Johnson Controls VMA 1410, VMA 1400 Series, VMA 1430, VMA 1420 Overview And Engineering Manuallines

Technical Bulletin
Issue Date February 28, 2006
Variable Air Volume Modular Assembly (VMA) 1400
Series Overview and Engineering Guidelines
VMA1400 Series Overview and Engineering Guidelines ...................2
Key Concepts...................................................................................................... 3
VMA1400 Series Models...................................................................................................3
VAV System......................................................................................................................6
Definition of Terms............................................................................................................9
Room Sensor Placement ................................................................................................10
Pressure Independence..................................................................................................10
VMA Airflow Rate............................................................................................................10
Power Source..................................................................................................................11
N2 Bus Rules..................................................................................................................12
Inputs and Outputs..........................................................................................................13
Zone Bus.........................................................................................................................14
CablePRO.......................................................................................................................15
CVTPRO.........................................................................................................................15
Related Documentation...................................................................................................16
Application Examples......................................................................................................17
Reference Information.....................................................................................................26
Specifications..................................................................................................................27
Detailed Procedures.........................................................................................32
Determining VAV Box Requirements..............................................................................32
Establishing the Room Schedule....................................................................................32
Developing the Bill of Material and Placing Orders.........................................................33
Configuring the VMA.......................................................................................................35
© 2006 Johnson Controls, Inc. www.johnsoncontrols.com Code No. LIT-6363120
VMA1400 Series Overview and Engineering Guidelines Technical Bulletin 2
VMA1400 Series Overview and Engineering Guidelines
Introduction
The Variable Air Volume Modular Assembly (VMA) 1400 Series is a configurable, integrated module that includes a Variable Air Volume (VAV) controller, differential pressure sensor, and, with the exception of the VMA1430, an actuator.
Note: This document focuses on the VMA1410, 1420, and 1430 controllers. The VMA1400 Series also includes the VMA1440, which is used exclusively as part of the Metasys® Zoning Package. See the
Metasys Zoning Package Product Bulletin (LIT-639050) and the Metasys Zoning Package Overview Technical Bulletin (LIT-639100)
for information on this specialized product. The VMA engineering procedures vary from location to location. The
information provided here is a general engineering guideline. Where available, use the Advanced Installation Management (AIM) tools for developing schedules and drawings.
This document provides a VMA1400 Series overview and describes how to:
determine VAV box requirements establish the room schedule develop bills of material and place orders configure the VMA
VMA1400 Series Overview and Engineering Guidelines Technical Bulletin 3
Key Concepts
VMA1400 Series Models
VMA1410 VMA1420
Figure 1: VMA1400 Series Models
VMA1430
VMA14xx
The VMA is a configurable, integrated module that includes a VAV controller and differential pressure sensor. The VMA1400 Series includes three models:
VMA1410 (cooling only, includes actuator) VMA1420 (cooling with reheat, includes actuator) VMA1430 (controller and differential pressure sensor only for use
with an external incremental or proportional actuator)
Note: The VMA1400 Series also includes the VMA1440, which is used exclusively as part of the Metasys Zoning Package. See the
Metasys Zoning Package Product Bulletin (LIT-639050) and the Metasys Zoning Package Overview Technical Bulletin (LIT-639100)
for information on this specialized product. The models are designed for pressure independent, single duct
(all VMA1400 Series models), and dual duct (VMA1420 and 1430 only) applications. The VMA1420 and 1430 models can be used with parallel or series fan-powered boxes.
Note: The VMA1420 can be configured for the Metasys Zoning Package application, but the internal pressure sensor can only be used for monitoring purposes. Refer to the Metasys Zoning Package Commissioning Technical Bulletin (LIT-639250).
