.6 98.0 76.3 54.7 - ­67 140.4 14.8 140.4 129.5 108.3 87.0 65.7 - 135.6 16.3 135.6 128.3 106.7 85.1 63.5 ­62 130.8 14.5 130.8 130.8 138.8 117.5 96.2 75.0 124.4 16.0 124.4 124.4 124.4 115.8 93.5 71.9 57 134.8 14.7 134.8 134.8 132.5 111.2 90.0 68.7 129.0 16.2 129.0 129.0 126.0 105.2 82.8 61.2 72 154.3 15.2 133.5 110.3 87.0 63.8 - - 144.6 16.7 130.8 107.3 83.8 60.3 - ­67 143.2 14.9 143.2 137.8 118.8 95.5 72.3 - 137.4 16.4 137.4 134.1 117.1 93.6 70.1 ­62 133.4 14.6 133.4 133.4 137.4 114.1 90.8 67.6 126.0 16.1 126.0 126.0 126.0 109.0 85.1 61.6 57 137.4 14.8 137.4 137.4 136.3 113.0 89.8 66.5 130.7 16.3 130.7 130.7 129.2 106.1 82.2 58.7 72 157.3 15.3 145.3 120.0 94.7 69.5 - - 146.4 16.8 142.0 116.6 91.2 65.8 - ­67 146.0 15.0 146.0 146.0 129.3 104.1 78.8 - 139.2 16.5 139.2 139.2 127.5 102.1 76.7 ­62 136.0 14.7 136.0 136.0 136.0 110.7 85.4 60.2 127.6 16.2 127.6 127.6 127.6 102.2 76.8 51.4 57 140.1 14.9 140.1 140.1 140.1 114.8 89.6 64.3 132.4 16.5 132.4 132.4 132.4 107.0 81.6 56.2
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
Johnson Controls Unitary Products 29
Page 30
505430-BTG-P-0316
YH-15/NH-15
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB (°F)
Total
Capacity
(MBh)
77 223.5 11.8 104.0 85.0 66.0 - - - 214.6 13.1 101.2 82.2 63.3 - - ­72 207.2 11.5 132.3 113.3 94.4 75.4 - - 198.3 12.8 129.0 110.1 91.2 72.2 - ­67 191.0 11.1 160.6 141.7 122.7 103.7 84.7 - 181.9 12.4 156.8 137.9 119.0 100.1 81.1 ­62 176.0 10.8 176.0 171.9 151.4 132.5 113.5 94.5 168.5 12.2 168.5 166.4 147.5 128.6 109.7 90.8 57 175.0 10.8 175.0 175.0 158.1 139.1 120.1 101.1 168.1 12.1 168.1 168.1 150.6 131.7 112.8 93.8 77 229.4 11.9 113.7 92.3 70.8 - - - 220.1 13.2 110.7 89.4 68.1 - - ­72 212.8 11.6 144.1 122.7 101.2 79.7 - - 203.3 12.8 140.7 119.4 98.1 76.8 - ­67 196.1 11.2 174.5 153.0 131.6 110.1 88.7 - 186.5 12.5 170.6 149.3 128.0 106.7 85.4 ­62 180.7 11.0 180.7 178.6 162.4 141.9 119.5 98.1 172.7 12.2 172.7 171.7 158.7 137.4 116.1 94.8 57 179.7 10.9 179.7 179.7 169.6 149.6 126.6 105.2 172.4 12.2 172.4 172.4 162.0 140.7 119.4 98.1 77 235.4 12.0 123.5 99.5 75.6 - - - 225.5 13.3 120.3 96.6 72.9 - - ­72 218.3 11.7 155.9 132.0 108.0 84.1 - - 208.3 12.9 152.3 128.6 105.0 81.3 - ­67 201.2 11.3 188.3 164.4 140.5 116.5 92.6 - 191.1 12.6 184.4 160.7 137.0 113.4 89.7 ­62 185.4 11.1 185.4 185.4 173.4 151.3 125.5 101.6 177.0 12.3 177.0 177.0 169.9 146.2 122.6 98.9 57 184.4 11.0 184.4 184.4 181.0 160.1 133.2 109.2 176.6 12.3 176.6 176.6 173.5 149.8 126.1 102.4 72 221.3 11.3 165.2 139.4 113.7 88.0 - - 213.7 13.6 165.8 140.1 114.5 88.8 - ­67 204.0 11.0 197.5 174.0 147.8 122.0 96.3 - 196.0 13.3 192.7 175.1 149.4 123.8 98.1 ­62 187.9 10.7 187.9 187.9 181.9 157.1 130.4 104.7 181.5 13.0 181.5 181.5 178.0 152.4 126.7 101.1 57 186.8 10.6 186.8 186.8 185.2 161.0 133.7 108.0 181.2 13.0 181.2 181.2 179.6 153.9 128.3 102.6 72 224.2 10.9 174.4 146.9 119.4 91.8 - - 219.0 14.3 179.2 151.6 123.9 96.3 - ­67 206.7 10.6 206.7 183.6 155.1 127.6 100.0 - 201.0 14.0 201.0 189.4 161.8 134.1 106.5 ­62 190.4 10.3 190.4 190.4 190.4 162.8 135.3 107.8 186.1 13.7 186.1 186.1 186.1 158.5 130.9 103.2 57 189.3 10.3 189.3 189.3 189.3 161.8 134.3 106.7 185.7 13.7 185.7 185.7 185.7 158.1 130.5 102.9
77 205.8 14.4 98.3 79.5 60.6 - - - 195.5 15.9 95.5 76.6 57.7 - - ­72 189.3 14.0 125.7 106.8 87.9 69.1 - - 179.9 15.7 122.5 103.6 84.7 65.9 - ­67 172.8 13.7 153.0 134.1 115.3 96.4 77.5 - 164.3 15.4 149.5 130.7 111.8 92.9 74.0 ­62 161.0 13.5 161.0 161.0 143.6 124.7 105.9 87.0 153.2 15.2 153.2 153.2 139.8 120.9 102.0 83.1 57 161.3 13.5 161.3 161.3 143.1 124.3 105.4 86.6 154.3 15.2 154.3 154.3 136.3 117.4 98.5 79.6 77 210.7 14.4 107.7 86.6 65.4 - - - 199.9 16.0 107.5 83.6 62.4 - - ­72 193.8 14.1 137.2 116.1 94.9 73.8 - - 183.9 15.8 134.0 112.8 91.6 70.4 - ­67 176.9 13.8 166.7 145.6 124.4 103.3 82.2 - 168.0 15.5 160.4 142.0 120.8 99.6 78.3 ­62 164.8 13.5 164.8 164.8 155.0 132.9 112.7 91.6 156.6 15.2 156.6 156.6 151.0 129.4 108.6 87.4 57 165.1 13.6 165.1 165.1 154.5 131.9 112.2 91.1 157.7 15.2 157.7 157.7 147.2 125.3 104.8 83.6 77 215.5 14.5 117.1 93.7 70.2 - - - 204.2 16.1 119.5 90.5 67.0 - - ­72 198.3 14.2 148.7 125.3 101.9 78.5 - - 187.9 15.8 145.4 121.9 98.4 74.9 - ­67 181.0 13.8 180.4 157.0 133.6 110.2 86.8 - 171.6 15.6 171.3 153.3 129.7 106.2 82.7 ­62 168.6 13.6 168.6 168.6 166.4 141.1 119.6 96.2 160.0 15.3 160.0 160.0 162.3 137.8 115.3 91.7 57 168.9 13.6 168.9 168.9 165.9 139.4 119.1 95.6 161.2 15.3 161.2 161.2 158.2 133.2 111.2 87.6 72 206.1 15.9 166.4 140.8 115.2 89.7 - - 192.5 16.7 159.1 133.4 107.7 82.0 - ­67 188.1 15.6 187.8 176.1 151.0 125.5 99.9 - 175.8 16.4 175.7 166.6 142.0 116.3 90.7 ­62 175.2 15.3 175.2 175.2 174.1 147.6 123.0 97.4 164.0 16.2 164.0 164.0 165.1 139.0 113.7 88.1 57 175.5 15.3 175.5 175.5 174.0 146.9 122.9 97.3 165.1 16.2 165.1 165.1 163.6 137.2 112.3 86.6 72 213.9 17.7 184.0 156.3 128.5 100.8 - - 197.2 17.6 172.7 144.9 117.0 89.2 - ­67 195.2 17.3 195.2 195.2 168.5 140.7 113.0 - 180.0 17.3 180.0 180.0 154.3 126.5 98.6 ­62 181.9 17.0 181.9 181.9 181.9 154.1 126.4 98.6 167.9 17.0 167.9 167.9 167.9 140.1 112.2 84.4 57 182.2 17.0 182.2 182.2 182.2 154.4 126.7 99.0 169.0 17.0 169.0 169.0 169.0 141.2 113.4 85.6
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
30 Johnson Controls Unitary Products
Page 31
505430-BTG-P-0316
YH-15/NH-15 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB (°F)
77 185.3 17.5 92.7 73.7 54.8 - - - 175.0 19.1 89.8 70.9 51.9 - - ­72 170.5 17.3 119.4 100.5 81.5 62.6 - - 161.1 18.9 116.2 97.3 78.4 59.4 - ­67 155.8 17.1 146.1 127.2 108.3 89.3 70.4 - 147.2 18.8 142.6 123.7 104.8 85.8 66.9 ­62 145.5 16.9 145.5 145.5 136.0 117.1 98.2 79.3 137.7 18.6 137.7 137.7 132.2 113.3 94.3 75.4 57 147.3 16.8 147.3 147.3 129.4 110.5 91.6 72.7 140.3 18.5 140.3 140.3 122.6 103.6 84.7 65.8 77 189.1 17.6 107.3 80.6 59.3 - - - 178.3 19.2 107.1 77.6 56.2 - - ­72 174.1 17.4 130.7 109.5 88.2 66.9 - - 164.2 19.1 127.5 106.2 84.8 63.5 - ­67 159.0 17.2 154.2 138.3 117.1 95.8 74.5 - 150.1 18.9 147.9 134.7 113.4 92.1 70.7 ­62 148.5 17.0 148.5 148.5 147.1 125.8 104.5 83.3 140.3 18.7 140.3 140.3 140.3 122.2 100.4 79.1 57 150.4 16.9 150.4 150.4 140.0 118.7 97.4 76.2 143.0 18.6 143.0 143.0 132.7 112.1 90.0 68.7 77 192.9 17.7 121.9 87.4 63.8 - - - 181.6 19.3 124.4 84.3 60.5 - - ­72 177.6 17.5 142.1 118.5 94.8 71.2 - - 167.3 19.2 138.8 115.0 91.3 67.6 - ­67 162.2 17.3 162.2 149.5 125.9 102.3 78.6 - 152.9 19.0 152.9 145.8 122.1 98.3 74.6 ­62 151.5 17.0 151.5 151.5 158.2 134.5 110.9 87.3 142.9 18.8 142.9 142.9 142.9 131.2 106.6 82.8 57 153.4 17.0 153.4 153.4 150.5 126.9 103.3 79.6 145.7 18.7 145.7 145.7 142.8 120.6 95.4 71.6 72 179.0 17.5 151.7 126.0 100.2 74.4 - - 165.5 18.3 144.4 118.5 92.7 66.8 - ­67 163.5 17.3 163.5 157.2 133.0 107.2 81.5 - 151.3 18.2 151.3 147.7 124.0 98.1 72.3 ­62 152.7 17.0 152.7 152.7 156.0 130.3 104.5 78.7 141.4 17.9 141.4 141.4 141.4 121.6 95.3 69.4 57 154.7 17.0 154.7 154.7 153.2 127.4 101.7 75.9 144.2 17.9 144.2 144.2 142.8 117.7 91.0 65.2 72 180.4 17.5 161.4 133.5 105.5 77.6 - - 163.7 17.4 150.1 122.1 94.1 66.0 - ­67 164.8 17.3 164.8 164.8 140.1 112.2 84.3 - 149.7 17.3 149.7 149.7 125.9 97.9 69.9 ­62 153.9 17.0 153.9 153.9 153.9 126.0 98.1 70.2 140.0 17.1 140.0 140.0 140.0 112.0 83.9 55.9 57 155.9 17.0 155.9 155.9 155.9 128.0 100.1 72.1 142.7 17.0 142.7 142.7 142.7 114.7 86.7 58.7
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
Johnson Controls Unitary Products 31
Page 32
505430-BTG-P-0316
YH-15/NH-20
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB (°F)
Total
Capacity
(MBh)
77 214.3 12.1 111.5 92.2 72.8 - - - 213.3 13.3 110.6 91.3 71.9 - - ­72 201.7 11.8 138.5 119.1 99.8 80.4 - - 199.0 13.0 137.0 117.6 98.3 78.9 - ­67 189.0 11.6 165.4 146.1 126.7 107.3 88.0 - 184.6 12.7 163.3 144.0 124.6 105.2 85.9 ­62 181.2 11.3 181.2 177.5 156.5 137.1 117.7 98.4 171.9 12.5 171.9 170.0 150.7 131.3 112.0 92.6 57 177.1 11.3 177.1 177.1 160.6 141.3 121.9 102.5 170.3 12.5 170.3 170.3 153.8 134.5 115.1 95.8 77 220.7 12.2 121.6 99.7 77.7 - - - 219.3 13.4 120.7 98.7 76.7 - - ­72 207.6 11.9 150.4 128.4 106.4 84.5 - - 204.6 13.1 148.8 126.8 104.9 82.9 - ­67 194.6 11.7 179.1 157.2 135.2 113.2 91.2 - 189.9 12.8 176.9 154.9 133.0 111.0 89.0 ­62 186.5 11.4 186.5 184.7 167.0 145.2 123.0 101.0 176.8 12.6 176.8 175.8 160.8 138.8 116.9 94.9 57 182.3 11.4 182.3 182.3 171.4 150.0 127.4 105.5 175.1 12.6 175.1 175.1 164.2 142.2 120.3 98.3 77 227.1 12.3 131.7 107.1 82.6 - - - 225.4 13.5 130.7 106.1 81.6 - - ­72 213.6 12.0 162.3 137.7 113.1 88.5 - - 210.2 13.2 160.6 136.0 111.5 86.9 - ­67 200.2 11.8 192.8 168.2 143.7 119.1 94.5 - 195.1 12.9 190.5 165.9 141.3 116.8 92.2 ­62 191.9 11.5 191.9 191.9 177.4 153.3 128.3 103.7 181.6 12.7 181.6 181.6 170.9 146.4 121.8 97.2 57 187.6 11.5 187.6 187.6 182.1 158.8 133.0 108.4 179.9 12.7 179.9 179.9 174.5 150.0 125.4 100.8 72 218.3 12.1 172.7 145.8 118.9 92.0 - - 214.0 13.3 170.8 143.9 117.0 90.1 - ­67 204.5 11.9 200.9 177.9 151.0 124.1 97.2 - 198.6 13.0 196.2 175.2 148.4 121.5 94.6 ­62 196.0 11.6 196.0 196.0 188.7 162.0 134.9 108.0 184.9 12.7 184.9 184.9 179.4 152.6 125.7 98.8 57 191.6 11.6 191.6 191.6 188.9 162.6 135.1 108.2 183.1 12.7 183.1 183.1 180.4 153.6 126.7 99.8 72 223.0 12.2 183.1 153.9 124.7 95.5 - - 217.7 13.4 180.9 151.7 122.6 93.4 - ­67 208.9 11.9 208.9 187.5 158.3 129.2 100.0 - 202.0 13.1 202.0 184.6 155.4 126.2 97.0 ­62 200.2 11.7 200.2 200.2 199.9 170.7 141.5 112.3 188.1 12.8 188.1 188.1 187.9 158.8 129.6 100.4 57 195.7 11.6 195.7 195.7 195.7 166.5 137.3 108.1 186.3 12.8 186.3 186.3 186.3 157.1 128.0 98.8
77 212.3 14.6 109.7 90.4 71.0 - - - 207.7 16.7 107.9 88.6 69.2 - - ­72 196.3 14.2 135.5 116.1 96.8 77.4 - - 191.8 16.2 133.6 114.2 94.9 75.5 - ­67 180.3 13.9 161.2 141.8 122.5 103.1 83.8 - 175.9 15.8 159.2 139.9 120.5 101.2 81.9 ­62 162.6 13.6 162.6 162.6 144.9 125.5 106.2 86.8 158.2 15.4 158.2 158.2 141.1 121.7 102.4 83.0 57 163.6 13.6 163.6 163.6 147.1 127.7 108.4 89.0 160.7 15.4 160.7 160.7 144.1 124.7 105.4 86.0 77 218.0 14.6 119.7 97.8 75.8 - - - 213.3 16.8 118.7 95.9 74.0 - - ­72 201.6 14.3 147.2 125.2 103.3 81.3 - - 197.0 16.3 145.3 123.3 101.4 79.4 - ­67 185.2 14.0 174.6 152.7 130.7 108.8 86.8 - 180.7 15.9 171.8 150.8 128.8 106.9 84.9 ­62 167.0 13.7 167.0 167.0 154.6 132.5 110.7 88.8 162.4 15.5 162.4 162.4 150.8 128.7 106.9 84.9 57 167.9 13.7 167.9 167.9 157.0 134.4 113.1 91.1 165.0 15.5 165.0 165.0 154.0 131.7 110.1 88.1 77 223.7 14.7 129.7 105.1 80.6 - - - 218.9 16.9 129.6 103.3 78.7 - - ­72 206.8 14.4 158.9 134.3 109.8 85.3 - - 202.1 16.4 157.0 132.5 107.9 83.4 - ­67 190.0 14.1 188.1 163.5 139.0 114.5 89.9 - 185.4 16.0 184.4 161.6 137.1 112.6 88.0 ­62 171.4 13.8 171.4 171.4 164.4 139.4 115.3 90.8 166.7 15.6 166.7 166.7 160.4 135.7 111.4 86.8 57 172.3 13.8 172.3 172.3 166.9 141.1 117.8 93.3 169.3 15.6 169.3 169.3 163.8 138.7 114.8 90.2 72 209.6 14.5 168.9 142.0 115.1 88.3 - - 205.1 16.5 167.0 140.1 113.2 86.4 - ­67 192.6 14.2 191.6 172.6 145.7 118.9 92.0 - 188.1 16.0 187.6 170.7 143.9 117.0 90.2 ­62 173.7 13.9 173.7 173.7 170.2 143.1 116.5 89.6 169.1 15.6 169.1 169.1 166.0 139.0 112.2 85.4 57 174.7 13.9 174.7 174.7 172.0 144.5 118.2 91.4 171.8 15.6 171.8 171.8 169.0 141.9 115.3 88.5 72 212.4 14.5 178.8 149.6 120.4 91.3 - - 208.0 16.5 176.9 147.8 118.6 89.4 - ­67 195.1 14.2 195.1 181.7 152.5 123.3 94.1 - 190.8 16.1 190.8 179.8 150.7 121.5 92.3 ­62 176.0 13.9 176.0 176.0 176.0 146.8 117.6 88.4 171.5 15.7 171.5 171.5 171.5 142.3 113.1 84.0 57 177.0 13.9 177.0 177.0 177.0 147.8 118.6 89.5 174.2 15.6 174.2 174.2 174.2 145.0 115.9 86.7
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
32 Johnson Controls Unitary Products
Page 33
505430-BTG-P-0316
YH-15/NH-20 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB (°F)
77 203.2 18.8 106.1 86.7 67.4 - - - 198.7 21.0 104.2 84.9 65.6 - - ­72 187.4 18.3 131.7 112.3 93.0 73.7 - - 182.9 20.3 129.8 110.4 91.1 71.8 - ­67 171.6 17.7 157.3 137.9 118.6 99.3 79.9 - 167.2 19.6 155.3 136.0 116.7 97.3 78.0 ­62 153.7 17.2 153.7 153.7 137.3 117.9 98.6 79.3 149.3 19.0 149.3 149.3 133.5 114.1 94.8 75.5 57 157.8 17.1 157.8 157.8 141.1 121.7 102.4 83.0 154.9 18.9 154.9 154.9 138.0 118.7 99.4 80.1 77 208.6 19.0 117.7 94.1 72.1 - - - 204.0 21.1 116.8 92.2 70.3 - - ­72 192.4 18.4 143.4 121.4 99.5 77.6 - - 187.8 20.4 141.5 119.6 97.6 75.7 - ­67 176.2 17.8 169.0 148.8 126.9 105.0 83.0 - 171.7 19.7 166.2 146.9 125.0 103.0 81.1 ­62 157.8 17.3 157.8 157.8 146.9 124.9 103.0 81.1 153.3 19.1 153.3 153.3 143.0 121.2 99.1 77.2 57 162.0 17.2 162.0 162.0 150.9 129.0 107.0 85.1 159.1 19.0 159.1 159.1 147.9 126.3 104.0 82.1 77 214.1 19.1 129.4 101.4 76.8 - - - 209.3 21.2 129.3 99.5 74.9 - - ­72 197.4 18.5 155.1 130.6 106.0 81.5 - - 192.8 20.5 153.2 128.7 104.1 79.6 - ­67 180.8 17.9 180.8 159.7 135.2 110.7 86.1 - 176.2 19.8 176.2 157.8 133.3 108.8 84.2 ­62 162.0 17.4 162.0 162.0 156.5 131.9 107.4 82.8 157.3 19.2 157.3 157.3 152.5 128.2 103.4 78.9 57 166.3 17.3 166.3 166.3 160.8 136.3 111.7 87.2 163.2 19.1 163.2 163.2 157.8 133.8 108.7 84.1 72 200.5 18.5 165.1 138.2 111.4 84.5 - - 195.9 20.5 163.2 136.3 109.5 82.6 - ­67 183.6 17.9 183.6 168.9 142.0 115.2 88.3 - 179.1 19.7 179.1 167.0 140.2 113.3 86.5 ­62 164.5 17.4 164.5 164.5 161.7 134.9 108.0 81.2 159.9 19.2 159.9 159.9 157.5 130.8 103.8 77.0 57 168.8 17.3 168.8 168.8 166.1 139.3 112.4 85.6 165.9 19.0 165.9 165.9 163.2 136.7 109.5 82.7 72 203.6 18.5 175.0 145.9 116.7 87.6 - - 199.1 20.4 173.1 144.0 114.9 85.7 - ­67 186.4 17.9 186.4 178.0 148.8 119.7 90.5 - 182.0 19.7 182.0 176.2 147.0 117.9 88.7 ­62 167.0 17.4 167.0 167.0 167.0 137.8 108.7 79.5 162.5 19.2 162.5 162.5 162.5 133.3 104.2 75.0 57 171.4 17.3 171.4 171.4 171.4 142.3 113.1 83.9 168.6 19.0 168.6 168.6 168.6 139.5 110.3 81.2
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
Johnson Controls Unitary Products 33
Page 34
505430-BTG-P-0316
YJ-15 / Two NH-07
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB (°F)
Total
Capacity
(MBh)
77 216.0 12.0 105.9 88.7 71.5 - - - 208.8 13.2 103.4 86.2 69.0 - - ­72 200.4 11.7 130.4 113.2 96.0 78.8 - - 194.2 12.9 128.0 110.9 93.7 76.5 - ­67 184.8 11.4 154.8 137.7 120.5 103.3 86.1 - 179.6 12.6 152.7 135.5 118.3 101.2 84.0 ­62 173.1 11.2 173.1 164.2 147.0 129.8 112.6 95.4 165.4 12.4 165.4 161.0 143.8 126.6 109.4 92.3 57 165.6 11.1 165.6 165.6 150.2 133.0 115.8 98.6 162.3 12.3 162.3 162.3 147.5 130.3 113.1 95.9 77 222.3 12.1 114.8 95.5 76.2 - - - 215.7 13.2 112.2 93.0 73.7 - - ­72 206.2 11.8 140.8 121.5 102.3 83.0 - - 200.5 13.0 138.5 119.3 100.0 80.8 - ­67 190.2 11.5 166.9 147.6 128.3 109.0 89.8 - 185.4 12.7 164.9 145.6 126.3 107.1 87.8 ­62 178.1 11.2 178.1 173.7 156.5 137.8 118.0 98.7 170.8 12.4 170.8 168.6 153.5 134.2 115.0 95.7 57 170.4 11.2 170.4 170.4 159.9 141.5 121.4 102.1 167.6 12.4 167.6 167.6 157.4 138.2 118.9 99.6 77 228.6 12.1 123.6 102.2 80.9 - - - 222.5 13.3 121.1 99.7 78.4 - - ­72 212.1 11.9 151.3 129.9 108.5 87.1 - - 206.9 13.1 149.0 127.7 106.4 85.0 - ­67 195.6 11.6 178.9 157.6 136.2 114.8 93.4 - 191.3 12.8 177.0 155.7 134.3 113.0 91.6 ­62 183.2 11.3 183.2 183.2 166.1 145.8 123.4 102.0 176.2 12.5 176.2 176.2 163.2 141.9 120.5 99.2 57 175.2 11.3 175.2 175.2 169.7 149.9 127.0 105.6 172.9 12.5 172.9 172.9 167.4 146.0 124.7 103.3 72 216.4 11.9 159.1 136.1 113.1 90.1 - - 209.8 13.1 156.5 133.5 110.6 87.6 - ­67 199.6 11.6 188.8 164.9 141.9 118.9 95.9 - 193.9 12.8 185.6 162.6 139.7 116.7 93.7 ­62 186.9 11.4 186.9 186.9 173.4 150.9 127.4 104.4 178.7 12.6 178.7 178.7 169.7 146.7 123.8 100.8 57 178.8 11.3 178.8 178.8 176.1 153.9 130.1 107.1 175.3 12.5 175.3 175.3 172.5 149.6 126.6 103.7 72 220.7 12.0 166.9 142.3 117.7 93.0 - - 212.6 13.2 163.9 139.3 114.8 90.2 - ­67 203.5 11.7 198.6 172.3 147.7 123.0 98.4 - 196.6 12.9 194.1 169.5 145.0 120.4 95.8 ­62 190.6 11.4 190.6 190.6 180.6 156.0 131.4 106.8 181.1 12.6 181.1 181.1 176.1 151.6 127.0 102.4 57 182.4 11.4 182.4 182.4 182.4 157.8 133.2 108.6 177.7 12.6 177.7 177.7 177.7 153.1 128.5 104.0
77 201.7 14.3 100.9 83.7 66.6 - - - 197.4 16.0 98.8 81.6 64.5 - - ­72 188.0 14.1 125.7 108.5 91.4 74.2 - - 183.8 15.7 123.8 106.6 89.4 72.3 - ­67 174.3 13.8 150.5 133.4 116.2 99.1 81.9 - 170.2 15.4 148.7 131.6 114.4 97.2 80.0 ­62 157.8 13.5 157.8 157.8 140.6 123.4 106.3 89.1 156.2 15.2 156.2 156.2 139.1 121.9 104.8 87.6 57 159.0 13.5 159.0 159.0 144.7 127.6 110.4 93.3 155.4 15.2 155.4 155.4 140.6 123.4 106.2 89.1 77 209.0 14.4 109.7 90.5 71.2 - - - 204.0 16.1 107.4 88.2 69.0 - - ­72 194.9 14.2 136.3 117.0 97.8 78.6 - - 189.9 15.8 134.1 114.9 95.7 76.4 - ­67 180.7 13.9 162.8 143.6 124.4 105.1 85.9 - 175.8 15.5 160.9 141.6 122.4 103.1 83.9 ­62 163.5 13.6 163.5 163.5 150.5 130.7 112.0 92.7 161.4 15.3 161.4 161.4 148.8 129.3 110.4 91.1 57 164.8 13.6 164.8 164.8 154.9 134.8 116.4 97.2 160.6 15.3 160.6 160.6 150.4 130.8 111.9 92.7 77 216.4 14.5 118.5 97.2 75.9 - - - 210.6 16.2 116.1 94.8 73.5 - - ­72 201.7 14.2 146.8 125.5 104.2 82.9 - - 196.1 15.9 144.5 123.2 101.9 80.6 - ­67 187.0 14.0 175.1 153.8 132.5 111.2 89.9 - 181.5 15.6 173.0 151.7 130.4 109.1 87.8 ­62 169.3 13.7 169.3 169.3 160.3 137.9 117.7 96.4 166.6 15.4 166.6 166.6 158.6 136.7 116.0 94.7 57 170.5 13.7 170.5 170.5 165.0 142.1 122.4 101.1 165.8 15.3 165.8 165.8 160.2 138.1 117.6 96.3 72 203.1 14.3 153.9 131.0 108.0 85.1 - - 197.7 15.9 151.6 128.7 105.8 83.0 - ­67 188.3 14.0 182.4 160.3 137.4 114.5 91.6 - 183.1 15.7 178.8 158.3 135.4 112.5 89.6 ­62 170.5 13.8 170.5 170.5 166.0 142.5 120.2 97.2 168.0 15.4 168.0 168.0 164.0 140.9 118.2 95.4 57 171.7 13.7 171.7 171.7 169.0 145.3 123.2 100.2 167.2 15.4 167.2 167.2 164.4 141.1 118.7 95.8 72 204.5 14.3 160.9 136.4 111.9 87.4 - - 199.4 16.0 158.7 134.2 109.8 85.3 - ­67 189.6 14.1 189.6 166.8 142.3 117.8 93.2 - 184.7 15.7 184.7 164.9 140.4 115.9 91.4 ­62 171.7 13.8 171.7 171.7 171.7 147.1 122.6 98.1 169.5 15.5 169.5 169.5 169.5 145.0 120.5 96.1 57 173.0 13.8 173.0 173.0 173.0 148.4 123.9 99.4 168.6 15.4 168.6 168.6 168.6 144.1 119.7 95.2
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
34 Johnson Controls Unitary Products
Page 35
505430-BTG-P-0316
YJ-15 / Two NH-07 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB (°F)
77 193.0 17.7 96.7 79.6 62.4 - - - 188.7 19.3 94.6 77.5 60.3 - - ­72 179.5 17.4 121.8 104.6 87.5 70.3 - - 175.3 19.0 119.9 102.7 85.5 68.3 - ­67 166.0 17.1 146.9 129.7 112.6 95.4 78.2 - 161.9 18.7 145.1 127.9 110.7 93.5 76.4 ­62 154.6 16.8 154.6 154.6 137.6 120.4 103.3 86.1 152.9 18.5 152.9 152.9 136.1 118.9 101.7 84.6 57 151.8 16.8 151.8 151.8 136.4 119.2 102.1 84.9 148.2 18.4 148.2 148.2 132.2 115.1 97.9 80.7 77 198.9 17.8 105.2 86.0 66.7 - - - 193.8 19.4 103.0 83.7 64.5 - - ­72 185.0 17.5 132.0 112.8 93.6 74.3 - - 180.0 19.1 129.9 110.7 91.5 72.2 - ­67 171.0 17.2 158.9 139.6 120.4 101.2 81.9 - 166.2 18.8 156.9 137.7 118.4 99.2 80.0 ­62 159.2 16.9 159.2 159.2 147.2 128.0 108.7 89.5 157.1 18.6 157.1 157.1 145.6 126.6 107.1 87.9 57 156.4 16.9 156.4 156.4 145.9 126.7 107.5 88.2 152.2 18.5 152.2 152.2 141.4 122.6 103.0 83.7 77 204.7 17.9 113.7 92.4 71.1 - - - 198.9 19.5 111.3 90.0 68.7 - - ­72 190.4 17.6 142.3 121.0 99.7 78.4 - - 184.8 19.2 140.0 118.7 97.4 76.1 - ­67 176.1 17.2 170.9 149.6 128.3 107.0 85.7 - 170.6 18.9 168.7 147.4 126.1 104.9 83.6 ­62 163.9 17.0 163.9 163.9 156.8 135.5 114.2 92.9 161.3 18.7 161.3 161.3 155.1 134.3 112.5 91.2 57 161.0 17.0 161.0 161.0 155.4 134.2 112.9 91.6 156.2 18.6 156.2 156.2 150.7 130.2 108.1 86.8 72 192.4 17.6 149.4 126.5 103.6 80.8 - - 187.0 19.3 147.1 124.3 101.4 78.6 - ­67 177.9 17.3 175.3 156.2 133.4 110.5 87.7 - 172.7 18.9 171.7 154.2 131.4 108.5 85.7 ­62 165.6 17.1 165.6 165.6 162.1 139.2 116.3 93.5 163.2 18.7 163.2 163.2 160.1 137.5 114.4 91.6 57 162.6 17.0 162.6 162.6 159.9 137.0 114.1 91.3 158.1 18.7 158.1 158.1 155.3 132.9 109.6 86.8 72 194.3 17.7 156.5 132.0 107.6 83.2 - - 189.2 19.3 154.2 129.9 105.5 81.1 - ­67 179.7 17.4 179.7 162.9 138.5 114.1 89.6 - 174.7 19.0 174.7 161.0 136.6 112.2 87.8 ­62 167.3 17.1 167.3 167.3 167.3 142.9 118.4 94.0 165.1 18.8 165.1 165.1 165.1 140.7 116.3 92.0 57 164.3 17.1 164.3 164.3 164.3 139.8 115.4 91.0 159.9 18.7 159.9 159.9 159.9 135.6 111.2 86.8
