VG1000 Series Flanged Ball Valves
Installation Instructions
VG12A5xx, VG18A5xx
Refer to the QuickLIT website for the most up-to-date version of this document.
Part No. 14-1352-6, Rev. G
Issued October 2016
Applications
The VG1000 Series Flanged Ball Valves are designed
to regulate hot and chilled water , 50/50 glycol solutions,
and 25 psig steam in HVAC systems.
IMPORTANT: The VG1000 Series Flanged Ball
Valve is intended to control saturated steam, hot
water, and chilled water flow under normal operating
conditions. Where failure or malfunction of the ball
valve could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or
protect against failure or malfunction of the ball
valve.
IMPORTANT: Le VG1000 Series Flanged Ball Valve
est destiné à réguler un débit saturated steam, hot
water, and chilled water dans des conditions
normales de fonctionnement. Lorsqu'une défaillance
ou un dysfonctionnement du ball valve risque de
provoquer des blessures ou d'endommager
l'équipement contrôlé ou un autre équipement, la
conception du système de contrôle doit intégrer des
dispositifs de protection supplémentaires. Veiller
dans ce cas à intégrer de façon permanente
d'autres dispositifs, tels que des systèmes de
supervision ou d'alarme, ou des dispositifs de
sécurité ou de limitation, ayant une fonction
d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du ball valve.
To minimize heat transfer in steam applications, wrap
the valve and piping with insulation. Allow at least 4 in.
(102 mm) of clearance from the top of the shaft to
remove the actuator (as noted in Table 1).
When mounting the actuator in the field and before
installing the actuator, use an adjustable wrench to
manually rotate the valve stem several times. This
rotation breaks the torque th at may have built up during
long-term storage.
IMPORTANT: Do not attempt to manually rotate the
drive shaft while the actuator is installed without fir st
releasing the actuator gears. Manually rotating the
drive shaft without releasing the actuator gears may
result in permanent damage to the actuator.
IMPORTANT: Take care to prevent foreign material
such as weld slag, thread burrs, metal chips, and
scale from entering the piping system. This de br is
can damage or severely impede the operation of the
valve by embedding itself in the seats, scoring the
valve, and ultimately resulting in seat leakage. If the
debris becomes embedded in the seats, subseque nt
flushing and filtering of the piping system with the
valve installed does not remedy the problem.
For detailed installation information about using
specific equipment, refer to the appropriate
documentation from the following list.
• M9108, M9116, M9124, and M9132 Series Ele ctric
Non-Spring Return Actuators Installation
Instructions (Part No. 34-636-399)
Installation
Install the VG1000 Series Flanged Ball Valves with the
actuator at or above the centerline of the horizontal
piping, as shown in Figure 1.
IMPORTANT: In steam applications, install the
valve with the stem horizontal to the piping. Failure
to follow these guidelines may shorten the life of the
actuator.
VG1000 Series Flanged Ball Valves Installation Instructions
• M9220-AGx-3 Series Floating Electric Spring
Return Actuators Installation Instructions
(Part No. 34-636-1689)
• M9220-Bxx-3 Series On/Off Electric Spring Return
Actuators Installation Instructions
(Part No. 34-636-1239)
• M9220-GGx-3 Series Proportional Electric Spring
Return Actuators Installation Instructions
(Part No. 34-636-1697)
1

• M9000-330 and M9000-340 Series We ather Shield
Figure 1: Recommended Mounting Positions for Non-Steam Applications
F
I
G
.
V
G
1
0
0
0
-
i
i
0
1
Enclosures Installation Instructions
(Part No. 14-1330-26)
• M9000-51x Series Valve Linkage Kits Installation
Instructions (Part No. 14-1201-13)
B
A
A
B
A
A
B
A
A
A
B
A
A
A
B
A
A
B
A
A
B
VG1000 Series Flanged Ball Valves Installation Instructions
2

Dimensions
Figure 2: M9124 Actuated VG12A5xx
Two-Way Series Ball Valves, in. (mm)
Figure 3: M9124 Actuated
VG18A5xx Three-Way Series Ball Valves
Figure 4: M9220 Actuated VG12A5x x
Two-Way Series Ball Valves, in. (mm)
Figure 5: M9220 Actuated
VG18A5xx Three-Way Series Ball Valves
See Figure 2 for VG12A5xx Two-Way Series Flanged
Ball Valves with M9124 Series Actuators dimensions.
See Figure 3 for VG18A5xx Three-Way Series Flanged
Ball Valves with M9124 Series Actuators dimensions.
See Table 1 for specific model dimensions.
5.17
(131)
See Figure 4 for VG12A5xx Two-Way Series Flanged
Ball Valves with M9220 Series Actuators dimensions.
See Figure 5 for VG18A5xx Three-Way Series Flanged
Ball Valves with M9220 Series Actuators dimensions.
See Table 1 for specific model dimensions.
Table 1: VG1xA5xx Series Ball Valves Dimensions, in. (mm) (Part 1 of 2)
Valve
Size,
A Valve
Code
in. (DN)
2-1/2
(DN65)
3 (DN80) 3.75
3.50
(89)
(95)
VG1xA5Gx 5.71
VG1xA5Kx 3.60
VG1xA5Hx 6.10
VG1xA5Lx 4.30
VG1000 Series Flanged Ball Valves Installation Instructions
BC D F G
(Bolt
Circle)
5.50
(140)
6.00
(152)
(145)
(92)
(155)
(110)
1 1 .42
(290)
7.25
(184)
12.20
(310)
8.70
(220)
M9124
8.89
(226)
8.90
(226)
1
M9220
9.64
(245)
9.65
(245)
1
5.87
(149)
6.73
(171)
6.26
(159)
6.77
(172)
3
H Number
of Bolts
0.75
(19)
0.75
(19)
4
4