VMA1400 Series Overview and Engineering Guidelines Technical Bulletin 4
Table 1: VMA1400 Series Comparison Checklist
VMA Features 1410 1420 1430 Comments
Applications Pattern Recognition Adaptive
Control (PRAC) on Zone Proportional plus Integral plus Derivative (PID) Temperature Loops
Adaptive Flow Control Loops
Single Duct, Pressure Independent
VAV
Side Loops without Interlocking
Single Duct Supply/Exhaust VAV Fan Powered Boxes
Incremental, Proportional
Two Position, and Three Stages of Box Heat
Incremental, Proportional
Two Position, or One Stage Supplemental Heat
Dual Duct, Pressure Independent
VAV Damper Actuator (Internal) Accurate Positioning Stall Detection Automatic Damper End Stop
Detection at Power Up Clockwise (CW)/
Counterclockwise (CCW)
Rotation Selection EP8000 with Pneumatic Actuator Software Tools Ability To Download Code Firmware
Diagnostics Moving Average Flow/Temperature
Diagnostic
Actuator Stall Flow Test Data Graphing
Starved Box Detection
Actuator Duty Cycle Diagnostic Continued on next page . . .
Y Y Y Eliminates manual tuning and
seasonal re-tuning
Y Y Y Eliminates manual tuning,
improves control and energy savings
Y Y Y Meets most VAV applications
N Y Y Single Analog Input (AI) to Analog
Output (AO) or Binary Output (BO)
N Y Y Flow differential control N Y Y Series or parallel
N Y Y Staged heat or normally
open/normally closed valves
N Y Y Normally open or closed valves
N Y Y Flexible flow setpoint specification
Y Y N/A 23,000 step resolution Y Y N/A Detects damper travel stops Y Y N Sets damper stroke time
Y Y Y Set via HVAC PRO™ software for
either direction to close
N Y Y
Y Y Y Allows firmware code upgrade
without removing the VMA
Y Y Y Provides standard measure of
control loop performance over
time Y Y N/A Y Y Y Y Y Y Only for single duct applicatio ns
Y Y Y Allows air handler reset an d flow
diagnostics Y Y Y Indicates shaft slippage
VMA1400 Series Overview and Engineering Guidelines Technical Bulletin 5
VMA Features (Cont.) 1410 1420 1430 Comments
Commissioning
Balancing Tool with Automatic
Pickup Gain Calculation
Hardware
24 Volts Alternating Current (VAC)
Isolation Built-in
Multiple VMAs per 100 VA
Transformer
Isolated N2, Binary Outputs, and
24 VAC
Ability to Drive Low Current Relays
Down to 25 milliampere (mA)
15 Bit Analog Input/12 Bit Analog
Output Resolution
Analog Input Jumpers Eliminated
Differential Pressure Transducer
Dead Ended Transducer Stainless Steel Capacitive
Technology
Industry Accepted Flow
Measurement Accuracy
Temperature Sensors
Variety of Sensors
Temporary Occupied Button
Temporary Occupied Light-Emitting
Diode (LED)
LED Indicator for N2/Power
Physical
Small, One Piece Assembly:
VMA1410, VMA1420
152.4 x 101.6 x 101.6 mm (6 x 4 x 4 in.)
VMA1430
152.4 x 101.6 x 82.6 mm (6 x 4 x 3.25 in.)
Plenum Plastic Housing Rating
Removable I/O Screw Terminals
Y Y Y HVAC PRO software (single duct
only) or VMA Balancing Tool
(VBT) software on Zone Bus
Y Y Y Eliminates 24 to 24 VAC
transformer and polarity concerns Y Y Y Ten cooling only (VMA1410) or
14 VMA1430s. Reheat/fan unit
depends on valve/fan relays Y Y Y Saves installed cost and improves
electrical noise rejection N Y Y Eliminates relay chatter
AI only
Y Y Y Reduces labor because all analog
Y Y Y Requires no filters or maintenance Y Y Y Provides improved stability
Y Y Y Provides stability below 1 m/s
Y Y Y Nickel, 1 K platinum, silicon,
Y Y Y On TE-6700, TE-7000 (Europe
Y Y Y On TE-6700, TE-7000 (Europe
Y Y Y Verifies N2 and power
Y Y Y Reduces installation cost
Y Y Y Underwriters Laboratories®, Inc.