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
Johnson Controls Unitary Products 35
Page 36
505430-BTG-P-0316
YJ-15 / Two NH-10
Air on
Evaporator Coil
CFM
WB (°F)
6000
7000
8000
9000
10000
6000
7000
8000
9000
10000
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
90 85 80 75 70 65 90 85 80 75 70 65
Return Dry Bulb (°F) Return Dry Bulb (°F)
75°F 85°F
77 241.0 12.0 121.2 97.8 74.3 - - - 237.1 13.2 119.7 96.2 72.6 - - ­72 222.0 11.7 154.8 131.4 107.9 84.4 - - 219.2 12.9 153.8 130.2 106.7 83.1 - ­67 203.0 11.4 188.4 165.0 141.5 118.0 94.5 - 201.4 12.6 187.8 164.2 140.7 117.1 93.6 ­62 191.6 11.2 191.6 191.6 168.1 144.6 121.1 97.6 188.1 12.3 188.1 187.8 164.3 140.7 117.2 93.6 57 189.3 11.2 189.3 189.5 166.0 142.6 119.1 95.6 189.2 12.4 189.2 188.9 165.3 141.8 118.2 94.7 77 247.3 12.1 136.7 106.3 79.7 - - - 242.9 13.3 135.8 104.6 78.0 - - ­72 227.8 11.8 168.9 142.3 115.8 89.2 - - 224.6 13.0 167.7 141.1 114.5 87.9 - ­67 208.3 11.5 201.0 178.4 151.8 125.3 98.7 - 206.4 12.6 199.5 177.6 151.0 124.4 97.8 ­62 196.6 11.2 196.6 196.6 180.4 153.4 127.3 100.8 192.7 12.4 192.7 192.6 176.3 149.8 123.2 96.6 57 194.3 11.3 194.3 194.4 178.2 152.5 125.1 98.5 193.9 12.5 193.9 193.7 177.5 150.9 124.3 97.7 77 253.6 12.2 152.2 114.8 85.1 - - - 248.7 13.3 151.8 112.9 83.3 - - ­72 233.6 11.9 182.9 153.3 123.7 94.1 - - 230.0 13.0 181.6 151.9 122.3 92.7 - ­67 213.6 11.5 213.6 191.8 162.2 132.6 103.0 - 211.3 12.7 211.3 191.0 161.3 131.7 102.1 ­62 201.6 11.3 201.6 201.6 192.7 162.3 133.5 103.9 197.3 12.5 197.3 197.3 188.4 158.8 129.2 99.6 57 199.3 11.4 199.3 199.3 190.3 162.5 131.1 101.5 198.5 12.5 198.5 198.5 189.6 160.0 130.4 100.8 72 238.5 11.9 193.5 161.5 129.6 97.6 - - 234.0 13.1 192.0 160.0 128.1 96.1 - ­67 218.1 11.6 218.1 201.9 169.9 138.0 106.1 - 215.0 12.8 215.0 200.9 168.9 136.9 105.0 ­62 205.8 11.4 205.8 205.8 201.3 169.0 137.4 105.5 200.7 12.5 200.7 200.7 196.3 164.3 132.3 100.3 57 203.4 11.4 203.4 203.4 199.0 167.9 135.1 103.1 201.9 12.6 201.9 201.9 197.5 165.5 133.5 101.6 72 243.3 12.0 204.1 169.8 135.5 101.2 - - 238.0 13.1 202.5 168.1 133.8 99.5 - ­67 222.5 11.7 222.5 212.0 177.7 143.4 109.1 - 218.6 12.8 218.6 210.8 176.5 142.1 107.8 ­62 210.0 11.4 210.0 210.0 210.0 175.7 141.4 107.1 204.1 12.6 204.1 204.1 204.1 169.8 135.4 101.1 57 207.6 11.5 207.6 207.6 207.6 173.3 139.0 104.7 205.4 12.6 205.4 205.4 205.4 171.0 136.7 102.4
95°F 105°F
77 233.2 14.3 118.3 94.6 71.0 - - - 229.8 15.1 117.0 93.3 69.7 - - ­72 216.5 14.0 152.7 129.1 105.5 81.9 - - 213.6 14.8 151.7 128.1 104.5 80.8 - ­67 199.8 13.7 187.1 163.5 139.9 116.3 92.7 - 197.4 14.5 186.4 162.8 139.2 115.6 92.0 ­62 184.5 13.4 184.5 184.1 160.5 136.8 113.2 89.6 185.1 14.2 185.1 183.8 160.2 136.5 112.9 89.3 57 189.1 13.5 189.1 188.2 164.6 141.0 117.4 93.8 187.3 14.3 187.3 185.9 162.2 138.6 115.0 91.4 77 238.5 14.4 134.9 102.9 76.3 - - - 233.4 15.8 135.0 101.2 74.6 - - ­72 221.5 14.1 166.5 139.8 113.2 86.6 - - 216.9 15.5 165.0 138.4 111.7 85.1 - ­67 204.4 13.8 198.1 176.8 150.2 123.6 97.0 - 200.5 15.2 195.0 175.5 148.9 122.3 95.6 ­62 188.8 13.5 188.8 188.5 172.3 146.1 119.0 92.4 187.9 14.9 187.9 187.3 171.3 144.9 118.1 91.5 57 193.4 13.6 193.4 193.0 176.7 149.3 123.5 96.9 190.3 14.9 190.3 189.5 173.6 146.5 120.3 93.7 77 243.9 14.5 151.5 111.1 81.5 - - - 237.0 16.4 153.0 109.1 79.5 - - ­72 226.4 14.2 180.2 150.6 121.0 91.4 - - 220.3 16.1 178.3 148.7 119.0 89.4 - ­67 209.0 13.9 209.0 190.1 160.5 130.9 101.3 - 203.6 15.8 203.6 188.2 158.6 129.0 99.3 ­62 193.0 13.6 193.0 193.0 184.1 155.3 124.9 95.2 190.8 15.5 190.8 190.8 182.5 153.3 123.2 93.6 57 197.8 13.7 197.8 197.8 188.9 157.5 129.6 100.0 193.2 15.5 193.2 193.2 184.9 154.4 125.6 96.0 72 229.5 14.2 190.6 158.6 126.6 94.5 - - 222.9 16.1 188.2 156.3 124.3 92.3 - ­67 211.8 13.9 211.8 199.9 167.9 135.9 103.9 - 206.0 15.8 206.0 197.0 165.6 133.6 101.7 ­62 195.6 13.7 195.6 195.6 191.2 159.6 127.2 95.2 193.1 15.5 193.1 193.1 188.9 157.1 124.9 93.0 57 200.5 13.7 200.5 200.5 196.0 163.1 132.0 100.0 195.5 15.5 195.5 195.5 191.3 158.9 127.4 95.4 72 232.6 14.3 200.9 166.5 132.1 97.7 - - 225.4 16.1 198.2 163.9 129.6 95.3 - ­67 214.7 14.0 214.7 209.6 175.2 140.8 106.5 - 208.3 15.8 208.3 205.8 172.6 138.3 104.0 ­62 198.3 13.7 198.3 198.3 198.3 163.9 129.5 95.1 195.3 15.5 195.3 195.3 195.3 161.0 126.7 92.4 57 203.2 13.8 203.2 203.2 203.2 168.8 134.4 100.0 197.7 15.5 197.7 197.7 197.7 163.4 129.1 94.8
Temperature of Air on Condenser Coil
1
Total
Capacity
(MBh)
1
(kW)
Total Input
Sensible Capacity (MBh)
2
1
36 Johnson Controls Unitary Products
Page 37
505430-BTG-P-0316
YJ-15 / Two NH-10 (Continued)
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
1
WB
(°F)
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
77 226.4 15.9 115.7 92.1 68.4 - - - 223.0 16.7 114.4 90.8 67.1 - - ­72 210.6 15.6 150.7 127.1 103.5 79.8 - - 207.7 16.4 149.7 126.1 102.5 78.8 - ­67 194.9 15.3 185.7 162.1 138.5 114.9 91.2 - 192.4 16.1 185.0 161.4 137.8 114.1 90.5 ­62 185.6 15.0 185.6 183.5 159.8 136.2 112.6 89.0 186.1 15.8 186.1 183.2 159.5 135.9 112.3 88.7 57 185.6 15.0 185.6 183.5 159.9 136.3 112.6 89.0 183.8 15.8 183.8 181.1 157.5 133.9 110.3 86.7 77 228.3 17.1 135.1 99.6 72.9 - - - 223.2 18.5 135.2 97.9 71.3 - - ­72 212.4 16.8 163.5 136.9 110.3 83.6 - - 207.9 18.2 162.0 135.4 108.8 82.1 - ­67 196.5 16.5 191.9 174.2 147.6 121.0 94.3 - 192.6 17.9 188.9 172.9 146.3 119.6 93.0 ­62 187.1 16.2 187.1 186.1 170.4 143.7 117.1 90.5 186.3 17.5 186.3 184.8 169.4 142.6 116.1 89.5 57 187.1 16.2 187.1 186.1 170.4 143.8 117.1 90.5 184.0 17.5 184.0 182.6 167.2 141.0 114.0 87.3 77 230.2 18.3 154.5 107.1 77.4 - - - 223.4 20.2 156.0 105.1 75.4 - - ­72 214.2 18.0 176.3 146.7 117.1 87.4 - - 208.1 19.9 174.4 144.7 115.1 85.5 - ­67 198.2 17.7 198.2 186.3 156.7 127.1 97.4 - 192.7 19.6 192.7 184.4 154.8 125.1 95.5 ­62 188.7 17.3 188.7 188.7 180.9 151.2 121.6 92.0 186.5 19.2 186.5 186.5 179.3 149.2 120.0 90.3 57 188.7 17.3 188.7 188.7 180.9 151.3 121.6 92.0 184.2 19.1 184.2 184.2 176.9 148.2 117.7 88.0 72 216.2 17.9 185.9 154.0 122.0 90.1 - - 209.6 19.8 183.6 151.7 119.8 87.9 - ­67 200.1 17.6 200.1 194.1 163.4 131.4 99.5 - 194.2 19.5 194.2 191.3 161.1 129.2 97.3 ­62 190.5 17.3 190.5 190.5 186.6 154.7 122.7 90.8 187.9 19.1 187.9 187.9 184.3 152.2 120.5 88.6 57 190.5 17.3 190.5 190.5 186.6 154.7 122.8 90.8 185.5 19.0 185.5 185.5 181.9 150.5 118.1 86.2 72 218.3 17.9 195.5 161.3 127.0 92.8 - - 211.1 19.7 192.8 158.6 124.5 90.3 - ­67 202.0 17.6 202.0 202.0 170.0 135.8 101.6 - 195.6 19.4 195.6 195.6 167.4 133.3 99.1 ­62 192.3 17.2 192.3 192.3 192.3 158.1 123.8 89.6 189.3 19.0 189.3 189.3 189.3 155.2 121.0 86.9 57 192.3 17.2 192.3 192.3 192.3 158.1 123.9 89.6 186.9 18.9 186.9 186.9 186.9 152.8 118.6 84.5
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
90 85 80 75 70 65 90 85 80 75 70 65
Return Dry Bulb (°F) Return Dry Bulb (°F)
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
1
Total
Capacity
(MBh)
1
Total Input (kW)
Sensible Capacity (MBh)
2
nameplate rated motor
1
Johnson Controls Unitary Products 37
Page 38
505430-BTG-P-0316
YJ-15/NJ-15
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB (°F)
Total
Capacity
(MBh)
77 208.6 11.7 106.3 87.7 69.0 - - - 205.9 13.0 103.7 84.9 66.2 - - ­72 198.3 11.4 132.6 113.9 95.3 76.6 - - 192.8 12.7 129.9 111.1 92.4 73.6 - ­67 188.0 11.0 158.8 140.2 121.5 102.9 84.2 - 179.7 12.4 156.1 137.4 118.6 99.9 81.1 ­62 170.5 10.9 170.5 170.5 152.4 133.8 115.1 96.5 166.3 12.2 166.3 166.3 150.1 131.4 112.6 93.9 57 177.8 11.0 177.8 177.8 161.5 142.9 124.2 105.6 172.3 12.2 172.3 172.3 155.9 137.1 118.4 99.6 77 217.2 11.7 117.1 95.9 74.6 - - - 213.0 13.0 114.0 92.6 71.2 - - ­72 206.4 11.4 145.5 124.2 102.9 81.6 - - 199.5 12.7 142.3 120.9 99.5 78.1 - ­67 195.7 11.1 173.8 152.5 131.2 110.0 88.7 - 186.0 12.5 170.5 149.1 127.7 106.3 84.9 ­62 177.6 10.9 177.6 177.6 164.6 144.0 122.0 100.8 172.0 12.2 172.0 172.0 161.7 140.3 118.9 97.5 57 185.1 11.0 185.1 185.1 174.5 153.9 131.9 110.6 178.3 12.3 178.3 178.3 167.8 146.5 125.1 103.7 77 225.8 11.8 128.0 104.0 80.1 - - - 220.1 13.1 124.4 100.3 76.3 - - ­72 214.6 11.4 158.4 134.5 110.5 86.6 - - 206.1 12.8 154.6 130.6 106.6 82.5 - ­67 203.4 11.1 188.9 164.9 141.0 117.0 93.1 - 192.2 12.5 184.9 160.9 136.8 112.8 88.8 ­62 184.6 11.0 184.6 184.6 176.9 154.2 129.0 105.1 177.8 12.3 177.8 177.8 173.2 149.1 125.1 101.1 57 192.4 11.1 192.4 192.4 187.4 165.0 139.5 115.6 184.2 12.4 184.2 184.2 179.8 155.8 131.7 107.7 72 214.6 11.5 167.9 142.4 116.8 91.2 - - 206.7 12.9 164.3 138.6 113.0 87.3 - ­67 203.4 11.2 196.2 174.5 149.0 123.4 97.8 - 192.7 12.6 189.0 170.7 145.0 119.3 93.7 ­62 184.6 11.1 184.6 184.6 180.7 155.8 129.6 104.0 178.3 12.4 178.3 178.3 176.0 150.3 124.6 98.9 57 192.4 11.1 192.4 192.4 189.9 165.1 138.8 113.2 184.7 12.4 184.7 184.7 182.5 156.8 131.2 105.5 72 214.6 11.6 177.4 150.3 123.1 95.9 - - 207.2 12.9 174.0 146.6 119.3 92.0 - ­67 203.5 11.3 203.5 184.1 157.0 129.8 102.6 - 193.2 12.6 193.2 180.5 153.2 125.9 98.6 ­62 184.6 11.1 184.6 184.6 184.6 157.4 130.2 103.0 178.7 12.4 178.7 178.7 178.7 151.4 124.1 96.8 57 192.5 11.2 192.5 192.5 192.5 165.3 138.1 110.9 185.2 12.5 185.2 185.2 185.2 157.9 130.6 103.3
77 203.1 14.3 101.0 82.1 63.3 - - - 189.1 16.0 95.4 76.6 57.9 - - ­72 187.3 14.0 127.2 108.4 89.5 70.7 - - 175.6 15.7 122.5 103.8 85.0 66.3 - ­67 171.5 13.7 153.5 134.6 115.8 96.9 78.1 - 162.1 15.5 149.7 130.9 112.2 93.5 74.7 ­62 162.0 13.5 162.0 162.0 147.9 129.0 110.2 91.3 153.3 15.3 153.3 153.3 141.3 122.5 103.8 85.0 57 166.8 13.5 166.8 166.8 150.2 131.4 112.5 93.7 156.8 15.2 156.8 156.8 145.7 126.9 108.2 89.5 77 208.8 14.3 110.9 89.4 67.9 - - - 195.1 16.0 108.5 84.0 62.7 - - ­72 192.5 14.1 139.0 117.6 96.1 74.6 - - 181.2 15.8 134.8 113.4 92.1 70.8 - ­67 176.2 13.8 167.2 145.7 124.2 102.7 81.2 - 167.3 15.5 161.0 142.8 121.5 100.2 78.8 ­62 166.5 13.5 166.5 166.5 158.7 136.5 115.7 94.2 158.2 15.3 158.2 158.2 153.0 131.3 110.3 89.0 57 171.4 13.6 171.4 171.4 161.2 139.0 118.2 96.7 161.8 15.3 161.8 161.8 157.8 136.1 115.1 93.8 77 214.4 14.4 120.8 96.7 72.5 - - - 201.1 16.1 121.6 91.4 67.4 - - ­72 197.7 14.2 150.9 126.7 102.6 78.5 - - 186.8 15.8 147.0 123.1 99.1 75.2 - ­67 181.0 13.9 180.9 156.8 132.7 108.5 84.4 - 172.4 15.6 172.4 154.8 130.8 106.9 83.0 ­62 171.0 13.6 171.0 171.0 169.5 144.0 121.2 97.1 163.0 15.4 163.0 163.0 164.7 140.1 116.8 92.9 57 176.1 13.7 176.1 176.1 172.2 146.5 123.9 99.8 166.8 15.4 166.8 166.8 169.9 145.2 122.0 98.1 72 198.8 14.2 160.7 134.9 109.1 83.3 - - 186.7 15.9 156.8 131.0 105.1 79.2 - ­67 182.0 13.9 181.9 166.9 141.1 115.3 89.5 - 172.4 15.6 172.4 162.0 138.7 112.8 86.9 ­62 171.9 13.7 171.9 171.9 171.2 144.7 119.6 93.8 163.0 15.4 163.0 163.0 163.8 137.6 112.1 86.2 57 177.0 13.7 177.0 177.0 175.1 148.5 123.5 97.7 166.7 15.4 166.7 166.7 168.3 142.0 116.5 90.6 72 199.8 14.3 170.5 143.0 115.6 88.2 - - 186.7 15.9 166.7 138.9 111.0 83.2 - ­67 183.0 14.0 183.0 176.9 149.5 122.0 94.6 - 172.3 15.7 172.3 169.3 146.5 118.7 90.9 ­62 172.9 13.7 172.9 172.9 172.9 145.4 118.0 90.6 162.9 15.5 162.9 162.9 162.9 135.1 107.3 79.5 57 178.0 13.8 178.0 178.0 178.0 150.5 123.1 95.6 166.7 15.4 166.7 166.7 166.7 138.8 111.0 83.2
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
38 Johnson Controls Unitary Products
Page 39
505430-BTG-P-0316
YJ-15/NJ-15 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB (°F)
77 175.1 17.7 89.8 71.1 52.5 - - - 161.0 19.4 84.1 65.6 47.1 - - ­72 163.9 17.4 117.8 99.2 80.6 61.9 - - 152.2 19.1 113.1 94.6 76.1 57.6 - ­67 152.8 17.2 145.9 127.3 108.6 90.0 71.4 - 143.4 18.9 142.1 123.6 105.1 86.6 68.0 ­62 144.6 17.1 144.6 144.6 134.7 116.0 97.4 78.8 135.8 18.8 135.8 135.8 128.1 109.5 91.0 72.5 57 146.8 17.0 146.8 146.8 141.1 122.5 103.9 85.2 136.8 18.7 136.8 136.8 136.6 118.0 99.5 81.0 77 181.4 17.7 106.1 78.6 57.4 - - - 167.8 19.4 103.6 73.2 52.2 - - ­72 169.9 17.5 130.5 109.3 88.1 66.9 - - 158.6 19.2 126.2 105.2 84.1 63.1 - ­67 158.3 17.2 154.9 140.0 118.8 97.6 76.4 - 149.4 18.9 148.7 137.1 116.1 95.1 74.0 ­62 149.8 17.1 149.8 149.8 147.3 126.1 104.9 83.7 141.5 18.9 141.5 141.5 141.5 120.9 99.5 78.5 57 152.1 17.0 152.1 152.1 154.3 133.1 112.0 90.8 142.5 18.7 142.5 142.5 142.5 130.2 108.8 87.8 77 187.8 17.8 122.4 86.1 62.3 - - - 174.5 19.4 123.1 80.8 57.2 - - ­72 175.8 17.5 143.1 119.4 95.6 71.9 - - 164.9 19.2 139.2 115.7 92.2 68.6 - ­67 163.9 17.3 163.9 152.7 129.0 105.2 81.5 - 155.3 19.0 155.3 150.7 127.1 103.6 80.0 ­62 155.1 17.2 155.1 155.1 159.9 136.1 112.4 88.7 147.1 18.9 147.1 147.1 147.1 132.2 108.0 84.4 57 157.5 17.1 157.5 157.5 167.5 143.8 120.1 96.3 148.2 18.8 148.2 148.2 148.2 142.4 118.1 94.6 72 174.6 17.6 153.0 127.0 101.1 75.1 - - 162.6 19.2 149.2 123.1 97.0 71.0 - ­67 162.8 17.3 162.8 157.2 136.3 110.3 84.3 - 153.2 19.0 153.2 152.4 133.9 107.8 81.8 ­62 154.0 17.2 154.0 154.0 156.4 130.5 104.5 78.5 145.1 19.0 145.1 145.1 145.1 123.3 96.9 70.9 57 156.4 17.1 156.4 156.4 161.4 135.5 109.5 83.5 146.1 18.8 146.1 146.1 146.1 128.9 102.5 76.4 72 173.5 17.6 162.9 134.7 106.5 78.3 - - 160.3 19.3 159.1 130.5 101.9 73.3 - ­67 161.7 17.3 161.7 161.7 143.6 115.4 87.2 - 151.0 19.0 151.0 151.0 140.6 112.0 83.5 ­62 153.0 17.2 153.0 153.0 153.0 124.8 96.6 68.4 143.0 19.0 143.0 143.0 143.0 114.5 85.9 57.3 57 155.4 17.1 155.4 155.4 155.4 127.2 99.0 70.8 144.0 18.8 144.0 144.0 144.0 115.5 86.9 58.3
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
Johnson Controls Unitary Products 39
Page 40
505430-BTG-P-0316
YJ-15/NJ-20
Air on
Evaporator Coil
CFM
WB (°F)
77 213.8 12.1 109.1 89.8 70.5 - - - 212.3 13.3 108.9 89.6 70.3 - - ­72 201.0 11.8 136.0 116.7 97.4 78.1 - - 197.9 13.0 134.7 115.4 96.1 76.9 - -
4500
67 188.1 11.5 162.8 143.5 124.2 104.9 85.6 - 183.4 12.7 160.6 141.3 122.0 102.7 83.4 ­62 171.4 11.3 171.4 168.3 149.0 129.7 110.4 91.1 166.5 12.5 166.5 164.9 145.6 126.3 107.0 87.7 57 175.2 11.3 175.2 175.2 157.4 138.1 118.8 99.5 168.8 12.5 168.8 168.8 151.2 131.9 112.6 93.3 77 220.6 12.2 120.2 98.1 76.0 - - - 219.0 13.4 120.0 97.9 75.8 - - ­72 207.3 11.9 149.2 127.0 104.9 82.8 - - 204.1 13.1 147.9 125.8 103.7 81.6 - -
5250
67 194.1 11.6 178.1 156.0 133.8 111.7 89.6 - 189.2 12.8 175.9 153.7 131.6 109.5 87.4 ­62 176.8 11.4 176.8 175.2 160.5 138.7 116.3 94.2 171.8 12.6 171.8 170.9 157.1 134.9 112.8 90.7 57 180.7 11.4 180.7 180.7 169.6 148.2 125.4 103.2 174.1 12.5 174.1 174.1 163.1 141.0 118.8 96.7 77 227.3 12.3 131.3 106.4 81.5 - - - 225.7 13.5 131.2 106.3 81.3 - - ­72 213.6 12.0 162.3 137.4 112.5 87.5 - - 210.4 13.2 161.2 136.2 111.3 86.4 - -
6000
67 200.0 11.7 193.3 168.4 143.5 118.5 93.6 - 195.0 12.9 191.1 166.2 141.2 116.3 91.4 ­62 182.2 11.5 182.2 182.2 172.1 147.8 122.2 97.3 177.0 12.7 177.0 177.0 168.5 143.6 118.7 93.7 57 186.3 11.5 186.3 186.3 181.8 158.2 132.0 107.0 179.5 12.6 179.5 179.5 175.0 150.0 125.1 100.2 72 217.5 12.1 172.8 145.5 118.2 90.9 - - 213.5 13.3 171.4 144.1 116.9 89.6 - -
6750
67 203.6 11.8 200.3 178.1 150.8 123.5 96.2 - 197.9 13.0 196.0 175.6 148.3 121.1 93.8 ­62 185.5 11.6 185.5 185.5 180.5 153.5 125.9 98.6 179.7 12.7 179.7 179.7 175.4 148.2 120.9 93.6 57 189.6 11.5 189.6 189.6 187.4 160.8 132.8 105.6 182.2 12.7 182.2 182.2 179.9 152.7 125.4 98.1 72 221.4 12.2 183.2 153.5 123.9 94.3 - - 216.7 13.3 181.7 152.1 122.5 92.8 - -
7500
67 207.3 11.9 207.3 187.7 158.1 128.4 98.8 - 200.9 13.0 200.9 185.0 155.4 125.8 96.2 ­62 188.8 11.6 188.8 188.8 188.8 159.2 129.5 99.9 182.4 12.8 182.4 182.4 182.4 152.8 123.1 93.5 57 193.0 11.6 193.0 193.0 193.0 163.4 133.7 104.1 184.9 12.8 184.9 184.9 184.9 155.3 125.7 96.1
77 210.9 14.5 108.6 89.3 70.0 - - - 205.7 16.4 106.6 87.3 68.0 - - ­72 194.8 14.2 133.5 114.2 94.9 75.7 - - 190.4 16.0 131.6 112.3 93.1 73.8 - -
4500
67 178.7 13.9 158.4 139.1 119.8 100.6 81.3 - 175.1 15.6 156.7 137.4 118.1 98.9 79.6 ­62 161.6 13.6 161.6 161.5 142.2 122.9 103.6 84.4 157.3 15.3 157.3 157.2 139.1 119.9 100.6 81.3 57 162.4 13.6 162.4 162.4 144.9 125.7 106.4 87.1 159.4 15.3 159.4 159.4 142.1 122.8 103.6 84.3 77 217.5 14.6 119.8 97.7 75.6 - - - 212.5 16.5 118.4 95.7 73.6 - - ­72 200.9 14.3 146.7 124.6 102.5 80.4 - - 196.6 16.1 144.9 122.8 100.7 78.6 - -
5250
67 184.4 14.0 173.6 151.5 129.4 107.3 85.2 - 180.8 15.8 171.3 149.9 127.8 105.7 83.6 ­62 166.7 13.7 166.7 166.7 153.6 131.2 109.4 87.2 162.5 15.4 162.5 162.4 150.5 128.3 106.3 84.2 57 167.5 13.7 167.5 167.5 156.5 133.8 112.3 90.2 164.7 15.4 164.7 164.7 153.7 131.3 109.5 87.4 77 224.2 14.7 131.1 106.2 81.2 - - - 219.2 16.6 130.3 104.1 79.1 - - ­72 207.1 14.4 160.0 135.0 110.1 85.2 - - 202.9 16.2 158.2 133.2 108.3 83.4 - -
6000
67 190.0 14.1 188.9 163.9 139.0 114.1 89.1 - 186.6 15.9 186.0 162.4 137.5 112.5 87.6 ­62 171.8 13.8 171.8 171.8 164.9 139.4 115.1 90.1 167.6 15.5 167.6 167.6 161.9 136.7 112.0 87.1 57 172.7 13.8 172.7 172.7 168.1 141.8 118.3 93.3 169.9 15.5 169.9 169.9 165.3 139.7 115.5 90.6 72 209.6 14.4 170.1 142.8 115.6 88.3 - - 205.0 16.3 168.2 140.9 113.7 86.4 - -
6750
67 192.3 14.2 191.7 173.1 145.9 118.6 91.4 - 188.5 15.9 188.2 171.5 144.3 117.0 89.7 ­62 173.9 13.9 173.9 173.9 170.4 142.9 115.9 88.7 169.4 15.5 169.4 169.4 166.5 139.1 112.0 84.8 57 174.7 13.9 174.7 174.7 172.4 144.5 117.9 90.7 171.7 15.5 171.7 171.7 169.4 141.8 114.9 87.6 72 212.0 14.5 180.2 150.6 121.0 91.4 - - 207.1 16.3 178.2 148.6 119.0 89.4 - -
7500
67 194.5 14.2 194.5 182.3 152.8 123.2 93.6 - 190.5 15.9 190.5 180.6 151.0 121.5 91.9 ­62 175.9 13.9 175.9 175.9 175.9 146.3 116.8 87.2 171.2 15.5 171.2 171.2 171.2 141.6 112.0 82.4 57 176.8 13.9 176.8 176.8 176.8 147.2 117.6 88.0 173.5 15.5 173.5 173.5 173.5 143.9 114.3 84.7
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
90 85 80 75 70 65 90 85 80 75 70 65
Return Dry Bulb (°F) Return Dry Bulb (°F)
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
1
Total
Capacity
(MBh)
1
(kW)
Total Input
Sensible Capacity (MBh)
2
1
40 Johnson Controls Unitary Products
Page 41
505430-BTG-P-0316
YJ-15/NJ-20 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB (°F)
77 200.6 18.3 104.5 85.3 66.0 - - - 195.5 20.2 102.5 83.2 64.0 - - ­72 186.0 17.8 129.7 110.5 91.2 72.0 - - 181.6 19.6 127.9 108.6 89.4 70.1 - ­67 171.4 17.4 154.9 135.7 116.4 97.2 77.9 - 167.7 19.1 153.2 134.0 114.7 95.5 76.3 ­62 153.0 16.9 153.0 153.0 136.1 116.8 97.6 78.3 148.7 18.5 148.7 148.7 133.0 113.8 94.5 75.3 57 156.4 16.9 156.4 156.4 139.2 120.0 100.7 81.5 153.5 18.5 153.5 153.5 136.4 117.1 97.9 78.7 77 207.4 18.4 117.0 93.6 71.5 - - - 202.4 20.4 115.6 91.6 69.5 - - ­72 192.3 18.0 143.0 120.9 98.9 76.8 - - 188.1 19.8 141.2 119.1 97.0 75.0 - ­67 177.2 17.5 169.0 148.3 126.2 104.1 82.0 - 173.7 19.2 166.7 146.6 124.6 102.5 80.4 ­62 158.2 17.0 158.2 158.2 147.5 125.4 103.3 81.2 154.0 18.7 154.0 154.0 144.4 122.5 100.2 78.2 57 161.8 17.0 161.8 161.8 150.9 128.8 106.7 84.6 158.9 18.7 158.9 158.9 148.1 126.3 103.9 81.9 77 214.3 18.6 129.6 102.0 77.1 - - - 209.4 20.5 128.8 99.9 75.0 - - ­72 198.7 18.1 156.3 131.4 106.5 81.6 - - 194.5 20.0 154.5 129.6 104.7 79.8 - ­67 183.1 17.6 183.1 160.9 135.9 111.0 86.1 - 179.7 19.4 179.7 159.3 134.4 109.5 84.6 ­62 163.5 17.1 163.5 163.5 158.8 133.9 109.0 84.1 159.3 18.8 159.3 159.3 155.8 131.2 106.0 81.1 57 167.1 17.1 167.1 167.1 162.6 137.6 112.7 87.8 164.4 18.8 164.4 164.4 159.8 135.5 110.0 85.1 72 200.5 18.1 166.3 139.0 111.8 84.5 - - 196.0 19.9 164.4 137.1 109.8 82.6 - ­67 184.7 17.6 184.7 169.9 142.6 115.4 88.1 - 181.0 19.4 181.0 168.3 141.0 113.8 86.5 ­62 164.9 17.1 164.9 164.9 162.6 135.4 108.1 80.8 160.4 18.8 160.4 160.4 158.7 131.6 104.2 76.9 57 168.6 17.1 168.6 168.6 166.3 139.1 111.8 84.6 165.6 18.8 165.6 165.6 163.3 136.4 108.8 81.5 72 202.3 18.1 176.2 146.6 117.0 87.4 - - 197.4 19.9 174.2 144.6 115.0 85.4 - ­67 186.4 17.6 186.4 178.9 149.3 119.7 90.1 - 182.3 19.3 182.3 177.2 147.6 118.0 88.4 ­62 166.4 17.1 166.4 166.4 166.4 136.8 107.2 77.6 161.6 18.7 161.6 161.6 161.6 132.0 102.4 72.8 57 170.1 17.1 170.1 170.1 170.1 140.5 110.9 81.3 166.8 18.7 166.8 166.8 166.8 137.2 107.6 78.0
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
90 85 80 75 70 65 90 85 80 75 70 65
Return Dry Bulb (°F) Return Dry Bulb (°F)
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
1
Total
Capacity
(MBh)
1
Total Input (kW)
Sensible Capacity (MBh)
2
nameplate rated motor
1
Johnson Controls Unitary Products 41
Page 42
505430-BTG-P-0316
YH-20/NH-20
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
6000
7000
8000
9000
10000
(°F)
Total
Capacity
WB
(MBh)
77 286.3 15.3 136.1 113.4 90.6 - - - 280.0 16.9 131.5 108.2 84.9 - - ­72 267.4 14.8 169.4 146.7 123.9 101.2 - - 260.2 16.5 166.3 143.0 119.7 96.4 - ­67 248.5 14.4 202.7 180.0 157.2 134.5 111.7 - 240.5 16.1 201.0 177.7 154.4 131.1 107.8 ­62 228.9 14.1 228.9 216.8 194.0 171.3 148.5 125.8 223.4 15.7 223.4 213.8 190.5 167.2 143.9 120.6 57 227.5 14.0 227.5 227.5 205.1 182.4 159.6 136.9 220.8 15.7 220.8 220.8 201.8 178.5 155.2 131.9 77 296.6 15.4 148.2 122.8 97.4 - - - 287.9 17.0 143.1 117.2 91.3 - - ­72 277.0 14.9 184.0 158.6 133.2 107.8 - - 267.6 16.6 180.5 154.5 128.6 102.7 - ­67 257.5 14.5 219.8 194.4 169.0 143.6 118.3 - 247.4 16.1 217.8 191.9 165.9 140.0 114.1 ­62 237.1 14.2 237.1 231.1 208.6 184.8 157.8 132.4 229.7 15.8 229.7 224.9 204.7 178.7 152.8 126.9 57 235.7 14.1 235.7 235.7 220.5 197.5 169.7 144.3 227.0 15.8 227.0 227.0 216.9 190.9 165.0 139.0 77 306.9 15.5 160.3 132.3 104.2 - - - 295.8 17.1 154.7 126.2 97.6 - - ­72 286.6 15.0 198.6 170.6 142.5 114.5 - - 275.0 16.7 194.7 166.1 137.5 108.9 - ­67 266.4 14.6 236.9 208.9 180.8 152.8 124.8 - 254.2 16.2 234.6 206.0 177.4 148.8 120.3 ­62 245.4 14.3 245.4 245.4 223.1 198.3 167.1 139.0 236.1 15.9 236.1 236.1 218.8 190.3 161.7 133.1 57 243.8 14.2 243.8 243.8 235.9 212.7 179.8 151.8 233.3 15.9 233.3 233.3 231.9 203.3 174.7 146.2 72 296.2 15.1 209.5 179.3 149.0 118.8 - - 282.3 16.7 205.3 174.3 143.2 112.2 - ­67 275.2 14.7 251.9 219.4 189.1 158.9 128.6 - 261.0 16.3 246.8 215.8 184.8 153.8 122.8 ­62 253.5 14.4 253.5 253.5 233.4 204.7 172.9 142.6 242.4 15.9 242.4 242.4 228.0 197.0 165.9 134.9 57 251.9 14.3 251.9 251.9 248.0 220.1 187.5 157.2 239.5 15.9 239.5 239.5 238.8 207.8 176.8 145.8 72 305.7 15.2 220.5 188.0 155.6 123.1 - - 289.7 16.8 215.9 182.4 149.0 115.5 - ­67 284.0 14.8 266.9 229.9 197.4 165.0 132.5 - 267.7 16.3 259.1 225.7 192.2 158.8 125.3 ­62 261.7 14.5 261.7 261.7 243.6 211.1 178.7 146.2 248.7 16.0 248.7 248.7 237.1 203.7 170.2 136.8 57 260.0 14.4 260.0 260.0 260.0 227.6 195.1 162.7 245.7 16.0 245.7 245.7 245.7 212.3 178.8 145.4
77 273.6 18.5 126.9 103.1 79.2 - - - 259.0 21.0 123.8 99.6 75.3 - - ­72 253.1 18.1 163.1 139.3 115.4 91.6 - - 239.6 20.4 159.8 135.6 111.3 87.1 - ­67 232.5 17.7 199.3 175.5 151.6 127.8 103.9 - 220.3 19.9 195.8 171.6 147.4 123.1 98.9 ­62 217.9 17.3 217.9 210.8 186.9 163.1 139.2 115.4 205.1 19.5 205.1 201.5 182.5 158.3 134.0 109.8 57 214.0 17.4 214.0 214.0 198.6 174.7 150.9 127.0 204.2 19.6 204.2 204.2 186.7 162.4 138.2 114.0 77 279.2 18.6 138.0 111.6 85.1 - - - 264.6 21.0 137.3 108.0 81.0 - - ­72 258.2 18.2 176.9 150.4 123.9 97.5 - - 244.8 20.5 173.8 146.8 119.7 92.7 - ­67 237.3 17.8 215.8 189.3 162.8 136.3 109.9 - 225.0 20.0 210.4 185.5 158.5 131.4 104.4 ­62 222.3 17.4 222.3 218.8 200.7 172.6 147.8 121.3 209.5 19.5 209.5 207.7 196.3 168.4 142.2 115.1 57 218.4 17.5 218.4 218.4 213.2 184.3 160.3 133.8 208.6 19.6 208.6 208.6 200.7 172.5 146.6 119.6 77 284.7 18.7 149.2 120.1 90.9 - - - 270.2 21.1 150.8 116.5 86.7 - - ­72 263.4 18.3 190.7 161.6 132.5 103.4 - - 250.0 20.6 187.8 158.0 128.1 98.2 - ­67 242.0 17.9 232.2 203.1 174.0 144.9 115.8 - 229.8 20.0 224.9 199.4 169.6 139.7 109.8 ­62 226.8 17.5 226.8 226.8 214.5 182.2 156.3 127.2 213.9 19.6 213.9 213.9 210.0 178.5 150.3 120.4 57 222.7 17.5 222.7 222.7 227.9 193.9 169.6 140.5 213.0 19.7 213.0 213.0 214.8 182.5 155.0 125.2 72 268.5 18.3 201.0 169.2 137.4 105.7 - - 255.2 20.7 198.4 166.0 133.5 101.1 - ­67 246.7 17.9 241.8 212.3 180.5 148.7 117.0 - 234.6 20.1 232.1 209.2 176.8 144.3 111.9 ­62 231.2 17.5 231.2 231.2 222.6 189.2 159.0 127.2 218.4 19.7 218.4 218.4 215.2 181.9 150.3 117.8 57 227.1 17.5 227.1 227.1 229.6 195.4 166.1 134.3 217.5 19.8 217.5 217.5 218.3 184.7 153.4 121.0 72 273.6 18.3 211.3 176.8 142.4 108.0 - - 260.4 20.7 209.0 174.0 139.0 104.0 - ­67 251.4 17.9 251.4 221.5 187.0 152.6 118.2 - 239.3 20.2 239.3 219.0 184.0 148.9 113.9 ­62 235.6 17.5 235.6 235.6 230.6 196.2 161.7 127.3 222.8 19.8 222.8 222.8 220.3 185.3 150.3 115.2 57 231.4 17.5 231.4 231.4 231.4 196.9 162.5 128.1 221.9 19.9 221.9 221.9 221.9 186.9 151.8 116.8
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
42 Johnson Controls Unitary Products
Page 43
505430-BTG-P-0316
YH-20/NH-20 (Continued)
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
1
WB (°F)
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
77 244.4 23.4 120.7 96.0 71.4 - - - 229.9 25.9 117.5 92.5 67.5 - - ­72 226.2 22.8 156.5 131.9 107.2 82.6 - - 212.8 25.1 153.2 128.2 103.2 78.1 - ­67 208.0 22.1 192.4 167.7 143.1 118.5 93.8 - 195.7 24.3 188.9 163.9 138.9 113.8 88.8 ­62 192.2 21.6 192.2 192.2 178.1 153.5 128.8 104.2 179.4 23.8 179.4 179.4 173.7 148.6 123.6 98.6 57 194.4 21.8 194.4 194.4 174.8 150.2 125.5 100.9 184.6 23.9 184.6 184.6 162.9 137.9 112.9 87.8 77 250.0 23.5 136.5 104.5 76.9 - - - 235.5 25.9 135.8 101.0 72.8 - - ­72 231.4 22.8 170.8 143.1 115.5 87.9 - - 218.0 25.1 167.7 139.5 111.3 83.1 - ­67 212.8 22.1 205.0 181.7 154.1 126.5 98.9 - 200.5 24.3 199.6 178.0 149.8 121.6 93.4 ­62 196.7 21.7 196.7 196.7 191.8 164.2 136.5 108.9 183.8 23.8 183.8 183.8 183.8 159.9 130.9 102.7 57 198.9 21.8 198.9 198.9 188.3 160.6 133.0 105.4 189.1 24.0 189.1 189.1 175.8 148.8 119.4 91.2 77 255.7 23.5 152.4 113.0 82.4 - - - 241.1 25.9 154.0 109.5 78.1 - - ­72 236.6 22.8 185.0 154.4 123.7 93.1 - - 223.2 25.1 182.1 150.8 119.4 88.0 - ­67 217.6 22.2 217.6 195.7 165.1 134.5 103.9 - 205.3 24.3 205.3 192.1 160.7 129.3 97.9 ­62 201.1 21.7 201.1 201.1 205.5 174.9 144.3 113.6 188.2 23.9 188.2 188.2 188.2 171.2 138.2 106.9 57 203.3 21.8 203.3 203.3 201.7 171.1 140.5 109.8 193.6 24.0 193.6 193.6 188.6 159.7 125.9 94.5 72 241.9 23.0 195.9 162.8 129.7 96.5 - - 228.6 25.4 193.3 159.5 125.8 92.0 - ­67 222.4 22.3 222.4 206.1 173.0 139.9 106.8 - 210.3 24.6 210.3 203.0 169.3 135.5 101.7 ­62 205.6 21.9 205.6 205.6 207.8 174.6 141.5 108.4 192.7 24.1 192.7 192.7 192.7 167.4 132.8 99.0 57 207.9 22.0 207.9 207.9 207.0 173.9 140.8 107.7 198.3 24.2 198.3 198.3 195.8 163.2 128.2 94.4 72 247.2 23.2 206.8 171.2 135.6 100.0 - - 233.9 25.6 204.5 168.3 132.1 95.9 - ­67 227.3 22.5 227.3 216.5 180.9 145.3 109.7 - 215.2 24.8 215.2 214.0 177.8 141.6 105.4 ­62 210.0 22.0 210.0 210.0 210.0 174.4 138.8 103.2 197.3 24.3 197.3 197.3 197.3 163.5 127.4 91.2 57 212.4 22.2 212.4 212.4 212.4 176.8 141.2 105.6 202.9 24.5 202.9 202.9 202.9 166.7 130.5 94.3
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
Johnson Controls Unitary Products 43
Page 44
505430-BTG-P-0316
YJ-20 / Two NH-10
Air on
Evaporator Coil
CFM
WB (°F)
77 268.6 15.0 134.0 111.2 88.5 - - - 270.6 16.5 131.5 108.7 85.9 - - ­72 253.5 14.6 166.7 144.0 121.3 98.6 - - 252.1 16.1 164.6 141.8 119.0 96.1 - -
6000
67 238.3 14.2 199.5 176.8 154.1 131.3 108.6 - 233.6 15.7 197.6 174.8 152.0 129.2 106.4 ­62 214.5 13.9 214.5 210.2 187.4 164.7 142.0 119.3 213.4 15.4 213.4 208.2 185.4 162.6 139.8 117.0 57 213.5 13.9 213.5 216.8 196.1 173.3 150.6 127.9 212.8 15.4 212.8 212.8 190.9 168.1 145.3 122.5 77 280.9 15.1 145.1 119.6 94.1 - - - 280.0 16.6 142.7 117.1 91.5 - - ­72 265.0 14.7 179.9 154.5 129.0 103.5 - - 260.9 16.2 177.9 152.3 126.7 101.1 - -
7000
67 249.1 14.3 214.8 189.3 163.9 138.4 112.9 - 241.8 15.8 213.1 187.5 161.9 136.3 110.7 ­62 224.2 14.0 224.2 222.1 199.4 174.6 148.4 123.0 220.8 15.5 220.8 218.2 197.5 171.9 146.3 120.7 57 223.1 14.0 223.1 224.8 208.6 184.1 157.6 132.2 220.2 15.5 220.2 220.2 203.4 177.8 152.2 126.6 77 293.1 15.2 156.2 128.0 99.8 - - - 289.4 16.7 153.9 125.5 97.1 - - ­72 276.4 14.8 193.1 164.9 136.7 108.5 - - 269.6 16.3 191.2 162.8 134.5 106.1 - -
8000
67 259.8 14.4 230.1 201.9 173.7 145.5 117.3 - 249.9 16.0 228.6 200.2 171.8 143.4 115.1 ­62 234.0 14.1 234.0 234.0 211.3 184.5 154.9 126.7 228.2 15.6 228.2 228.2 209.6 181.2 152.8 124.4 57 232.8 14.1 232.8 232.8 221.0 194.8 164.6 136.4 227.5 15.6 227.5 227.5 215.8 187.4 159.1 130.7 72 278.2 14.9 206.2 175.3 144.3 113.4 - - 274.3 16.4 204.4 173.3 142.2 111.2 - -
9000
67 261.5 14.5 246.7 214.3 183.3 152.4 121.5 - 254.2 16.0 243.6 212.8 181.8 150.7 119.6 ­62 235.5 14.2 235.5 235.5 223.0 192.8 161.2 130.2 232.2 15.7 232.2 232.2 221.7 190.6 159.5 128.5 57 234.3 14.1 234.3 234.3 228.4 198.5 166.5 135.6 231.5 15.7 231.5 231.5 225.6 194.6 163.5 132.4 72 280.0 15.0 219.3 185.6 151.9 118.3 - - 279.0 16.5 217.5 183.8 150.0 116.3 - -
10000
67 263.2 14.6 263.2 226.7 193.0 159.3 125.6 - 258.6 16.1 258.6 225.5 191.7 158.0 124.2 ­62 236.9 14.2 236.9 236.9 234.8 201.1 167.4 133.8 236.1 15.8 236.1 236.1 233.8 200.1 166.3 132.6 57 235.7 14.2 235.7 235.7 235.7 202.1 168.4 134.7 235.4 15.8 235.4 235.4 235.4 201.7 167.9 134.2
77 272.5 18.0 129.1 106.2 83.3 - - - 233.1 17.0 161.4 149.9 138.5 - - ­72 250.7 17.6 162.4 139.5 116.6 93.7 - - 228.1 18.4 184.0 172.5 153.8 131.0 - -
6000
67 228.9 17.3 195.8 172.9 150.0 127.1 104.2 - 223.1 19.7 193.2 170.4 147.5 124.7 101.9 ­62 212.2 17.0 212.2 206.2 183.3 160.5 137.6 114.7 206.1 19.3 206.1 203.1 186.5 163.7 140.8 118.0 57 212.1 17.0 212.1 208.7 185.8 162.9 140.0 117.2 197.7 19.2 197.7 196.1 184.6 161.8 138.9 116.1 77 279.1 18.1 140.3 114.6 88.8 - - - 243.8 17.2 183.8 164.3 144.9 - - ­72 256.8 17.7 175.9 150.1 124.4 98.7 - - 239.1 18.5 194.4 175.0 151.9 126.8 - -
7000
67 234.5 17.4 211.5 185.7 160.0 134.3 108.5 - 234.3 19.9 198.4 173.3 148.2 123.0 97.9 ­62 217.3 17.1 217.3 214.3 195.6 169.1 144.1 118.4 216.4 19.5 213.5 205.4 186.9 161.4 136.6 111.5 57 217.2 17.1 217.2 215.5 198.2 171.5 146.8 121.0 207.4 19.4 207.4 206.5 195.0 169.3 144.7 119.6 77 285.6 18.2 151.5 123.0 94.4 - - - 254.6 17.3 206.2 178.8 151.3 - - ­72 262.8 17.8 189.3 160.8 132.2 103.6 - - 250.0 18.7 204.9 177.5 150.1 122.6 - -
8000
67 240.0 17.5 227.2 198.6 170.0 141.4 112.8 - 245.4 20.0 203.7 176.2 148.8 121.4 93.9 ­62 222.4 17.2 222.4 222.4 207.8 177.8 150.7 122.1 226.7 19.7 220.9 207.8 187.3 159.1 132.4 105.0 57 222.3 17.2 222.3 222.3 210.6 180.1 153.5 124.9 217.0 19.6 217.0 217.0 205.4 176.9 150.5 123.0 72 270.4 17.9 202.6 171.4 140.1 108.9 - - 258.5 18.8 220.4 198.2 172.7 142.1 - -
9000
67 246.9 17.6 240.5 211.4 180.2 149.0 117.8 - 253.9 20.1 228.3 198.7 168.1 137.5 106.9 ­62 228.9 17.2 228.9 228.9 220.3 188.4 157.9 126.7 234.5 19.8 231.6 225.0 212.1 181.2 150.9 120.3 57 228.7 17.2 228.7 228.7 222.9 190.7 160.5 129.3 224.4 19.6 224.4 224.4 218.6 187.5 157.4 126.8 72 278.0 18.0 215.8 181.9 148.1 114.3 - - 267.0 18.8 235.9 219.0 195.4 161.7 - -
10000
67 253.9 17.6 253.9 224.3 190.5 156.6 122.8 - 262.3 20.2 252.9 221.2 187.5 153.7 119.9 ­62 235.3 17.3 235.3 235.3 232.8 199.0 165.2 131.4 242.2 19.8 242.2 242.2 237.0 203.2 169.4 135.6 57 235.1 17.3 235.1 235.1 235.1 201.3 167.5 133.7 231.8 19.7 231.8 231.8 231.8 198.0 164.3 130.5
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
90 85 80 75 70 65 90 85 80 75 70 65
Return Dry Bulb (°F) Return Dry Bulb (°F)
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
1
Total
Capacity
(MBh)
1
Total Input
(kW)
Sensible Capacity (MBh)
2
1
44 Johnson Controls Unitary Products
Page 45
505430-BTG-P-0316
YJ-20 / Two NH-10 (Continued)
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
1
WB (°F)
77 193.7 16.1 193.7 193.7 193.7 - - - 154.3 15.2 154.3 154.3 154.3 - - ­72 205.5 19.1 205.5 205.5 190.9 168.2 - - 182.9 19.8 182.9 182.9 182.9 182.9 - ­67 217.3 22.1 190.7 167.9 145.1 122.3 99.5 - 211.5 24.5 188.1 165.4 142.6 119.9 97.2 ­62 200.0 21.7 200.0 200.0 189.6 166.9 144.1 121.3 194.0 24.1 194.0 194.0 192.8 170.1 147.3 124.6 57 183.4 21.4 183.4 183.4 183.4 160.6 137.8 115.1 169.1 23.7 169.1 169.1 169.1 159.4 136.7 114.0 77 208.6 16.3 227.3 214.1 201.0 - - - 173.4 15.4 173.4 173.4 173.4 - - ­72 221.4 19.3 213.0 199.9 179.4 154.9 - - 203.6 20.1 203.6 203.6 203.6 183.0 - ­67 234.1 22.3 185.4 160.9 136.4 111.8 87.3 - 233.9 24.8 172.4 148.5 124.5 100.6 76.6 ­62 215.5 22.0 209.7 196.6 178.2 153.7 129.1 104.6 214.5 24.5 205.9 187.7 169.5 145.9 121.6 97.7 57 197.5 21.7 197.5 197.5 191.7 167.2 142.7 118.1 187.7 24.0 187.7 187.7 187.7 165.1 140.6 116.7 77 223.6 16.5 260.9 234.6 208.3 - - - 192.5 15.7 192.5 192.5 192.5 - - ­72 237.2 19.6 220.5 194.2 167.9 141.6 - - 224.4 20.4 224.4 211.0 185.8 160.6 - ­67 250.9 22.6 180.2 153.9 127.6 101.3 75.0 - 256.3 25.2 156.8 131.6 106.4 81.2 56.1 ­62 230.9 22.3 219.4 193.1 166.8 140.5 114.2 87.9 235.1 24.8 217.9 178.4 146.3 121.8 95.9 70.8 57 211.7 22.0 211.7 211.7 200.1 173.8 147.5 121.2 206.4 24.4 206.4 206.4 194.8 170.7 144.5 119.3 72 246.6 19.6 238.3 225.1 205.3 175.3 - - 234.7 20.5 234.7 234.7 234.7 208.5 - ­67 260.8 22.7 216.1 186.0 156.0 126.0 96.0 - 267.7 25.2 203.8 173.3 143.9 114.5 85.1 ­62 240.1 22.3 234.3 221.1 203.9 173.9 143.9 113.9 245.6 24.9 237.0 217.3 195.7 166.7 136.9 107.5 57 220.1 22.0 220.1 220.1 214.3 184.3 154.3 124.3 215.8 24.4 215.8 215.8 210.0 181.1 151.2 121.7 72 256.0 19.6 256.0 256.0 242.8 209.0 - - 245.0 20.5 245.0 245.0 245.0 245.0 - ­67 270.8 22.7 251.9 218.2 184.5 150.7 117.0 - 279.2 25.3 250.9 215.1 181.5 147.8 114.1 ­62 249.2 22.4 249.2 249.2 241.1 207.4 173.7 139.9 256.2 24.9 256.2 256.2 245.2 211.6 177.9 144.2 57 228.5 22.1 228.5 228.5 228.5 194.8 161.0 127.3 225.1 24.4 225.1 225.1 225.1 191.5 157.8 124.2
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
90 85 80 75 70 65 90 85 80 75 70 65
Return Dry Bulb (°F) Return Dry Bulb (°F)
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
1
Total
Capacity
(MBh)
1
Total Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
1
Johnson Controls Unitary Products 45
Page 46
505430-BTG-P-0316
YJ-20/NJ-20
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
6000
7000
8000
9000
10000
WB
(°F)
Total
Capacity
(MBh)
77 292.8 14.7 136.9 111.9 87.0 - - - 284.3 16.4 135.2 110.2 85.1 - - ­72 272.9 14.4 174.4 149.4 124.5 99.5 - - 263.5 16.1 171.7 146.7 121.7 96.6 - ­67 253.0 14.0 211.9 186.9 162.0 137.0 112.0 - 242.6 15.8 208.2 183.2 158.2 133.2 108.1 ­62 231.8 13.8 231.8 220.2 195.2 170.2 145.2 120.2 225.5 15.5 225.5 219.3 194.3 169.2 144.2 119.2 57 224.6 13.7 224.6 224.6 207.1 182.1 157.1 132.1 219.3 15.5 219.3 219.3 201.5 176.5 151.5 126.5 77 302.2 14.8 149.9 121.7 93.5 - - - 292.0 16.5 147.3 119.2 91.1 - - ­72 281.7 14.5 190.2 162.0 133.8 105.6 - - 270.5 16.2 186.4 158.3 130.2 102.2 - ­67 261.1 14.2 230.5 202.3 174.1 145.9 117.7 - 249.1 15.9 225.5 197.4 169.3 141.3 113.2 ­62 239.3 13.9 239.3 233.5 209.9 182.9 153.5 125.3 231.5 15.6 231.5 228.4 208.0 179.9 151.8 123.8 57 231.8 13.9 231.8 231.8 222.6 196.1 166.2 138.0 225.2 15.6 225.2 225.2 215.7 187.7 159.6 131.5 77 311.7 14.9 162.8 131.4 100.0 - - - 299.6 16.6 159.4 128.2 97.1 - - ­72 290.5 14.6 206.0 174.5 143.1 111.7 - - 277.6 16.3 201.0 169.9 138.8 107.7 - ­67 269.3 14.3 249.1 217.7 186.2 154.8 123.4 - 255.6 16.0 242.7 211.6 180.5 149.4 118.3 ­62 246.8 14.0 246.8 246.8 224.5 195.6 161.7 130.3 237.6 15.7 237.6 237.6 221.7 190.5 159.4 128.3 57 239.1 14.0 239.1 239.1 238.1 210.2 175.3 143.9 231.1 15.7 231.1 231.1 229.9 198.8 167.7 136.6 72 299.4 14.9 217.9 184.4 150.9 117.3 - - 284.7 16.6 212.0 178.6 145.2 111.7 - ­67 277.5 14.6 267.1 229.8 196.3 162.8 129.3 - 262.2 16.3 255.6 222.1 188.7 155.3 121.9 ­62 254.3 14.3 254.3 254.3 236.8 204.5 169.7 136.2 243.7 16.0 243.7 243.7 231.8 198.4 165.0 131.5 57 246.4 14.2 246.4 246.4 245.9 214.1 178.9 145.4 237.0 16.0 237.0 237.0 236.4 203.0 169.6 136.2 72 308.2 15.2 229.9 194.2 158.6 123.0 - - 291.8 16.9 222.9 187.2 151.5 115.8 - ­67 285.7 14.8 285.0 242.0 206.4 170.8 135.2 - 268.7 16.5 268.4 232.7 197.0 161.3 125.6 ­62 261.9 14.6 261.9 261.9 249.0 213.4 177.7 142.1 249.7 16.3 249.7 249.7 241.9 206.2 170.5 134.8 57 253.7 14.5 253.7 253.7 253.7 218.1 182.5 146.9 242.9 16.3 242.9 242.9 242.9 207.2 171.5 135.8
77 275.8 18.1 133.4 108.4 83.3 - - - 262.8 20.3 129.8 104.7 79.5 - - ­72 254.0 17.8 169.0 143.9 118.8 93.8 - - 242.0 20.1 164.8 139.7 114.6 89.5 - ­67 232.2 17.5 204.5 179.5 154.4 129.3 104.3 - 221.1 19.8 199.8 174.7 149.6 124.5 99.4 ­62 219.1 17.2 219.1 218.4 193.3 168.3 143.2 118.2 208.7 19.6 208.7 208.3 185.8 160.7 135.6 110.5 57 214.1 17.3 214.1 214.1 196.0 170.9 145.9 120.8 205.0 19.6 205.0 205.0 186.2 161.1 136.0 110.9 77 281.7 18.2 144.7 116.7 88.8 - - - 268.8 20.4 144.0 113.4 85.3 - - ­72 259.4 17.9 182.5 154.6 126.7 98.7 - - 247.4 20.1 179.0 150.9 122.8 94.7 - ­67 237.1 17.6 220.4 192.5 164.6 136.6 108.7 - 226.1 19.9 214.1 188.4 160.3 132.2 104.1 ­62 223.7 17.3 223.7 223.4 206.1 176.9 150.2 122.3 213.4 19.7 213.4 213.2 199.1 170.4 142.9 114.8 57 218.6 17.4 218.6 218.6 208.9 179.2 153.0 125.1 209.7 19.7 209.7 209.7 199.6 170.6 143.4 115.2 77 287.5 18.3 155.9 125.1 94.3 - - - 274.7 20.5 158.2 122.1 91.0 - - ­72 264.8 18.0 196.1 165.3 134.5 103.7 - - 252.9 20.2 193.2 162.1 131.0 99.9 - ­67 242.0 17.7 236.3 205.5 174.7 143.9 113.1 - 231.1 19.9 228.3 202.2 171.1 140.0 108.8 ­62 228.4 17.4 228.4 228.4 218.8 185.5 157.2 126.4 218.1 19.7 218.1 218.1 212.5 180.1 150.3 119.1 57 223.1 17.4 223.1 223.1 221.8 187.5 160.1 129.3 214.3 19.8 214.3 214.3 212.9 180.1 150.7 119.6 72 270.1 18.3 206.1 172.7 139.4 106.1 - - 258.4 20.5 202.9 169.4 136.0 102.5 - ­67 246.9 18.0 244.1 214.5 181.1 147.8 114.5 - 236.1 20.2 234.7 211.0 177.5 144.1 110.6 ­62 233.0 17.7 233.0 233.0 226.8 192.3 160.2 126.9 222.8 20.0 222.8 222.8 219.3 185.2 152.4 118.9 57 227.6 17.7 227.6 227.6 226.9 191.9 160.3 127.0 218.9 20.0 218.9 218.9 218.2 183.9 151.3 117.8 72 275.4 18.6 216.0 180.2 144.4 108.6 - - 263.8 20.8 212.6 176.7 140.9 105.1 - ­67 251.8 18.2 251.8 223.4 187.6 151.8 116.0 - 241.1 20.5 241.1 219.8 184.0 148.2 112.3 ­62 237.6 18.0 237.6 237.6 234.9 199.1 163.3 127.5 227.5 20.3 227.5 227.5 226.1 190.3 154.5 118.6 57 232.1 18.0 232.1 232.1 232.1 196.3 160.5 124.7 223.6 20.3 223.6 223.6 223.6 187.7 151.9 116.1
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
46 Johnson Controls Unitary Products