Y Y Y Two or three position accessories
Y Y Provides improved control device
resolution
inputs are preset
(200 fpm)
2.25K NTC
only), and TMZ1600 Series room
sensors
only), or TMZ1600 for timed
override (Temporary Occupied)
connections
(UL) 94-5VB plenum flammability
eliminates metal box
VMA1400 Series Overview and Engineering Guidelines Technical Bulletin 6
VAV System
Theory of Operation
A VAV air handling system typically consists of a single air handling unit and multiple terminal units. Terminal units typically consist of a damper and flow sensing probe installed in an enclosure. VAV terminal units are also called VAV boxes. VAV systems are predominantly single duct, but about 15% are dual duct designs. In either case, the supply air temperature and static pressure of the air handling unit are controlled by an AHU (Air Handling Unit) controller, while each zone has its own VMA controller.
The air handling unit typically maintains a static pressure in the range of 125 to 375 Pa (0.5 to 1.5 inches water column (w.c.) inside the longest run of duct away from the supply fan. This ensures that each VAV terminal unit has enough pressure at its inlet to deliver the maximum required flow of air into the space. The supply temperature is typically in the range of 7 to 16°C (45 to 60°F) for a single duct VAV system or the cold deck of a dual duct VAV system. The hot deck temperature of a dual duct VAV system is typically in the range of 29 to 49°C (85 to 120°F).
VAV systems are most easily understood by first considering a cooling-only application. As the zone temperature increases, the VAV controller opens the VAV box damper to allow more cool air to reach the space. The volume of air required to maintain a particular zone temperature setpoint is dictated by the size of the space and the internal and external heat loads. In addition, since the size of the VAV box dictates its maximum cooling capacity, a VAV box’s performance is dependent upon the mechanical engineer’s correct box sizing for each zone.
Sometimes the size, and thus the capacity, of the VAV box may not match the zone loads. If the installed unit is too small, insufficient cooling results and noise may be emitted at high flow. If the installed unit is too large, proper control may be difficult to attain, since a small change in damper position causes a large change in airflow. Boxes can be oversized to allow for quieter operation or reserve cooling capacity at the expense of controllability.
VMA1400 Series Overview and Engineering Guidelines Technical Bulletin 7
The VMA quickly adjusts the damper position to new conditions, and minimizes position hunting and motor runtime. The fast response stepper actuator on the VMA1410 and 1420 drives the damper from full open to full closed in 30 seconds. This significantly reduces the time to commission a VAV box. Response time of the VMA1430 with an external synchronous actuator is dependent upon the speed of the actuator used. The VMA incorporates flow feedback to accurately position the damper. Control performance metrics are recorded and are available via the Metasys Operator Workstation (OWS) for timely indication of system problems.
The VMA is configured for most VAV applications. Configuration Tools (HVAC PRO software), Version 7.00 or later builds the applications for VMA1410/1420. Version 7.02 or later includes the VMA1430 as well as the VMA1410/1420.
VMA1400 Series Overview and Engineering Guidelines Technical Bulletin 8
V
V
Ethernet LAN
Network
Control Unit
(NCU)
DX9100
TC9102
Unitary
Controller
(UNT)
Palm Compatible Handheld Device
CVTPRO Converter
Network
Control
Module
N30
N30
(NCM)
MA1400
Operator Workstation
DX9100
AHU
VAV
UNT
MA1400
UNT
VMA1400
N2
Zone
N2
CablePRO
Converter
Laptop
Room
Bus
Room
Sensor
Sensor
Zone
Bus
VMAMTSY6
Figure 2: VMA in Metasys Network Diagram
VMA1400 Series Overview and Engineering Guidelines Technical Bulletin 9
Definition of Terms
Autocalibration
To correct for pressure sensor drifts over time, the VMA has an Autocalibration mode that automatically compensates for temperature and humidity effects.
N2 Switches
Single-pole, single-throw switches used to set the N2 address of a controller.
Room Schedule
A set of information listing all parameters required in a room or zone.
Test and Balance (TAB)
Test and Balance (TAB) is a function performed to ensure the installed system operates to design specifications. Balancing of the VMA zone indicates whether the VAV terminal box is able to achieve minimum/maximum airflow settings. TAB must also be performed for the air handler and the air duct distribution to the VAV box.
Zones
When designing VMA systems, it is critical to establish zones correctly to take full advantage of VMA’s exceptional accuracy and rapid response capabilities.
The designer strives for the most uniform indoor environmental conditions possible. A single thermostatic device (room sensor) controls each area. Also, you may consider a zone any area where the load is approximately the same for every square foot of floor space.