Page 47
505430-BTG-P-0316
YJ-20/NJ-20 (Continued)
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
1
WB (°F)
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
77 249.8 22.6 126.1 101.0 75.8 - - - 236.8 24.9 122.5 97.3 72.0 - - ­72 229.9 22.3 160.6 135.4 110.3 85.1 - - 217.9 24.6 156.4 131.2 106.0 80.8 - ­67 210.1 22.0 195.1 169.9 144.8 119.6 94.4 - 199.0 24.3 190.3 165.1 139.9 114.7 89.5 ­62 198.2 21.9 198.2 198.2 178.3 153.1 128.0 102.8 187.8 24.3 187.8 187.8 170.7 145.5 120.3 95.1 57 196.0 21.9 196.0 196.0 176.5 151.3 126.1 101.0 187.0 24.2 187.0 187.0 166.7 141.5 116.3 91.1 77 255.8 22.7 143.3 110.0 81.7 - - - 242.9 24.9 142.6 106.7 78.2 - - ­72 235.5 22.4 175.5 147.2 118.9 90.6 - - 223.6 24.7 172.0 143.5 115.0 86.6 - ­67 215.2 22.1 207.7 184.4 156.1 127.8 99.5 - 204.2 24.4 201.3 180.3 151.8 123.4 94.9 ­62 203.0 22.0 203.0 203.0 192.2 163.9 135.7 107.4 192.7 24.3 192.7 192.7 185.3 157.5 128.4 99.9 57 200.8 22.0 200.8 200.8 190.3 162.0 133.7 105.4 191.9 24.3 191.9 191.9 181.0 153.4 124.1 95.6 77 261.9 22.8 160.5 119.1 87.7 - - - 249.1 25.0 162.8 116.1 84.4 - - ­72 241.1 22.5 190.4 159.0 127.5 96.1 - - 229.3 24.8 187.5 155.8 124.1 92.3 - ­67 220.3 22.2 220.3 198.8 167.4 136.0 104.6 - 209.4 24.5 209.4 195.5 163.8 132.0 100.3 ­62 207.8 22.1 207.8 207.8 206.2 174.8 143.3 111.9 197.6 24.4 197.6 197.6 197.6 169.4 136.4 104.7 57 205.5 22.1 205.5 205.5 204.1 172.7 141.3 109.8 196.7 24.4 196.7 196.7 195.3 165.3 131.8 100.1 72 246.6 22.7 199.8 166.1 132.5 98.8 - - 234.9 25.0 196.6 162.8 129.0 95.2 - ­67 225.3 22.4 225.3 207.6 173.9 140.3 106.6 - 214.6 24.7 214.6 204.1 170.3 136.5 102.7 ­62 212.6 22.3 212.6 212.6 211.8 178.2 144.5 110.9 202.4 24.6 202.4 202.4 202.4 171.1 136.7 102.9 57 210.3 22.3 210.3 210.3 209.5 175.9 142.3 108.6 201.6 24.6 201.6 201.6 200.8 167.9 133.2 99.4 72 252.2 23.0 209.2 173.3 137.4 101.6 - - 240.5 25.2 205.7 169.9 134.0 98.1 - ­67 230.4 22.7 230.4 216.3 180.4 144.6 108.7 - 219.7 24.9 219.7 212.7 176.8 141.0 105.1 ­62 217.4 22.5 217.4 217.4 217.4 181.5 145.7 109.8 207.3 24.8 207.3 207.3 207.3 172.8 136.9 101.0 57 215.0 22.5 215.0 215.0 215.0 179.1 143.3 107.4 206.4 24.8 206.4 206.4 206.4 170.5 134.7 98.8
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
Johnson Controls Unitary Products 47
Page 48
505430-BTG-P-0316
YH-25/NH-25
Air on
Evaporator Coil
CFM
7500
8750
10000
11250
12500
7500
8750
10000
11250
12500
WB
(°F)
Total
Capacity
(MBh)
77 390.0 20.3 208.7 177.2 145.6 - - - 362.1 23.0 180.5 148.9 117.3 - - ­72 360.6 19.9 242.2 210.6 179.1 147.5 - - 336.8 22.5 224.3 192.7 161.1 129.5 - ­67 331.2 19.5 275.6 244.1 212.5 181.0 149.4 - 311.5 21.9 268.0 236.5 204.9 173.3 141.7 ­62 305.3 18.6 305.3 311.5 279.9 248.4 216.8 185.2 295.7 21.4 295.7 289.4 257.8 226.2 194.6 163.0 57 308.5 18.5 308.5 314.3 282.8 251.2 219.7 188.1 298.5 21.3 298.5 293.5 261.9 230.3 198.7 167.1 77 399.4 20.7 217.9 188.8 153.3 - - - 368.5 23.2 196.3 160.6 124.8 - - ­72 369.3 20.4 258.8 223.4 187.9 152.4 - - 342.8 22.7 242.9 207.2 171.4 135.7 - ­67 339.2 20.0 299.8 258.0 222.5 187.0 151.5 - 317.1 22.2 289.5 253.8 218.0 182.3 146.6 ­62 312.8 19.0 312.8 315.9 293.5 259.6 222.5 187.0 300.9 21.6 300.9 297.8 274.3 238.6 202.9 167.1 57 316.1 18.9 316.1 319.0 296.4 262.8 225.5 190.0 303.8 21.5 303.8 301.3 278.8 243.0 207.3 171.6 77 408.8 21.2 227.1 200.4 161.0 - - - 374.9 23.4 212.1 172.2 132.4 - - ­72 378.0 20.8 275.5 236.1 196.7 157.3 - - 348.8 22.9 261.5 221.7 181.8 141.9 - ­67 347.2 20.4 323.9 271.8 232.4 193.0 153.6 - 322.6 22.4 311.0 271.1 231.2 191.3 151.5 ­62 320.3 19.4 320.3 320.3 307.0 270.9 228.2 188.8 306.2 21.8 306.2 306.2 290.9 251.1 211.2 171.3 57 323.7 19.3 323.7 323.7 310.1 274.3 231.3 191.9 309.1 21.7 309.1 309.1 295.6 255.7 215.9 176.0 72 390.1 20.5 302.2 259.4 216.7 173.9 - - 360.2 22.9 285.4 241.8 198.2 154.6 - ­67 358.3 20.2 346.7 299.2 256.5 213.7 170.9 - 333.2 22.3 327.4 295.7 252.1 208.5 164.9 ­62 330.5 19.2 330.5 330.5 323.9 282.8 238.4 195.6 316.2 21.8 316.2 316.2 308.6 265.0 221.4 177.8 57 334.0 19.1 334.0 334.0 327.2 286.2 241.7 198.9 319.3 21.7 319.3 319.3 312.5 268.9 225.3 181.7 72 402.1 20.3 328.9 282.7 236.6 190.5 - - 371.7 22.8 309.2 261.9 214.6 167.3 - ­67 369.4 19.9 369.4 326.6 280.5 234.4 188.3 - 343.8 22.3 343.8 320.3 272.9 225.6 178.3 ­62 340.7 18.9 340.7 340.7 340.7 294.6 248.5 202.4 326.3 21.8 326.3 326.3 326.3 278.9 231.6 184.3 57 344.3 18.8 344.3 344.3 344.3 298.2 252.1 205.9 329.4 21.6 329.4 329.4 329.4 282.1 234.8 187.5
77 334.1 25.7 152.2 120.6 89.0 - - - 325.6 28.6 147.7 116.1 84.4 - - ­72 313.0 25.0 206.4 174.7 143.1 111.4 - - 300.7 27.9 200.5 168.9 137.2 105.6 - ­67 291.9 24.3 260.5 228.8 197.2 165.5 133.9 - 275.8 27.3 253.3 221.6 190.0 158.4 126.7 ­62 286.0 24.3 286.0 267.3 235.6 204.0 172.3 140.7 266.2 27.0 266.2 251.2 219.5 187.9 156.3 124.6 57 288.6 24.1 288.6 272.7 241.0 209.4 177.8 146.1 273.7 26.8 273.7 255.7 224.1 192.5 160.8 129.2 77 337.6 25.6 174.7 132.3 96.4 - - - 328.2 28.6 177.7 128.5 92.4 - - ­72 316.3 25.0 226.9 191.0 155.0 119.0 - - 303.2 28.0 222.3 186.2 150.2 114.1 - ­67 294.9 24.3 279.2 249.6 213.6 177.6 141.6 - 278.1 27.3 266.8 244.0 207.9 171.9 135.8 ­62 289.0 24.3 289.0 279.6 255.2 217.6 183.2 147.3 268.4 27.1 268.4 260.9 240.2 203.3 168.1 132.0 57 291.6 24.1 291.6 283.7 261.1 223.3 189.1 153.1 275.9 26.9 275.9 266.9 245.2 208.2 173.1 137.0 77 341.1 25.6 197.1 144.1 103.8 - - - 330.9 28.7 207.8 140.8 100.4 - - ­72 319.6 24.9 247.5 207.2 166.9 126.5 - - 305.6 28.1 244.1 203.6 163.1 122.6 - ­67 298.0 24.3 298.0 270.3 230.0 189.7 149.3 - 280.4 27.4 280.4 266.3 225.9 185.4 144.9 ­62 292.0 24.2 292.0 292.0 274.8 231.2 194.2 153.8 270.6 27.1 270.6 270.6 260.8 218.7 179.8 139.4 57 294.6 24.0 294.6 294.6 281.1 237.2 200.5 160.2 278.2 27.0 278.2 278.2 266.2 223.9 185.3 144.8 72 330.4 25.2 268.6 224.1 179.7 135.3 - - 316.3 28.2 265.2 220.4 175.6 130.8 - ­67 308.1 24.5 308.1 292.1 247.7 203.3 158.8 - 290.2 27.5 290.2 282.1 243.2 198.4 153.5 ­62 301.9 24.4 301.9 301.9 293.3 247.2 204.4 160.0 280.0 27.2 280.0 280.0 275.1 229.5 185.5 140.7 57 304.6 24.3 304.6 304.6 297.9 251.6 209.0 164.6 287.9 27.1 287.9 287.9 281.9 236.2 192.3 147.5 72 341.2 25.4 289.6 241.1 192.5 144.0 - - 327.0 28.3 286.4 237.2 188.1 139.0 - ­67 318.2 24.7 318.2 313.9 265.4 216.8 168.3 - 300.0 27.6 300.0 297.8 260.5 211.3 162.2 ­62 311.8 24.7 311.8 311.8 311.8 263.3 214.7 166.2 289.5 27.4 289.5 289.5 289.5 240.4 191.2 142.1 57 314.6 24.5 314.6 314.6 314.6 266.1 217.6 169.0 297.6 27.2 297.6 297.6 297.6 248.5 199.3 150.2
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
48 Johnson Controls Unitary Products
Page 49
505430-BTG-P-0316
YH-25/NH-25 (Continued)
Air on
Evaporator Coil
CFM
7500
8750
10000
11250
12500
1
WB (°F)
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
77 317.1 31.5 143.2 111.6 79.9 - - - 308.6 34.3 138.7 107.1 75.4 - - ­72 288.5 30.8 194.6 163.0 131.4 99.7 - - 276.2 33.7 188.8 157.2 125.5 93.9 - ­67 259.8 30.2 246.1 214.4 182.8 151.2 119.5 - 243.8 33.1 238.9 207.2 175.6 144.0 112.4 ­62 246.4 29.7 246.4 235.1 203.5 171.8 140.2 108.6 226.6 32.4 226.6 219.0 187.4 155.7 124.1 92.5 57 258.8 29.6 258.8 238.8 207.2 175.5 143.9 112.3 243.9 32.3 243.9 221.9 190.3 158.6 127.0 95.4 77 318.9 31.6 180.8 124.6 88.5 - - - 309.5 34.7 183.9 120.7 84.5 - - ­72 290.1 31.0 217.6 181.5 145.4 109.2 - - 277.0 34.0 212.9 176.7 140.6 104.4 - ­67 261.3 30.4 254.4 238.4 202.3 166.1 130.0 - 244.4 33.4 242.0 232.8 196.6 160.4 124.2 ­62 247.8 29.9 247.8 242.1 225.1 189.0 152.9 116.7 227.2 32.6 227.2 223.4 210.1 174.7 137.7 101.5 57 260.2 29.7 260.2 250.2 229.2 193.1 157.0 120.9 244.6 32.6 244.6 233.5 213.3 178.0 140.9 104.7 77 320.7 31.8 218.4 137.6 97.0 - - - 310.4 35.0 229.1 134.3 93.6 - - ­72 291.7 31.2 240.6 200.0 159.3 118.7 - - 277.7 34.3 237.1 196.3 155.6 114.8 - ­67 262.7 30.5 262.7 262.3 221.7 181.1 140.5 - 245.1 33.7 245.1 245.1 217.6 176.8 136.1 ­62 249.2 30.0 249.2 249.2 246.8 206.1 165.5 124.9 227.8 32.9 227.8 227.8 227.8 193.6 151.2 110.4 57 261.7 29.9 261.7 261.7 251.3 210.7 170.0 129.4 245.2 32.9 245.2 245.2 236.3 197.4 154.8 114.1 72 302.2 31.2 261.9 216.7 171.5 126.3 - - 288.2 34.2 258.5 213.0 167.4 121.8 - ­67 272.2 30.5 272.2 272.0 238.6 193.5 148.3 - 254.3 33.6 254.3 254.3 234.1 188.5 143.0 ­62 258.2 30.0 258.2 258.2 257.0 211.8 166.6 121.4 236.3 32.8 236.3 236.3 236.3 194.1 147.7 102.1 57 271.1 29.9 271.1 271.1 265.9 220.8 175.6 130.4 254.4 32.8 254.4 254.4 250.0 205.3 158.9 113.3 72 312.8 31.2 283.2 233.4 183.7 133.9 - - 298.6 34.1 279.9 229.6 179.2 128.8 - ­67 281.7 30.6 281.7 281.7 255.6 205.8 156.0 - 263.5 33.5 263.5 263.5 250.6 200.3 149.9 ­62 267.2 30.0 267.2 267.2 267.2 217.4 167.7 117.9 244.9 32.7 244.9 244.9 244.9 194.5 144.2 93.8 57 280.6 29.9 280.6 280.6 280.6 230.9 181.1 131.4 263.6 32.7 263.6 263.6 263.6 213.2 162.9 112.5
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
Johnson Controls Unitary Products 49
Page 50
505430-BTG-P-0316
Condenser Only Cooling Capacities Condenser Only Ratings
Suction Press.
Model
Corresponding Temp.
PSIG °F MBH KW EER MBH KW EER MBH KW EER MBH KW EER MBH KW EER MBH KW EER
YH-07
YH-10
YJ-10
YH-12
YJ-12
YH-15
YJ-15
YH-20
YJ-20
YH-25
and
108 35 78 4.8 16.1 75 5.3 14.2 72 5.8 12.4 68 6.5 10.3 61 7.6 8.1 55 8.6 6.4 120 40 88 5.0 17.6 84 5.5 15.5 81 5.9 13.6 76 6.7 11.4 70 7.7 9.1 64 8.7 7.3 131 45 98 5.1 19.1 94 5.6 16.7 89 6.1 14.7 85 6.8 12.4 79 7.8 10.0 72 8.9 8.2 143 50 108 5.3 20.5 103 5.8 17.8 98 6.2 15.7 93 6.9 13.4 87 8.0 10.9 81 9.0 9.0 157 55 118 5.4 21.8 112 5.9 18.9 107 6.4 16.7 102 7.1 14.4 96 8.1 11.8 90 9.2 9.8 108 35 102 6.5 15.8 95 7.3 13.1 89 8.0 11.1 84 9.0 9.3 78 10.3 7.6 73 11.4 6.4 120 40 120 6.6 18.1 111 7.4 15.1 104 8.2 12.8 97 9.1 10.6 90 10.4 8.7 84 11.5 7.3 131 45 138 6.7 20.4 128 7.5 17.1 119 8.3 14.4 110 9.3 11.9 102 10.5 9.7 94 11.6 8.1 143 50 155 6.9 22.6 145 7.6 19.0 134 8.4 16.0 123 9.4 13.2 114 10.6 10.8 105 11.7 8.9 157 55 173 7.0 24.7 161 7.7 20.8 149 8.5 17.5 136 9.5 14.4 126 10.7 11.8 115 11.8 9.7 108 35 106 6.4 16.3 96 7.2 13.4 88 7.9 11.2 82 8.8 9.3 73 9.8 7.5 65 11.1 5.9 120 40 120 6.5 18.4 111 7.3 15.2 103 8.0 12.8 95 9.0 10.5 85 10.0 8.5 78 11.3 6.9 131 45 136 6.7 20.5 126 7.4 17.0 117 8.2 14.3 108 9.1 11.8 97 10.2 9.5 90 11.5 7.9 143 50 152 6.8 22.5 142 7.5 18.7 132 8.3 15.8 120 9.3 13.0 109 10.4 10.5 103 11.6 8.8 157 55 168 6.9 24.4 157 7.7 20.4 146 8.5 17.2 133 9.4 14.1 121 10.6 11.4 115 11.8 9.8 108 35 190 8.2 23.2 190 9.1 20.8 113 9.8 11.5 105 11.1 9.5 102 12.4 8.2 98 13.8 7.1 120 40 190 8.5 22.4 190 9.4 20.3 127 10.1 12.6 118 11.3 10.4 113 12.6 8.9 108 14.1 7.7 131 45 190 8.8 21.7 190 9.6 19.8 140 10.3 13.6 131 11.5 11.3 123 12.8 9.6 118 14.4 8.2 143 50 190 9.1 21.0 190 9.8 19.3 154 10.6 14.5 144 11.8 12.2 134 13.0 10.3 127 14.6 8.7 157 55 190 9.3 20.3 190 10.1 18.9 168 10.9 15.4 156 12.0 13.0 145 13.2 10.9 137 14.9 9.2 108 35 132 8.4 15.7 124 9.2 13.5 119 9.9 11.9 109 11.0 9.9 103 12.4 8.3 94 13.6 6.9 120 40 149 8.6 17.4 140 9.4 14.9 133 10.2 13.1 123 11.2 10.9 116 12.7 9.1 107 13.9 7.7 131 45 166 8.7 19.0 156 9.6 16.3 148 10.4 14.2 136 11.5 11.8 128 13.0 9.9 119 14.3 8.3 143 50 183 8.9 20.5 173 9.8 17.6 163 10.7 15.2 149 11.7 12.7 141 13.3 10.6 131 14.6 9.0 157 55 200 9.1 21.9 189 10.0 18.8 177 10.9 16.2 163 12.0 13.6 153 13.5 11.3 144 14.9 9.6 108 35 169 9.7 17.4 153 10.8 14.3 135 11.5 11.7 125 12.7 9.8 116 14.5 8.0 104 16.0 6.5 120 40 184 10.1 18.2 170 11.0 15.4 154 11.9 13.0 142 13.0 10.9 133 14.8 9.0 121 16.4 7.4 131 45 198 10.4 19.1 186 11.3 16.4 172 12.2 14.1 160 13.4 12.0 149 15.1 9.9 137 16.7 8.2 143 50 213 10.7 19.8 203 11.6 17.5 191 12.6 15.2 178 13.7 13.0 166 15.4 10.7 153 17.0 9.0 157 55 227 11.0 20.6 219 11.9 18.4 210 12.9 16.2 196 14.0 14.0 182 15.7 11.6 169 17.3 9.8 108 35 160 10.1 15.9 149 11.0 13.6 141 11.6 12.2 136 12.8 10.6 127 14.5 8.8 121 16.3 7.4 120 40 179 10.2 17.6 168 11.2 15.0 158 11.9 13.3 151 13.1 11.5 141 14.8 9.5 133 16.6 8.0 131 45 199 10.3 19.2 186 11.3 16.5 175 12.2 14.4 166 13.4 12.3 154 15.1 10.2 145 16.8 8.6 143 50 218 10.5 20.8 205 11.5 17.8 192 12.5 15.4 180 13.8 13.1 168 15.4 10.9 157 17.1 9.2 157 55 238 10.6 22.4 224 11.7 19.2 209 12.8 16.4 195 14.1 13.9 181 15.7 11.5 169 17.4 9.7 108 35 215 12.5 17.2 200 13.6 14.7 185 14.8 12.5 171 16.3 10.5 155 18.2 8.5 139 19.7 7.0 120 40 244 13.1 18.7 228 14.2 16.1 213 15.3 13.9 197 16.9 11.7 180 18.8 9.6 163 20.5 7.9 131 45 274 13.6 20.1 257 14.8 17.4 240 15.9 15.2 223 17.4 12.8 204 19.4 10.5 186 21.2 8.8 143 50 303 14.2 21.4 286 15.4 18.6 268 16.4 16.4 249 18.0 13.8 229 20.0 11.4 210 21.9 9.6 157 55 332 14.8 22.5 315 15.9 19.7 296 17.0 17.5 275 18.6 14.8 253 20.6 12.3 233 22.6 10.3 108 35 210 12.4 17.0 196 13.6 14.3 184 15.1 12.2 173 16.7 10.4 157 18.9 8.3 137 21.2 6.5 120 40 237 12.7 18.6 221 14.0 15.8 208 15.4 13.5 195 17.0 11.5 179 19.2 9.4 161 21.4 7.5 131 45 264 13.1 20.1 247 14.3 17.3 231 15.7 14.8 217 17.3 12.6 201 19.5 10.3 184 21.7 8.5 143 50 291 13.5 21.6 273 14.7 18.6 255 15.9 16.0 239 17.6 13.6 223 19.8 11.3 207 22.0 9.4 157 55 317 13.8 22.9 299 15.0 19.9 279 16.2 17.2 261 17.9 14.6 245 20.1 12.2 230 22.3 10.4 108 35 271 17.3 15.7 245 18.6 13.2 215 20.0 10.8 201 22.5 9.0 193 24.9 7.8 188 26.9 7.0 120 40 310 17.8 17.4 282 19.3 14.6 253 20.7 12.2 236 23.1 10.2 223 25.6 8.7 213 27.9 7.6 131 45 348 18.4 19.0 320 20.0 16.0 290 21.4 13.6 271 23.7 11.4 253 26.3 9.6 238 28.8 8.3 143 50 387 18.9 20.4 357 20.6 17.3 328 22.2 14.8 306 24.2 12.6 283 27.1 10.4 263 29.7 8.8 157 55 425 19.5 21.8 395 21.3 18.5 365 22.9 16.0 340 24.8 13.7 313 27.8 11.2 288 30.7 9.4
65 75 85 95 105 115
Temperature of Air on Condenser Coil °F
50 Johnson Controls Unitary Products
Page 51
Heat Pump and Air Handling Cooling Capacities PH-07/NH-07 Cooling Capacities
Air on
Evaporator Coil CFM
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
Total WB (°F)
Capacity
(MBh)
77 112.8 5.9 54.5 44.9 35.3 - - - 107.0 6.5 51.9 42.4 32.9 - - ­72 104.8 5.8 68.7 59.1 49.5 40.0 - - 99.3 6.4 66.3 56.8 47.3 37.9 - ­67 96.7 5.7 82.9 73.4 63.8 54.2 44.6 - 91.7 6.3 80.8 71.3 61.8 52.3 42.8 ­62 89.0 5.5 89.0 89.0 80.5 70.9 61.3 51.7 84.4 6.2 84.4 84.4 76.5 67.0 57.5 48.0 57 88.9 5.6 88.9 88.9 80.5 70.9 61.4 51.8 84.6 6.2 84.6 84.6 75.7 66.2 56.8 47.3 77 117.0 5.9 58.7 48.7 37.9 - - - 110.7 6.6 57.0 46.2 35.5 - - ­72 108.6 5.8 74.8 64.0 53.2 42.5 - - 102.7 6.5 72.5 61.8 51.1 40.4 - ­67 100.3 5.7 90.9 79.3 68.5 57.8 47.0 - 94.8 6.3 88.1 77.4 66.7 56.0 45.3 ­62 92.3 5.6 92.3 92.3 86.5 76.2 64.9 54.1 87.3 6.2 87.3 87.3 82.6 71.9 61.1 50.4 57 92.2 5.6 92.2 92.2 86.6 76.3 65.0 54.2 87.5 6.2 87.5 87.5 81.7 71.0 60.3 49.6 77 121.1 5.9 63.0 52.6 40.6 - - - 114.3 6.6 62.0 50.1 38.1 - - ­72 112.5 5.8 80.9 68.9 56.9 45.0 - - 106.1 6.5 78.7 66.8 54.9 42.9 - ­67 103.8 5.7 98.9 85.3 73.3 61.3 49.3 - 97.9 6.4 95.4 83.5 71.6 59.6 47.7 ­62 95.6 5.6 95.6 95.6 92.5 81.5 68.6 56.6 90.2 6.3 90.2 90.2 88.6 76.7 64.8 52.8 57 95.4 5.6 95.4 95.4 92.6 81.7 68.6 56.6 90.4 6.2 90.4 90.4 87.7 75.8 63.9 51.9 72 114.6 5.8 88.6 75.6 62.6 49.6 - - 108.6 6.5 85.9 73.0 60.0 47.1 - ­67 105.7 5.7 103.3 93.6 80.6 67.6 54.6 - 100.3 6.4 99.0 91.3 78.3 65.4 52.4 ­62 97.4 5.6 97.4 97.4 95.8 83.3 69.8 56.8 92.3 6.3 92.3 92.3 91.6 78.6 65.7 52.7 57 97.2 5.6 97.2 97.2 95.8 83.3 69.7 56.7 92.5 6.3 92.5 92.5 91.2 78.3 65.3 52.3 72 116.6 5.8 96.3 82.3 68.3 54.2 - - 111.2 6.5 93.1 79.2 65.2 51.2 - ­67 107.7 5.7 107.7 101.9 87.9 73.8 59.8 - 102.6 6.4 102.6 99.0 85.1 71.1 57.1 ­62 99.1 5.6 99.1 99.1 99.1 85.1 71.0 57.0 94.5 6.3 94.5 94.5 94.5 80.5 66.5 52.6 57 99.0 5.6 99.0 99.0 99.0 84.9 70.9 56.8 94.7 6.3 94.7 94.7 94.7 80.7 66.7 52.8
77 101.2 7.2 49.3 39.9 30.6 - - - 100.5 8.0 59.5 50.1 40.7 - - ­72 93.9 7.1 63.9 54.6 45.2 35.8 - - 90.2 7.9 67.7 58.3 48.9 39.4 - ­67 86.6 7.0 78.6 69.2 59.8 50.4 41.0 - 79.9 7.8 75.8 66.4 57.0 47.6 38.2 ­62 79.8 6.9 79.8 79.8 72.5 63.1 53.7 44.4 74.8 7.7 74.8 74.8 67.3 57.9 48.5 39.0 57 80.3 6.8 80.3 80.3 70.9 61.5 52.1 42.8 74.9 7.7 74.9 74.9 65.7 56.2 46.8 37.4 77 104.3 7.3 55.2 43.8 33.1 - - - 103.7 8.0 68.8 55.1 44.4 - - ­72 96.8 7.1 70.2 59.6 49.0 38.3 - - 93.0 8.0 74.6 63.9 53.3 42.6 - ­67 89.3 7.0 85.3 75.4 64.8 54.2 43.5 - 82.4 7.9 80.4 72.8 62.1 51.4 40.8 ­62 82.3 6.9 82.3 82.3 78.6 67.5 57.4 46.7 77.2 7.7 77.2 77.2 73.3 62.4 52.0 41.3 57 82.8 6.9 82.8 82.8 76.9 65.7 55.6 45.0 77.2 7.7 77.2 77.2 71.5 60.6 50.2 39.5 77 107.5 7.3 61.0 47.6 35.7 - - - 106.8 8.1 78.1 60.0 48.1 - - ­72 99.7 7.2 76.5 64.6 52.8 40.9 - - 95.9 8.0 81.5 69.6 57.7 45.8 - ­67 92.0 7.0 92.0 81.7 69.8 57.9 46.1 - 84.9 7.9 84.9 79.1 67.2 55.3 43.4 ­62 84.7 6.9 84.7 84.7 84.7 71.9 61.0 49.1 79.6 7.8 79.6 79.6 79.3 66.9 55.5 43.6 57 85.3 6.9 85.3 85.3 82.9 69.9 59.1 47.2 79.6 7.7 79.6 79.6 77.4 64.9 53.6 41.6 72 102.7 7.2 83.2 70.3 57.4 44.6 - - 98.8 8.0 87.6 76.1 63.2 50.2 - ­67 94.8 7.1 94.8 88.9 76.0 63.1 50.2 - 87.5 7.9 87.5 84.2 73.6 60.6 47.7 ­62 87.3 6.9 87.3 87.3 87.3 73.9 61.5 48.6 82.0 7.8 82.0 82.0 81.8 68.6 55.9 43.0 57 87.8 6.9 87.8 87.8 86.6 73.2 60.8 48.0 82.0 7.8 82.0 82.0 80.9 67.7 55.0 42.1 72 105.7 7.2 89.9 76.0 62.1 48.2 - - 101.7 8.0 93.8 82.7 68.7 54.7 - ­67 97.5 7.1 97.5 96.1 82.2 68.3 54.4 - 90.1 7.9 90.1 89.4 79.9 65.9 52.0 ­62 89.8 7.0 89.8 89.8 89.8 75.9 62.0 48.1 84.4 7.8 84.4 84.4 84.4 70.4 56.4 42.4 57 90.4 6.9 90.4 90.4 90.4 76.5 62.6 48.7 84.4 7.8 84.4 84.4 84.4 70.5 56.5 42.5
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
505430-BTG-P-0316
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 51
Page 52
505430-BTG-P-0316
PH-07/NH-07 Cooling Capacities (Continued)
Air on
Evaporator Coil CFM
2250
2625
3000
3375
3750
1
WB (°F)
77 99.8 8.8 69.7 60.3 50.9 - - - 99.1 9.6 79.9 70.5 61.0 - - ­72 86.5 8.7 71.4 62.0 52.6 43.1 - - 82.7 9.5 75.2 65.7 56.3 46.8 - ­67 73.1 8.7 73.1 63.7 54.2 44.8 35.4 - 66.4 9.5 66.4 60.9 51.5 42.0 32.6 ­62 69.9 8.5 69.9 69.9 62.0 52.6 43.2 33.7 64.9 9.4 64.9 64.9 56.8 47.3 37.9 28.4 57 69.5 8.5 69.5 69.5 60.4 50.9 41.5 32.1 64.1 9.4 64.1 64.1 55.1 45.6 36.2 26.7 77 103.0 8.8 82.4 66.4 55.7 - - - 102.3 9.6 92.7 77.7 67.0 - - ­72 89.2 8.8 78.9 68.2 57.6 46.9 - - 85.4 9.6 83.3 72.6 61.9 51.2 - ­67 75.5 8.7 75.5 70.1 59.4 48.7 38.0 - 68.5 9.6 68.5 67.4 56.7 46.0 35.3 ­62 72.1 8.6 72.1 72.1 67.9 57.3 46.6 35.9 67.0 9.4 67.0 67.0 62.6 52.1 41.2 30.5 57 71.7 8.6 71.7 71.7 66.1 55.4 44.8 34.1 66.2 9.4 66.2 66.2 60.7 50.3 39.3 28.6 77 106.2 8.9 95.1 72.5 60.5 - - - 105.6 9.7 105.6 84.9 73.0 - - ­72 92.0 8.8 86.4 74.5 62.6 50.6 - - 88.1 9.6 88.1 79.4 67.5 55.5 - ­67 77.8 8.7 77.8 76.5 64.6 52.6 40.7 - 70.7 9.6 70.7 70.7 62.0 50.0 38.0 ­62 74.4 8.6 74.4 74.4 73.8 61.9 50.0 38.0 69.2 9.5 69.2 69.2 68.4 56.9 44.5 32.5 57 73.9 8.6 73.9 73.9 71.9 59.9 48.0 36.1 68.3 9.5 68.3 68.3 66.4 54.9 42.4 30.5 72 94.8 8.8 92.1 81.9 68.9 55.9 - - 90.9 9.7 90.9 87.7 74.6 61.5 - ­67 80.2 8.8 80.2 79.6 71.1 58.1 45.1 - 72.9 9.6 72.9 72.9 68.7 55.6 42.5 ­62 76.7 8.6 76.7 76.7 76.4 63.4 50.4 37.4 71.3 9.5 71.3 71.3 71.0 58.1 44.8 31.7 57 76.2 8.6 76.2 76.2 75.2 62.2 49.2 36.2 70.4 9.5 70.4 70.4 69.5 56.7 43.3 30.3 72 97.7 8.8 97.7 89.3 75.2 61.1 - - 93.7 9.7 93.7 93.7 81.8 67.6 - ­67 82.6 8.8 82.6 82.6 77.7 63.6 49.5 - 75.2 9.6 75.2 75.2 75.2 61.2 47.0 ­62 79.0 8.7 79.0 79.0 79.0 64.9 50.8 36.7 73.5 9.5 73.5 73.5 73.5 59.3 45.2 31.0 57 78.5 8.6 78.5 78.5 78.5 64.4 50.3 36.3 72.6 9.5 72.6 72.6 72.6 58.4 44.2 30.0
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
52 Johnson Controls Unitary Products
Page 53

PH-10/NH-10

Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
3000
3500
4000
4500
5000
WB (°F)
77 140.5 7.5 70.2 58.2 46.2 - - - 134.2 8.6 65.0 52.8 40.6 - - ­72 133.6 7.5 87.5 75.5 63.5 51.5 - - 127.3 8.5 84.4 72.2 59.9 47.7 - ­67 126.6 7.4 104.8 92.8 80.8 68.9 56.9 - 120.3 8.5 103.8 91.5 79.3 67.1 54.8 ­62 120.2 7.4 120.2 120.2 107.7 95.7 83.8 71.8 113.2 8.4 113.2 113.2 101.2 88.9 76.7 64.5 57 121.8 7.3 121.8 123.0 114.5 102.5 90.5 78.6 117.1 8.4 117.1 117.1 106.6 94.4 82.2 69.9 77 147.3 7.7 74.8 62.4 49.1 - - - 140.4 8.7 71.4 57.6 43.7 - - ­72 140.0 7.6 93.9 80.6 67.3 54.1 - - 133.2 8.7 92.3 78.4 64.6 50.7 - ­67 132.8 7.6 112.9 98.8 85.5 72.3 59.0 - 125.9 8.6 113.2 99.3 85.5 71.6 57.8 ­62 126.0 7.6 126.0 126.0 114.2 101.0 87.6 74.4 118.5 8.5 118.5 118.5 109.0 95.2 81.3 67.5 57 127.7 7.5 127.7 128.3 121.4 108.7 94.9 81.6 122.5 8.5 122.5 122.5 114.9 101.1 87.2 73.4 77 154.1 7.8 79.4 66.6 52.0 - - - 146.6 8.9 77.8 62.3 46.9 - - ­72 146.5 7.8 100.2 85.7 71.1 56.6 - - 139.0 8.8 100.2 84.7 69.2 53.8 - ­67 138.9 7.8 121.1 104.8 90.2 75.7 61.1 - 131.5 8.7 122.5 107.1 91.6 76.2 60.7 ­62 131.8 7.8 131.8 131.8 120.6 106.3 91.5 76.9 123.7 8.7 123.7 123.7 116.9 101.4 86.0 70.5 57 133.6 7.6 133.6 133.6 128.3 114.8 99.2 84.6 127.9 8.6 127.9 127.9 123.2 107.7 92.3 76.8 72 148.2 7.7 110.0 94.1 78.1 62.2 - - 140.9 8.7 108.1 91.5 74.8 58.1 - ­67 140.5 7.7 131.6 115.2 99.3 83.4 67.5 - 133.2 8.6 128.7 115.6 99.0 82.3 65.6 ­62 133.4 7.7 133.4 133.4 127.8 112.0 95.9 80.0 125.3 8.6 125.3 125.3 121.9 105.3 88.6 71.9 57 135.2 7.5 135.2 135.2 132.5 117.2 100.7 84.8 129.6 8.6 129.6 129.6 127.2 110.6 93.9 77.2 72 150.0 7.6 119.7 102.4 85.1 67.9 - - 142.7 8.6 116.1 98.2 80.3 62.5 - ­67 142.2 7.5 142.2 125.6 108.3 91.1 73.8 - 134.9 8.5 134.9 124.2 106.3 88.4 70.5 ­62 134.9 7.5 134.9 134.9 134.9 117.6 100.4 83.1 127.0 8.5 127.0 127.0 127.0 109.1 91.2 73.3 57 136.7 7.4 136.7 136.7 136.7 119.5 102.2 84.9 131.3 8.5 131.3 131.3 131.3 113.4 95.5 77.6
77 128.0 9.7 59.9 47.4 34.9 - - - 120.6 10.9 59.2 46.6 34.0 - - ­72 121.0 9.6 81.3 68.8 56.3 43.8 - - 113.1 10.8 79.6 67.0 54.4 41.8 - ­67 114.1 9.5 102.8 90.3 77.8 65.3 52.8 - 105.6 10.7 100.0 87.4 74.7 62.1 49.5 ­62 106.3 9.3 106.3 106.3 94.7 82.2 69.7 57.2 101.1 10.6 101.1 101.1 90.6 78.0 65.4 52.8 57 112.4 9.5 112.4 111.3 98.8 86.3 73.8 61.3 104.8 10.7 104.8 104.2 92.7 80.1 67.5 54.9 77 133.6 9.8 68.0 52.7 38.3 - - - 126.1 11.0 69.7 51.8 37.3 - - ­72 126.3 9.7 90.7 76.3 61.9 47.4 - - 118.3 10.9 88.6 74.1 59.6 45.1 - ­67 119.0 9.6 113.4 99.8 85.4 71.0 56.5 - 110.4 10.8 107.6 96.5 82.0 67.5 53.0 ­62 111.0 9.4 111.0 111.0 103.9 89.4 75.1 60.6 105.7 10.7 105.7 105.7 99.3 84.8 70.3 55.8 57 117.3 9.6 117.3 116.7 108.4 93.4 79.6 65.1 109.5 10.8 109.5 109.3 101.6 86.9 72.6 58.1 77 139.1 9.9 76.2 58.1 41.7 - - - 131.6 11.1 80.1 56.9 40.5 - - ­72 131.6 9.8 100.1 83.7 67.4 51.0 - - 123.4 11.0 97.7 81.3 64.9 48.5 - ­67 124.0 9.7 124.0 109.4 93.0 76.6 60.3 - 115.2 10.9 115.2 105.6 89.2 72.8 56.4 ­62 115.6 9.5 115.6 115.6 113.2 96.5 80.5 64.1 110.3 10.8 110.3 110.3 108.1 91.6 75.3 58.9 57 122.2 9.7 122.2 122.2 118.1 100.6 85.4 69.0 114.3 10.9 114.3 114.3 110.6 93.6 77.8 61.4 72 133.5 9.7 106.3 88.9 71.5 54.0 - - 124.9 10.9 104.6 86.9 69.3 51.7 - ­67 125.8 9.6 125.8 116.1 98.6 81.2 63.8 - 116.6 10.8 116.6 110.6 95.3 77.7 60.1 ­62 117.3 9.5 117.3 117.3 116.1 98.5 81.2 63.8 111.6 10.7 111.6 111.6 110.5 92.8 75.3 57.6 57 124.0 9.6 124.0 124.0 122.0 104.0 87.1 69.7 115.7 10.8 115.7 115.7 113.8 95.9 78.6 61.0 72 135.4 9.6 112.5 94.0 75.5 57.0 - - 126.3 10.9 111.5 92.6 73.8 55.0 - ­67 127.6 9.5 127.6 122.8 104.3 85.8 67.3 - 118.0 10.8 118.0 115.5 101.5 82.6 63.8 ­62 119.0 9.4 119.0 119.0 119.0 100.5 82.0 63.5 112.9 10.7 112.9 112.9 112.9 94.1 75.2 56.4 57 125.8 9.5 125.8 125.8 125.8 107.3 88.8 70.3 117.0 10.7 117.0 117.0 117.0 98.2 79.4 60.5
Total
Capacity
(MBh)
505430-BTG-P-0316
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 53
Page 54
505430-BTG-P-0316
PH-10/NH-10 (Continued)
Air on
Evaporator Coil
CFM
3000
3500
4000
4500
5000
1
WB (°F)
77 113.3 12.1 58.5 45.8 33.1 - - - 105.9 13.2 57.8 45.0 32.1 - - ­72 105.2 12.0 77.8 65.1 52.4 39.7 - - 97.3 13.2 76.1 63.2 50.4 37.6 - ­67 97.2 11.9 97.2 84.4 71.7 59.0 46.3 - 88.7 13.1 88.7 81.5 68.7 55.8 43.0 ­62 95.9 11.8 95.9 95.9 86.5 73.8 61.1 48.4 90.6 13.1 90.6 90.6 82.5 69.6 56.8 43.9 57 97.1 11.8 97.1 97.1 86.6 73.9 61.2 48.4 89.5 13.0 89.5 89.5 80.5 67.7 54.8 42.0 77 118.7 12.2 71.3 50.8 36.2 - - - 111.3 13.4 72.9 49.8 35.2 - - ­72 110.2 12.1 86.5 72.0 57.4 42.8 - - 102.2 13.3 84.4 69.8 55.1 40.5 - ­67 101.8 12.0 101.8 93.1 78.5 64.0 49.4 - 93.2 13.2 93.2 89.8 75.1 60.4 45.8 ­62 100.4 11.9 100.4 100.4 94.8 80.2 65.6 51.0 95.2 13.2 95.2 95.2 90.2 75.6 60.9 46.2 57 101.8 12.0 101.8 101.8 94.8 80.3 65.7 51.1 94.0 13.2 94.0 94.0 88.1 73.7 58.8 44.1 77 124.1 12.3 84.0 55.8 39.4 - - - 116.6 13.5 88.0 54.6 38.2 - - ­72 115.3 12.2 95.2 78.8 62.4 45.9 - - 107.1 13.4 92.8 76.3 59.9 43.4 - ­67 106.4 12.1 106.4 101.8 85.4 68.9 52.5 - 97.7 13.3 97.7 97.7 81.5 65.1 48.6 ­62 105.0 12.1 105.0 105.0 103.0 86.6 70.1 53.7 99.7 13.3 99.7 99.7 97.9 81.6 65.0 48.5 57 106.4 12.1 106.4 106.4 103.1 86.7 70.2 53.8 98.5 13.3 98.5 98.5 95.6 79.7 62.7 46.2 72 116.3 12.1 102.8 85.0 67.2 49.4 - - 107.6 13.3 101.0 83.1 65.1 47.1 - ­67 107.3 12.0 107.3 105.0 92.0 74.2 56.4 - 98.1 13.3 98.1 98.1 88.7 70.7 52.7 ­62 105.9 12.0 105.9 105.9 104.9 87.1 69.3 51.5 100.2 13.2 100.2 100.2 99.3 81.4 63.3 45.4 57 107.3 12.0 107.3 107.3 105.7 87.9 70.1 52.3 98.9 13.2 98.9 98.9 97.5 79.8 61.5 43.6 72 117.2 12.1 110.4 91.2 72.0 52.9 - - 108.1 13.3 108.1 89.8 70.3 50.8 - ­67 108.3 12.0 108.3 108.3 98.6 79.5 60.3 - 98.6 13.2 98.6 98.6 95.8 76.3 56.8 ­62 106.8 11.9 106.8 106.8 106.8 87.6 68.5 49.3 100.7 13.2 100.7 100.7 100.7 81.2 61.7 42.2 57 108.2 11.9 108.2 108.2 108.2 89.0 69.9 50.7 99.4 13.1 99.4 99.4 99.4 79.9 60.4 40.9
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
(kW)
Total Input
Sensible Capacity (MBh)
2
nameplate rated motor
54 Johnson Controls Unitary Products
Page 55
PH-15/NH-15
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB (°F)
77 223.0 12.5 104.1 85.2 66.4 - - - 216.7 13.8 104.7 85.9 67.0 - - ­72 209.3 12.3 134.7 115.8 97.0 78.1 - - 200.9 13.6 133.0 114.1 95.2 76.3 - ­67 195.7 12.1 165.2 146.4 127.6 108.7 89.9 - 185.0 13.4 161.2 142.3 123.4 104.5 85.7 ­62 176.7 11.8 176.7 176.7 152.0 133.2 114.3 95.5 169.4 13.0 169.4 169.4 151.2 132.4 113.5 94.6 57 179.6 11.8 179.6 179.6 159.1 140.3 121.4 102.6 173.1 13.1 173.1 173.1 154.4 135.5 116.7 97.8 77 229.0 12.6 113.8 93.3 71.8 - - - 221.4 13.9 114.8 93.3 71.7 - - ­72 215.0 12.4 147.9 126.3 104.8 83.3 - - 205.2 13.6 145.0 123.5 101.9 80.3 - ­67 200.9 12.2 181.9 159.4 137.8 116.3 94.8 - 189.1 13.4 175.2 153.7 132.1 110.5 88.9 ­62 181.4 11.8 181.4 181.4 164.3 143.6 121.3 99.8 173.0 13.1 173.0 173.0 161.9 140.3 118.7 97.1 57 184.5 11.9 184.5 184.5 171.9 151.4 128.9 107.4 176.9 13.1 176.9 176.9 165.3 143.7 122.1 100.6 77 235.0 12.6 123.5 101.4 77.2 - - - 226.1 13.9 124.9 100.6 76.4 - - ­72 220.6 12.4 161.0 136.9 112.7 88.5 - - 209.6 13.7 157.1 132.8 108.6 84.3 - ­67 206.2 12.2 198.5 172.3 148.1 123.9 99.8 - 193.1 13.4 189.3 165.0 140.8 116.5 92.2 ­62 186.2 11.9 186.2 186.2 176.7 154.1 128.3 104.1 176.7 13.1 176.7 176.7 172.5 148.2 124.0 99.7 57 189.3 11.9 189.3 189.3 184.8 162.6 136.4 112.2 180.6 13.2 180.6 180.6 176.1 151.8 127.6 103.3 72 223.2 12.5 170.5 144.3 118.1 91.9 - - 213.0 13.7 168.5 142.1 115.7 89.3 - ­67 208.6 12.3 204.8 181.5 155.3 129.1 102.9 - 196.2 13.5 194.3 176.4 150.0 123.6 97.3 ­62 188.4 11.9 188.4 188.4 183.6 158.3 131.3 105.1 179.6 13.2 179.6 179.6 177.5 151.1 124.7 98.3 57 191.6 12.0 191.6 191.6 189.3 164.1 136.9 110.7 183.6 13.2 183.6 183.6 181.3 154.9 128.5 102.2 72 225.9 12.6 179.9 151.7 123.5 95.3 - - 216.4 13.8 179.9 151.4 122.9 94.4 - ­67 211.1 12.4 211.1 190.7 162.5 134.3 106.1 - 199.4 13.5 199.4 187.8 159.3 130.8 102.3 ­62 190.6 12.0 190.6 190.6 190.6 162.4 134.2 106.0 182.5 13.2 182.5 182.5 182.5 154.0 125.5 97.0 57 193.8 12.1 193.8 193.8 193.8 165.6 137.4 109.2 186.5 13.3 186.5 186.5 186.5 158.0 129.5 101.0
77 210.5 15.1 105.4 86.5 67.6 - - - 192.8 16.7 98.9 80.0 61.1 - - ­72 192.4 14.9 131.3 112.4 93.4 74.5 - - 177.2 16.5 125.6 106.7 87.8 68.9 - ­67 174.4 14.6 157.1 138.2 119.3 100.4 81.4 - 161.6 16.3 152.4 133.5 114.6 95.7 76.8 ­62 162.0 14.3 162.0 162.0 150.5 131.6 112.6 93.7 150.1 16.0 150.1 150.1 142.4 123.5 104.6 85.7 57 166.6 14.4 166.6 166.6 149.8 130.8 111.9 93.0 155.1 16.1 155.1 155.1 137.9 119.0 100.1 81.2 77 213.8 15.2 115.9 93.2 71.6 - - - 196.5 16.7 114.1 86.9 65.3 - - ­72 195.5 14.9 142.2 120.6 99.0 77.3 - - 180.6 16.5 137.1 115.5 93.8 72.2 - ­67 177.2 14.6 168.6 148.0 126.3 104.7 83.1 - 164.7 16.3 160.1 144.1 122.4 100.8 79.2 ­62 164.7 14.4 164.7 164.7 159.4 136.9 116.1 94.5 153.0 16.1 153.0 153.0 152.2 130.1 108.9 87.3 57 169.2 14.4 169.2 169.2 158.6 136.0 115.3 93.7 158.1 16.1 158.1 158.1 147.3 125.2 104.1 82.4 77 217.2 15.2 126.3 99.9 75.6 - - - 200.2 16.8 129.3 93.8 69.4 - - ­72 198.6 14.9 153.1 128.8 104.5 80.1 - - 184.1 16.5 148.6 124.2 99.9 75.5 - ­67 180.0 14.6 180.0 157.7 133.4 109.0 84.7 - 167.9 16.3 167.9 154.7 130.3 106.0 81.6 ­62 167.3 14.4 167.3 167.3 168.3 142.3 119.6 95.3 155.9 16.1 155.9 155.9 162.0 136.8 113.2 88.9 57 171.9 14.4 171.9 171.9 167.5 141.1 118.8 94.5 161.1 16.1 161.1 161.1 156.7 131.4 108.0 83.7 72 202.8 15.0 166.5 139.9 113.4 86.8 - - 187.4 16.6 160.8 134.3 107.7 81.1 - ­67 183.8 14.7 183.8 171.3 144.7 118.2 91.6 - 170.9 16.4 170.9 163.6 140.5 113.9 87.3 ­62 170.8 14.4 170.8 170.8 171.3 143.9 118.2 91.6 158.7 16.1 158.7 158.7 161.7 134.7 108.6 82.0 57 175.6 14.5 175.6 175.6 173.3 145.8 120.2 93.6 164.0 16.2 164.0 164.0 161.8 134.7 108.6 82.1 72 207.0 15.0 179.8 151.0 122.2 93.5 - - 190.7 16.6 173.1 144.3 115.5 86.7 - ­67 187.6 14.7 187.6 184.9 156.1 127.3 98.5 - 173.9 16.4 173.9 172.5 150.7 121.9 93.1 ­62 174.3 14.4 174.3 174.3 174.3 145.5 116.7 87.9 161.5 16.2 161.5 161.5 161.5 132.7 103.9 75.1 57 179.2 14.5 179.2 179.2 179.2 150.4 121.6 92.8 166.8 16.2 166.8 166.8 166.8 138.1 109.3 80.5
Total
Capacity
(MBh)
505430-BTG-P-0316
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 55
Page 56
505430-BTG-P-0316
PH-15/NH-15 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB (°F)
77 175.1 18.3 92.4 73.5 54.6 - - - 157.4 19.9 85.8 67.0 48.1 - - ­72 162.0 18.1 120.0 101.1 82.2 63.3 - - 146.7 19.8 114.3 95.5 76.6 57.8 - ­67 148.8 18.0 147.6 128.7 109.8 91.0 72.1 - 136.1 19.6 136.1 124.0 105.1 86.3 67.4 ­62 138.1 17.8 138.1 138.1 134.4 115.5 96.6 77.7 126.2 19.5 126.2 126.2 126.2 107.5 88.6 69.7 57 143.6 17.8 143.6 143.6 126.1 107.2 88.3 69.4 132.1 19.6 132.1 132.1 114.2 95.4 76.5 57.6 77 179.2 18.3 112.3 80.6 58.9 - - - 161.8 19.9 110.6 74.3 52.6 - - ­72 165.7 18.1 132.0 110.4 88.7 67.1 - - 150.8 19.8 126.9 105.3 83.6 62.0 - ­67 152.3 18.0 151.7 140.2 118.6 96.9 75.3 - 139.9 19.6 139.9 136.3 114.7 93.0 71.4 ­62 141.3 17.8 141.3 141.3 145.0 123.4 101.7 80.1 129.7 19.5 129.7 129.7 129.7 116.6 94.6 72.9 57 146.9 17.8 146.9 146.9 136.1 114.4 92.8 71.1 135.7 19.6 135.7 135.7 124.8 103.6 81.5 59.9 77 183.2 18.3 132.3 87.6 63.3 - - - 166.2 19.9 135.3 81.5 57.1 - - ­72 169.5 18.1 144.0 119.6 95.3 70.9 - - 154.9 19.8 139.5 115.1 90.6 66.2 - ­67 155.8 18.0 155.8 151.6 127.3 102.9 78.5 - 143.6 19.6 143.6 143.6 124.2 99.8 75.4 ­62 144.5 17.8 144.5 144.5 155.7 131.3 106.9 82.5 133.2 19.5 133.2 133.2 133.2 125.8 100.5 76.1 57 150.2 17.9 150.2 150.2 146.0 121.6 97.3 72.9 139.4 19.6 139.4 139.4 135.3 111.9 86.5 62.1 72 171.9 18.2 155.2 128.6 102.0 75.4 - - 156.4 19.8 149.5 122.9 96.3 69.7 - ­67 158.0 18.0 158.0 155.9 136.3 109.7 83.1 - 145.1 19.7 145.1 145.1 132.0 105.4 78.8 ­62 146.6 17.8 146.6 146.6 152.1 125.6 99.0 72.4 134.5 19.5 134.5 134.5 134.5 116.4 89.4 62.7 57 152.4 17.9 152.4 152.4 150.3 123.7 97.1 70.5 140.8 19.6 140.8 140.8 138.8 112.7 85.5 58.9 72 174.3 18.2 166.3 137.5 108.8 80.0 - - 158.0 19.9 158.0 130.8 102.0 73.2 - ­67 160.2 18.1 160.2 160.2 145.3 116.5 87.7 - 146.5 19.8 146.5 146.5 139.9 111.1 82.3 ­62 148.6 17.9 148.6 148.6 148.6 119.8 91.0 62.3 135.8 19.6 135.8 135.8 135.8 107.0 78.2 49.4 57 154.5 18.0 154.5 154.5 154.5 125.7 96.9 68.1 142.2 19.7 142.2 142.2 142.2 113.4 84.6 55.8
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
56 Johnson Controls Unitary Products
Page 57
PJ-15/NJ-15
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
4500
5250
6000
6750
7500
WB (°F)
77 231.4 12.4 111.6 93.0 74.5 - - - 219.9 13.7 106.4 87.9 69.5 - - ­72 215.6 12.0 142.9 124.4 105.8 87.2 - - 204.0 13.4 138.2 119.7 101.2 82.8 - ­67 199.7 11.7 174.3 155.7 137.2 118.6 100.0 - 188.1 13.1 169.9 151.4 133.0 114.5 96.0 ­62 183.7 11.4 183.7 183.7 170.7 152.1 133.6 115.0 174.3 12.8 174.3 174.3 163.8 145.3 126.9 108.4 57 184.6 11.4 184.6 184.6 173.2 154.6 136.1 117.5 175.3 12.8 175.3 175.3 164.8 146.3 127.8 109.4 77 233.6 12.4 117.3 98.2 76.9 - - - 222.0 13.7 114.1 92.9 71.7 - - ­72 217.6 12.1 151.9 130.6 109.3 88.0 - - 206.0 13.4 146.9 125.7 104.5 83.3 - ­67 201.6 11.7 186.5 163.0 141.7 120.4 99.1 - 189.9 13.1 179.7 158.5 137.2 116.0 94.8 ­62 185.5 11.4 185.5 185.5 176.3 155.6 133.7 112.4 176.0 12.8 176.0 176.0 169.1 147.9 126.6 105.4 57 186.3 11.4 186.3 186.3 178.9 158.5 136.3 115.0 177.0 12.8 177.0 177.0 170.1 148.8 127.6 106.4 77 235.8 12.4 123.1 103.4 79.4 - - - 224.2 13.7 121.8 97.9 73.9 - - ­72 219.7 12.1 160.9 136.9 112.8 88.7 - - 208.0 13.4 155.6 131.7 107.7 83.8 - ­67 203.5 11.7 198.8 170.3 146.2 122.2 98.1 - 191.8 13.1 189.4 165.5 141.5 117.6 93.6 ­62 187.2 11.4 187.2 187.2 182.0 159.2 133.8 109.8 177.7 12.9 177.7 177.7 174.3 150.4 126.4 102.5 57 188.0 11.4 188.0 188.0 184.6 162.4 136.5 112.4 178.7 12.9 178.7 178.7 175.4 151.4 127.5 103.5 72 222.5 12.1 171.1 144.6 118.1 91.7 - - 210.6 13.5 165.7 139.4 113.2 86.9 - ­67 206.2 11.8 203.8 179.6 153.2 126.7 100.2 - 194.2 13.2 193.0 174.9 148.6 122.4 96.1 ­62 189.7 11.5 189.7 189.7 187.0 161.2 134.1 107.6 180.0 12.9 180.0 180.0 178.3 152.0 125.7 99.5 57 190.5 11.5 190.5 190.5 188.8 163.3 135.9 109.4 181.0 12.9 181.0 181.0 179.3 153.1 126.8 100.5 72 225.4 12.2 181.3 152.4 123.5 94.6 - - 213.3 13.6 175.8 147.2 118.6 90.0 - ­67 208.9 11.8 208.9 189.0 160.1 131.2 102.3 - 196.7 13.2 196.7 184.4 155.8 127.2 98.6 ­62 192.1 11.5 192.1 192.1 192.1 163.2 134.3 105.5 182.2 13.0 182.2 182.2 182.2 153.6 125.0 96.4 57 193.0 11.5 193.0 193.0 193.0 164.1 135.2 106.3 183.3 13.0 183.3 183.3 183.3 154.7 126.1 97.5