Heating, Ventilating, and Air Conditioning (HVAC) system zones fall into two major categories: exterior zones and interior zones. Exterior zones are spaces directly affected by outdoor weather conditions. Interior zones are not influenced by heat losses or outdoor air conditions. Interior zones usually have cooling or ventilation requirements only.
Further division of interior/exterior zones is occasionally required to accommodate different occupancy schedules and/or solar loads. Variations in internal loading also dictate the selection of separate zones. For example, in a restaurant, the kitchen has much different heating and cooling requirements than the customer seating area.
VMA1400 Series Overview and Engineering Guidelines Technical Bulletin 10
Room Sensor Placement
When considering room sensor placement for each zone:
Verify that the room sensor is the correct one for the application.
Review architectural requirements such as furniture height and location, aesthetics, and type of mounting. Wall plates are required if mounting on a conduit handibox.
Review room sensor location. The best room sensor location is on an interior wall, about 1.5 m (5 feet) above the floor, out of direct sunlight, out of the direct path of supply air from the diffuser, away from heat sources, such as equipment, machines, and perimeter radiation, and away from doors and other draft sources. Local codes or disabilities act requirements occasionally influence the actual mounting height.
Do not locate a sensor near zone boundaries, where primary influence is from an adjacent zone.
Pressure Independence
The pressure independent VMA employs patented self-tuning, cascaded proportional/integral control loops. The zone temperature loop samples space temperature and resets the airflow setpoint between the minimum and maximum flow settings. Since inlet duct static pressure influences the amount of air passing through the VAV box, the VMA airflow loop samples airflow via a flow pickup in the box inlet. It modulates the damper to control the flow. Thus, the VAV box flow is independent of duct static pressure.
The engineering basis for this method of control is that the temperature of a space with a constant load is linearly proportional to the flow of conditioned air into the space. The engineer must accurately determine the required maximum and minimum flow for each space based on heating, cooling, and ventilation loads.
VMA Airflow Rate
The VMA determines airflow rate by dynamic pressure measurement. The VMA contains a Differential Pressure Transducer (DPT) to sense velocity pressure in pressure independent VAV applications.
The DPT is connected to the VAV box airflow pickups. It measures velocity pressure and generates a proportional voltage signal. The VMA reads voltage signal from the DPT and converts it to airflow in cubic feet per minute (cfm), liters/second, or cubic meters/hour. Calibration is not required, with the exception of zero calibration, which the controller performs automatically as set in the configuration.
VMA1400 Series Overview and Engineering Guidelines Technical Bulletin 11
The DPT provides maintenance-free performance within the control range of 1 to 18 m/s (200 to 3500 feet per minute [fpm]) when used as recommended.
Pressure independent VAV terminal boxes use an airflow pickup device, which amplifies the airflow velocity pressure between 1.5 to 3 times (varies by manufacturer). The airflow velocity and the gain of the airflow pickup produce an accurately measured pressure difference.
The VMA Autocalibration function helps reduce the temperature effect error by zeroing offset errors. As the ambient temperature swings relative to the temperature at which the Autocalibration occurred, an offset error occurs. In the worst case, the offset error ranges up to ±0.179 Pascal per °C (±0.0004 inch w.c. per °F). When calibration occurs, this error becomes zero.
The error envelope becomes smaller with increased airflow pickup gain and with smaller ambient temperature deviations at the transmitter location.
Power Source
You can use one 24 VAC power trunk to power multiple VMAs. Transformers of up to 100 VA can be centrally located and the secondary run can be without conduit (if allowed by local authority) and without concern about polarity. When using a single transformer to power multiple VMAs, use a wire gauge large enough to handle the current and minimize the voltage drop. The voltage drop depends on the current draw, wire gauge, and wire length. For more details about transformer wiring and calculating the number of VMAs per transformer, see the Mounting and Wiring Variable Air Volume
Modular Assembly (VMA) 1400 Series Controllers Technical Bulletin (LIT-6363125).
Note: The 24 V power transformer must be UL/Canadian Standards Association (CSA) listed as NEC Class 2 Power Limited. See NEC Article 725/Class 2 (30 VRMS maximum) and (100 VA maximum).
Loading...
+ 24 hidden pages