77 208.3 15.1 101.3 82.9 64.5 - - - 192.0 17.0 96.4 77.9 59.4 - - ­72 192.4 14.8 133.4 115.0 96.6 78.3 - - 177.3 16.7 128.6 110.2 91.7 73.2 - ­67 176.4 14.5 165.5 147.2 128.8 110.4 92.0 - 162.5 16.4 157.1 142.5 124.0 105.5 87.0 ­62 164.9 14.3 164.9 164.9 156.9 138.5 120.2 101.8 153.2 16.2 153.2 153.2 149.2 130.7 112.3 93.8 57 166.1 14.3 166.1 166.1 156.3 138.0 119.6 101.2 155.2 16.2 155.2 155.2 146.0 127.5 109.0 90.6 77 210.5 15.1 110.9 87.6 66.5 - - - 193.9 17.0 110.4 82.4 61.2 - - ­72 194.3 14.8 141.9 120.8 99.7 78.5 - - 179.0 16.7 136.8 115.7 94.5 73.4 - ­67 178.2 14.5 172.8 153.9 132.8 111.7 90.6 - 164.1 16.4 161.4 149.0 127.8 106.6 85.5 ­62 166.5 14.3 166.5 166.5 161.8 140.1 119.6 98.5 154.7 16.2 154.7 154.7 154.2 132.7 111.9 90.7 57 167.8 14.3 167.8 167.8 161.2 139.2 119.0 97.9 156.8 16.2 156.8 156.8 150.5 128.9 108.2 87.0 77 212.6 15.1 120.6 92.3 68.5 - - - 195.8 17.0 124.4 86.9 63.1 - - ­72 196.3 14.8 150.3 126.5 102.7 78.8 - - 180.8 16.7 145.0 121.2 97.3 73.5 - ­67 180.0 14.5 180.0 160.6 136.8 113.0 89.2 - 165.7 16.4 165.7 155.5 131.6 107.8 83.9 ­62 168.2 14.3 168.2 168.2 166.7 141.6 119.0 95.2 156.2 16.2 156.2 156.2 159.2 134.7 111.5 87.6 57 169.5 14.3 169.5 169.5 166.1 140.4 118.4 94.6 158.3 16.2 158.3 158.3 155.0 130.2 107.3 83.4 72 198.7 14.9 160.3 134.2 108.2 82.1 - - 183.0 16.8 155.6 129.3 103.0 76.7 - ­67 182.2 14.6 182.2 170.2 144.1 118.0 92.0 - 167.8 16.5 167.8 161.5 139.3 113.0 86.7 ­62 170.3 14.3 170.3 170.3 169.5 142.8 117.4 91.3 158.2 16.2 158.2 158.2 159.7 133.0 107.1 80.8 57 171.6 14.4 171.6 171.6 169.9 142.9 117.7 91.6 160.3 16.3 160.3 160.3 158.6 131.9 106.0 79.7 72 201.2 14.9 170.3 142.0 113.6 85.3 - - 185.3 16.8 166.3 137.5 108.8 80.0 - ­67 184.5 14.6 184.5 179.8 151.4 123.1 94.8 - 169.9 16.5 169.9 167.5 147.1 118.3 89.6 ­62 172.4 14.4 172.4 172.4 172.4 144.1 115.7 87.4 160.1 16.3 160.1 160.1 160.1 131.4 102.6 73.9 57 173.7 14.5 173.7 173.7 173.7 145.3 117.0 88.7 162.3 16.4 162.3 162.3 162.3 133.5 104.8 76.0
Total
Capacity
(MBh)
505430-BTG-P-0316
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 57
Page 58
505430-BTG-P-0316
PJ-15/NJ-15 (Continued)
Air on
Evaporator Coil
CFM
4500
5250
6000
6750
7500
1
WB (°F)
77 175.7 18.9 91.5 72.9 54.3 - - - 159.4 20.8 86.6 67.9 49.2 - - ­72 162.2 18.6 123.9 105.3 86.8 68.2 - - 147.1 20.5 119.1 100.5 81.8 63.1 - ­67 148.6 18.2 148.6 137.8 119.2 100.6 82.0 - 134.7 20.1 134.7 133.1 114.4 95.7 77.1 ­62 141.5 18.1 141.5 141.5 141.5 123.0 104.4 85.8 129.9 20.0 129.9 129.9 129.9 115.2 96.5 77.8 57 144.4 18.1 144.4 144.4 135.6 117.1 98.5 79.9 133.6 20.1 133.6 133.6 125.3 106.6 88.0 69.3 77 177.4 18.9 109.8 77.2 56.0 - - - 160.8 20.9 109.2 72.0 50.7 - - ­72 163.7 18.6 131.8 110.6 89.4 68.2 - - 148.4 20.5 126.8 105.5 84.3 63.0 - ­67 150.0 18.3 150.0 144.0 122.8 101.6 80.4 - 135.9 20.1 135.9 135.9 117.8 96.5 75.3 ­62 142.9 18.1 142.9 142.9 146.6 125.4 104.2 82.9 131.0 20.0 131.0 131.0 131.0 118.0 96.4 75.2 57 145.8 18.1 145.8 145.8 139.8 118.5 97.3 76.1 134.8 20.1 134.8 134.8 129.1 108.2 86.5 65.2 77 179.0 18.9 128.1 81.5 57.6 - - - 162.3 20.9 131.9 76.1 52.2 - - ­72 165.2 18.6 139.8 115.9 92.0 68.2 - - 149.7 20.5 134.5 110.6 86.7 62.8 - ­67 151.4 18.3 151.4 150.3 126.4 102.6 78.7 - 137.1 20.1 137.1 137.1 121.3 97.4 73.5 ­62 144.2 18.1 144.2 144.2 151.7 127.8 103.9 80.1 132.2 20.0 132.2 132.2 132.2 120.9 96.4 72.5 57 147.1 18.2 147.1 147.1 143.9 120.0 96.1 72.3 136.0 20.1 136.0 136.0 132.8 109.8 85.0 61.1 72 167.3 18.7 151.0 124.5 97.9 71.4 - - 151.6 20.6 146.3 119.6 92.8 66.1 - ­67 153.3 18.3 153.3 152.8 134.6 108.0 81.5 - 138.9 20.2 138.9 138.9 129.8 103.0 76.3 ­62 146.0 18.1 146.0 146.0 149.8 123.2 96.7 70.2 133.9 20.0 133.9 133.9 133.9 113.5 86.4 59.6 57 149.0 18.2 149.0 149.0 147.4 120.9 94.3 67.8 137.7 20.1 137.7 137.7 136.1 109.9 82.6 55.9 72 169.4 18.7 162.2 133.0 103.9 74.7 - - 153.5 20.6 153.5 128.6 99.0 69.4 - ­67 155.3 18.4 155.3 155.3 142.7 113.5 84.3 - 140.7 20.3 140.7 140.7 138.3 108.7 79.1 ­62 147.9 18.2 147.9 147.9 147.9 118.7 89.5 60.3 135.6 20.1 135.6 135.6 135.6 106.0 76.4 46.8 57 150.9 18.3 150.9 150.9 150.9 121.7 92.5 63.3 139.5 20.2 139.5 139.5 139.5 109.9 80.3 50.6
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
58 Johnson Controls Unitary Products
Page 59
PJ-20/NJ-20
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
6000
7000
8000
9000
10000
WB (°F)
505430-BTG-P-0316
Total
Capacity
(MBh)
77 314.8 15.1 142.6 118.0 93.5 - - - 300.0 17.0 137.0 112.4 87.8 - - ­72 285.9 14.8 177.4 152.9 128.3 103.8 - - 271.7 16.7 171.9 147.4 122.8 98.3 - ­67 257.1 14.5 212.3 187.7 163.2 138.6 114.0 - 243.5 16.4 206.9 182.4 157.8 133.2 108.7 ­62 239.1 14.2 239.1 225.1 200.5 175.9 151.4 126.8 227.5 16.1 227.5 219.3 194.7 170.2 145.6 121.1 57 239.5 14.3 239.5 237.8 213.3 188.7 164.1 139.6 230.2 16.2 230.2 227.8 203.3 178.7 154.1 129.6 77 321.1 15.2 154.7 127.4 100.0 - - - 305.7 17.1 148.9 121.5 94.1 - - ­72 291.7 14.9 192.0 164.7 137.3 110.0 - - 276.9 16.8 186.4 159.0 131.6 104.2 - ­67 262.3 14.6 229.3 201.9 174.6 147.2 119.9 - 248.1 16.5 223.9 196.5 169.1 141.7 114.4 ­62 243.9 14.3 243.9 236.9 214.5 188.2 159.8 132.5 231.9 16.2 231.9 227.7 208.7 181.3 154.0 126.6 57 244.3 14.5 244.3 243.5 228.2 203.0 173.5 146.1 234.5 16.3 234.5 233.4 217.9 190.5 163.1 135.7 77 327.5 15.3 166.9 136.7 106.6 - - - 311.4 17.2 160.9 130.7 100.5 - - ­72 297.5 15.0 206.6 176.5 146.3 116.2 - - 282.1 16.9 200.9 170.7 140.5 110.2 - ­67 267.5 14.8 246.3 216.2 186.0 155.9 125.7 - 252.8 16.6 240.9 210.7 180.5 150.2 120.0 ­62 248.8 14.4 248.8 248.8 228.6 200.4 168.3 138.1 236.2 16.2 236.2 236.2 222.7 192.5 162.3 132.1 57 249.2 14.6 249.2 249.2 243.2 217.3 182.9 152.7 238.9 16.4 238.9 238.9 232.5 202.2 172.0 141.8 72 303.3 15.2 219.3 184.7 150.2 115.7 - - 287.2 17.1 212.0 178.0 144.0 110.1 - ­67 272.7 14.9 262.1 225.5 191.0 156.5 122.0 - 257.4 16.8 251.5 219.1 185.1 151.1 117.1 ­62 253.6 14.6 253.6 253.6 234.7 201.2 165.6 131.1 240.5 16.4 240.5 240.5 228.4 194.4 160.4 126.5 57 254.0 14.7 254.0 254.0 249.7 217.3 180.6 146.1 243.3 16.6 243.3 243.3 238.4 204.4 170.4 136.4 72 309.0 15.4 231.9 193.0 154.1 115.2 - - 292.4 17.3 223.1 185.4 147.6 109.9 - ­67 277.8 15.1 277.8 234.9 196.0 157.1 118.2 - 262.0 17.0 262.0 227.4 189.7 151.9 114.2 ­62 258.4 14.7 258.4 258.4 240.8 201.9 163.0 124.1 244.8 16.6 244.8 244.8 234.1 196.4 158.6 120.9 57 258.8 14.9 258.8 258.8 256.2 217.3 178.4 139.5 247.6 16.8 247.6 247.6 244.3 206.6 168.8 131.1
77 285.2 18.9 131.3 106.8 82.2 - - - 264.8 21.2 126.0 101.4 76.8 - - ­72 257.5 18.6 166.4 141.9 117.3 92.8 - - 240.1 20.9 161.0 136.3 111.7 87.1 - ­67 229.9 18.2 201.5 177.0 152.4 127.9 103.3 - 215.3 20.5 195.9 171.3 146.7 122.1 97.5 ­62 216.0 18.0 216.0 213.5 189.0 164.4 139.9 115.3 203.2 20.2 203.2 202.0 183.1 158.5 133.9 109.2 57 220.8 18.1 220.8 217.8 193.2 168.7 144.1 119.6 209.8 20.4 209.8 206.5 181.9 157.3 132.6 108.0 77 290.2 19.0 143.1 115.7 88.3 - - - 269.2 21.3 142.0 110.2 82.7 - - ­72 262.1 18.6 180.8 153.4 126.0 98.5 - - 244.1 20.9 175.3 147.8 120.3 92.8 - ­67 234.0 18.3 218.5 191.1 163.7 136.3 108.8 - 219.0 20.6 208.6 185.4 157.9 130.4 102.9 ­62 219.8 18.0 219.8 218.6 202.9 174.5 148.1 120.7 206.6 20.3 206.6 206.0 197.1 169.1 142.1 114.6 57 224.7 18.2 224.7 223.2 207.5 177.9 152.6 125.2 213.3 20.5 213.3 211.7 195.8 167.2 140.8 113.3 77 295.2 19.0 154.9 124.6 94.3 - - - 273.7 21.4 158.1 119.0 88.5 - - ­72 266.6 18.7 195.2 164.9 134.6 104.3 - - 248.1 21.0 189.7 159.3 128.9 98.4 - ­67 238.0 18.4 235.5 205.2 174.9 144.6 114.3 - 222.6 20.7 221.3 199.6 169.2 138.8 108.3 ­62 223.6 18.1 223.6 223.6 216.9 184.6 156.3 126.0 210.0 20.4 210.0 210.0 211.2 179.7 150.3 119.9 57 228.6 18.3 228.6 228.6 221.8 187.2 161.2 130.9 216.9 20.6 216.9 216.9 209.7 177.2 148.9 118.5 72 271.1 19.0 204.8 171.3 137.9 104.4 - - 252.2 21.2 199.3 165.7 132.2 98.6 - ­67 242.1 18.6 240.8 212.6 179.1 145.7 112.3 - 226.2 20.9 225.6 207.1 173.6 140.0 106.4 ­62 227.4 18.3 227.4 227.4 222.1 187.7 155.2 121.8 213.4 20.6 213.4 213.4 213.0 179.0 145.9 112.4 57 232.5 18.5 232.5 232.5 227.1 191.5 160.2 126.8 220.4 20.8 220.4 220.4 215.2 180.5 148.0 114.5 72 275.7 19.2 214.3 177.7 141.1 104.5 - - 256.2 21.5 208.9 172.2 135.5 98.8 - ­67 246.1 18.8 246.1 219.9 183.4 146.8 110.2 - 229.8 21.1 229.8 214.6 177.9 141.2 104.6 ­62 231.2 18.6 231.2 231.2 227.3 190.8 154.2 117.6 216.8 20.8 216.8 216.8 214.9 178.2 141.5 104.8 57 236.4 18.7 236.4 236.4 232.5 195.9 159.3 122.7 223.9 21.0 223.9 223.9 220.6 183.9 147.2 110.5
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 59
Page 60
505430-BTG-P-0316
PJ-20/NJ-20 (Continued)
Air on
Evaporator Coil
CFM
6000
7000
8000
9000
10000
1
WB
(°F)
77 244.4 23.6 120.7 96.0 71.4 - - - 224.0 25.9 115.4 90.7 65.9 - - ­72 222.6 23.2 155.5 130.8 106.2 81.5 - - 205.1 25.5 150.0 125.3 100.6 75.8 - ­67 200.8 22.8 190.3 165.6 140.9 116.3 91.6 - 186.2 25.1 184.7 159.9 135.2 110.5 85.7 ­62 190.4 22.5 190.4 190.4 177.2 152.5 127.8 103.2 177.6 24.8 177.6 177.6 171.3 146.5 121.8 97.1 57 198.8 22.8 198.8 195.2 170.5 145.8 121.2 96.5 187.8 25.1 187.8 183.9 159.2 134.4 109.7 85.0 77 248.3 23.6 140.9 104.7 77.1 - - - 227.3 25.9 139.8 99.1 71.4 - - ­72 226.1 23.2 169.8 142.2 114.6 87.0 - - 208.1 25.5 164.3 136.6 108.9 81.3 - ­67 204.0 22.9 198.7 179.8 152.2 124.6 97.0 - 188.9 25.2 188.8 174.1 146.4 118.7 91.1 ­62 193.4 22.6 193.4 193.4 191.3 163.7 136.1 108.5 180.2 24.8 180.2 180.2 180.2 158.3 130.1 102.4 57 201.9 22.8 201.9 200.1 184.1 156.5 128.9 101.3 190.6 25.1 190.6 188.6 172.4 145.8 117.0 89.3 77 252.1 23.7 161.2 113.3 82.7 - - - 230.6 26.0 164.3 107.6 76.9 - - ­72 229.6 23.3 184.1 153.6 123.1 92.5 - - 211.1 25.6 178.6 148.0 117.3 86.7 - ­67 207.1 22.9 207.1 194.0 163.4 132.9 102.4 - 191.7 25.2 191.7 188.3 157.7 127.0 96.4 ­62 196.4 22.6 196.4 196.4 205.4 174.9 144.4 113.8 182.8 24.9 182.8 182.8 182.8 170.1 138.4 107.8 57 205.1 22.9 205.1 205.1 197.7 167.2 136.6 106.1 193.3 25.2 193.3 193.3 185.7 157.2 124.4 93.7 72 233.2 23.5 193.9 160.2 126.5 92.8 - - 214.2 25.8 188.4 154.6 120.8 87.0 - ­67 210.3 23.2 210.3 201.6 168.0 134.3 100.6 - 194.5 25.5 194.5 194.5 162.4 128.6 94.8 ­62 199.4 22.8 199.4 199.4 203.9 170.3 136.6 102.9 185.4 25.1 185.4 185.4 185.4 161.6 127.3 93.5 57 208.3 23.1 208.3 208.3 203.2 169.5 135.9 102.2 196.1 25.4 196.1 196.1 191.3 158.5 123.7 89.9 72 236.7 23.8 203.6 166.8 129.9 93.1 - - 217.2 26.1 198.2 161.3 124.3 87.4 - ­67 213.5 23.4 213.5 209.3 172.5 135.7 98.9 - 197.2 25.7 197.2 197.2 167.1 130.2 93.2 ­62 202.5 23.1 202.5 202.5 202.5 165.6 128.8 92.0 188.1 25.4 188.1 188.1 188.1 153.1 116.1 79.2 57 211.4 23.4 211.4 211.4 208.7 171.9 135.1 98.3 198.9 25.7 198.9 198.9 196.8 159.9 123.0 86.0
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
nameplate rated motor
60 Johnson Controls Unitary Products
Page 61
505430-BTG-P-0316

Heat Pump And Air Handler Heating Capacities

PH-07 / NH-07

Air Over Evaporator Coil
CFM DB (°F ) -10 0 10 20 30 40 50 60
55
2250
3000
3750
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 motor efficiency.
70
80
55
70
80
55
70
80
Capacity
1
&
kW
MBH 34.0 39.6 46.2 53.9 62.9 73.5 86.0 100.6
KW 4.9 5.3 5.6 6.0 6.3 6.7 7.0 7.3
MBH 31.0 36.6 43.2 50.9 60.0 70.6 83.0 97.6
KW 5.8 6.1 6.5 6.8 7.1 7.5 7.8 8.2
MBH 28.7 34.3 40.9 48.6 57.7 68.3 80.7 95.3
KW 6.4 6.8 7.1 7.4 7.8 8.1 8.5 8.8
MBH 35.3 40.9 47.5 55.2 64.3 74.9 87.3 101.9
KW 4.7 5.1 5.4 5.8 6.1 6.5 6.8 7.1
MBH 32.4 38.0 44.5 52.3 61.3 71.9 84.4 99.0
KW 5.6 5.9 6.3 6.6 6.9 7.3 7.6 8.0
MBH 30.1 35.7 42.3 50.0 59.0 69.6 82.1 96.7
KW 6.2 6.5 6.9 7.2 7.6 7.9 8.3 8.6
MBH 36.6 42.2 48.8 56.5 65.6 76.2 88.6 103.2
KW 5.2 5.6 5.9 6.3 6.6 7.0 7.3 7.6
MBH 33.7 39.3 45.8 53.6 62.6 73.2 85.7 100.3
KW 6.1 6.4 6.8 7.1 7.4 7.8 8.1 8.5
MBH 31.4 37.0 43.6 51.3 60.3 70.9 83.4 98.0
KW 6.7 7.0 7.4 7.7 8.1 8.4 8.8 9.1
Outdoor Temperature (°F @ 72% RH)
nameplate rated

PH-10 / NH-10

Air Over Evaporator Coil
CFM DB (°F ) -10 0 10 20 30 40 50 60
55
3000
4000
5000
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.
70
80
55
70
80
55
70
80
Capacity
1
&
kW
MBH 29.1 36.4 45.3 56.0 69.0 84.7 103.8 126.8
KW 6.9 7.3 7.6 8.0 8.3 8.7 9.1 9.4
MBH 26.3 33.6 42.4 53.1 66.1 81.8 100.9 124.0
KW 8.2 8.6 8.9 9.3 9.7 10.0 10.4 10.7
MBH 24.2 31.5 40.4 51.1 64.1 79.8 98.8 121.9
KW 9.2 9.6 10.0 10.3 10.7 11.1 11.4 11.8
MBH 37.4 44.7 53.5 64.3 77.2 93.0 112.0 135.1
KW 6.7 7.1 7.4 7.8 8.1 8.5 8.9 9.2
MBH 34.5 41.8 50.7 61.4 74.4 90.1 109.2 132.2
KW 8.0 8.4 8.7 9.1 9.5 9.8 10.2 10.6
MBH 32.5 39.8 48.6 59.3 72.3 88.0 107.1 130.2
KW 9.0 9.4 9.8 10.1 10.5 10.9 11.2 11.6
MBH 44.1 51.4 60.3 71.0 84.0 99.7 118.7 141.8
KW 6.9 7.2 7.6 8.0 8.3 8.7 9.0 9.4
MBH 41.3 48.6 57.4 68.1 81.1 96.8 115.9 138.9
KW 8.2 8.6 8.9 9.3 9.6 10.0 10.4 10.7
MBH 39.2 46.5 55.3 66.1 79.0 94.8 113.8 136.9
KW 9.2 9.6 9.9 10.3 10.7 11.0 11.4 11.7
Outdoor Temperature (°F @ 72% RH)
Johnson Controls Unitary Products 61
Page 62
505430-BTG-P-0316

PH-15 / NH-15

Air Over Evaporator Coil
Capacity
CFM DB (°F ) -10 0 10 20 30 40 50 60
55
4500
70
80
55
6000
70
80
55
7500
70
80
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated
1
&
kW
MBH 68.2 80.0 93.8 110.0 129.1 151.5 177.8 208.7
KW 11.8 12.2 12.7 13.2 13.7 14.1 14.6 15.1
MBH 61.5 73.2 87.0 103.2 122.3 144.7 171.0 201.9
KW 13.5 14.0 14.4 14.9 15.4 15.9 16.3 16.8
MBH 57.6 69.3 83.1 99.3 118.4 140.8 167.1 198.0
KW 15.0 15.5 16.0 16.4 16.9 17.4 17.9 18.3
MBH 74.0 85.8 99.6 115.8 134.9 157.3 183.6 214.5
KW 11.2 11.7 12.2 12.6 13.1 13.6 14.1 14.6
MBH 67.3 79.0 92.8 109.0 128.1 150.5 176.8 207.7
KW 12.9 13.4 13.9 14.4 14.8 15.3 15.8 16.3
MBH 63.4 75.1 88.9 105.1 124.2 146.6 172.9 203.8
KW 14.5 14.9 15.4 15.9 16.4 16.8 17.3 17.8
MBH 72.4 84.1 97.9 114.1 133.2 155.6 181.9 212.8
KW 12.0 12.5 13.0 13.4 13.9 14.4 14.9 15.4
MBH 65.6 77.3 91.1 107.4 126.4 148.8 175.1 206.0
KW 13.7 14.2 14.7 15.2 15.6 16.1 16.6 17.1
MBH 61.7 73.4 87.3 103.5 122.5 144.9 171.2 202.1
KW 15.3 15.7 16.2 16.7 17.2 17.6 18.1 18.6
motor efficiency.
Outdoor Temperature (°F @ 72% RH)

PJ-15 / NJ-15

Air Over Evaporator Coil
Capacity
CFM DB (°F ) -10 0 10 20 30 40 50 60
55
4500
70
80
55
6000
70
80
55
7500
70
80
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated
1
&
kW
MBH 65.6 77.0 90.3 105.8 123.9 145.1 169.7 198.5
KW 10.0 10.5 11.1 11.6 12.2 12.7 13.3 13.8
MBH 62.2 73.6 86.9 102.4 120.5 141.6 166.3 195.1
KW 12.0 12.5 13.1 13.6 14.2 14.7 15.3 15.8
MBH 59.5 70.9 84.1 99.7 117.8 138.9 163.6 192.4
KW 13.4 13.9 14.5 15.0 15.6 16.1 16.7 17.2
MBH 71.6 83.0 96.3 111.8 129.9 151.0 175.7 204.5
KW 9.6 10.2 10.7 11.3 11.8 12.4 12.9 13.4
MBH 68.1 79.5 92.8 108.3 126.5 147.6 172.3 201.1
KW 11.6 12.2 12.7 13.3 13.8 14.3 14.9 15.4
MBH 65.4 76.8 90.1 105.6 123.7 144.9 169.6 198.3
KW 13.0 13.6 14.1 14.7 15.2 15.8 16.3 16.9
MBH 74.0 85.4 98.7 114.2 132.4 153.5 178.2 207.0
KW 11.3 11.8 12.4 12.9 13.5 14.0 14.6 15.1
MBH 70.6 82.0 95.3 110.8 128.9 150.1 174.7 203.5
KW 13.3 13.8 14.4 14.9 15.5 16.0 16.6 17.1
MBH 67.9 79.3 92.6 108.1 126.2 147.4 172.0 200.8
KW 14.7 15.3 15.8 16.4 16.9 17.5 18.0 18.5
motor efficiency.
Outdoor Temperature (°F @ 72% RH)
62 Johnson Controls Unitary Products
Page 63
505430-BTG-P-0316

PJ-20 / NJ-20

Air Over Evaporator Coil
Capacity
CFM DB (°F ) -10 0 10 20 30 40 50 60
55
6000
70
80
55
8000
70
80
55
10000
70
80
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated
1
&
kW
MBH 64.6 79.5 97.4 118.8 144.3 174.9 211.4 255.1
KW 15.7 16.5 17.3 18.1 19.0 19.8 20.6 21.4
MBH 69.5 84.4 102.3 123.7 149.2 179.8 216.3 260.0
KW 15.4 16.2 17.0 17.9 18.7 19.5 20.3 21.2
MBH 63.3 78.3 96.2 117.5 143.1 173.6 210.2 253.8
KW 17.2 18.0 18.8 19.6 20.5 21.3 22.1 23.0
MBH 71.6 86.6 104.5 125.8 151.4 181.9 218.5 262.1
KW 15.1 15.9 16.8 17.6 18.4 19.2 20.1 20.9
MBH 76.5 91.5 109.4 130.7 156.3 186.8 223.4 267.0
KW 14.8 15.6 16.5 17.3 18.1 19.0 19.8 20.6
MBH 70.4 85.3 103.2 124.6 150.1 180.7 217.2 260.9
KW 16.6 17.4 18.3 19.1 19.9 20.7 21.6 22.4
MBH 73.3 88.3 106.1 127.5 153.1 183.6 220.1 263.8
KW 15.3 16.1 17.0 17.8 18.6 19.4 20.3 21.1
MBH 78.2 93.2 111.0 132.4 158.0 188.5 225.0 268.7
KW 15.0 15.8 16.7 17.5 18.3 19.1 20.0 20.8
MBH 72.1 87.0 104.9 126.3 151.8 182.4 218.9 262.6
KW 16.8 17.6 18.5 19.3 20.1 20.9 21.8 22.6
motor efficiency.
Outdoor Temperature (°F @ 72% RH)
Johnson Controls Unitary Products 63
Page 64
505430-BTG-P-0316

Air Handling and Hot Water Coil Accessory Heating Capacity

NH-25 / 1HW0406

UNIT
MODEL
NH-25 1HW0406 50
1
NOTE: Temperature Water Drop (ºF) = (2 X MBH) / GPM.
COIL MODEL
These capacities do not include any blower motor heat.
1
HOT WATER
GPM CFM
6,000 204 263 325 384 443
8,000 236 304 372 440 508 10,000 265 341 416 492 568 12,000 291 374 457 540 623
ENTERING WATER TEMPERATURE MINUS ENTRY AIR TEMPERATURE °F.
70 90 110 130 150
Hot Water Coil Capacity Correction And Pressure Drop Vs GPM1
HOT WATER COIL MODEL GPM
25 0.4 0.79
1HW0406
1
For pressure drop in feet (water), multiply these values by 2.31.
50 1.0 1.00 75 1.8 1.04
100 3.4 1.07
PRESSURE DROP
CAPACITY (MBH)
PSI
CAPACITY CORRECTION
FACTOR
Air Handling and Steam Coil Accessory Heating Capacity NH-25 / 1NF0454
1
UNIT
MODEL
NH-25 1NF0454
1
These capacities do not include any blower motor heat.
STEAM COIL
MODEL
CFM DRY BULB TEMPERATURE OF AIR ENTERING COIL (°F)
6,000 471 424 380 330
8,000 535 483 432 380 10,000 592 535 478 422 12,000 642 580 518 456
CAPACITY (MBH) @ 2 PSIG
10 30 50 70

Steam Coil Capacity Correction Factors For High Steam Pressure

STEAM PRESSURE (PSIG) 5101520 25
CAPACITY CORRECTION FACTOR 1.05 1.12 1.19 1.25 1.30
NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH
64 Johnson Controls Unitary Products
Page 65
505430-BTG-P-0316

Airflow Performance

NH-07 Upflow and Horizontal Airflow Performance

NH-07 Upflow

Available External Static Pressure - IWG
(CFM)
2250 754 0.8 828 0.9 902 1.0 988 1.1 1051 1.3 1116 1.4 1183 1.5 2500 707 0.8 777 0.9 851 1.0 925 1.1 996 1.3 1059 1.4 1124 1.5 1191 1.7 2750 735 0.9 805 1.1 879 1.2 953 1.3 1012 1.4 1076 1.6 1141 1.7 3000 705 1.0 767 1.1 837 1.2 911 1.3 973 1.5 1035 1.6 1099 1.7 1164 1.9 3250 741 1.1 802 1.3 872 1.4 947 1.5 1002 1.7 1064 1.8 1127 2.0 3500 780 1.4 842 1.5 912 1.6 974 1.8 1035 1.9 1097 2.1 1161 2.2 3750 823 1.6 884 1.7 954 1.9 1012 2.0 1072 2.2 1134 2.3 Exceeds BHP Limitations
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine t he maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

NH-07 Horizontal

(CFM)
2250 747 0.8 816 0.9 889 1.0 954 1.2 1013 1.3 1071 1.5 1128 1.6 2500 703 0.8 768 0.9 837 1.0 909 1.1 977 1.2 1036 1.4 1094 1.5 1151 1.7 2750 728 0.9 793 1.0 862 1.1 934 1.2 998 1.4 1056 1.5 1114 1.7 3000 696 0.9 757 1.1 822 1.2 891 1.3 961 1.4 1019 1.6 1077 1.7 1135 1.9 3250 729 1.1 790 1.3 855 1.4 924 1.5 984 1.6 1042 1.8 1100 1.9 1159 2.1 3500 766 1.3 826 1.5 892 1.6 953 1.6 1010 1.9 1069 2.0 1127 2.2 3750 806 1.6 867 1.7 932 1.8 984 1.9 1041 2.1 1099 2.3 Exceeds BHP Limitations
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 1.5 HP & Field
Supplied Drive
Standard 1.5 HP & Drive High Static 2 HP & Drive
Available External Static Pressure - IWG
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 1.5 HP & Field
Supplied Drive
Standard 1.5 HP & Drive High Static 2 HP & Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine t he maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
Johnson Controls Unitary Products 65
Page 66
505430-BTG-P-0316

NH/ND-10 Upflow and Horizontal Airflow Performance

NH/ND-10 Upflow

Available External Static Pressure - IWG
(CFM)
2500 671 0.8 728 0.9 788 1.0 853 1.1 926 1.3 975 1.5 1026 1.6 1077 1.7 2750 684 0.9 741 1.0 801 1.1 866 1.2 933 1.4 982 1.6 1032 1.7 1084 1.8 3000 701 1.0 757 1.1 817 1.3 882 1.4 941 1.5 991 1.7 1041 1.8 1092 2.0 3250 664 1.0 719 1.1 776 1.3 836 1.4 903 1.5 952 1.7 1002 1.8 1052 2.0 3500 685 1.1 741 1.3 797 1.4 858 1.5 917 1.7 966 1.9 1015 2.0 1066 2.2 3750 653 1.1 709 1.3 764 1.4 821 1.6 884 1.7 933 1.9 982 2.0 1031 2.2 1082 2.3 4000 679 1.3 735 1.5 790 1.6 847 1.8 903 1.9 952 2.1 1001 2.3 1050 2.4 4250 707 1.5 762 1.6 818 1.8 875 1.9 924 2.1 973 2.3 1022 2.5 1072 2.7 4500 737 1.7 792 1.9 850 2.0 899 2.2 948 2.4 997 2.6 1046 2.8 4750 768 1.9 824 2.1 877 2.2 926 2.5 975 2.7 1024 2.9 1073 3.0 5000 801 2.1 856 2.3 906 2.5 956 2.8 1005 3.0 1053 3.2 High Static 3 HP & Field Supplied Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

NH/ND-10 Horizontal

(CFM)
2500 686 0.8 730 0.9 778 0.9 840 1.0 917 1.3 964 1.5 1011 1.6 1060 1.7 2750 698 0.9 742 1.0 790 1.0 852 1.1 924 1.4 971 1.6 1019 1.7 1067 1.9 3000 714 1.0 758 1.1 806 1.1 868 1.2 935 1.6 981 1.7 1029 1.9 1078 2.0 3250 684 1.0 734 1.2 778 1.2 826 1.3 902 1.6 948 1.7 995 1.9 1042 2.0 3500 707 1.2 757 1.3 801 1.4 849 1.4 917 1.7 964 1.9 1010 2.0 1058 2.2 3750 669 1.2 734 1.4 784 1.5 828 1.6 890 1.7 936 1.9 982 2.1 1029 2.2 1076 2.4 4000 699 1.4 764 1.6 814 1.7 858 1.8 910 2.0 956 2.1 1002 2.3 1049 2.4 4250 732 1.6 798 1.8 847 1.9 887 2.0 933 2.2 978 2.4 1025 2.5 1071 2.7 4500 769 1.8 834 2.0 884 2.1 911 2.3 957 2.4 1003 2.6 1049 2.8 4750 808 2.1 874 2.3 891 2.3 937 2.5 983 2.7 1029 2.9 1075 3.1 5000 850 2.3 873 2.4 919 2.6 965 2.8 1011 3.0 1057 3.2 High Static 3 HP & Field Supplied Drive
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 2 HP & Field
Supplied Drive
Standard 2 HP & Drive High Static 3 HP & Drive
Available External Static Pressure - IWG
0.20.40.60.81.01.21.41.61.82.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 2 HP & Field
Supplied Drive
Standard 2 HP & Drive High Static 3 HP & Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
66 Johnson Controls Unitary Products
Page 67
505430-BTG-P-0316

NH/NJ-15 Upflow and Horizontal Airflow Performance

NH/NJ-15 Upflow

Available External Static Pressure - IWG
(CFM)
4500 583 1.1 634 1.3 688 1.5 738 1.9 782 2.3 827 2.6 4750 592 1.2 643 1.4 700 1.8 744 2.1 788 2.4 833 2.7 5000 602 1.2 653 1.4 707 1.9 751 2.2 795 2.6 840 2.9 5250 613 1.3 664 1.5 716 2.1 759 2.4 804 2.7 848 3.1 5500 577 1.1 625 1.4 676 1.6 725 2.3 768 2.6 813 2.9 857 3.2 5750 590 1.2 638 1.4 689 1.7 735 2.5 778 2.8 822 3.1 6000 603 1.3 651 1.6 702 2.3 745 2.7 789 3.0 833 3.3 6250 617 1.5 664 1.7 714 2.6 757 2.9 801 3.2 845 3.5 6500 587 1.4 631 1.6 679 1.8 726 2.8 769 3.1 813 3.4 857 3.8 6750 601 1.6 645 1.8 693 2.0 739 3.0 782 3.4 826 3.7 7000 616 1.8 660 2.0 710 2.9 753 3.3 796 3.6 839 3.9 7250 632 2.1 675 2.3 725 3.2 767 3.6 810 3.9 854 4.2 7500 647 2.3 691 2.5 740 3.5 782 3.9 825 4.2 High Static 5 HP & Field Supplied Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine t he maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
0.20.40.60.81.01.21.41.61.8
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 3 HP & Field Supplied Drive Standard 3 HP & Drive High Static 5 HP & Drive

NH/NJ-15 Horizontal

Available External Static Pr essure - IWG
(CFM)
4500 585 1.5 634 1.6 687 1.8 735 2.0 780 2.5 827 2.7 875 2.9 4750 595 1.6 644 1.7 697 1.9 741 2.4 787 2.7 834 2.9 5000 605 1.7 655 1.8 708 2.0 749 2.6 795 2.9 842 3.1 5250 617 1.8 666 2.0 719 2.1 757 2.8 804 3.1 851 3.3 5500 582 1.8 629 1.9 678 2.1 731 2.3 767 3.0 813 3.2 860 3.4 5750 594 1.9 642 2.1 691 2.2 737 2.4 778 3.2 824 3.4 871 3.7 6000 608 2.1 655 2.2 705 2.4 744 3.1 789 3.4 835 3.7 6250 622 2.2 670 2.4 719 2.6 756 3.3 801 3.6 847 3.9 6500 589 2.2 637 2.4 684 2.6 733 2.7 769 3.6 814 3.9 860 4.1 6750 604 2.4 652 2.6 699 2.8 738 3.5 782 3.8 827 4.1 873 4.4 7000 620 2.6 667 2.8 715 3.0 752 3.8 796 4.1 841 4.4 7250 636 2.8 683 3.0 731 3.2 766 4.1 811 4.4 856 4.7 7500 652 3.0 700 3.2 738 4.0 781 4.4 825 4.7 High Static 5 HP & Field Supplied Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine t he maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 3 HP & Field Supplied Drive Standard 3 HP & Drive High Static 5 HP & Drive
Johnson Controls Unitary Products 67
Page 68
505430-BTG-P-0316

NH/NJ-20 Upflow and Horizontal Airflow Performance

NH/NJ-20 Upflow

Available External Static Pres sure - IWG
(CFM)
6000 732 2.2 789 2.6 846 2.9 900 3.1 959 4.0 1008 4.5 1056 4.9 1102 5.2 1146 5.3 6250 685 1.9 742 2.3 799 2.7 856 3.0 910 3.3 967 4.2 1016 4.7 1064 5.1 1110 5.4 1154 5.5 6500 696 2.1 752 2.5 809 2.8 866 3.2 920 3.4 976 4.4 1025 4.9 1072 5.3 1118 5.6 6750 706 2.2 763 2.6 820 3.0 877 3.3 935 4.0 985 4.6 1034 5.1 1081 5.5 1127 5.8 7000 718 2.4 774 2.8 831 3.2 888 3.5 945 4.2 994 4.8 1043 5.3 1091 5.7 1137 6.0 7250 729 2.6 786 3.0 843 3.3 900 3.6 954 4.5 1004 5.0 1053 5.5 1100 5.9 1146 6.2 7500 741 2.8 798 3.1 855 3.5 912 3.8 965 4.7 1014 5.3 1063 5.8 1111 6.2 7750 700 2.6 754 2.9 810 3.3 868 3.7 925 4.3 975 4.9 1025 5.5 1074 6.0 1121 6.4 8000 712 2.8 767 3.1 823 3.5 881 3.9 936 4.6 986 5.2 1036 5.8 1085 6.3 1132 6.7 8250 726 3.0 780 3.3 837 3.7 894 4.1 948 4.9 998 5.5 1047 6.0 1096 6.5 1144 6.9 8500 740 3.2 794 3.6 850 3.9 908 4.3 959 5.1 1010 5.8 1059 6.3 1108 6.8 8750 754 3.4 808 3.8 865 4.2 922 4.8 972 5.4 1022 6.0 1071 6.6 1120 7.1 9000 768 3.6 823 4.0 879 4.4 934 5.1 984 5.7 1034 6.4 1084 6.9 1133 7.4 9250 783 3.9 838 4.3 894 4.6 947 5.4 997 6.1 1047 6.7 1097 7.2 9500 799 4.1 853 4.5 910 4.9 961 5.8 1011 6.4 1061 7.0 1110 7.6 9750 815 4.4 869 4.8 925 5.5 974 6.1 1024 6.7 1074 7.3 1124 7.9
10000 831 4.7 885 5.0 939 5.9 988 6.5 1038 7.1 1088 7.7 1138 8.3 High Static 7.5 HP & Field Supplied Drive
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 5 HP &
Field Supplied Drive
High Static 5 HP & Drive High Static 7.5 HP & Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

NH/NJ-20 Horizontal

Available External Static Pressure - IWG
(CFM)
6000 708 2.0 754 2.3 801 2.6 849 2.8 898 2.9 976 4.0 1021 4.4 1066 4.8 1111 5.1 1155 5.3 6250 715 2.1 761 2.4 808 2.7 856 2.9 906 3.0 984 4.2 1029 4.6 1074 5.0 1118 5.3 1163 5.5 6500 723 2.3 769 2.6 816 2.8 864 3.0 947 3.9 991 4.4 1036 4.8 1081 5.2 1126 5.4 6750 731 2.4 777 2.7 824 3.0 872 3.2 955 4.1 999 4.6 1044 5,0 1089 5.3 1134 5.6 7000 740 2.5 786 2.8 833 3.1 881 3.3 963 4.3 1007 4.7 1052 5.2 1097 5.5 1142 5.8 7250 749 2.7 796 3.0 842 3.3 890 3.5 971 4.5 1015 4.9 1060 5.3 1105 5.7 1150 6.0 7500 712 2.6 759 2.9 806 3.2 852 3.4 900 3.6 979 4.7 1024 5.1 1069 5.5 1114 5.9 1158 6.2 7750 722 2.8 770 3.0 816 3.3 863 3.6 945 4.4 988 4.9 1033 5.3 1078 5.8 1123 6.1 8000 733 2.9 781 3.2 827 3.5 874 3.8 954 4.6 998 5.1 1042 5.5 1087 6.0 1132 6.3 8250 745 3.1 793 3.4 839 3.7 886 4.0 964 4.8 1007 5.3 1052 5.8 1096 6.2 1141 6.5 8500 757 3.3 805 3.6 851 3.9 898 4.2 974 5.1 1017 5.6 1062 6.0 1107 6.4 1152 6.8 8750 770 3.6 818 3.8 864 4.1 942 4.8 984 5.3 1028 5.8 1072 6.3 1117 6.7 9000 784 3.8 831 4.1 878 4.4 953 5.1 995 5.6 1039 6.1 1083 6.5 1128 6.9 9250 798 4.0 845 4.3 923 4.9 964 5.4 1006 5.9 1050 6.3 1094 6.8 1139 7.2 9500 812 4.3 859 4.6 935 5.2 976 5.7 1018 6.2 1062 6.6 1106 7.1 1151 7.5 9750 827 4.5 908 5.1 947 5.5 988 6.0 1030 6.5 1074 6.9 1118 7.4
10000 842 4.8 921 5.4 960 5.8 1001 6.3 1043 6.8 1087 7.3 1131 7.7 High Static 7.5 HP & Field Supplied Drive
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 5 HP &
Field
Supplied
Drive
Standard 5 HP & Drive High Static 7.5 HP & Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
68 Johnson Controls Unitary Products
Page 69
505430-BTG-P-0316
NH-25 Airflow Performance
CFM
7500 600 2.04 648 2.50 694 3.00 738 3.54 781 4.08 823 4.63 863 5.16 903 5.66 942 6.10 981 6.49 7750 603 2.17 652 2.63 698 3.13 742 3.67 785 4.22 827 4.76 867 5.29 907 5.79 946 6.24 984 6.62 8000 608 2.32 656 2.78 702 3.28 747 3.81 789 4.36 831 4.91 871 5.44 911 5.93 950 6.38 989 6.77 8250 613 2.48 661 2.93 707 3.44 752 3.97 795 4.52 836 5.07 877 5.60 916 6.09 955 6.54 994 6.92 8500 619 2.65 667 3.10 713 3.61 758 4.14 800 4.69 842 5.24 882 5.77 922 6.26 961 6.71 1000 7.09 8750 575 2.43 625 2.83 673 3.28 720 3.79 764 4.32 807 4.87 848 5.42 889 5.95 928 6.44 967 6.89 1006 7.27 9000 581 2.62 632 3.02 680 3.47 726 3.98 771 4.51 814 5.06 855 5.61 896 6.14 935 6.63 974 7.08 1013 7.46 9250 589 2.82 639 3.21 687 3.67 734 4.17 778 4.71 821 5.26 862 5.80 903 6.33 942 6.83 982 7.28 9500 596 3.02 647 3.42 695 3.88 741 4.38 786 4.91 829 5.46 870 6.01 910 6.54 950 7.03 989 7.48
9750 604 3.23 655 3.63 703 4.09 749 4.59 794 5.13 836 5.67 878 6.22 918 6.75 958 7.25 10000 613 3.45 663 3.85 711 4.31 758 4.81 802 5.34 845 5.89 886 6.44 927 6.97 966 7.46 10250 621 3.68 672 4.07 720 4.53 766 5.03 811 5.57 853 6.12 895 6.66 935 7.19 10500 630 3.9 680 4.30 729 4.76 775 5.26 819 5.80 862 6.34 904 6.89 944 7.42 10750 639 4.14 689 4.53 738 4.99 784 5.50 828 6.03 871 6.58 913 7.12 11000 648 4.37 699 4.77 747 5.23 793 5.73 837 6.27 880 6.82 922 7.36 11250 657 4.62 708 5.01 756 5.47 802 5.97 847 6.51 890 7.06 11500 667 4.86 717 5.26 766 5.71 812 6.22 856 6.75 899 7.30 11750 676 5.11 727 5.50 775 5.96 821 6.46 866 7.00 12000 686 5.36 737 5.75 785 6.21 831 6.71 876 7.25 12250 696 5.61 746 6.00 795 6.46 841 6.97 885 7.50 12500 706 5.86 756 6.26 805 6.72 851 7.22
0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP & Field
supplied
Drive
1
Available External Static Pressure - IWG
5 HP Motor & Drive 7.5 HP Motor & Drive
High static 7.5 HP & Field Supplied Drive
1. NH-25 requires the selection, purchase and field installation of the Supply Fan Motor, Drive Kit and Motor Overloads (See Following Page for Item Selection Tables).

RPM Selection

Unit Model HP Max BHP Motor Sheave Blower Sheave
NH-07
NH/NJ-10
NH/NJ-15
NH/NJ-20
1 2
Std. 1.5 1.73 1VL40 AK69 -
HS 2 2.30 1VL40 AK56 -
Std. 2 2.30 1VL40 AK74 -
HS 3 3.45 1VP56 AK84 -
Std. 3 3.45 1VP50 AK114 -
HS 5 5.75 2VP50 2B5V94 707 745 782 819 856 894 -
Std. 5 5.75 2VP50 2B5V94 686 722 758 794 830 866 -
HS 7.5 8.63 2VP65 2B5V94 925 960 996 1031 1067 1103 1138
Setting not available. Setting not recommended for use with Type B v-belts.
6 Turns
Open
5 Turns
Open
1 1 1 1 1
4 Turns
Open
3 Turns
Open
2 Turns
Open
690 743 796 849 902 955 863 929 995 1062 1128 1194 641 690 739 789 838 887 906 949 992 1035 1078 1121 565 596 627 659 690 721
1 Turn
Open

NH-07 thru -20 And NJ-10 thru -20 Blower Motor A nd D riv e Dat a

Blower Motor Data Drive Data
Unit
Model
NH-07
NH/NJ-10
NH/NJ-15
HP RPM SF
Std 1.5 HS 2 56HZ 1VL40 863 - 1194 2.6 - 3.6 0.875 AK56 5.2 1.000 1 40.3 A39
Std. 2
HS 3 56HZ 1VP56 906 - 1121 4.2 - 5.2 0.875 AK84 8.0 1.000 1 48.3 A47
Std. 3
HS 5 184T 2VP50 707 - 894 3.7 - 4.7 1.125 2B5V94 9.7 1.000 2 41.8 B40
1725 1.15
1725 1.15
1725 1.15
Frame
Model
Size
Number
56 1VL40 690 - 955 2.6 - 3.6 0.875 AK69 6.5 1.000 1 42.3 A41
56HZ 1VL40 641 - 887 2.6 - 3.6 0.875 AK74 7.0 1.000 1 45.3 A44
56HZ 1VP50 565 - 721 3.6 - 4.6 0.875 AK114 11.0 1.000 1 45.3 A44
Blower
RPM
Range
Adjustable Motor Sheave
Pitch
Diameter
(in.)
Bore
(in.)
Model
Number
Fixed Blower Sheave Belts
Pitch
Diameter
(in.)
Bore (in.) Qty.
Pitch
Length
(in.)
Fully
Closed
2 2
Desig­nation
Johnson Controls Unitary Products 69
Page 70
505430-BTG-P-0316
NH-07 thru -20 And NJ-10 thru -20 Blower Motor And Drive Data
NH/NJ-20
Std. 5
HS 7.5 213T 2VP65 925 - 1138 5.2 - 6.4 1.375 2B5V94 9.7 1.188 2 46.8 B45
1725 1.15
184T 2VP50 686 - 866 3.7 - 4.7 1.125 2B5V94 9.7 1.188 2 41.8 B40

NH-25 Drive Kit Data

Unit
Model
NH-25
Drive Kit Model
Number
1LD0440 2VP56 575 - 719 4.0 - 5.0 1 1/8 2AK124 12.0 1 3/16 2 63.3 A62 1LD0407 2VP60 659 - 815 4.2 - 5.2 1 3/8 2AK114 11.0 1 3/16 2 63.3 A62 1LD0442 2VP71 762 - 906 5.3 - 6.3 1 3/8 2AK124 12.0 1 3/16 2 63.3 A62
Sheave Number
Adjustable Motor Sheave Fixed Blower Sheave Belts
Model
Blower
RPM
Range
Pitch
Diameter
(in.)
Bore
(in.)
Sheave
Model
Number
Pitch
Diameter
(in.)
Bore
(in.)
Qty.
Pitch
Length
(in.)
Desig­nation

NH-25 Motor Kit Data

Unit Model HP
NH-25
7.5
Motor Kit
Model
Number
2LP04605133
5
2LP04605158 575 2LP04607133 2LP04607158 575
Frame
Size
184
213
Voltage
(3PH-60HZ)
208/230/460
208/230/460

NH-25 Overload Relay Kit

UNIT VOLTAGE 208/230V 460V 575V
MODEL MOTOR HP OVERLOAD RELAY KIT
NH-25
5 2MP04708500 2MP04708300 2MP04708300
7.5 2MP04708700 2MP04708400 2MP04708300

NH-25 Overload Relay Setting

UNIT VOLTAGE 208/230V 460V 575V
MODEL MOTOR HP OVERLOAD RELAY SETTING (Full Load Amps)
NH-25
1
Motors with Service Factor of 1.15 or Greater: Adjust overload relay dial to the motor nameplate Full Load Amps (FLA).
2
Motors with Service Factor Less Than 1.15: Adjust overload relay dial based on the formula: Motor nameplate FLA x 0.90 = relay setting
5 14/13 6.5 5
7.5 21/20 9.5 7.5
1,2
70 Johnson Controls Unitary Products
Page 71

Additional Static Resistance

Model CFM
2250 0.03 0.10 0.02 0.01 0.02 0.03 0.04 --- 2500 0.03 0.11 0.03 0.01 0.02 0.03 0.05 --- 2750 0.02 0.11 0.03 0.01 0.03 0.04 0.07 ---
NH-07
NH/NJ-10
NH/NJ-15
3000 0.02 0.12 0.04 0.01 0.03 0.05 0.08 --- 3250 0.01 0.13 0.04 0.02 0.04 0.06 0.09 --- 3500 0.00 0.14 0.05 0.02 0.04 0.07 0.10 --- 3750 0.00 0.15 0.06 0.02 0.05 0.08 0.12 --- 3000 0.08 0.12 0.04 0.01 0.03 0.05 0.08 --- 3250 0.07 0.13 0.04 0.02 0.04 0.06 0.09 --- 3500 0.07 0.14 0.05 0.02 0.04 0.07 0.10 --- 3750 0.06 0.15 0.06 0.02 0.05 0.08 0.12 --- 4000 0.05 0.16 0.07 0.03 0.06 0.09 0.14 --- 4250 0.04 0.18 0.08 0.03 0.06 0.10 0.15 --- 4500 0.03 0.19 0.09 0.03 0.07 0.11 0.17 --- 4750 0.02 0.21 0.10 0.04 0.08 0.13 0.19 --- 5000 0.00 0.23 0.11 0.04 0.09 0.14 0.21 --- 4500 0.07 0.11 0.03 0.03 0.07 0.11 0.17 0.21 4750 0.06 0.11 0.03 0.04 0.08 0.13 0.19 0.22 5000 0.06 0.11 0.04 0.04 0.09 0.14 0.21 0.24 5250 0.06 0.12 0.04 0.05 0.10 0.15 0.23 0.26 5500 0.05 0.12 0.04 0.05 0.11 0.17 0.25 0.29 5750 0.05 0.12 0.05 0.06 0.12 0.19 0.28 0.32 6000 0.05 0.13 0.05 0.06 0.13 0.20 0.30 0.35 6250 0.04 0.14 0.06 0.07 0.14 0.22 0.33 0.38 6500 0.03 0.14 0.06 0.07 0.15 0.24 0.35 0.42 6750 0.03 0.15 0.07 0.08 0.17 0.26 0.38 0.47 7000 0.02 0.16 0.07 0.08 0.18 0.28 0.41 0.50 7250 0.01 0.16 0.08 0.09 0.19 0.30 0.44 0.53 7500 0.00 0.17 0.08 0.10 0.20 0.32 0.47 0.56
Wet Indoor
Coil
505430-BTG-P-0316
1
2” Filters
Bottom
Return
10 16 26 36 50
Electric Heat kW
Model CFM
Wet Indoor
Coil
6000 0.08 0.12 0.06 0.01 0.03 0.05 6250 0.08 0.13 0.06 0.02 0.03 0.05 6500 0.08 0.13 0.07 0.02 0.04 0.06 6750 0.07 0.14 0.07 0.02 0.04 0.06 7000 0.07 0.14 0.08 0.02 0.04 0.07 7250 0.06 0.15 0.08 0.02 0.05 0.07 7500 0.06 0.16 0.09 0.02 0.05 0.08 7750 0.05 0.16 0.09 0.02 0.05 0.08
NH/NJ-20
8000 0.05 0.17 0.10 0.03 0.06 0.09 8250 0.04 0.18 0.10 0.03 0.06 0.09 8500 0.04 0.19 0.11 0.03 0.06 0.10 8750 0.03 0.20 0.12 0.03 0.07 0.11 9000
0.02 0.21 0.12 0.03 0.07 0.11
9250 0.01 0.22 0.13 0.04 0.08 0.12 9500 0.00 0.23 0.00 0.04 0.08 0.13 9750 0.00 0.24 0.00 0.04 0.09 0.13
10000 0.00 0.25 0.00 0.04 0.09 0.14
1
Pressure drop added by condensate over a dry coil.
2” Filters
Bottom
Return
Electric Heat kW
20 32 52
Johnson Controls Unitary Products 71
Page 72
505430-BTG-P-0316
Additional Static Resistance (Continued)
Model CFM Hot Water Coil Steam Coil
8000 0.06 0.11 9000 0.07 0.14
NH-25
10000 0.08 0.17 11000 0.09 0.20 12000 0.10 0.23

CFM Static Pressure and Power-Altitude and Temperature Corrections

The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level.
The air flow rates listed in the standard blower performance tables are based on standard air at sea level. As the altitude or temperature increases, the density of air decreases. In
order to use the indoor blower tables for high altitude applications, certain corrections are necessary.
A centrifugal fan is a "constant volume" device. This means that, if the rpm remains constant, the CFM delivered is the same regardless of the density of the air. However, since the air at high altitude is less dense, less static pressure will be generated and less power will be required than a similar application at sea level. Air density correction fa ctors are shown in Altitude Factors Table and Temperature Correction Figure.
72 Johnson Controls Unitary Products
Page 73
505430-BTG-P-0316
0.600
0.650
0.700
0.750
0.800
0.850
0.900
0.950
1.000
1.050
1.100
40 50 60 70 80 90 100
Air Temperature (ºF)
Correction Factor
Sea Level
1000 ft
2000 ft
3000 ft
4000 ft
6000 ft 7000 ft
8000 ft
9000 ft
10000 ft
5000 ft

Altitude/Temperature Correction Factors Table

Air
Temp.
40 1.060 1.022 0.98 6 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729 50 1.039 1.002 0.96 6 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715 60 1.019 0.982 0.94 8 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.701 70 1.000 0.964 0.93 0 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.688 80 0.982 0.947 0.91 3 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.676 90 0.964 0.929 0.89 7 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663
100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
Altitude (Ft.)

Altitude/Temperature Correction Factors Figure

The examples below will assist in determining the airflow performance of the product at altitude.
Example 1: Wha t are the corrected CF M, static pressure, and BHP at an elevation of 5,000 ft. if the blower performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?
Solution: At an elevation of 5,000 ft. the indoor blower will still deliver 6,000 CFM if the rpm is unchanged. However, the Altitude/Temperature Correction Factors table must be used to determine the static pressure and BHP. Since no temperature data is given, we will assume an air temperature of 70°F. The table shows the correction factor to be 0.832.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC Corrected BHP = 4.0 x 0.832 = 3.328
Example 2: A system, located at 5,000 feet of elevation, is to deliver 6,000 CFM at a static pressure of 1.5". Use the unit
blower tables to select the blower speed and the BHP requirement.
Solution: As in the example above, no temperature information is given so 70°F is assumed.
The 1.5" static pressure given is at an elevation of 5,000 ft. The first step is to convert this static pressure to equivalent sea level conditions.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft. Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation. BHP at 5,000 ft. = 3.2 x .832 = 2.66
Johnson Controls Unitary Products 73
Page 74
505430-BTG-P-0316
Drive Selection

1. Determine Upflow or Horizontal supply duct Application.

2. Determine desired airflow.

3. Calculate or measure the amount of external static pressure.

4. Using the operating point, determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table. (Linear interpolation may be necessary.)

5. Noting the RPM and BHP from step 4, locate the appropriate motor and/or drive on the RPM selection table.

6. Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.

7. Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the chosen motor.

8. Determine turns open to obtain the desired operation point.

Example

1. 3250 CFM

2. 1.4 iwg

3. Using the supply air blower performance table below, the following data point was located: 1100 RPM & 1.8 BHP.

4. Using the RPM selection table below, Model X is found.

5. 1.8 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.

6. 1100 RPM is within the range of the 2 HP drives.

7. Using the 2 HP motor and drive, 1 turn open will achieve 1128 RPM.

Airflow Performance

Example Supply Air Blower Performance
Available External Static Pressure - IWG
(CFM)
3000 696 0.9 757 1.1 822 1.2 891 1.3 961 1.3 1019 1.5 1077 1.6 1135 1.8 3250 729 1.1 790 1.3 855 1.4 924 1.5 984 1.6 1042 1.7 1100 1.8 1159 2.0 3500 766 1.3 826 1.5 892 1.6 953 1.6 1010 1.8 1069 1.9 1127 2.0
RPM Selection
Unit Model HP
X
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard 1.5 HP & Drive High Static 2 HP & Drive
Max
BHP
Std. 1.5 1.73 1VL40 AK69 N/A 690 743 796 849 902 955
HS 2 2.30 1VL40 AK56 N/A 863 929 995 1062 1128 1194
Motor
Sheave
Blower
Sheave
6 Turns
Open
5 Turns
Open
4 Turns
Open
3 Turns
Open
2 Turns
Open
1 Turn
Open
Fully
Closed
74 Johnson Controls Unitary Products
Page 75

Sound Performance

Outdoor Sound Power Levels (dB), 60 Hz

Size
(Tons)
-07
(7.5)
-10
(10.0)
-12
(12.5)
-15
(15.0)
-20
(20.0)
-25
(25.0)
1
Rated in accordance with AHRI 270 Standard.
Model PH-07 89 88 90 89 87 84 81 77 72
YH-07 89 88 89 89 87 84 81 78 73 PH-10 89 88 90 89 87 84 81 77 72 YH-10 90 91 87 90 88 85 80 76 70
YJ-10 90 92 89 91 88 85 80 77 71
YH-12 91 96 88 90 89 86 82 77 71
YJ-12 91 92 92 92 89 86 81 78 73
PH-15 93 93 96 93 90 89 84 77 71
PJ-15 93 93 96 93 90 89 84 77 71
YH-15 89 88 90 89 87 84 81 77 72
YJ-15 89 88 90 89 87 84 81 77 72
PH-20 93 93 96 93 90 89 84 77 71
PJ-20 93 93 96 93 90 89 84 77 71
YH-20 93 93 96 93 90 89 84 77 71
YJ-20 93 93 96 93 90 89 84 77 71
YH-25 93 93 96 93 90 89 84 77 71
Sound
Rating
1
505430-BTG-P-0316
Octave Bands (Hz)
63 125 250 500 1000 2000 4000 8000
Johnson Controls Unitary Products 75
Page 76
505430-BTG-P-0316

Electrical Data

Electrical Data For Outdoor Models Electrical Data - Outdoor Unit - AC Without Powered Convenience Outlet
Compressors Outdoor Fan Motor Pwr Conv Outlet
Model
YH-07
YH-10
YJ-10
YH-12
YJ-12
YH-15
YJ-15
YH-20
YJ-20
YH-25
1
2
Power
Supply
208/230-3-60 1 25.0 39 164 208/230-1-60 1/3 2 2.1 - 35.5 45
460-3-60 1 12.2 19 100 460-1-60 1/3 2 1.2 - 17.6 25 575-3-60 1 9.0 14 78 575-1-60 1/3 2 0.9 - 13.1 20
208/230-3-60 2 15.7 24.5 110 208/230-1-60 3/4 2 3.0 - 41.4 50
460-3-60 2 7.8 12.0 52 460-1-60 3/4 2 1.6 - 20.8 25 575-3-60 2 5.8 9.1 39 575-1-60 3/4 2 1.4 - 15.8 20
208/230-3-60 2 16.0 25 110 208/230-1-60 3/4 2 3.0 - 42.1 50
460-3-60 2 7.8 12 52 460-1-60 3/4 2 1.6 - 20.8 25 575-3-60 2 5.7 9 39 575-1-60 3/4 2 1.4 - 15.5 20
208/230-3-60 2 22.4 35 149 208/230-1-60 3/4 2 3.0 - 56.5 70
460-3-60 2 10.6 17 75 460-1-60 3/4 2 1.6 - 27.1 35 575-3-60 2 7.7 12 54 575-1-60 3/4 2 1.4 - 20.0 25
208/230-3-60 2 22.4 35 149 208/230-1-60 3/4 2 3.0 - 56.5 70
460-3-60 2 10.6 17 75 460-1-60 3/4 2 1.6 - 27.1 35 575-3-60 2 7.7 12 54 575-1-60 3/4 2 1.4 - 20.0 25
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 - 64.7 80
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 - 32.2 40 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 - 24.0 30
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 - 64.7 80
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 - 32.2 40 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 - 24.0 30
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 - 79.8 100
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 - 44.0 60 575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 - 32.9 45
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 - 79.8 100
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 - 44.0 60 575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 - 32.9 45
208/230-3-60 2 48.1 75 245 208/230-1-60 3/4 4 3.0 - 120.3 150
460-3-60 2 18.6 29 125 460-1-60 3/4 4 1.6 - 48.3 60 575-3-60 2 14.7 23 100 575-1-60 3/4 4 1.4 - 38.5 50
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C. Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP Qty
FLA
(each)
FLA
Minimum
Circuit
Ampacity
1
Maximum Fuse Size
2
(A)
76 Johnson Controls Unitary Products
Page 77

Electrical Data - Outdoor Unit - AC With Powered Convenience Outlet

Model
YH-07
YH-10
YJ-10
YH-12
YJ-12
YH-15
YJ-15
YH-20
YJ-20
YH-25
1
2
Power
Supply
208/230-3-60 1 25.0 39 164 208/230-1-60 1/3 2 2.1 10.0 45.5 60
460-3-60 1 12.2 19 100 460-1-60 1/3 2 1.2 5.0 22.6 30 575-3-60 1 9.0 14 78 575-1-60 1/3 2 0.9 4.0 17.1 25
208/230-3-60 2 15.7 24.5 110 208/230-1-60 3/4 2 3.0 10.0 51.4 60
460-3-60 2 7.8 12.0 52 460-1-60 3/4 2 1.6 5.0 25.8 30 575-3-60 2 5.8 9.1 39 575-1-60 3/4 2 1.4 4.0 19.8 25
208/230-3-60 2 16.0 25 110 208/230-1-60 3/4 2 3.0 10.0 52.1 60
460-3-60 2 7.8 12 52 460-1-60 3/4 2 1.6 5.0 25.8 30 575-3-60 2 5.7 9 39 575-1-60 3/4 2 1.4 4.0 19.5 25
208/230-3-60 2 22.4 35 149 208/230-1-60 3/4 2 3.0 10.0 66.5 80
460-3-60 2 10.6 17 75 460-1-60 3/4 2 1.6 5.0 32.1 40 575-3-60 2 7.7 12 54 575-1-60 3/4 2 1.4 4.0 24.0 30
208/230-3-60 2 22.4 35 149 208/230-1-60 3/4 2 3.0 10.0 66.5 80
460-3-60 2 10.6 17 75 460-1-60 3/4 2 1.6 5.0 32.1 40 575-3-60 2 7.7 12 54 575-1-60 3/4 2 1.4 4.0 24.0 30
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 5.0 37.2 45 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 4.0 28.0 35
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 5.0 37.2 45 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 4.0 28.0 35
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 10.0 89.8 110
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 5.0 49.0 60 575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 4.0 36.9 45
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 10.0 89.8 110
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 5.0 49.0 60 575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 4.0 36.9 45
208/230-3-60 2 48.1 75 245 208/230-1-60 3/4 4 3.0 10.0 130.3 175
460-3-60 2 18.6 29 125 460-1-60 3/4 4 1.6 5.0 53.3 70 575-3-60 2 14.7 23 100 575-1-60 3/4 4 1.4 4.0 42.5 50
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C. Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disco nnect sizing.
Compressors Outdoor Fan Motor Pwr Conv Outlet
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP Qty
FLA
(each)
FLA
505430-BTG-P-0316
1
Maximum Fuse Size
2
(A)
Minimum
Circuit
Ampacity
Johnson Controls Unitary Products 77
Page 78
505430-BTG-P-0316

Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet

Model
Power
Supply
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP Qty
208/230-3-60 1 25.0 39 164 208/230-1-60 1/3 2 2.1 - 35.5 45
Compressors Outdoor Fan Motor Pwr Conv Outlet
PH-07
460-3-60 1 12.2 19 100 460-1-60 1/3 2 1.2 - 17.6 25 575-3-60 1 9.0 14 78 575-1-60 1/3 2 0.9 - 13.1 20
PH-10
208/230-3-60 2 15.7 24.5 110 208/230-1-60 3/4 2 3.0 - 41.4 50
460-3-60 2 7.7 12.0 52 460-1-60 3/4 2 1.6 - 20.8 25
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 - 64.7 80
PH-15
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 - 32.2 40 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 - 24.0 30
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 - 64.7 80
PJ-15
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 - 32.2 40 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 - 24.0 30
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 - 79.8 100
PJ-20
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 - 44.0 60 575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 - 32.9 45
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC). Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
FLA
(each)
FLA
Minimum
Circuit
Ampacity
1
Maximum Fuse Size
2
(A)

Electrical Data - Outdoor Unit - HP With Powered Convenience Outlet

Compressors Outdoor Fan Motor Pwr Conv Outlet
Model
PH-07
PH-10
PH-15
PJ-15
PJ-20
1
2
Power
Supply
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP Qty
FLA
(each)
208/230-3-60 1 25.0 39 164 208/230-1-60 1/3 2 2.1 10.0 45.5 60
460-3-60 1 12.2 19 100 460-1-60 1/3 2 1.2 5.0 22.6 30 575-3-60 1 9.0 14 78 575-1-60 1/3 2 0.9 4.0 17.1 25
208/230-3-60 2 15.7 24.5 110 208/230-1-60 3/4 2 3.0 10.0 51.4 60
460-3-60 2 7.7 12.0 52 460-1-60 3/4 2 1.6 5.0 25.8 30
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 5.0 37.2 45 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 4.0 28.0 35
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 10.0 74.7 90
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 5.0 37.2 45 575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 4.0 28.0 35
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 10.0 89.8 110
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 5.0 49.0 60 575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 4.0 36.9 45
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C. Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
FLA
Minimum
Circuit
Ampacity
1
Maximum Fuse Size
2
(A)
78 Johnson Controls Unitary Products
Page 79

Electrical Data For Indoor Models

Electrical Data - Indoor Units
Motor HP Power Supply
208-3-60 5.0
230-3-60 5.2
1.5
460-3-60 2.5
575-3-60 2.0
208-3-60 6.6
230-3-60 6.8
2.0
460-3-60 3.4
575-3-60 2.4
Supply Blower
Motor
Electric Heat Option
FLA Model KW Stages Amps
NH-07C00B
None --- --- --- 6.3 15 10 KW 7.5 1 20.8 32.3 35 16 KW 12 2 33.4 47.9 50 26 KW 19.5 2 54.2 73.9 80 36 KW 27 2 75.1 99.9 100
None --- --- --- 6.5 15 10 KW 10 1 24.1 36.6 40 16 KW 16 2 38.5 54.6 60 26 KW 26 2 62.5 84.7 90 36 KW 36 2 86.6 1 14.8 125
None --- --- --- 3.1 15 10 KW 10 1 12.0 18.2 20 16 KW 16 2 19.2 27.2 30 26 KW 26 2 31.3 42.2 45 36 KW 36 2 43.3 57.3 60
None --- --- --- 2.5 15 10 KW 10 1 9.6 14.5 15 16 KW 16 2 15.4 21.7 25 26 KW 26 2 25.0 33.8 35 36 KW 36 2 34.6 45.8 50
NH/NJ-07C00C, NH/NJ-10C00C,
None --- --- --- 8.3 15 10 KW 7.5 1 20.8 34.3 35 16 KW 12 2 33.4 49.9 50 26 KW 19.5 2 54.2 75.9 80 36 KW 27 2 75.1 1 01.9 110
None --- --- --- 8.5 15 10 KW 10 1 24.1 38.6 40 16 KW 16 2 38.5 56.6 60 26 KW 26 2 62.5 86.7 90 36 KW 36 2 86.6 1 16.8 125
None --- --- --- 4.3 15 10 KW 10 1 12.0 19.3 20 16 KW 16 2 19.2 28.3 30 26 KW 26 2 31.3 43.3 45 36 KW 36 2 43.3 58.4 60
None --- --- --- 3.0 15 10 KW 10 1 9.6 15.0 15 16 KW 16 2 15.4 22.2 25 26 KW 26 2 25.0 34.3 35 36 KW 36 2 34.6 46.3 50
MCA
(Amps)
505430-BTG-P-0316
1
Max Fuse
Breaker
3
(Amps)
2
Size
/
Johnson Controls Unitary Products 79
Page 80
505430-BTG-P-0316
Electrical Data - Indoor Units (Continued)
Motor HP Power Supply
208-3-60 9.6
230-3-60 9.4
3.0
460-3-60 4.7
575-3-60 3.6
208-3-60 14.0
230-3-60 14.0
5.0
460-3-60 7.0
575-3-60 5.2
Supply Blower
Electric Heat Option
Motor
FLA Model KW Stages Amps
NH/NJ-10C00D, NH/NJ-15C00D
None --- --- --- 12.0 15 10 KW 7.5 1 20.8 38.0 40 16 KW 12 2 33.4 53.6 60 26 KW 19.5 2 54.2 79.7 80 36 KW 27 2 75.1 1 05.7 110
4
50 KW
37.6 2 104.2 142.5 150
None --- --- --- 11.8 15 10 KW 10 1 24.1 41.8 45 16 KW 16 2 38.5 59.9 60 26 KW 26 2 62.5 89.9 90 36 KW 36 2 86.6 1 20.0 125
4
50 KW
50 2 120.3 132.0 150
None --- --- --- 5.9 15 10 KW 10 1 12.0 20.9 25 16 KW 16 2 19.2 29.9 30 26 KW 26 2 31.3 45.0 45 36 KW 36 2 43.3 60.0 60
4
50 KW
50 2 60.1 66.0 70
None --- --- --- 4.5 15 10 KW 10 1 9.6 16.5 20 16 KW 16 2 15.4 23.7 25 26 KW 26 2 25.0 35.8 40 36 KW 36 2 34.6 47.8 50
4
50 KW
50 2 48.1 52.6 60
NH/NJ-15C00E
None --- --- --- 17.5 20 10 KW 7.5 1 20.8 43.5 45 16 KW 12 2 33.4 59.1 60 26 KW 19.5 2 54.2 85.2 90 36 KW 27 2 75.1 1 11.2 125 50 KW 37.6 2 104.2 148.0 150
None --- --- --- 17.5 20 10 KW 10 1 24.1 47.6 50 16 KW 16 2 38.5 65.6 70 26 KW 26 2 62.5 95.7 100 36 KW 36 2 86.6 1 25.8 150 50 KW 50 2 120.3 137.8 150
None --- --- --- 8.8 15 10 KW 10 1 12.0 23.8 25 16 KW 16 2 19.2 32.8 35 26 KW 26 2 31.3 47.8 50 36 KW 36 2 43.3 62.9 70 50 KW 50 2 60.1 68.9 70
None --- --- --- 6.5 15 10 KW 10 1 9.6 18.5 20 16 KW 16 2 15.4 25.7 30 26 KW 26 2 25.0 37.8 40 36 KW 36 2 34.6 49.8 50 50 KW 50 2 48.1 54.6 60
MCA
(Amps)
1
Max Fuse
Breaker
3
(Amps)
2
Size
/
80 Johnson Controls Unitary Products
Page 81
Electrical Data - Indoor Units (Continued)
Supply
Motor HP Power Supply
208-3-60 14.0
230-3-60 14.0
5.0
460-3-60 7.0
575-3-60 5.2
208-3-60 16.7 None --- --- --- 21.0 35
5.0
7.5
7.5
1
Minimum Circuit Ampacity.
2
Dual Element, Time Delay Type.
3
HACR type per NEC.
4
(NC/ND)180C00D Models Only
5
Motors are not shipped with these models. Motor and Drive Kits are required.
230-3-60 15.2 None --- --- --- 19.0 30 460-3-60 7.6 None --- --- --- 10.0 15 575-3-60 6.1 None --- --- --- 8.0 15
208-3-60 21.7
230-3-60 20.0
460-3-60 10.0
575-3-60 7.8
208-3-60 24.2 None --- --- --- 30.0 35 230-3-60 22.0 None --- --- --- 28.0 30 460-3-60 11.0 None --- --- --- 14.0 15 575-3-60 9.0 None --- --- --- 8.0 15
Blower
Motor
FLA Model KW Stages Amps
NH/NJ-20C00E
None --- --- --- 17.5 20 20 KW 15 1 41.7 69.5 70 32 KW 24 2 66.7 1 00.8 110 52 KW 39.1 2 108.4 153.2 175
None -- --- --- 17.5 20 20 KW 20 1 48.1 77.6 80 32 KW 32 2 77.0 1 13.7 125 52 KW 52 2 125.1 142.6 150
None --- --- --- 8.8 15 20 KW 20 1 24.1 38.8 40 32 KW 32 2 38.5 56.9 60 52 KW 52 2 62.5 71.3 80
None --- --- --- 6.5 15 20 KW 20 1 19.2 30.6 35 32 KW 32 2 30.8 45.0 45 52 KW 52 2 50.0 56.5 60
NH-25C00N
NH/NJ-20C00F
None --- --- --- 27.1 30 20 KW 15 1 41.7 79.2 80 32 KW 24 2 66.7 1 10.4 125 52 KW 39.1 2 108.4 162.8 175
None -- --- --- 25.0 25 20 KW 20 1 48.1 85.1 90 32 KW 32 2 77.0 1 21.2 125 52 KW 52 2 125.1 150.1 175
None --- --- --- 12.5 15 20 KW 20 1 24.1 42.6 45 32 KW 32 2 38.5 60.6 70 52 KW 52 2 62.5 75.0 80
None --- --- --- 9.8 15 20 KW 20 1 19.2 33.8 35 32 KW 32 2 30.8 48.2 50 52 KW 52 2 50.0 59.8 60
NH-25C00N
Electric Heat Option
5
5
MCA
(Amps)
505430-BTG-P-0316
1
Max Fuse
Breaker
3
(Amps)
2
Size
/
Johnson Controls Unitary Products 81
Page 82
505430-BTG-P-0316

Typical Wiring Diagrams

Air Conditioning Condensing Units

Typical YH-07 Wiring Diagram
82 Johnson Controls Unitary Products
Page 83
Typical YH-10 thru -12 Wiring Diagram
505430-BTG-P-0316
Johnson Controls Unitary Products 83
Page 84
505430-BTG-P-0316
Typical YJ-10 thru -12 Wiring Diagram
84 Johnson Controls Unitary Products
Page 85
Typical YH-15 Wiring Diagram
505430-BTG-P-0316
Johnson Controls Unitary Products 85
Page 86
505430-BTG-P-0316
Typical YH-20 Wiring Diagram
86 Johnson Controls Unitary Products
Page 87
Typical YH-25 Wiring Diagram
505430-BTG-P-0316
Johnson Controls Unitary Products 87
Page 88
505430-BTG-P-0316
Typical YJ-25 Wiring Diagram
88 Johnson Controls Unitary Products
Page 89
Typical YJ-15 thru -20 Wiring Diagram
505430-BTG-P-0316
Johnson Controls Unitary Products 89
Page 90
505430-BTG-P-0316

Heat Pump Units

Typical PH-07 Wiring Diagram
90 Johnson Controls Unitary Products
Page 91
Typical PH-10 Wiring Diagram
505430-BTG-P-0316
Johnson Controls Unitary Products 91
Page 92
505430-BTG-P-0316
Typical PH-15 thru -20 Wiring Diagram
92 Johnson Controls Unitary Products
Page 93
Typical PH-20 Wiring Diagram
505430-BTG-P-0316
Johnson Controls Unitary Products 93
Page 94
505430-BTG-P-0316
Typical PJ-15 thru -20 Wiring Diagram
94 Johnson Controls Unitary Products
Page 95

Air Handling Units

Typical NH-07 Wiring Diagram
505430-BTG-P-0316
Johnson Controls Unitary Products 95
Page 96
505430-BTG-P-0316
Typical NH-10 thru -20, 1.5 thru 5 HP Blower Motor Only Wiring Diagram
96 Johnson Controls Unitary Products
Page 97
Typical NH-20, 7.5 HP Blower Motor 208/230 V Only Wiring Diagram
505430-BTG-P-0316
Johnson Controls Unitary Products 97
Page 98
505430-BTG-P-0316
Typical NH-20, 7.5 HP Blower Motor 460/575 V Only Wiring Diagram
98 Johnson Controls Unitary Products
Page 99
Typical NH-25 Wiring Diagram
505430-BTG-P-0316
Johnson Controls Unitary Products 99
Page 100
505430-BTG-P-0316
Typical NJ-20, 1.5 Thru 5 HP Blower Motor Only Wiring Diagram
100 Johnson Controls Unitary Products